Dfi400200PX
ECT400200PX
Dff40020030iPX short chamber + end
to which
normative
this dectardtion retates is in conformity with the fottowing standard(s) or other
document(s)
EN(|5O)12100-2: 2003 Safety of l,lachinery - B6ic Concepts, Generat Principtes for Design.
EN1012-2t 1997 Compr6sors and Vacuum
EN610'l0-1: 2001t Safety
EN6t326: 1997 Eectrical equipment for measurement, control and laboratory use
(immunity,
Cla5s B Emissions)
C22.2 No 61010.1-04F
UL6101O-1
'
pumps
The
manuat supplied
"
24V Pumps onty compty with the Canadian Standard Authority and UnderwriteB laboratory
when used with D(DC 24V famitv of controtlers.
'optiport'
'optiport'
(2'd
Edition;# safety requirements for etectricat equipment for medurement,
compty with EN61010-1 when instatled in accordance with the instruction
+
Technicat Principats,
laboratory use.
E IC requirements,
Safety requirements for
Controt and taboratory use, Part 1: General requirements
Controt ard taboratory use, Part 1!
with
the
that the
port
end
requirements for
pump.
of Conformity
product(s)
pump:
8760-61-991
8760-62-991
oott 8760-67-991
pumps,
etectricat equipment
electricat
Safety Requirements. Vacuum Pumps.
equipment ior measurement,
Generat
for meaiurement controt and
requirements
following the
2006t95tEC
2@4t't08tEc
98tX7tEC
provisions
of
Vottage Directive.
Low
ElectrorEgnetic
^,lachirErv Directive
e.ca----t^',
B, D, Brewster,
&)rge5s Hill
Technical hlanager
PrducE
product
This
has been manufactured
Compatibitity Directive
zL?t<^
9,)d,a\e59
Date and Place
quality
under a
system
O.l€
registered to |SO9W1
>',r
a
t
Lr.-
Z'cxlr
c
-
s
Page 3
l?nwa,FrD=
Declaration
We,
Edwards,
Manor Royat,
Crdwtey,
West Sussex RH10 9LW, UK
declare under our sote rGponsibitity that the madfne(s)
Description
EXT40020030iPX Cartridge inGrstage
to which this dectaration relates is intended to be incorporated into other equipment and not
function independentty. The machine(s) is in conformity with the fottowing standard(s)
normative
document(5)
(l5O)12100-2:
EN
EN1012-2: 1997 Compressors and Vacuum
EN61010-l: 2001.
EN61326: 1997
(immunity,
2003 Safety of Machinery - Basic Concepts, General Principtes for
Design. Technicat Principals.
PumDs.
Safety requirements for electrical equipment for measurement
control and laboratory use.
EtectricaI equipment for measurement, control and [abordtory use
EMC requi rements.
of Incorporation
Item number
8760-53-991
or other
pumps.
safety Requirements. Vacuum
Ctass B Emissions)
C22.2 No 61010.1-04 Safety requirements for electrical equipment for measurement,
Ut6101o-1
*
The
manual supptied with the
'
24V Pumps onty compty with the Canadian Standard Authority and
when used
(2"d
Edition)' safety requirements for etectricat equipment for measurement,
pumps
compty with EN61010-1 when instatled in accordance
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 9
B760-60-880 Issue A
CAUTION
WARNING
1Introduction
1.1Scope and definitions
This manual provides installation, operation, maintenance and storage instructions for the range of Edwards
EXT400/200PX and EXT400/200/30iPX split f low com pound t urbomo lecular vacuum pu mps, he reaf ter re ferred to as
EXTPX split flow pumps. Please read and follow all instructions in this manual.
The EXTPX split flow pump is designed for use with an Edwards 24 V EXDC160 drive module unless using Argon (please
refer to Section 2.2) when an EXDC80 drive module may be recommended. Read this manual and the instruction
manual supplied with your EXDC before you attempt to install or operate the equipment. The EXDC drive module
manual contains details of electrical installation.
Important safety information in this manual is highlighted as WARNING and CAUTION instructions; please obey these
instructions. The use of WARNINGS and CAUTIONS is defined below.
Warnings are given where failure to observe the instruction could result in injury to or death of
people.
Introduction
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and process.
In accordance with the recommendations of EN61010, the following warning symbols may appear on the p ump or its
accessories:
Warning - refer to accompanying documentation.
Warning - risk of electric shock.
Warning - hot surfaces.
The units used throughout this manual conform to the SI international system of units of measurement.
Also throughout this manual, wherever flow rates are specified, the abbreviation 'sccm' is used to mean standard
3
cm
min-1: this is a flow of 1 cm3 min-1 at an ambient temperature of 0 °C and a pressure of 1013 mbar
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 11
B760-60-880 Issue A
2Technical data
2.1General
Table 1 - General data
General itemsReference data
PerformanceRefer to Table 2
DimensionsRefer to Table 2 and Figure 2 to 5
Maximum inlet-flange temperature70 °C
Maximum radial and axial magnetic field 3.5 mT
Installation categoryEN61010 part 1, Category 1
Pollution degreeEN61010 part 1, Category 2
Table 2 - Technical data
ParameterEXTPX split flow pumpNotes
Mass12 kg or lessWeight dependent on specific
variant.
Main inlet portRefer to Figure 2 to 5
Side inlet portRefer to Figure 2 to 5
Interstage portRefer to Figure 2 to 5
Booster portDN 25NW
Exhaust portDN 25NW
Vent port1/8 inch BSPP
Purge port1/8 inch BSPP
Peak end inlet pumping speed
Peak booster port pumping speed N
using XDS10 24 m3 h-1 (6.7 l s-1)
using RV1226 m3 h-1 (7.2 l s-1)
Peak compression ratio from the
backing-port to the main inlet
, He and H
N
2
2
Peak compression ratio from the side
inlet to the main inlet
, He and H
N
2
2
Maximum booster port pressure- N
Maximum backing pressure- N
Recommended backing-pump Application dependentPlease consult Edwards.
Maximum single continuous
inlet pressure
Main inlet 1.2 x 10
Side inlet4.1 x 10
Interstage inlet (where fitted) 2.2 x 10 -1 mbar
Operating attitudeRefer to Figure 8
Nominal rotational speed 60,000 rpm
Starting time to 90% speed
Using an EXDC 160
Cooling methodForced air/ water-coolingRefer to Section 3.7.
Ambient air temperature
(forced air-cooling)
Water-cooling supply temperature10- 20°C
Noise level at 1 metre< 45 dBA
Recommended controllerEXDC 160 W 24 VD396-46-000
Recommended controller (Argon)EXDC 80 24 VD396-45-000 also refer to
EXDC160 maximum VA output250 VA
Quiescent power25-40 WP ower at ultimate pressure with
*
All pumping speeds are peak valu es for a horizontal envelope pump without inlet screen. Inlet screens may
reduce performance by up to 15%. Actual pumpin g speed for different envelope variants will be dependent
on inlet geometry and flow distribution between ports.
2
N2 > 1 x 10
He 1 x 10
H2 2 x 10
N2 1 x 10
8
6
5
4
*
He 100
H2 35
2
4.5 mbarAir cooled at 25 °C ambient with
RV12 backing-pump (1400 sccm flow)
and with no flow through other inlet
ports, and no strainer fitted.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 13
B760-60-880 Issue A
WARNING
WARNING
WARNING
WARNING
Figure 1 - Booster port performance with lines of constant backing pressure
Technical data
*
Power Limit Zone: The temperatures shown are pump local ambients. The tests were performed with a single
radial fan cooling the pump. If extra cooling is added, extra performance can be obtained. Exact limits will be
based on application requirements, cooling metho d and pump configuration; please consult Edwards to ensure
suitability. Also refer to Section 3.7 and 7.4 for cooling requirements and accessories.
2.2Pumping med ia
If pumping hazardous gases or vapours, the customer must observe the safety recommendations
of the supplier of the gas or vapour. Vent hazardous gases and gas mixtures safely. Do not expose
people to these gases.
Do not pump explosive gas mixtures through the EXTPX split flow pump as the pump is not suitable
for this purpose.
If pyrophoric gases are pumped then the customer must supply adequate dilution with an inert gas.
It is the customers' responsibility to leak check their system to ensure that the process gases will
not escape to the atmosphere where this would cause a hazard.
Gases entering from different pump inlets may combine to cause dangerous mixtures.
An EXDC160 drive module is recommended for most applications. However, when pumpi ng high concentrations
of Argon (over 50% of gas mixture) an EXDC80 drive module is recommended to protect the pump against
overheating. If in any doubt, please contact your local Edwards Vacuum Representative.
Do not use the EXTPX split flow pump to pump particulates or condensable media. Deposition may occur within
the pump which will degrade pump performance and reduce the pump life.
Do not use the EXTPX split flow pump to pump gases containing more than 20% oxygen. If you do, the lubricant
will polymerise and the pump will fail prematurely.
Note:Concentrations of gases may be modified by the compression of the pump.
The pump is designed to pump the following residual gases normally used in high-vacuum systems:
z Airz Nitrogenz Carbon Dioxide
z Carbon Monoxidez Kryptonz Helium
z Neonz Argonz Hydrogen
z Ethanez Propanez Butane
z Methane
You can use the pump to pump oxygen and water vapour, subject to the following conditions:
z Oxygen - The oxygen concentration must be less than 20% by volume; also refer to Section 2.4.
z Water vapour - You must ensure that vapour does not condense inside the pump.
If you wish to pump a gas not in the list above, co ntact your supplier for advice. If you do not contact your supplier,
you may invalidate the warranty on the pump. The pump is not suitable for pumping aggressive or corrosive gases.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 15
B760-60-880 Issue A
2.3Vent gas specification and vent control data
Although the pump may be vented to atmosphere, high relative humidity of the air may greatly increase the
subsequent pump-down time. To reduce pump-down times you should vent the pump with dry, clean gases. Refer to
Table 3.
Table 3 - Vent gas and vent control data
Vent itemsReference data
Vent gasDry air, nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure-22°C
Maximum size of particulate1
Maximum concentration of oil0.1 parts per million
Time for rotational speed to reduce to 50%≥15 seconds
Maximum purge gas pressure< 0.5 bar gauge (7 psig, 0.5 x 10
*
If you wish to use vent pressures in excess of this value, please consult Edwards.
µm
5
Pa gauge)
*
2.4Purge gas specification and data
Technical data
When purged with an inert gas, the pumps can be used to pump oxygen in concentrations above 20% by volume.
Table 4 - Purge gas specification
Purge gas system itemsReference data
Purge gasDry nitrogen, argon or other inert gas
Maximum dew point at atmospheric pressure-22°C
Maximum size of particulate1
Maximum concentration of oil0.1 parts per million
Allowable purge gas flow (when required)20- 150 sccm (0.33- 2.5 mbar l s
Recommended purge gas flow25 sccm minimum (0.42 mbar l s-1, 42 pa l s-1)
Maximum allowable purge gas supply pressure0.5 bar gauge (7 psig, 0.5 x 105 Pa)
*
If you wish to use pressures in excess of this value, plea se consult Edwards.
µm
-1
, 33- 250 Pa l s-1)
*
2.5Materials exposed to gases pumped
The following materials and component types are exposed to the gases pumped: aluminium alloys, steels, stainless
steels, fluoroelastomer and nitrile O-rings, hydrocarbon lubricant, felt, rare earth magnets, silicon nitride, phenolic
resin, and carbon-fibre reinforced epoxy resin.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 21
B760-60-880 Issue A
WARNING
3Installation
3.1Unpack and inspect
The pump weighs up to 12 kg (26 lbs). Appropriate care should be taken when lifting and moving
the pump to avoid injury.
Take care when unpacking the pump to avoid excessive sh ocks which co uld damage the beari ngs and re duce th e life
of the pump. The pump is supplied with the inlets and outlet sealed to prevent entry of dust and vapour. Do not
remove these seals until you are ready to install the pump on your vacuum system.
Open the cardboard box from the top. Once the box lid is open, remove the upper piece(s) of foam and cut open the
bag.
If the pump is damaged, notify your supplier and the carrier in writing within three days; state the Item Number of
the pump together with your order number and your supplier's invoice number. Retain all packing materials for
inspection. Do not use the pump if it is damaged.
Check that your package contains the items listed in Table 5. If any of these items are missing, notify your supplier
in writing within three days.
Installation
If the pump is not to be used immediately, store in suitable conditions as described in Section 6.1.
It is advised to retain all packing materials for use, should you return the pump for service.
Install the pump in the vacuum system before you connect the controller to the power supply. This
will ensure that the pump cannot operate and injure people during installation.
Under no circumstances must any part of the human body be exposed to a vacuum.
Carefully remove the pump from the packaging media and connect to the vacuum system.
3.3.1Mechanical fixing
Ensure the EXTPX split flow pump is either securely fixed to the vacuum system via its inlet-flange
using all available mounting points, or that it is securely restrained to a fixed point. If the pump
were to seize when not securely mounted or restrained, the stored energy of the rotor (approx
20 kJ) could cause rapid movement of the pump, which may cause further damage and injury to
personnel.
If you wish to base-mount your pump, you will need to remove the 3 feet that are supplied fitted to the base of the
pump before mounting with qty. 5 M8 bolts. Refer also to the warning in Section 3.3.3.
3.3.2Inlet screens
Inlet screens are supplied fitted to the pump.
The impeller blades on an EXTPX split flow pump are very sharp. The absence or removal of inlet
screens or strainers exposes the risk of injury from sharp edges or moving parts. Care should be
taken when handling the pump not to dislodge or damage the protective inlet screens.
For B76062991 and B76067991 only: There is no inlet screen fitted to the end of the chamber
pump and the blades of the turbo-pump are visible and accessible through the pump envelope at
this point. These blades represent a rotational safety hazard when the pump is operational and a
sharp edged hazard when the pump is stationary. Retain plastic transport covers over inlets until
ready to install in order to minimize any risk of injury.
Care must be taken to avoid foreign objects entering the pump when installing equipment to the
chambers.
Do not remove the inlet screens unless you can be sure that there is no danger that debris can fall into the pump.
To remove an inlet screen, carefully extract it from the inlet-flange using a bent wire hook. Once removed, a screen
is not reusable. Spares are available (refer to Section 7).
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 25
B760-60-880 Issue A
CAUTION
WARNING
WARNING
1. Inlet screen
2. Inlet-flange
In the unlikely event of a pump fracture, it is possible that the inlet screen may not trap all debris
within the pump. Ensure that the system can contain any debris that may escape from the pump.
Figure 7 - Correct installation of inlet screen
Installation
3.3.3Inlet connection and pump orientation
It is important that the pump is correctly orientated. Incorrect orientation may lead to premature pump failure.
Do not store or orientate the pump such that the pump inlets face towards the ground, nor store the pump such
that the end of the envelope faces towards the ground (with the pump body - containing electrical connector facing directly upwards). In either of these orientations it could be possible for oil used to lubricate the lower
bearing to escape from a reservoir at the base of the pump into the pump mechanism or vacuum system. This
may reduce performance and bearing life.
For base-mounting, use qty. 5 x M8 bolts tightened to a minimum torque of 10 Nm (7.5 lb ft) to
attach to the mounting. Use ISO898-1 material property class 12.9 or greater.
3.3.3.1Inlet connection and pump orientation (non-cartridge pumps)
It is recommended that the pump is f lange mounte d. However, if this is not the case, please obs erve the warning in
Section 3.3.1. The exhaust port must not be tilted at more than 60° from the vertical position, (refer to Figure 8)
otherwise oil may leak into the pumping mechanism; refer to the Caution above.
Make sure that the pump inlets and all components fitted to the pump-inlets are clean and dust-free. If the pump-
inlets are not kept clean, the pump-down time may be increased or HV chamber pressures may not be achieved.
Use the O-rings supplied with the pump and use four M8 bolts tightened to a torque of 20 Nm (15 lb ft) to connect
the inlet-flange of the pump to the vacuum system.
3.3.3.2Inlet connection and pump orientation (cartridge pumps)
Use 6 x M8 fixing screws of appropriate length to attach the pum p to the vacuum chamber. Ensure
the chamber is robust enough to restrain the pump in the highly unlikely event of a rotor burst
where a peak torque of approximately 13,000 Nm may be transmitted to the chamber for a very
short time. It is the responsibility of the user to ensure that the vacuum system is capable of
containing the rotor fragments in the event of a catastrophic failure. Contact Edwards for further
information if required.
O-rings included with the cartridge pump must be fitted to the grooves before installing the cartridge pump into its
system. To ensure a proper seal between the inlets these should be untwisted, undamaged, dry, clean and dust-free.
Please refer to Edwards for recommended housing sizes.
The customer must ensure safe ducting of the backing-line if oil mist or hazardous substances are
present.
The EXTPX split flow pump must not be operated, or vented from a positive pressure gas supply,
with a restricted / blocked backing-line.
Do not use the EXTPX split flow pump with a backing pressure below 5 x 10-4 mbar (5 x 10-2 Pa). Lower backing
pressures will increase the evaporation rate of the lubricating oil reducing the bearing life.
Use suitable vacuum tubing and connectors to connect the NW25 flange of the backing-port to your backing-pump.
If necessary, use flexible pipe or bellows to reduce the transmission of vibration from the backing-pump to the EXTPX
split flow pump.
The EXTPX split flow pump is suitable for use with Edwards Rotary Vane, Scroll or diaphragm backing-pumps. The
system performance may depend upon which pump is used, hence we recommend that you consult Edwards to help
select an appropriate backing-pump for your application.
3.3.5Booster port connection
During operation the booster port must either be connected to the vacuum system or have a blanking flange attached.
Use suitable vacuum tubing and connectors to connect the NW25 flange of the booster port to your vacuum system
in the first instance. The strainer fitted is to prevent foreign object ingress. Refer also to the first Warning in
Section 3.3.2.
3.4Vent options, vent-valve connection and control
To maintain the cleanliness of your vacuum system, we recommend that you vent the pump (or vacuum system)
whenever you switch the pump off.
If you manually vent the pump when it is at full rotational speed and the rate of pressure rise is too high, the
pump life may be reduced. When using the manual vent-valve supplied, we recommend that you either limit the
vent or only open the vent-valve after the EXTPX split flow pump speed has fallen to 50% of full rotational speed.
Do not vent from the backing-line, this may lead to contamination. If you vent into your vacuum system, and
use an oil-sealed rotary vane backing-pump, select a point upstream of the pump, to prevent oil back-streaming
from the backing-line.
Table 6 gives an indication of the appropriate orifice size to be fitted to the vent-valve for given vacuum system
volumes in order that the vent rate is kept within the limits given in Section 2.3.
Venting may be accomplished by one of the following means and by using the procedure below:
z Use a TAV5 or TAV6 solenoid vent-valve accessory (refer to Section 7) in the manual vent-valve position.
z Use a TAV5 or TAV6 solenoid vent-valve connected to a convenient flange on your vacuum system.
z Use an alternative valve, with an appropriate restriction, connected to your vacuum system. For further
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 29
B760-60-880 Issue A
WARNING
WARNING
WARNING
WARNING
1. Turn off the EXTPX split flow pump, but keep the backing-pump on.
2. When speed has fallen to 50%, open the vent-valve.
3. When the EXTPX split flow pump reaches standstill, the vent-valve may be closed.
Table 6 - Vent-restrictor orifice diameter (with atmospheric pressure at the inlet of the vent-valve)
Vacuum system volume (l)Orifice diameter (mm)
< 20< 1.0
< 10< 0.7
< 5< 0.5
< 2< 0.35
3.5Purge gas connection
If you want to supply a purge gas to the pump, fit a vent port adaptor (refer to Section 7) in place of the blank plug
(refer to Figure 2 to 5). Connect your gas supply to the purge p ort . Your purge gas must comply with the limits/
specification given in Section 2.4. To limit the flow rate, use a fl ow controller or a pressure regulator and calibrated
flow restrictor. The PRX10 purge restrictor accessory ( refer to Section 7) is suitable for this purpose. Adjust the PRX10
as described in the instruction manual supplied with it.
Installation
3.6Electrical installation
This product requires a separate power supply (not included). The power supply should be
adequately protected against a hazardous live condition (for example in case of a short circuit).
The customer must ensure that any electrical circuits are protected from dripping water caused
by condensation on cold surfaces.
It is the responsibility of the customer to ensure that the power supply used is correctly rated /
protected.
The customer must ensure appropriate routing of cables and pipe work to avoid slip/ trip hazards.
It is recommended that you fit a separate earth (ground) conductor to earth the EXTPX split flow pump and
accessories: use an uninsulated braid or a separate insulated green/yellow conductor, and use the M5 x 10 screw and
shake proof washer supplied (fitted in the earth hole on the pump) to secure the ea rth conductor to th e EXTPX split
flow pump and accessories.
For external protective earth systems: the installation should be permanent and use the same earth system as the
EXDC drive module; the impedance between the pump-body and earth connection point must be less than 0.1 Ohms.
Refer to the instruction manual supplied with the controller to complete the electrical installation.
The customer must provide an emergency stop circuit to turn off power to the EXDC drive module.
Allow the pump to stop before removing the EXDC drive module.
An EXDC drive module requires connection to a suitably rated power supply. The EXDC drive module is designed to
allow a pumping system to operate in a fully automatic system.
3.6.2TIC controller
The TIC controller can be used to provide the electrical supply to the EXDC (please refer to Section 7.4.3 for details).
The EXDC drive module connects to the back of the TIC via a 15 pin D-type connector.
The TIC controller is designed to allow a pumping system to be configured in a variety of ways, from a basic manuallyoperated system to a fully automatic system with remote control; refer to the TIC instruction manual.
3.7Cooling
3.7.1Introduction
The pump must be cooled either by forced-air or through a water-cooling accessory to prevent pump damage
and to maximize pump performance.
If you are using forced-air cooling to cool the pump you must ensure that there is an adequate supply of cooling-air
to the pump (refer to Section 3.7.2). During operation, if the tempera ture of any surface of the pump is hi gher than
60 °C, the cooling is inadequate and should be increased.
3.7.2Forced-air cooling
Air-cooler accessories are available for the EXTPX split flow pu mp (refer to Section 7). Fit the air-cooler as described
in the instruction manual supplied with it (also refer to Figure 9). If you wish to use an alternative fa n for air-cooling,
ensure that the flow rate is above 80 m
module.
Pump performance may be affected if you do not cool the pump adequately.
3.7.3Water-cooling
3h-1
(47 cfm) and is directed across the pump (base) and the EXDC drive
In the event of coolant failure, the pump must be allowed to cool down (to ambient temperature) before
restarting.
An accessory is available to enable the EXTPX split flow pump to be water cooled (refer to Section 7). Fit the
water-cooler as described in the instruction manual supplied with it. Ensure that the water supply is constant and
within the quality, temperature and flow rate limits detailed in Table 7.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 31
B760-60-880 Issue A
WARNING
Table 7 - Water-cooling block supply requirements
ParameterSpecification
QualityMechanically and optically clean with no deposits or
turbidity
pH Value6.0 to 8.0
Maximum calcium carbonate concentration75 parts per million
Maximum chloride concentration100 parts per million
Minimum oxygen concentration4 parts per million
Minimum water-cooling flo w rate (at 15 °C)15 l h
Water temperature10 to 20 °C
Maximum water pressure5 bar (gauge), 72.5 psig, 5 x 105 Pa (gauge)
Materials exposed to cooling-waterNickel plated brass
-1
3.8Magnetic fields
Installation
If you wish to use the pump in or near magnetic fields please consult Edwards.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 33
4Operation
WARNING
WARNING
WARNING
WARNING
WARNING
Do not operate the EXTPX split flow pump unless it is connected to your vacuum system. If you do,
the pump-rotor can cause injury. The pump-rotor rotates at very high speeds and the rotating
blades might not be visible.
Do not move the pump whilst it is running. The gyroscopic forces generated by this movement can
cause excessive use of the back-up bearing and may result in catastrophic failure of the pump.
When power is restored following a power cut, the pump may restart automatically depending
upon the electrical configuration. The pump must remain connected to the vacuum system to
prevent risk of injury.
B760-60-880 Issue A
Operation
After power to the pump has been switched off, either through emergency or as a requirement,
the rotor will continue to spin at very high speeds. The rotor possesses considerable mechanical
energy until it slows down/ stops.
Do not remove the EXDC cable from the pump until the pump is completely at rest. If the pump is
still rotating when the cable is removed, the pump operator could be exposed to hazardous voltage
and potentially damage the EXDC drive module.
4.1Start-up
Use the procedure below to start up a basic, manually-controlled pumping system with a manual vent-valve and an
EXDC drive module. Refer to the EXDC instruction manual.
1. Ensure any vent-valves are closed (including the manual vent-valve on the pump body).
2. Switch on the power to the air-cooler.
3. Start the backing-pump.
4. When the vacuum system pressure is approximately 10 mbar or less, start the E XTP X spli t f low pump . Fo r fas te r
ramp-up times, this pressure should be well below this figure.
5. The pump will then accelerate to full operating speed. The normal-speed LED on the EXDC drive module will
illuminate once nominal operating speed is reached.
Note:Refer to the controller manual if using the TIC controller.
Note:In an emergency only, open the vent-valve quickly to decelerate the pump-rotor in the shortest possible
time.
Use the procedure below to shut down a basic, manually-controlled pumping system with a manual vent-valve and a
TIC controller.
1. Close the valve in the backing-line connecting the EXTPX split flow pump to the backing-pump.
2. Switch off/ deactivate the start command to the EXTPX split flow pump.
3. When the EXTPX split flow pump rotational speed has fallen to below 50% of full rotational speed, turn the
manual vent-valve anti-clockwise slowly to open it. Refer to Section 3.4 for the venting procedure.
4.3Safety interlocks and control system
The pump protection and safety interlock features are listed below. Refer to the instruction manual supplied with
the controller for a full description of these features.
4.3.1EXDC drive module
The EXDC drive module monitors the temperature of the EXTPX split flow pump and the electrical power con sumption
of the pump. If the EXDC drive module detects excessive power consumption or temperature, the rotational speed
of the pump motor is reduced until the power and temperature return to normal.
4.3.2TIC controller
The TIC controller monitors the pump rotational speed. If the EXDC drive module detects excessive power
consumption or temperature of the EXTPX split flow pump, it will reduce the operational speed of the unit. If this
speed is reduced to below 50% for a user-defined period of time, the TIC controller will automatically disconnect the
power supply. An error diagnostic message will then be displayed on the TIC controller. If the error message
‘Droop timeout’ is displayed on the TIC controller, switch off the backing-pump immediately and vent the EXTPX split
flow pump. Once the pump has stopped, rectify the cause of the failure and restart the pump. If the pump is hot,
allow sufficient time for it to cool before restarting.
4.4Bakeout
Bakeout of envelopes would lead to damage of this product - do not bake.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 35
B760-60-880 Issue A
CAUTION
WARNING
WARNING
WARNING
WARNING
5Maintenance
The EXTPX split flow pump is not to be serviced by the customer. Pumps requiring servicing should
be returned to Edwards or serviced by a qualified Edwards engineer.
Allow the pump-rotor to stop, then disconnect the controller before you remove the pump from
your vacuum system for maintenance or fault finding procedures.
5.1Introduction
The maintenance operations for the EXTPX split flow pump are described in the following sections. The inlet screens
and inlet-flange seals are available as spares (refer to Section 7). Fit the inlet screens as shown in Figure 7.
5.2Bearing maintenance
Maintenance
The bearings will need to be replaced at the recommended service interval. This is typically more than 20,000 hours,
but may be less; this depends on the type of pumping duty on which the pump is used.
When the bearings need replacement, we recommend that you exchange your pump for a factory reconditioned
replacement. Alternatively, you can send your own pump to an Edwards Service Centre to have the bearings replaced.
Lubricants can contain toxic substances from the pumping media. The oil felt cartridge must be
disposed of in accordance with relevant regulations.
When you return the EXTPX split flow pump to an Edwards Service Centre please use the procedure included at the
end of this manual. Please note that the instruction to drain all fluids does not apply to the lubricant in the EXTPX
split flow pump oil-reservoir.
5.3Rotor life
The fatigue life of the EXTPX split flow rotor is typically 40,000 to 50,000 cycles of acceleration fr om rest to full
speed and then back to rest. As a precautionary measure, Edwards recommends that pumps are returned for a
major service (rotor replacement) after 20,000 cycles or ten years, whichever occurs first.
5.4Cleaning the pump
Clean the external surfaces of the EXTPX split flow pump in a well-ventilated location. When you
use cleaning solutions and solvents to clean the pump, observe all precautions specified by the
manufacturer. Avoid inhalation of any particulates which may be present in the pump.
Do not attempt to clean any parts of the EXTPX split flow pump other than external surfaces. Organic solvents
may damage internal pump components. Do not use abrasive materials to clean any part of the pump.
If the inside of the EXTPX split flow pump is contaminated, it may not be possible to achieve the specified ultimate
vacuum performance, or pump-down times may increase. In these circumstances the pump must be returned to an
Edwards Service Centre, where the pump will be dismantled and cleaned. Use the procedure given in the forms at
the end of this manual to return the pump.
You can use any organic solvent to clean the external surfaces of the EXTPX s plit flow pump. Edwards recommends
the use of non-CFC solvents such as isopropanol or ethanol. Use a cleaning solution which is suitable for the
contaminants on the pump surfaces.
For environmental reasons, keep wastage of cleaning solutions and solvents to a minimum.
5.5Fault finding
Refer to Table 8 for the possible causes of faults and for the recommended actions to rectify faults. Table 8 is
applicable to a basic, manually controlled pumping system with an EXDC drive module.
Table 8 - Fault finding
SymptomCheckAction
The impeller does not rotate after
giving a start signal.
‘Droop timeout’ displayed on th e
TIC.
Are the three red phase LEDs on the
EXDC drive module lit?
Is the EXDC correctly connected to
the EXTPX split flow pump?
Is the start signal being given
across the correct pins of the
EXDC logic interface plug?
None of the above.If all the above checks are OK but
Refer to Section 4.3.2.Refer to Section 4.3.2.
If not, check that power is supplied
to the EXDC.
If power is supplied but one or more
of the LEDs are not lit, then the
EXDC drive module may be faulty;
change the EXDC and try to start the
pump.
If the problem persists then the
EXTPX split flow pump may be faulty.
Consult Edwards or your supplier.
If the red LEDs are all lit, check that
the EXDC is properly connected to
the pump.
Refer to Section 3.4 of the EXDC
instruction manual for electrical
connections.
the impeller still does not rotate,
the EXTPX split flow pump may be
faulty; consult Edwards or your
supplier.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 39
B760-60-880 Issue A
WARNING
6Storage and disposal
6.1Storage
Use the following procedure to store the pump.
1. Place protective covers over all ports, the main inlet, side inlet, booster port, exhaust, purge and vent ports.
2. Place the pump in its packing materials. For fastest pump-down when the pump is put back into service, seal the
pump inside a plastic bag together with a suitable desiccant.
3. Store the pump in cool, dry conditions, preferably not exposed to atmospheric air until required for use. When
required, prepare and install the pump as described in Section 3.
4. Keep the pump upright at all times to prevent the drainage of oil from the bearing reservoir.
5. Avoid long-term storage if possible. W hen long-term storage is necessary, the pump should be set up and run for
at least eight hours every six months.
6.2Disposal
Storage and disposal
In the unlikely event of a failure of the pump-rotor, dust can be generated from the carbon fibre
reinforced components. In this event, use appropriate Personal Protective Equipment when
handling and disposing of the pump, and ensure that all pump inlets and outlets are capped off
before disposal.
Take appropriate action to avoid inhalation of any particles which may be present in the pump. Do
not incinerate the pump. The pump contains phenolic and fluorosilicone materials which can
decompose to very dangerous substances when heated to high temperatures.
Be aware that any hazardous gases may remain in the system after it has been switched off.
Dispose of the EXTPX split flow pump and any components and accessories safely in accordance with all local and
national safety and environmental requirements.
Particular care must be taken with any components which have been contaminated with dangerous process
substances.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 41
B760-60-880 Issue A
7Service, spares and accessories
7.1Introduction
Edwards products, spares and accessories are avai lable from Edwards com panies in Belgium, Brazil, C anada, Peoples
Republic of China, France, Germany, Hong Kong, India, Israel, Italy, Japan, Korea, Singapore, Taiwan, United
Kingdom, USA and a worldwide network of distributors. The majority of these employ service engineers who have
undergone comprehensive Edwards training courses.
Order spare parts and accessories from your nearest Edwards company o r dist ri but or. When you order, p lease state
for each part required:
z Model and item number of your equipment.
z Serial number (if any).
z Item number and description of the part.
7.2Service
Edwards products are supported by a worldwide network of Edwards Service Centres. Each Service Cent re offers a
wide range of options including: equipment decontamination; service exchange; repair; rebuild and testing to factory
specifications. Equipment which has been serviced, repaired or rebuilt is returned with a full warranty.
Service, spares and accessories
Your local Service Centre can also provide Edwards engineers to support on-site maintenance, service or repair of
your equipment.
For more information about service options, contact your nearest Service Centre or other Edwards company.
7.3Spares kits
7.3.1Inlet screens
Inlet screens are fitted to your pump as supplied to prevent damage from the entry of debris into the pump. The Item
Number of replacement inlet screens is given in Table 9.
7.3.2Inlet strainer
An inlet strainer is supplied fitted into the booster port. The Item Number for replacement strainers is given in
Table 9.
7.3.3Inlet-flange seal
The EXTPX split flow pump is supplied with inlet seals. The Item Number of replacement seals is given in Table 9.
The accessories available for use with the EXTPX split flow pump are described in the following sections. Figure 9
shows how the accessories are fitted to an EXTPX split flow pump.
7.4.2EXDC drive module
The Item Numbers of the EXDC drive modules are shown in Table 10.
Table 10 - EXDC drive module
Drive Module Item Number
EXDC 160 24 V D396-46-000
EXDC 80 24 V D396-45-000
7.4.3TIC controller
A TIC controller can be used to supp ly p ower t o t he EXDC driv e modu le . Ref er to Table 11. To minimise pump ramp
up time and to maximise the pump performance the 200 W TIC controller is recommended.
Table 11 - TIC controller
ControllerVoltageItem Number
TIC 200 W (Turbo controller)90 - 264 V a.c. 47 to 63 HzD397-12-000
TIC 200 W (Turbo and Instruments controller)90 - 264 V a.c. 47 to 63 HzD397-22-000
7.4.4TAV vent-valve and vent port adaptor
Two solenoid-operated vent-valves are available for system venting. The valves are 24 V d.c., normally-open, and
can be driven automatically from the TIC controller. The solenoid-valve is fitted in place of the manual-valve , or
alternatively can be fitted with an adaptor (supplied with th e valve) and be used with any suitable NW10 flanged port
on your vacuum system. The vent port adaptor allows the vent port or the purge port to be used with any suitable
NW10 fitting. Refer to Table 12.
Table 12 - TAV vent-valve and vent port adaptor
ProductItem NumberOrifice diameterVac system (litres)
TAV5 vent-valveB580-66-0100.5 mm<5
TAV6 vent-valveB580-66-0201.0 mm<20
NW10-1/8 inch BSP male adaptorB580-66-011
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 43
B760-60-880 Issue A
7.4.5VRX vent-restrictor
Use a VRX fixed orifice vent-restrictor to restrict the flow of vent gas into the EXTPX split flow pump. Refer to Table 6
for information on the selection of the correct VRX vent-restrictor. Also refer to Table 13.
A modified DN10NW centering-ring is available to filter the purge gas and restrict its flow rate to the recommended
flow of 25 sccm. The restrictor is suitable for all EXTPX split flow pumps fitted with a purge port. Refer to Table 14.
Table 14 - PRX purge restrictor
Service, spares and accessories
Purge-restrictorFlange sizeItem number
PRX10NW10B580-65-001
7.4.7ACX air-cooler
A choice of ACX air-coolers can be fitted to the EXTPX split flow pump. Please refer to Section 3.7 to check the
suitability of air-cooling in a particular application. Both radial and axial air-coolers may be used simultaneously if
so desired and space allows. TICs can be used to provide power for one fan. Refer to Table 15.