in combination with the following TIM units: C3, E73, SPI, TEL, LAM, HIT, MCM and also
pumps with no TIM unit fitted
to which this declaration relates is in conformity with the following standard(s) or other
normative document(s)
EN1012-2 (1997) Safety Requirements, Vacuum Pumps.
EN61010-1 (2001) Safety Requirements for Electrical Equipment for Measurement,
Control and Laboratory Use.
EN61326 (1998) Electrical Equipment for Measurement, Control and Laboratory
(Industrial location, Use – EMC Requirements
Class A Emissions)
UL61010A-1 Electrical Equipment for Laboratory Use; Part 1 – General
(First edition) Requirements
SEMI S2-0302 Product Safety Assessment
SEMI S8-0701 Ergonomic Assessment
SEMI F47-0200 Voltage Sag Immunity
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 7
A419-00-880 Issue F
CAUTION
WARNING
1Introduction
1.1Scope and definitions
This manual provides installation, operation and maintenance instructions for the Edwards EPX HiVac Series of dry
vacuum pumps (these are abbreviated to ‘EPX pump’ for the remainder of this manual). You must use the EPX pump
as specified in this manual.
Read this manual before you install, operate, and maintain the EPX pump. Important safety information is highlighted
as WARNING and CAUTION instructions; you must obey these instructions. The use of WARNINGS and CAUTIONS is
defined below.
Statements and instructions in the following manual that refer to the EPX variant pump are equally applicable to the
EPX Twin pump unless stated otherwise. Differences between the two pump variants are restricted to power
characteristics, external connections to the exhaust extraction system and external dimensions/appearance.
Warnings are given where failure to observe the instruction could result in injury or death to
people.
Introduction
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and process.
Throughout this manual, page, figure and table numbers are sequential.
The units used throughout this manual conform to the SI international system of units of measurement; US equivalent
units of measurement are also given.
The following IEC warning labels appear on the pump or in the manual:
Edwards take no responsibility for damage or injury caused by improper use of the equipment.
The EPX Dry Vacuum Pump must only be used for the applications depicted in Figure 1. Incorrect
use of the EPX system could invalidate your warranty. Contact your local Edwards representative
if you are unsure whether the EPX system is appropriate for your application.
The EPX pump should not be used to pump explosive mixtures or pyrophoric gases.
The EPX series of pumps are not suitable for pumping Xenon.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 9
A419-00-880 Issue F
The EPX pump system operates at pressures between atmospheric and ultimate vacuum, with no lubricating or
sealing fluid in the pumping chamber. This ensures a clean pumping system without back-migration of oil or fluid into
the system being evacuated.
Between 1 bar and 0.2 mbar, the EPX Twin pump offers a significant pumping performance advantage over the
standard EPX pump. As such, the EPX Twin pump is ideal for use on load lock applications, rapid cycling applications
etc.
The stator of the pump and the enclosed motor are cooled by an integrated water cooling circuit. The EPX pump is
therefore suitable for applications in cleanroom environments where fan cooling is unacceptable. The cooling water
supply and return pipelines are connected to the pump by water connectors (customer specified) (Figure 2, items 4
and 9). Cooling water must be provided commensurate with environmental conditions (humidity and temperature)
such that the dewpoint is not reached. Refer to Table 9 for the water supply specifications.
Refer to Figure 2 and 4. The pump incorporates an EMC supply filter and an inverter drive, which provides and
controls the electrical supply to the pump-motor. LEDs on the front cover identify the status of the EPX pump: (refer
to Figure 4, items 2, 3, 4, and 5 and Table 1). Motor speed depends on the pressure at the pump inlet. When the
pump is started with the inlet pressure at or close to atmospheric pressure, the motor accelerates to a speed which
is limited by the current which can be supplied by the inverter drive. As the pressure at the inlet is reduced, the
motor speed increases, until it eventually reaches its preset maximum speed. If the pressure at the inlet increases,
the motor will slow down again.
The EPX pump is supported by four vibration isolators (Figure 2, item 7).
Introduction
Pump protection sensors automatically shut down the pump if a fault condition arises: refer to Section 1.3.
The EPX pump is available in a number of different variants. The nomenclature is arranged to help identify which
variants are suitable for which applications, and which method of control is required for the pump. The four base
variants are described in more detail below:
1.2.1The EPX L
This pump is for use on clean duty applications pumping inert gas mixtures, such as loadlock, whereby control is
provided by the process tool interface. (Refer to Figure 2).
1.2.2The EPX LE
This pump is for use on clean duty applications such as loadlock, and is augmented with an End User Controller (EUC).
The End User Controller enables local control for stand-alone use as well as the ability to connect to a fab-wide
network for remote control and monitoring. A Pump Display Terminal (PDT) may also be used with the End User
Controller to facilitate local control. (Refer to Figure 5).
1.2.3The EPX N
This is fitted with a gas module that supplies nitrogen purge gas to the shaft seal and pump mechanism areas to
provide dilution of process gases for the light duty applications specified in Figure 1. (Refer to Figure 5, Table 5 and
Section 3.6 for further information).
1.2.4The EPX NE
This system is a light process application pump with network and local control capability through the EUC as described
in Section 1.2.2. (Refer to Figure 5).
The four base variants, the L, LE, N and NE are also available in two capacities, 180 m
with 180 for example EPX180LE) and 500 m3/hr (letter designation prefixed with 500 for example EPX500N).
The EPX pump can also be specified as either 200/208 V or 400 V compatible and a choice of either
1/4 inch BSP, 3/8 inch BSP, 9/16 inch BSP quick connect water fittings or no quick connects.
The EPX pump is fitted with a Tool Interface Module (TIM), which allows ‘plug and play’ connection with all major
process tools. This communication includes control and monitoring of the EPX by the tool for example Run, Stop,
Alarm.
A number of different tool interface options (TIMs) can be specified when the pump is first ordered: SPI, C3, TEL,
E73, MCM or HIT.
Note:The LE and NE versions of the EPX pump can be operated via the end user controller and so do not require
a TIM for operation.
The illustrations throughout this manual show the E73 variant of the TIM.
1.3Pump protection sensors
For EPX N-series pumps, if the pump has been fitted with a C3 or E73 tool interface, there is no
provision for warnings, generated by the pump, to be passed onto the tool. The installer must fit
suitable monitoring equipment to check the nitrogen purge flow, as detailed in Section 3.
For EPX N-series pumps, the nitrogen purge flow switch in the Gas Module is set to 12 slm. The
flow switch provides an indication that a flow in excess of 12 slm is present, but gives no guarantee
that there is sufficient flow to meet the process requirements. The flow switch is not a guaranteed
safety interlock.
When the pump protection sensor operates, only the electrical supply of the pump-motor is
switched off; the EPX is not isolated from the electrical supply.
A thermal snap-switch located within the pump, monitors the temperature of the body of the EPX pump. When the
temperature of the body exceeds a preset limit, the snap-switch operates, generating an alarm and causing the pump
to stop.
When the EPX pump is automatically shut down by a pump protection sensor, the Alarm LED is lit (Figure 4, item 5).
On the EPX N series of pumps, a nitrogen purge flow switch is fitted to the Gas Module to monitor the total purge
flow to the pump. If the purge flow drops below 12 slm, the warning LED on the front panel (or EUC if fitted), will
light (Figure 4, item 4). The pump will continue to run.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 15
A419-00-880 Issue F
Table 3 - EPX L pump labelling information (Refer to Figure 4)
NumberLabel NameDescription
1Pump detailsThis provides specific information about the pump including: pump
type; code number; serial number; pump weight; year of
manufacture; and name and address of the manufacturer. It also
includes electrical supply requirements, and compliance marks.
2PowerThe power LED. See Ta bl e 1 for details.
3RunThe run LED. See Ta bl e 1 for details.
4WarningThe warning LED. See Ta bl e 1 for details.
5AlarmThe alarm LED. See Ta bl e 1 for details.
6Warning - risk of electric
shock
7Warning - risk of electric
shock
8Status LED labelStatus LED label.
9 and 10Lifting pointThe pump must be lifted using the eyebolts on the pump and
11Warning - risk of high
temperature
12Direction of rotationArrow shows the correct direction of rotation of the rotor.
13Warning - danger of injury
from rotating parts
14Water inThe cooling water supply pipeline connects to the pump at this
15Protective earth studThis equipment must have a second protective earth. See
16Pump interfaceTool Interface Module (TIM) fits in this position. The pump may be
17Warning - risk of electric
shock
18Warning - risk of electric
shock
19Warning - thermal shockIf the pump has overheated or the cooling water has failed,
20Water outThe cooling water return pipeline connects to the pump at this
21Product labelProduct name.
Do not remove cover until 4 minutes after disconnection of the
power.
Do not remove cover until 4 minutes after disconnection of the
power.
suitable lifting equipment.
o
Surface temperatures can exceed 65
Turn off and lock-out all power prior to servicing.
location.
Section 3.10.
controlled through this. See Section 3.11.
Do not remove cover until 4 minutes after disconnection of the
power.
Do not remove cover until 4 minutes after disconnection of the
power.
connecting cooling water to a hot pump will cause severe damage to
the pump.
Always allow the pump to cool for at least 20 minutes before
connecting cooling water.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 17
Figure 6 - EPX N series dry pump
A419-00-880 Issue F
Introduction
Table 5 - EPX N (Refer to Figure 6)
NumberDescription
1Pipe fitting - Nitrogen supply to the seal purge.
2Label - Warning; If the pump has overheated or the cooling water has failed, connecting
cooling water to a hot pump will cause severe damage to the pump.
Always allow the pump to cool for at least 20 minutes before connecting the cooling water.
3Label - Warning; do not remove cover until 4 minutes after disconnecting power from the
pump.
4Gas supply fitting - Connect the gas supply to this connection. This compression fitting accepts
1/4 inch (6.35 mm) diameter tube. Ensure that the tube used is suitable for your application.
5Label - Gas Module identifier.
6Pipe fitting - Nitrogen supply to the gas ballast.
The EPX L and N series of pumps cannot be manually operated; they must be controlled and monitored by external
control equipment, which must be connected to the EPX pump through the TIM (Figure 2, item 5).
The EPX E series of pumps can be manually operated using the EUC local display and keypad, or remotely using a PDT,
if fitted; it can also be controlled and monitored over the network, which connects to the EPX pump through the
Network connector (Figure 5, item 2). When the EPX ‘E’ series of pumps is controlled via the TIM, the EUC simply
monitors the status of the pump.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 19
A419-00-880 Issue F
1.8End user controller
The End User Controller (EUC) allows manual control of the EPX pump and also displays the pump status. Refer to
Figure 7 which shows the front panel of the EUC display.
Use the run button (Figure 7, item 1) to start the EPX pump. The run button has an LED which is on when the EPX
pump is running. Use the stop button (Figure 7, item 10) to stop the pump.
The display (Figure 7, item 2) shows two l i n e s o f t e x t ; e a c h l ine is 16 characters long. In normal operation, the Normal
display is shown; the Normal display has two pages, and each has two lines. Each page of the Normal display shows
the status of one or more EPX EUC sensors or internal clocks and counters. As supplied, the first page of Normal
display shows the pump serial number and pump current. It is possible to change the information shown on the Normal
display.
At any time, press one of the four menu buttons (Figure 7, item 7) to select a new menu. Then use the up (Figure 7,
item 5), down (Figure 7, item 3), ENTER (Figure 7, item 6) and CANCEL (Figure 7, item 4) buttons to move through
the menu. The appropriate menu selected LED (Figure 7, item 8) is on when the corresponding menu is in use.
Use the menu (Figure 7, item 7), up (Figure 7, item 5), down (Figure 7, item 3), CANCEL (Figure 7, item 4) and ENTER
(Figure 7, item 6) buttons as described below. Refer to Section 4 for a full definition of the menu structures and the
display formats.
Status: Press this button to select the Status menu. This menu displays the current pump status.
Introduction
Normal: Press this button to select the Normal display.
Control: Press this button to select the Control menu, then take control or release control of the pumping system
(refer to Section 4).
Setup: Press this button to select the Setup menu. In this menu it is possible to display parameters (such as the
pressure units used when pressures are displayed).
Enter (6): Use this button to select a currently displayed menu option or to enter a currently displayed parameter.
Cancel (4): Use this button to cancel the currently displayed menu or option and return to the previous menu or
option.
Up (5)/Down (3): Use these buttons to move up or down menu options or to increase or decrease a displayed
parameter.
The status LEDs (Figure 7, item 9) show the current status of the EPX system.
Alarm: This LED shows when an alarm condition exists.
Warning: This LED shows when a warning condition exists.
Local control: This LED is on when the EUC has control of the EPX system.
The ALARM and WARNING LEDs flash when the corresponding alarm or warning condition first occurs. When
acknowledging the condition, the corresponding LED goes on permanently. For most alarms and warnings, if the
condition clears (that is, the fault which caused the condition is no longer present), the corresponding LED goes off
once the condition has been acknowledged.
Parallel pump interfaceAs per TIM interface supplied (refer to Section 3.11)
Nominal voltage rating24 V
Shut-down thermal snap-switch
Opening temperature70
Closing temperature59 oC, 138 oF
*
Maximum recommended fuse rating; requires a multipole isolator with a minimum contact gap of 3 mm.
The mains disconnect device AIC (Amperes Interrupting Capacity) must be rated to at least 10 000 A.
See clause 13 of SEMI S2 - 0200 and SEMI S8 for further details.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 33
A419-00-880 Issue F
CAUTION
WARNING
WARNING
WARNING
3Installation
3.1Safety
Obey the safety instructions given below and take note of appropriate precautions. If you do not,
you can cause injury to people and damage to equipment. Do not use this pump in a manner that
is not specified in this manual.
Cooling water must be provided commensurate with environmental conditions (humidity and temperature) such
that the dew point is not reached.
z Ensure that the EPX pump is suitable for your application. The EPX L series of pumps are designed for
semiconductor loadlock or transfer pumping applications, or clean general vacuum applications. The EPX N
series of pumps are designed for the light-duty applications detailed in Figure 1. Contact Edwards or your
supplier if you want to use the EPX pump on any other application. Incorrect use of the EPX pump may
invalidate your warranty.
Installation
z Ensure that you comply with all local and national safety requirements during installation.
z Ensure that the installation technician is familiar with the safety procedures which relate to the products
pumped. Wear the appropriate safety-clothing when you come into contact with contaminated components.
Dismantle and clean contaminated foreline components inside a fume-cupboard. The EPX pump should NOT
be dismantled under any circumstances.
z Vent and purge the process system before you start installation work.
z Disconnect the other components in the process system from the electrical supply so that they cannot be
operated accidentally.
Further details are available from the Edwards publication ‘Vacuum pump and Vacuum System Safety’, part no.
P300-20-200.
3.2Unpack and inspect
Heavy objects can cause muscle strain or back injury. Use suitable lifting equipment to move the
pump. Refer to Section 2 for the pump mass.
Ensure that M12 metric eyebolts are fitted to the EPX pump as per Figure 2, item 2 when lifting
the pump. Do not handle the pump using the gas module pipework.
1. Use suitable lifting equipment attached to the lifting bolts (Figure 2, item 2) to move the EPX pump into a
convenient position, then remove any protective packaging and covers.
2. Inspect the pump. If the pump is damaged notify your supplier and the carrier in writing within three days; state
the Item Number of the EPX pump together with your order number and your supplier's invoice number. Retain
all packing materials for inspection. Do not use the pump if it is damaged.
Note:A ‘tip and tell’ indicator is fitted to the EPX pump packaging to indicate any damage or mishandling during
shipment. If the indicator shows that the EPX pump has been tilted or mishandled during shipment, do not
use the pump. Please contact your local Edwards representative for advice.
3. If the EPX pump is not to be used immediately, replace the packing materials. Store the EPX pump in suitable
conditions as described in Section 7.
3.3Securing the EPX pump
Heavy objects can cause muscle strain or back injury. Use suitable lifting equipment to move the
pump. Refer to Section 2 for the pump mass.
For safety reasons you must make sure that any frame you mount the pump on is securely fixed to
the building structure or the assembly complies with clause 7.3 (stability) of EN61010-1. Secure
the EPX pump in its operating location. If you do not and the pump fails during operation,
movement of the pump may damage equipment and injure people.
In operation the surfaces on the top half of the pump can exceed 65°C; in certain fault conditions
these surfaces can exceed 105°C. If the pump is to be installed in a location where the surfaces
of the pump could be touched easily then the pump should be installed with adequate guarding.
1. Use suitable lifting equipment attached to the lifting bolts (Figure 2, item 2) to move the EPX pump into its
required operating position. When installed, the EPX pump must be level: refer to Section 2.1.
2. Fit a suitable M8 bolt, nut and washer through the exposed fixing hole in each of the vibration isolators (4 bolts
in total) (Figure 2, item 7), to secure the EPX pump to the floor, or to a frame; the floor or the frame must be
able to withstand a reaction torque of at least 1000 Nm (738 lbf ft), applied rotationally about the vertical axis
of the pump for at least 10 ms.
Note:The weight of the pump is evenly distributed across each of the vibration isolators. The position of the
centre of gravity is given in Figure 16.
3.4Connect the inlet to your process system
Install the pump in the vacuum system before you connect the pump to the electrical supply. If
you do not, the pump may operate during installation and cause injury to people and damage to
the surrounding equipment.
Do not remove the Inlet screen from the pump. Do not operate the pump with the Inlet exposed.
You must be able to isolate the pump from the atmosphere and from your process system if you
have pumped or produced dangerous substances.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 35
A419-00-880 Issue F
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
WARNING
When you connect the pump to the process system:
The vacuum system and foreline assembly MUST NOT be supported by the EPX Pump. The foreline assembly
should be supported by the vacuum system and connected to the EPX pump inlet by a flexible connection to
reduce vibration and stress in the system pipelines.
Use a flexible connection in the pipeline from the process system to the pump to reduce vibration and stress in
the system pipelines.
z To get the best pumping speed, ensure that the pipeline which connects the process system to the pump is as
short as possible and has an internal diameter not less than the pump inlet.
z Do not allow debris to get into the pump during installation. Ensure that debris (such as weld slag) cannot get
into the pump during operation.
z If necessary, contact Edwards or your supplier for advice on inlet isolation valves or other components
suitable for your application and system design.
The EPX180 and EPX500 pumps are supplied with a clear plastic protective cap on the inlet flange. The cap prevents
debris entering the pump during transit and protects the inlet flange from scratches.
Installation
The plastic cap must be removed prior to installation and operation of the pump.
Connect the inlet flange to a foreline or inlet reducing adapter, using an Edwards centring O-ring and claw clamps
(Refer to Section 2.1 for details of fittings).
A centring O-ring must be used to seal the inlet flange and retain the inlet screen.
3.5Connect the outlet to your exhaust extraction system
Pipe the exhaust to a suitable treatment plant to prevent the discharge of dangerous gases or
vapours to the surrounding atmosphere.
Do not incorporate check-valves or one-way valves in the exhaust pipeline. If you do, the EPX pump will not
operate correctly and may be damaged.
Install an outlet catchpot to prevent the drainage of condensate back into the pump. If you do not, condensate
which drains back into the pump may damage it or cause it to seize.
It is essential that on the EXP Twin pump, both exhaust ports are connected to a suitable exhaust system.
Note:If your exhaust extraction system is unrestricted, and so cannot be sealed for leak test purposes, you must
leak test the system (refer to Section 3.7) before you connect the pump outlet.
Remove the blanking plugs from the outlet(s) (Figure 2, item 8 [there are two outlets on the EPX Twin]), use a
suitable clamp and seals to connect the outlet(s) to your exhaust pipeline. Take note of the following when you
connect the exhaust pipeline:
z If your exhaust pipeline incorporates any shut-off valves, you must be able to prevent operation of the pump
when any of the valves are closed (that is, the pipeline is restricted or blocked). If the EPX (Twin) pump
operates when the pipeline is restricted or blocked, the pump will not operate correctly and may be severely
damaged.
z You should not incorporate a check valve in the exhaust line of the EPX (Twin) pump. If you do, the EPX
(Twin) pump may not operate properly and may become damaged. If an exhaust check valve is unavoidable
then you must ensure that the pump is at atmospheric pressure (for example by use of a foreline purge)
before you start the pump. This applies to all EPX (Twin) pump variants.
z Incorporate flexible bellows in the exhaust pipeline to reduce the transmission of vibration and to prevent
the loading of coupling-joints. If you use flexible bellows, you must ensure that you use bellows which have a
maximum pressure rating which is greater than the highest pressure that can be generated in your system,
and which can withstand the maximum temperatures that can be generated by your process conditions, for
example, braided flexible bellows may be used for this purpose.
z The exhaust pipeline must be a minimum diameter of NW25 throughout.
3.6Nitrogen purge (EPX N series pumps)
The EPX pump should not be used to pump pyrophoric gases or explosive mixtures.
Dilute flammable gases to less than 25% of the LEL (Lower Explosive Limit) before the pump inlet.
The responsibility for ensuring the correct dilution of the pumped gas lies with the operator.
The flow switch is set to 12 slm and therefore provides an indication that a flow in excess of 12 slm
is present, but gives no guarantee that there is sufficient flow to prevent condensation or to
provide sufficient dilution of the process gas to safe levels.
The flow switch is not a guaranteed interlock. To ensure dilution of the process gas to safe levels,
the system installer must fit appropriate interlocked hardware to ensure correct nitrogen purge
flow and monitoring.
The following instructions apply to EPX N series pumps. They are not applicable to EPX L series pumps.
A 1/4 inch compression fitting is provided on the pump, marked ‘N
nitrogen purge inlet connection using 1/4 inch OD tube, (refer to Figure 6, item 4).
Ensure that the nitrogen supply is stable to guarantee that the nitrogen purge flow is maintained. The nitrogen purge
gas should comply with the specifications detailed in Table 10.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 37
A419-00-880 Issue F
CAUTION
CAUTION
CAUTION
CAUTION
WARNING
WARNING
WARNING
3.7Leak test the system
Leak test the system and seal any leaks found to prevent the leakage of dangerous substances out
of the system and leakage of air into the system.
Note:If your exhaust extraction system is unrestricted, and so cannot be sealed for leak test purposes, you must
leak test the system before you connect to the pump outlet.
Leak test the system, then seal any leaks found. Substances which leak from the system may be dangerous to people,
and there may be a danger of explosion if air leaks into the system.
As supplied, the leak rate of the EPX pump is tested to be less than 1 x 10
2.1 x 10
-8
atm ft3 min-1). The required leak rate for your system will depend on your safety and process requirements.
-5
mbar l s-1 (1 x 10
-3
Pa l s-1,
3.8Connect the cooling-water supply
In products supplied with quick-release water connectors, a water expansion valve is installed
between the connector and the pump. This is to prevent over-pressurisation of the water circuit
in the event that the pump is incorrectly operated with water supply disconnected. When using or
maintaining this pump DO NOT REMOVE THE WATER EXPANSION VALVE.
Installation
A release of water under pressure constitutes a significant safety hazard. The water supply should
be provided with an isolator in accordance with SEMI S2-0200 Lockout/Tagout requirements.
Do not operate the pump without connecting the water supply and return lines, as permanent damage may be
caused to the equipment.
Appropriate filtration must be provided to ensure that the water supply quality is in accordance with Table 9.
Cooling water must be provided commensurate with environmental conditions (humidity and temperature) such
that the dew point is not reached.
To prevent damage to the pump in the event of cooling-water supply failure or a blockage in the pump, we
recommend that you incorporate a suitable flow-switch in the cooling-water return pipelines. You can connect
the outputs of the flow-switch to your control equipment to shut down the pump if the cooling-water flow
through the pump gets too low.
1. If the pump has been supplied with quick-release connectors, fit a suitable female quick-release connector to
your cooling water supply line, and a suitable male quick-release connector to your cooling water return line
(refer to Section 2).
2. Refer to Figure 2. Remove the yellow blanking-caps from the cooling-water inlet (Figure 2, item 4) and outlet
(Figure 2, item 9).
3. Fit the male quick-release connector on your cooling-water return pipeline to the cooling-water outlet (Figure 2,
item 9).
4. Fit the female quick-release connector on your cooling-water supply pipeline to the cooling-water inlet
(Figure 2, item 4).
5. Turn on the cooling water supply.
6. Inspect the water hoses, pipelines and connection to make sure that there are no leaks.
7. Turn off the water supply whilst the remainder of the installation procedure is completed.
Take note of the following when you connect the cooling-water supply and return pipelines:
z Route and secure cables, hoses and pipe-work neatly during installation to avoid possible risk of trips.
z Wipe up any water spilt during installation to avoid possible risk of slips.
z Each EPX pump must be connected to an independent water circuit not in series with each other or other
equipment.
z The cooling-water supply should have a lock out/tagout facility in accordance with SEMI S2-0200 clause 17.4.
z We recommend that you incorporate a suitable ball-type flow indicator in your water return pipeline, to
provide a visual indication of cooling water flow through the EPX pump.
z We recommend that you incorporate a suitable filter in the water supply pipeline, if the water supply
contains particulates. (For the cooling-water supply specification refer to Section 2.4).
To conserve resources we recommend that the return water is cooled and re-circulated.
3.9Connect to your emergency stop circuit
Refer to Figure 18. The pump must be connected to an emergency stop facility, which should be located near to the
pump. The operation of the emergency stop function should immediately disconnect power from the pump when the
emergency stop control is operated. Returning the emergency stop control to its normal operating position should
not result in power being re-applied to the pump; a separate start or reset control should be used for this.
The emergency stop control must be compliant with clause 12 of SEMI S2-0200.
Figure 18 - Schematic diagram of emergency stop facility
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 39
3.10Connect the EPX pump to the electrical supply
WARNING
WARNING
WARNING
WARNING
Connect the electrical supply to the EPX pump through a suitable fuse/ isolator rated as specified
in Section 2.3.
Do not operate the EPX pump unless it is correctly earthed (grounded) using the protective earth
stud (Figure 2, item 3).
Ensure that the electrical supply and connectors are rated for the voltage of the pump as marked
on the rating label attached to the mains inlet cover.
There are no user serviceable parts within the EPX pump. Metal covers must not be removed from
the pump; to do so may cause damage to the pump and injury to personnel and would invalidate
the declaration of conformity and the warranty. Qualified Edwards service personnel should allow
4 minutes after the isolation of power before removing any covers.
A419-00-880 Issue F
Installation
Use the following procedure to connect the EPX pump to the electrical supply:
1. Use a suitable earth (ground) cable to connect the M8 protective earth (ground) stud (Figure 2, item 3) on the
EPX pump to a suitable earth (ground) point: refer to Section 2.3 for the cable rating.
2. If an electrical supply plug is not fitted:
z Connect the four core electrical supply cable to earth (green/yellow) and three phases (1, 2, 3 respectively)
by direct connection to a suitable control box with a means of isolation, and by means of a suitably IP rated
four pin connector.
Notes: 1. If you connect the electrical supply to the EPX pump through ELCB relays, they must be suitable for the
protection of equipment with a d.c. component in the fault current, and suitable for short-duration
switch-on surges, and for high leakage currents (for example, type B, according to prEN50178).
2. If you have a plug to connect the EPX pump to your mains disconnect device, you must provide Lockout/
Tagout in conformance with the requirements of SEMI S2-0200 Section 17.
The mains disconnect device should conform with all the following statements:
z The mains disconnect device must be provided by the user and should be in a location satisfying the
requirements of SEMI S8 where it is readily accessible.
z The mains disconnect device should not be located where there is any risk of personnel tripping on cables,
being obstructed or exposed to other hazards.
z The mains disconnect device should be marked as a disconnection device.
z The mains disconnect device must be connected between the source of supply and the main power cable
entering the EPX pump.
z The mains disconnect device must have a lockout/tagout facility of the type specified in Section 17 of SEMI
S2-0200.
z The mains disconnect device must be rated at a minimum of 10,000 AIC.
Tool interface control signals are for control purposes only and should not be relied upon for safety
critical functions.
Do not connect voltages greater than 30 V to the EPX interface control. If you do, the interface control will not
comply with the low voltage safety directive and the equipment may be damaged.
The pump may be connected to your control equipment through the Tool Interface connector (TIM). The TIM is
supplied with a protective plastic cap fitted. Remove this before connecting the mating connector. Several different
tool interfaces are available. The label next to the tool connector identifies which TIM is fitted, refer to Table 12 to
identify the tool connectors and mating tool connector kits available (not supplied with the pump).
Table 12 - Tool connectors and mating tool connector kits
IdentificationPart NumberTool Side ConnectorTool Connector Kit
SPID373-60-310CPC 16/17 SocketD374-20-801
MCMD373-60-320CPC 16/17 SocketD374-22-802
TELD373-60-33025w D Type SocketD374-20-802
E73D373-60-34015w D Type PlugD374-20-803
LAMD373-60-35025w D Type PlugD374-22-801
C3D373-60-3609w D Type SocketD374-21-803
HITD373-60-37037w D Type SocketD374-21-804
Note:Plug/Socket designation refers to the pins of the connector.
3.11.1Inputs
Refer to Table 13 for a definition of the input signals to the pump system.
Table 13 - Tool input signals to the pump system
FunctionSignal TypePinsOperation
Pump On/OffVoltage inputSPI - 1 and 2
MCM - 1 and 2
LAM - 10 and 23
C3 - 2 and 6
Volt-free contact inputMCM - 5 and 6
TEL - 1 and 14
E73 - 1 and 9
HIT - 7 and 26
(or HIT - 1 and 20)
Notes: 1. Volt free contacts sensed at 24 V / 5 mA, these inputs should not be linked together.
2. Voltage inputs accept AC or DC voltage (except SPI pins 15 and 16), between 15 V and 24 V selects the
input as active, below 5 V selects inactive.
3. To ensure correct pump operation, at least 10 seconds must be allowed between successive operations
of the input signals.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 43
A419-00-880 Issue F
<Name>
4End User Controller (EUC) and Pump
Display Terminal (PDT) menus
4.1Introduction
The display and the control buttons used on both the EUC and the PDT are shown in Figure 7.
The menu structure is shown in Table 15. Note that if a particular system component or accessory is not fitted, the
corresponding menu option is shown as ‘NP’ (not present).
Menus used and the display messages shown on the EUC and PDT are described in the menu diagrams in Figure 19 to
28. The following symbols and conventions are used in the menu diagrams:
These are flow lines. Arrows on the lines show the direction of flow through a menu.
End User Controller (EUC) and Pump Display Terminal (PDT) menus
This symbol is used to connect different menus and shows the starting point (or continuation point) of a menu.
This symbol is used for the ENTER and CANCEL buttons and the four menu buttons: Normal, Status, Control and Setup.
This symbol is used for the up (▲) and down (▼) buttons and for the on () and off () buttons.
This symbol is used for the two-line display on the PDT.
This symbol is a submenu box; a submenu is a series of menu steps which are used in a number of different menus or
used in different parts of one menu. Completion of the menu returns to the previous menu.
This symbol shows additional text which is not part of the menu, but which further describes the operation of the
menu.
End User Controller (EUC) and Pump Display Terminal (PDT) menus
4.2General operation
When you first switch on the EPX system, the Normal display is shown: refer to Figure 22. You can then press the On
or Off button, or any of the four menu buttons to exit the current menu and enter the corresponding new menu.
Figure 19 shows this menu control logic.
Note that if a warning or alarm is displayed, the orange or red LED will flash until the warning or alarm is
acknowledged by pressing the <ENTER> button. Once acknowledged the LED will remain continuously lit. If a gas flow
warning is generated by low flow and then the gas flow is restored, the orange warning LED will flash until the warning
is acknowledged and will then go out.
4.3The CANCEL button
You can press the CANCEL button at any time during menu operation. For this reason, we have not shown the use of
the CANCEL button on all of the menu diagrams, but we have shown specific uses where there is no other obvious
way to cancel the current menu option and enter the previous menu option. In general, when you press the CANCEL
button, the current menu option is cancelled and the previous menu option is displayed. Other specific uses of the
CANCEL button are as follows:
z In the Switch On and Switch Off menus (Figure 20 and 21), when you press CANCEL, the menu is exited and
the display reverts to that which was displayed before On or Off were pressed.
z In the Status menu (Figure 23), when you press CANCEL the display shows the first two status parameters
(the defaults are EPX current consumption and power consumption).
z When you enter the password for the setup menu (Figure 25), if you press CANCEL, before you enter the
value, the menu moves back to entry of the previous digit of the password.
4.4Display text and variable text
In the menu diagrams in Figure 19 to 28, text shown without chevron brackets in the two-line display symbol is the
actual text that will be shown on the display. In this text, the 'Δ' symbol is used to show where a digit will be shown;
the value of the digit depends on the sensor data or information you enter into the system.
Text enclosed in chevron brackets (for example, <status>) defines variable text; what is shown on the display
depends on the menu or the EPX system and data entered by the user. The following variable text markers are used
on the menu diagrams:
<status>
Text message giving status of the selected parameter.
<serial number>
This specifies the serial number. The serial number is a number which you can use to identify the EPX system in the
installation.
<parameter>
This is a previously selected parameter or menu option.
<message>
This specifies a warning, alarm or advisory message.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 45
A419-00-880 Issue F
4.5Wrap-around
When you use the up and down buttons to change a digit or character on the display, the digit or character will 'wraparound' between its minimum and maximum values. For example, when you enter a password digit, if the digit is '0'
and you press the down button, the digit will change to '9'; if the digit is '9' and you press the up button, the digit will
change to '0'.
4.6Timeout
After you have entered a menu (other than the Normal menu), if you do not press a button for five minutes, the EUC
or PDT will automatically exit the current menu and enter the Normal menu. This facility (known as timeout) is
available so that if the setup menu is entered and then EPX system is accidentally left unattended, the menu is exited
to prevent unauthorized use of the menu options.
4.7Menu structure
The display and the control buttons are shown in Figure 7.
The menu structure is shown in Table 15. Note that if a particular system component or accessory is not fitted, the
corresponding menu option is shown as 'NP' (not present).
End User Controller (EUC) and Pump Display Terminal (PDT) menus
End User Controller (EUC) and Pump Display Terminal (PDT) menus
4.8Example
Here is an example of how to interpret the menu diagrams. The following procedure describes how to change the
parameters displayed on the normal display.
1. Press the Setup button to enter the Setup menu (Figure 25).
2. Use the up and down buttons to change the first digit of the setup password to the correct value, then press the
ENTER button.
3. Use the up and down buttons to change the second digit of the setup password to the correct value, then press
the ENTER button.
4. Use the up and down buttons to change the third digit of the setup password to the correct value, then press the
ENTER button.
5. If you have entered the correct password, the display will then show 'SETUP MENU' on the top line and the
software version on the bottom line. (Figure 26).
6. Press the down button or the up button twice; the display will then show 'SETUP MENU' on the top line and
Normal display on the bottom line.
7. Press the ENTER button; the display will then show 'SELECT LINE' on the top line and ‘Top Page 1’ on the bottom
line (refer to Figure 28).
8. Press the ENTER button; the display will then show 'SELECT PARAMETER' on the top line and the currently
selected parameter on the bottom line.
9. Press the up or down buttons to change the parameter displayed to the required parameter, then press the
ENTER button. The top line of the Normal Display will now display the parameter that was selected.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 57
5Operation
CAUTION
CAUTION
CAUTION
WARNING
WARNING
WARNING
WARNING
5.1Introduction
Do not operate the pump when the exhaust pipeline is restricted or blocked. If you do, the EPX
pump can generate pressures up to 16 bar (1.6 x 106 Pa) and be damaged.
Inlet and exhaust temperatures can exceed 65°C in extreme operating conditions.
The EPX N series of pumps must be purged for 30 minutes with the nitrogen purge gas flowing
before pumping process gas. This must be done with the pump running to allow it to warm up to
its full operating temperature.
A419-00-880 Issue F
Operation
There are no user serviceable parts within the EPX pump. Metal covers must not be removed from
the pump; to do so may cause damage to the pump and injury to personnel and would invalidate
the declaration of conformity and the warranty. Qualified Edwards service personnel should allow
4 minutes after the isolation of power before removing any covers.
The flow switch is set to 12 slm and therefore provides an indication that a flow in excess of 12 slm is present,
but gives no guarantee that there is sufficient flow to prevent condensation or to provide sufficient dilution of
the process gas to ensure pump reliability.
The flow switch is not a guaranteed interlock. To ensure correct, reliable operation of the pump the system
installer should fit appropriate, interlocked hardware to ensure correct nitrogen purge flow and monitoring.
If the electrical supply to the EPX pump fails for up to one second, the pump will continue to run once the power
is returned.
If the electrical supply to the EPX pump fails for only a few seconds, the pump will continue to operate normally
provided the run signal on the interface is maintained.
The EPX pump should not be used to pump pyrophoric gases or explosive mixtures.
Dilute flammable gases to less than 25% of the LEL (lower explosive limit) before the pump inlet.
The responsibility for ensuring the correct dilution of the pumped gas lies with the operator.
For flammable and toxic gases, the EPX pump must be fitted in an extracted enclosure (not
supplied), and the extract must be monitored. In order for the pump to comply with Semi S2-0200
extracted enclosures are required.
The nitrogen purge flows on the EPX N series of pumps are preset at the factory.
The approximate nitrogen purge flows for a given supply pressure are given in Table 10.
Flammable gases must be diluted to less than 25% of the LEL. Pyrophoric gases and explosive mixtures should not be
pumped using the EPX pump. The installer must ensure that suitable safety mechanisms are in place to ensure that
dilution is carried out to safe levels.
5.3Start-up
Do not operate the pump when the exhaust pipeline is restricted or blocked. If you do, the EPX
pump can generate pressures up to 16 bar (1.6 x 106 Pa) and be damaged.
1. Check the protective earth connection to the pump.
2. Check that the power and control connectors from the pump are connected.
3. Switch on the cooling-water supply and check that there are no leaks. If there are any leaks, switch off the
cooling-water supply, seal the leaks, then switch on the cooling-water supply and check for leaks again. Repeat
this process until the system is leak-tight.
4. Switch on the electrical supply to the EPX pump, and check that the Power LED (Figure 4, item 2) goes on; if the
Power LED does not go on, refer to Section 6.6.
5. Check that the exhaust-extraction system is not restricted, and that any valves in the exhaust-extraction system
are open.
6. Use your control equipment to set the pump run signal to the interface connector (refer to Section 3.11) and
check that the Run LED (Figure 4, item 3) goes on, and that the pump running status output closes. If the Run
LED does not go on, or if the pump running status output remains open, refer to Section 6.6.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 59
A419-00-880 Issue F
CAUTION
CAUTION
WARNING
WARNING
5.4Manual shut-down
Do not remove the inlet connection until the pump has been allowed to stop rotating and the
power has been isolated.
The pump can take up to three minutes to completely stop.
EPX N pumps must be purged for 30 minutes with nitrogen before the run signal is removed.
Use the following procedure to shut down the pump.
Use your control equipment to remove the run signal to the pump (refer to Section 3.11). The Run LED (Figure 4,
item 3) will then go off, and the pump running status output signal will open.
Note:After removing the run signal, the pump should be allowed to come to a stop before the run signal is
re-applied. If the run signal is removed for more than 1 second and then re-applied before the pump has
stopped, the pump will run down to a stop before restarting automatically. This is a function of the control
architecture of the pump.
Operation
If you are removing the pump, follow the instructions given in Section 7.
5.5Status and fault indications
During normal operation, only the Power and Run LEDs (Figure 4, items 2 and 3) should be on, and the pump running,
pump warning and pump alarm status outputs should be closed. If either or both of the other LEDs (Figure 4,
items 4 and 5) go on, or if either or both of the pump warning and pump alarm status output signals are open, refer
to Section 6.6.
5.6Unplanned shutdown and alarms
In the event of an unplanned shutdown the pump should not be restarted unless the cause is
identified and rectified. If this is not the case, seal the inlet and exhaust of the pump and call a
Edwards representative.
The EPX will automatically shutdown when a pump protection sensor operates (refer to Section 1.3), or should the
inverter drive fail. When the EPX automatically shuts down, the Alarm LED (Figure 4, item 5) is illuminated, and the
pump alarm status output signal opens.
If the EPX pump goes into an Alarm state, power to the pump must be completely switched off and then re-applied
in order for the alarm to clear. The pump fault must be identified and rectified before power is re-applied.
If there is an unplanned shutdown, ensure that the cause of the shutdown is identified and rectified before the pump
is restarted. If you are in doubt, please call a Edwards representative.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 61
6Maintenance
WARNING
WARNING
WARNING
WARNING
There are no user serviceable parts within the EPX. There is no requirement to remove the covers
from the pump during normal operation. Removing the covers could cause injury to people or
damage to equipment.
Toxic, flammable and corrosive chemicals may be present within the pump enclosure. Ensure that
the appropriate Personal Protective Equipment (PPE) is worn when carrying out any maintenance
tasks.
Before disconnecting EPX N pumps from the system, purge the pump for 30 minutes, then lockout/
tagout the nitrogen supply.
A419-00-880 Issue F
Maintenance
There are no user serviceable parts within the EPX pump. Metal covers must not be removed from
the pump; to do so may cause damage to the pump and injury to personnel and would invalidate
the declaration of conformity and the warranty. Qualified Edwards service personnel should allow
4 minutes after the isolation of power before removing any covers.
Purge the pump for 1/2 an hour with nitrogen before removing the power.
z There are no user serviceable parts in the EPX pump mechanism, electric motor or electrical controls.
Attempting to remove the pump rotor, separate the motor from the pump or remove electrical covers can
cause injury to people or damage to equipment.
z It is recommended that all maintenance and service operations are carried out by qualified Edwards Service
Personnel, e xcepting:
z Connection and inspection of pipelines and connections to foreline and exhaust. Routine external cleaning.
Connection and disconnection to electrical power. Connection and disconnection of electrical signals.
Obey the safety instructions given below and take note of appropriate precautions. If you do not
you can cause injury to people and damage to equipment.
Do not touch or inhale the thermal breakdown products of fluorinated materials which may be
present if the EPX pump has overheated to 260
are very dangerous. The pump may have overheated if it was misused, if it malfunctioned, or if it
was in a fire. Edwards Material Safety Data Sheets for the fluorinated materials used in the EPX
pump are available on request: contact your supplier or Edwards. MSDS: Mechanical Pump Oil Fomblin 6/6 Series P120-01-015, O-rings - Viton P120-04-015.
In the event of a pump seizure, dust is generated as a result of contact between the rotating and static surfaces.
This dust may contain aluminium sulphate in low concentrations and may be accompanied by a slightly
sulphurous smell.
It is recommended that when dealing with a pump which may have seized you wear gloves, eye protection and
a paper face mask.
z Allow the EPX pump to cool to ambient temperature before you start maintenance work.
z Wipe up any spilt water during maintenance so as to avoid possible risk of slips.
z Isolate the EPX pump and other components in the process system from the electrical supply so that they
cannot be operated accidentally.
z Lockout/Tagout the nitrogen supply and water supply.
z Do not reuse O-rings.
z Protect sealing-faces from damage.
º
C (500 ºF) and above. These breakdown products
z If you need to remove the pump, follow the instructions given in Section 7.1.
z If you disconnect the inlet from the process system, leak-test the system after maintenance work is
complete and seal any leaks found to prevent leakage of dangerous substances out of the system and leakage
of air into the system: refer to Section 3.7.
z The inverter drive contains capacitors which store electrical energy after the pump has been shut down.
Wait at least four minutes after the pump has been shut down before you start any work on the electrical
system of the EPX pump.
z The pump covers should not be removed as the pump contains sensitive electronic components. None of the
components in the pump are user serviceable.
6.2Maintenance plan
The plan shown in Table 16 details the maintenance operations we recommend to maintain the EPX pump in normal
operation. Instructions for each operation are given in the section shown.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 63
A419-00-880 Issue F
CAUTION
CAUTION
6.3Inspect the pipelines and connections
1. Inspect all cooling-water pipelines and connections; check that they are not corroded or damaged. Replace any
of the pipelines and connections that are corroded or damaged. Check that all cooling-water connections are
secure. Tighten any connections that are loose.
2. Inspect all electrical cables; check that they are not damaged and have not overheated. Replace any cables that
are damaged or have overheated. Check that all electrical connections are secure. Tighten any connections that
are loose.
3. Inspect all process and exhaust pipelines; check that they are not corroded or damaged. Replace any pipelines
that are corroded or damaged. Check that all process and exhaust connections are secure. Tighten any
connections that are loose.
6.4Cleaning the pump
Do not use cleaning materials based on strong alkalis, aggressive or chlorinated solvents.
Maintenance
Do not use cleaning materials containing abrasives.
Inspect the pump annually (or as part of any scheduled preventative maintenance schedule) and, if necessary, wipe
the outside clean with a soft lint free cloth and a proprietary cleaning material based or demineralised water or
isopropanol.
The service interval for the EPX series of dry pumps is shown in Table 16. Major service is outside the scope of this
manual and must be carried out by qualified Edwards Service personnel: contact your supplier or Edwards to arrange
a major service.
For removal of the pump for maintenance refer to Section 7.
Table 16 - Maintenance plan
OperationFrequency
Inspect the pipelines and connections Annually or as part of a preventative maintenance
schedule
Cleaning the pumpAnnually or as part of a preventative maintenance
schedule
Service the EPX L/LE pump
Service the EPX N/NE pump
Service the EPX TWIN pump (all
variants)
*
Main factors that will affect the service intervals of the EPX pump are:
z The ambient temperature in which the pump runs - Higher ambient temperatures will result in shorter
service intervals (refer to Ta bl e 6 for the ambient operating temperature range)
z The temperature and flow rate of the cooling water delivered to the pump - higher water temperatures and
a lower flow rates will result in shorter service intervals (refer to Ta b le 9 for cooling water supply details)
z Rapidity of cycling - rapid cycling applications will result in shorter service intervals
z Application - processes that require a Nitrogen purge (EPX N-series pumps) will typically result in shorter
service intervals
Pump service requirements are largely determined by
the pump’s operating environment and application.
Service intervals range from 2 to 5 years
contact your local Edwards service representative for
further advice on a suitable maintenance schedule.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 65
A419-00-880 Issue F
6.6Fault finding
Refer to Table 17 and 18 for fault finding.
Table 17 - Fault finding
SymptomCheckAction
The Power LED does not illuminate
when the electricity supply is
switched on
The Run LED does not illuminate, or
the pump running status output
signal is open, when the start signal
is set
The pump alarm status output signal
is open and the Alarm LED is off
The pump alarm status output signal
is open and the Alarm LED is
illuminated
A whistling sound is heard as the
pump decelerates
The pump warning status output
signal is open and the warning LED is
illuminated
OtherContact your nearest Edwards
Is the electrical supply correctly
connected?
Is the EPX pump incorrectly connected
to your control equipment?
Is the pump incorrectly connected to
your control equipment?
Has the cooling water supply failed?Allow the EPX pump to cool down
Has the run signal been removed and
then re-applied before the pump has
stopped?
Is nitrogen gas flowing?Check nitrogen purge gas is flowing
Ensure that the electrical supply is
correctly connected to the EPX
pump; refer to Section 3.9 and 3.10.
Ensure that the connections
between your control equipment
and the interface connector are
correct: refer to Section 3.11
Ensure that the connections
between your control equipment
and the interface connector are
correct to Section 3.11.
for at least 20 minutes. Ensure that
the cooling water supply is correctly
connected to the EPX pump, and is
switched on and meets the flow and
pressure requirements of
Section 2.4. Restart the pump.
Removal and re-application of the
run signal may cause a low volume
noise, but it is not harmful to the
pump. It is recommended that the
pump be allowed to come to a halt
before the run signal is re-applied.
into the gas module. If gas is flowing
and the warning does not clear,
contact your nearest Edwards
service centre.
EUC controller fault.Cycle power off and on. If fault still present,
The emergency trip circuit has triggered,
and the inverter is disabled.
A power loss of more than half a second
has occurred. This warning is shown as
the power is removed.
General Input/Output fault on EUC.Cycle the power off and on. If fault still
Inverter has indicated over-current.Monitor the pump. If the problem persists,
Inverter has received a Pump Thermal
Overload input.
Nitrogen flow low; need to check gas
supply.
Inverter running signal has not been
received for more than 20 seconds whilst
the pump should be running.
Usually caused by a dip in the 3-phase
supply.
Inverter has indicated a major fault/trip
condition across the serial link.
Inverter has not indicated ‘Running’
across the serial link when commanded
‘On’.
This will occur after a thermal trip if the
pump has not been allowed to cool for
long enough.
Inverter has indicated a minor fault/trip
condition across the serial link.
Lost communication with inverter.No action is required unless you need to stop
contact Edwards representative
Reset the emergency stop circuit.
Allow the pump to stop completely. Restart
the pump.
Restore power. Restart the pump
present, contact Edwards representative
stop the pump, remove power and contact
Edwards representative.
Remove power to the pump. Check that
cooling water flow rate is at least 2 l/min
and other services are correctly supplied.
Allow the pump to cool down completely.
Restart the pump. If the problem persists,
contact Edwards representative.
Check the nitrogen flow rate to the pump.
Ensure that supply exceeds 17 slm. If problem
persists, contact Edwards representative.
Remove power. Check that the power supply
is at full strength. Apply power and restart
the pump. If the problem persists, contact
Edwards representative.
Remove power to the pump. Check that
cooling water flow rate is at least 2 l/min
and other services are correctly supplied.
Allow the pump to cool down completely.
Restart the pump. If the problem persists,
contact Edwards representative.
Remove power to the pump. Check that
cooling water flow rate is at least 2 l/min
and other services are correctly supplied.
Check exhaust line is not blocked and pump
inlet is clear.
Allow the pump to cool down completely.
Restart the pump. If the problem persists,
contact Edwards representative.
Remove power to the pump. Check that
cooling water flow rate is at least 2 l/min
and other services are correctly supplied.
Allow the pump to cool down completely.
Restart the pump. If the problem persists,
contact Edwards representative.
the pump, in which case remove the power
to the pump (for example by operating the
EMS circuit).
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 67
A419-00-880 Issue F
CAUTION
WARNING
WARNING
7Storage and disposal
Lockout/tagout process delivery and the electrical and nitrogen purge supplies to the pump before
the pump is disconnected from the system.
Inlet and exhaust temperatures can exceed 65°C in a fault condition.
In the event of a pump seizure, dust is generated as a result of contact between the rotating and static surfaces.
This dust may contain aluminium sulphate in low concentrations and may be accompanied by a slightly
sulphurous smell.
It is recommended that when dealing with a pump which may have seized you wear gloves, eye protection and
a paper face mask.
Storage and disposal
7.1Storage
When the pump is disconnected from the vacuum system, avoid contact with, or inhalation of any gases or
particulates that may still be present in the pump.
Store the pump as follows:
1. Ensure that the EPX has been shut down as described in Section 5, then disconnect the pump from the electrical
supply.
2. Allow the pump to cool for approximately 30 minutes before disconnecting the water to the pump. Drain the
water from the cooling circuit. Place a suitable container under the water outlet connector connection
(Figure 2, item 9) and connect a suitable connector along with a short length of hose for a drain. Fit an airline
(maximum pressure 100 psi) to a second spare connector and connect it to the pump water inlet connector
connection (Figure 2, item 4). Blow the water out of the cooling circuit then remove the drain fittings.
3. Disconnect the pump inlet (Figure 2, item 1) and pump exhaust (Figure 2, item 8) from the system.
4. Fit blanking caps to the pump inlet (Figure 2, item 1) and pump exhaust (Figure 2, item 8).
5. Store the pump in clean dry conditions until required.
6. When required for use, prepare and install the pump as described in Section 3 of this manual.
Do not dispose of the EPX pump. Return the pump to Edwards (UK) in suitable packaging, following the return of
Edwards equipment forms at the rear of this manual.
The majority of the EPX packaging is made from recycled and/or recyclable materials. Contact Edwards for further
details.
Take particular care with the following:
z Fluoroelastomers which may have decomposed as the result of being subjected to high temperatures.
z Components which have been contaminated with dangerous process substances. Contaminated components
must be disposed of in accordance with local legislative requirements. Any remaining materials mentioned in
Section 2.6, with the exception of O-rings, may be recycled.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 69
A419-00-880 Issue F
8Service, spares and accessories
8.1Introduction
Edwards products and spares are available from Edwards companies in Belgium, Brazil, Canada, China, France,
Germany, Hong Kong, India, Italy, Israel, Japan, Korea, Singapore, Taiwan, United Kingdom, USA and a worldwide
network of distributors. The majority of these employ service engineers who have undergone comprehensive Edwards
training courses.
Order spare parts from your nearest Edwards company or distributor. When you order, please state for each part
required:
z Model and item number of your equipment.
z Serial number (if any).
z Item number and description of the part.
8.2Service
Edwards products are supported by a worldwide network of Edwards Service Centres. Each Service Centre offers a
wide range of options including: equipment decontamination; service exchange; repair; rebuild and testing to factory
specifications. Equipment which has been serviced, repaired or rebuilt is returned with a full warranty.
Service, spares and accessories
Your local Service Centre can also provide Edwards engineers to support on-site maintenance, service or repair of
your equipment.
For more information about service options, contact your nearest Service Centre or other Edwards company.
Table 19 - Accessory kits
Kit TypeItem NumberUse
IPX-EPX foot adaptorA41900186Allows EPX pumps to be retrofitted to a mounting
plate designed for IPX pumps.
Protection box accessory:Provides supply protection and configurable EMO/
200/208 V, 50/60 Hz
400 V, 50/60 Hz
Pump display terminal (PDT)D37272000Allows remote operation via the End User Controller.