Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 7
A344-02-880 Issue J
1Introduction
1.1Scope and definitions
This manual provides installation, operation and maintenance instructions for the Edwards E1M40, E1M80, E2M40,
E2M80 Rotary Vacuum Pumps. You must use your pump as specified in this manual.
Read this manual before you install and operate your pump. Important safety information is highlighted as WARNING
and CAUTION instructions; you must obey these instructions. The use of WARNINGS and CAUTIONS is defined below.
WARNING
Warnings are given where failure to observe the instruction could result in injury or death to
people.
CAUTION
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and process.
Introduction
The units used throughout this manual conform to the SI international system of units of measurement.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 9
A344-02-880 Issue J
1.2Description
Note:The following section refers to Figure 1 unless stated otherwise.
The E1M40, E1M80, E2M40 and E2M80 pumps are single or two-stage oil-sealed, high-vacuum pumps designed for
reliable, long-term operation in both laboratory and industrial environments. A single-phase motor or a four-pole
three-phase motor provides direct-drive through a flexible coupling. The pumps are free-standing mounted on steel
runners.
The E1M (single-stage) pumps have a high-vacuum rotor and stator assembly with integral sliding-vane oil-pump. The
E2M (two-stage) pumps have an additional low-vacuum rotor and stator assembly.
Lubrication is provided by a sliding vane oil pump. Oil is drawn into the pump through a wire mesh strainer. The oil
is pumped to a spring-loaded distributor valve. The distributor valve directs a lightly-pressurised supply of oil to the
main vacuum-pump and by-passes the excess back to the oil reservoir. Some of the excess oil is re-directed through
a large area, fine-pore filter and some through a relief-valve. When you switch off an E2M40 or E2M80 pump with the
gas ballast control closed, the spring loaded distributor valve provides oil and air suckback protection. The distributor
valve provides only oil suckback protection when you switch off an E1M40 or E1M80 pump. To obtain air suckback
protection when you switch off an E1M40 or E1M80 pump, you must fit a solenoid operated gas-ballast control valve:
refer to the information in Section 1.3.
You can inspect the level and condition of oil in the oil box through an oil-level sight-glass (7). An oil filler-plug (6)
is fitted at the top of the oil box. An oil drain-tap (8) is fitted at the bottom of the oil box.
Introduction
The inlet-port flange (4) is compatible with ISO40 or NW40 fittings. The outlet-port (5) has an NW25 flange.
The gas-ballast control (11) allows you to control the introduction of gas-ballast when pumping high vapour loads.
Refer to Section 1.3 for more information about gas-ballast.
Refer to Section 7 for details about vibration isolators and other recommended accessories.
1.3Gas-ballast
To pump high vapour loads, gas-ballast is delivered into the pump to prevent condensation of the vapour carried by
the pumped gases. This system reduces oil contamination and pump corrosion caused by condensed vapour from the
pumped gases.
You can introduce air or an inert gas into the low vacuum stage of the pump through the gas-ballast inlet (Figure 9,
item 3). A filter/silencer is fitted in the gas-ballast system, to prevent the entry of dust into the pump and to improve
silencing. You can control the gas-ballast either manually or remotely.
Note that the E1M40 and E1M80 pumps have a permanent air bleed through the gas-ballast inlet.
For manual control, use the gas-ballast control (Figure 9, item 4). The pumps are supplied with an open gas-ballast
inlet (Figure 9, item 3). If you leave this inlet open to the atmosphere, then:
With the gas-ballast control (Figure 9, item 4) open, when you switch the pump off, the pressure inside the
pump will rise to atmospheric pressure
With the gas-ballast control closed, when you switch the pump off:
E1M40 and E1M80: the pressure inside the pump will slowly rise to atmospheric pressure. (To maintain the
vacuum inside the pump, fit a solenoid operated gas-ballast control valve.)
E2M40 and E2M80: the vacuum will be maintained inside the pump.
For remote control, fit a solenoid-operated gas-ballast control valve (available as an accessory from Edwards, refer
to Section 7) to the gas-ballast inlet and open the gas-ballast control. Connect the gas-ballast valve to your control
system so that the valve is closed when the pump is switched off and if the electrical supply to the pump is
interrupted. Under these circumstances, when the pump is switched off, the vacuum will be maintained inside the
pump.
For more information about the use of gas-ballast, refer to Sections 3.10 and 4.1.
DimensionsSee Figure 2 (E1M40 and E2M40 pumps) and Figure 3 (E1M80 and
E2M80 pumps)
Degree of protection (IEC 34-5:1981)IP55
Pump inlet-portISO40 or NW40
Pump outlet-port25 mm flange, suitable for NW25 fittings
E1M40E2M40E1M80E2M80
Maximum mass (kg)70.57295105
Noise level at 1 metre (dB(A))65657070
2.4Electrical data: single-phase motor
When you start a cold pump, the motor draws the start-up current shown in Table 1 for less than one second. To
prevent unnecessary fuse failure during start-up use a slow-blow fuse. Within five minutes, as the oil in the pump
warms up, the start-up current reduces to the full-load current specified in Table 1.
Tab le 1 - E le ctr ic al d ata ( si ng le- ph as e mo to r)
Pump
E1M40
E2M40
Nominal
supply
(V)
240501.16.840254
Frequency
(Hz)
Power
(kW)
Full- load
current
(A)
Start-up
current
(A)
Recom-
mended
fuse rating
(A)
Electrical
Supply
Connection
Figure
2.5Electrical data: three-phase motors
Refer to the data in Table 2. You can configure the dual voltage motors to operate with either the high range or low
range electrical supply: refer to the diagram specified in Table 2. Dual voltage motors are supplied preset to the
highest of the selectable voltages.
When you start a cold pump, the motor draws the start-up current listed in Table 2 for less than one second. Within
five minutes, as the oil in the pump warms up, the current drawn slowly reduces to the full-load current specified in
Table 2.
When you restart a hot pump, the motor draws the start-up current specified in Table 2 for up to 0.5 seconds. The
current drawn then immediately falls to the full-load current value.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 17
A344-02-880 Issue J
WARNING
3Installation
3.1Safety
You must ensure that the pump is suitable for your application. If you have any doubt about the suitability of the
pump for your application, refer to the Edwards guidelines on vacuum pump and vacuum system safety. (See
Associated Publications at the end of the contents list).
Obey the safety instructions given below and take note of appropriate precautions. If you do not,
you may cause injury to people and damage to equipment.
Obey the safety instructions listed below when you install the pump, especially when you connect the pump into an
existing system. Details of specific safety precautions are given at the appropriate point in the instructions.
The installation of your pump must be performed by a suitably trained and supervised technician.
Wear the appropriate safety-clothing when you come into contact with contaminated components.
Vent and pu rge your vac uum syst em before you start installation work.
Installation
Ensure that the installation technician is familiar with the safety procedures which relate to the pump-oil
and the products handled by the pumping system. Take suitable precautions to avoid the inhalation of oil
mist and excessive skin contact with pump-oil, as prolonged exposure can be harmful.
Disconnect the other components in the pumping system from the electrical supply so that they cannot be
operated accidentally.
3.2System design considerations
Consider the following points when you design your pumping system:
Use a suitable valve to isolate the pump from your vacuum system if you need to allow the pump to warm up
before you pump condensable vapours or if you need to maintain vacuum when the pump is switched off.
Avoid hig h level s o f heat inp ut to the pump from the process gases, otherwise the pump may overheat and
seize.
If you use the pump in a high ambient temperature and have a high gas throughput, the temperature of the
pump-body may exceed 70°C. You must fit suitable guards to prevent contact with hot surfaces.
Make sure that the exhaust pipeline cannot become blocked. If you have an exhaust-isolation valve, make
sure that you cannot operate the pump with the valve closed.
Provide for a purge of inert gas when you shut down the pumping system, to dilute dangerous gases to safe
concentrations. A suitable solenoid operated gas-ballast control valve for introduction of purge-gas into the
pump is available as an accessory (see Section 7).
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 19
A344-02-880 Issue J
WARNING
WARNING
3.4Locate the pump
Use suitable lifting equipment to move the pump. The mass of the pump is between 70.5 kg and
105 kg.
Attach your mechanical lifting equipment to the lifting eyes on the pump.
Provide a firm, level platform for the pump. Locate the pump so that the oil-level sight-glass is visible and the oil
filler-plug, oil drain-tap, disposable oil-filter and gas-ballast control are accessible.
If your pump will be located inside an enclosure, make sure that there is adequate ventilation at both ends of the
pump, so that the ambient temperature around the pump does not exceed 40°C. There must be a minimum space of
25 mm between the pump and the enclosure walls.
3.5Fill the pump with oil
3.5.1Recommended pump oils
Installation
If you use a hyrdocarbon oil in this pump, you must not use the pump to process oxygen in
concentrations greater than 25% in volume. If you do, there is a risk of fire or explosion in the
oil-box of the pump.
When the ambient temperature is 12°C or higher, we recommend that you use Edwards Ultragrade 70 oil. This tested
and proven oil will give you the best performance, maintenance intervals and pump life. Otherwise, use another oil
with the specification VG ISO 68.
If you pump oxygen or other dangerous gases and vapours, you must use a chemically inert and stable oil (such as
perfluoropolyether). For information on pumping dangerous gases and vapours, refer to the Edwards guidelines on
vacuum pump and vacuum system safety (see Associated Publications at the end of the contents list).
Edwards and the Edwards logo are trademarks of Edwards Limited.
Installation
3.5.2Filling procedure
Fill the pump with oil as described below. Refer to Figure 1 for the item numbers in brackets.
1. Remove the oil filler-plug (6)
2. Pour oil into the pump until the oil-level just reaches the MAX mark on the bezel at the top of the sight-glass (7).
If the oil-level goes above the MAX mark, open the oil drain-tap (8) and drain the excess oil from the pump.
When the oil-level falls to the MAX mark close the oil drain-tap (8).
3. After a few minutes, recheck the oil-level. If the oil-level is now below the MAX mark, pour more oil into the
pump.
4. Refit the oil filler-plug (6). Tighten the plug firmly by hand. Do not over-tighten.
3.6Electrical installation: single-phase motor
Note:The pump will restart automatically when the electrical supply is restored after an interruption. If you do
not want the pump to restart automatically, use electrical control equipment which must be reset
manually.
1. Remove the motor terminal-box cover (Figure 1, item 10) and remove the 20 mm diameter plugs from the
cable-entry hole that you will use for the electrical supply cable. Choose the most suitable hole for your
application.
2. Fit a suitable cable-gland and nut to the entry hole. After the supply cable is fitted, the cable-gland must be a
protective seal to the standard of IP44 in IEC 529 or better.
3. Pass the motor electrical supply cable through the cable-gland.
4. Connect the cables to the terminals as shown in Figure 4.
Ensure that the electrical installation of your pump-motor conforms with your local and national
safety requirements. It must be connected to a suitably fused and protected electrical supply and
a suitable earth point.
L
N
U1
U2
AA/5004/A
Page 21
A344-02-880 Issue J
3.7Electrical installation: three-phase motors
3.7.1Connect the pump to your electrical supply
WARNING
Ensure that the electrical installation of your pump-motor conforms with your local and national
safety requirements. It must be connected to a suitably fused and protected electrical supply and
a suitable earth point.
CAUTION
If your pump-motor can be used with more than one voltage range, you must ensure that the motor is configured
for your electrical supply voltage. If you do not, you may damage the motor.
Note:The pump will restart automatically when the electrical supply is restored after an interruption. If you do
not want the pump to restart automatically, use electrical control equipment which must be reset
manually.
Figure 5 - Electrical supply connection, three-phase motors, 220-240 V 50 Hz, 208-230 V 60 Hz, or 208 V 50 Hz
Edwards and the Edwards logo are trademarks of Edwards Limited.
Installation
Figure 6 - Electrical supply connection, three-phase motors, 380-415 V 50 Hz, or 460 V 60 Hz
We recommend that you connect the electrical supply to the motor through a starter or circuit breaker which has
thermal over-current protection which can be adjusted to suit the full-load current ratings shown in Table 2. The
fuse ratings in Table 2 are provided for guidance only. The supplier of your thermal over-current protection device
may specify different values to ensure correct operation of the over-current protection device. Ensure that the fuse
you use is suitable for the starting currents given in Table 2.
1. Remove the cover from the motor terminal box.
2. Check your electrical supply voltage and frequency. If necessary, configure the motor to operate with your
electrical supply (see Figures 5 and 6).
3. Remove the 20 mm diameter plugs from the cable-entry hole that you will use for the electrical supply cable.
Choose the most suitable hole for your application.
4. Fit a suitable cable-gland and nut to the entry hole. After the supply cable is fitted, the cable-gland must be a
protective seal to the standard of IP44 in IEC 529 or better.
5. Pass the motor electrical supply cable through the cable-gland.
6. Connect the cables o the terminals as shown in Figures 5 and 6.
L1
L2
L3
3
U1
W2
U2
V2
V1
W1
W2
AA/5006/A
Page 23
A344-02-880 Issue J
3.7.2Check the direction of rotation
CAUTION
Ensure that the pump-motor rotates in the correct direction. If it does not, the pump and your vacuum system
can become pressurised.
1. Watch the motor cooling-fan through the motor fan-cover.
2. Switch-on the electrical supply to the motor for a few seconds and switch off.
3. Check that the motor cooling-fan rotates in the direction shown by the arrow on the motor mounting-plate. If
the direction of rotation is incorrect:
Isolate the pump from the electrical supply
Remove the terminal-box cover and swap wires L1 and L3 (see Figures 5 and 6).
Refit the cover to the terminal-box
Connect the pump to the electrical supply
Check the direction of rotation again.
Installation
3.8Connect the pump inlet to your system
3.8.1General information
Take note of the following information when you connect the pump to your vacuum system Refer to Section 7 for
details of the accessories mentioned below.
For optimum pumping speeds, ensure that the pipeline connected to the inlet-port is as short as possible and
has an internal diameter not less than the inlet-port diameter.
Support the vacuum pipelines to prevent loading of the coupling-joints.
If necessary, incorporate flexible bellows in your system pipelines to reduce the transmission of vibration and
to prevent loading of coupling-joints. If you use flexible bellows, you must ensure that you use bellows which
have a maximum pressure rating which is greater than the highest pressure that can be generated in your
system. You must use flexible bellows if your pump is mounted on vibration isolators. We recommend that
you use Edwards flexible bellows.
Use a suitable valve to isolate the pump from your vacuum system if you need to pump condensable vapours
or maintain vacuum when the pump is switched off.
Use a suitable inlet catchpot if you pump condensable vapours or if you use the pump for very dusty
applications.
Ensure that sealing surfaces are clean and scratch-free.
From the fitting pack, use the two ISO40 Co-seal halves, ISO40/NW40 seal, bolts and washers. Connect to your ISO40
fittings as shown in Figure 7.
3.8.3Connect to NW40 fittings
From the fitting pack, use the NW40 Co-seal half, ISO40/NW40 seal, the 'C clamp and the bolts and washers. Connect
to your NW40 fittings as shown in Figure 8.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 25
A344-02-880 Issue J
WARNING
3.9Connect the pump outlet to your system
Connect the pump outlet to a suitable treatment plant to prevent the discharge of dangerous gases
and vapours to the surrounding atmosphere. Use a catchpot to prevent the drainage of
contaminated condensate back into the pump.
Connect the pump outlet-port to your outlet accessories or your exhaust treatment plant using the NW25 fittings
(supplied).
Take note of the following information before you connect to the pump outlet. Refer to Section 7 for details of the
accessories mentioned below.
Installation
The exhaust system must be configured so that the maximum pressure at the pump outlet does not exceed
0.5 bar gauge (1.5 bar absolute, 1.5 x 10
In the following circumstances, we recommend that you fit an oil mist filter to the pump outlet:
if you use the pump with the gas-ballast control open
if you operate the pump with an inlet pressure greater than 10 mbar for extended periods
or
if you frequently pump down from atmospheric pressure.
The mist filter will trap the oil exhausted from the pump: you can re-use the oil if it is not contaminated.
5
Pa) at full pump throughput.
3.10Gas-ballast inlet connection
As shown in Figure 9 (item 3), the pump has two gas-ballast inlets. We supply the pump with a blanking plug fitted
to one inlet: the other inlet is open. You can use either of the inlets, but you must fit the blanking plug to the inlet
you do not use.
You can leave the gas-ballast inlet open to the atmosphere. Alternatively, you can fit a gas-ballast control valve,
(available as an accessory, refer to Section 7), for remote control of the gas-ballast supply. In either case, adjust the
gas-ballast control (Figure 9, item 4), to regulate the flow rate of the gas-ballast supply.
For more information about the use of gas-ballast, refer to Sections 1.3 and 4.1.
3.11Leak-test the system
Leak-test the system and seal any leaks found after you have installed the pump, to prevent leakage of substances
out of the system and leakage of air into the system.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 27
A344-02-880 Issue J
WARNING
WARNING
4Operation
We do not recommend that you use the E1M40, E2M40, E1M80 and E2M80 pumps to pump
hazardous substances.
4.1Gas-ballast control
Use the gas-ballast control (Figure 1, item 11) to change the amount of air (or inert gas) introduced into the
low-vacuum stage of the pump. Use of the gas-ballast will prevent the condensation of vapours in the pump. The
condensed vapours would contaminate the oil.
Turn the gas-ballast control fully clockwise:
to achieve ultimate vacuum
to pump dry gases.
Turn the gas-ballast control anti-clockwise to open. Use the gas-ballast control fully open:
Operation
to pump high concentrations of condensable vapour
to decontaminate the oil.
When you operate the pump with the gas-ballast control open, there is an increased rate of oil loss from the pump.
4.2Start-up procedure
Do not block the pump outlet or allow the outlet pressure to rise above 1.5 bar absolute. If you do,
the oil box may fracture: this may cause injury to people.
If the oil is contaminated, or if the pump temperature is below 13°C, or if the supply voltage is more than 10% below
the lowest voltage specified for the motor, the pump may operate at reduced speed for a few minutes.
1. Switch on the electrical supply to the pump.
2. Check that the oil-level in the sight-glass drops slightly (3 to 5 mm) after start-up. This shows that the pump has
primed with oil.
3. If the pump fails to prime, operate the pump with the inlet open to atmosphere for approximately 30 seconds.
Then isolate the inlet and check that the oil-level drops 3-5 mm.
4. If you want to achieve ultimate vacuum, to pump condensable vapours or to decontaminate the pump oil, refer
to the procedures in Sections 4.3, 4.4 and 4.5 respectively. Otherwise, open the vacuum system isolation-valve.
If the pump does not achieve the performance specified in Section 2, make sure that this is not due to your system
design before you contact your supplier or Edwards for advice. In particular, the vapour pressure of all materials used
in your vacuum system, including pump oil, must be much lower than the specified ultimate vacuum of the pump.
Refer to Section 5.13.2 for a list of possible causes for failure to achieve the specified performance. The most
common causes are:
Yo ur p re s su re m ea su re me nt te ch ni qu e or g au g e he ad is u ns u it ab le o r th e ga u ge h ea d i s fa ul ty
Yo u ha ve u se d a n oi l o th er t ha n t he r ec om me nd ed o il , a nd t he v ap o ur p re s su re o f t he o i l is h i gh er t h an t he
specified ultimate vacuum of the pump
Use the following procedure to achieve ultimate vacuum:
1. Isolate the pump from your vacuum system.
2. Turn the gas-ballast control (Figure 9, item 4) fully anti-clockwise (fully open) and operate the pump for at least
1hour (or overnight) to thoroughly purge the oil of contaminants.
3. Close the gas-ballast control (Figure 9, item 4).
4. Open the vacuum system isolation-valve and pump down to ultimate vacuum.
4.4To pump condensable vapours
Use gas-ballast when there is a high proportion of condensable vapours in the process gases.
1. Close the vacuum system isolation valve.
2. Turn the gas-ballast control (Figure 9, item 4) anti-clockwise to fully open and operate the pump for 30 minutes
to warm the oil. This will help to prevent vapour condensation in the pump.
3. Open the vacuum system isolation-valve and continue to operate the pump with the gas-ballast control open.
After you have pumped condensable vapours, you can (if necessary) decontaminate the oil. Use the procedure in
Section 4.5.
4.5To decontaminate the oil
The oil in the pump should be clear. If the oil is cloudy or discoloured it is contaminated with process vapours.
1. Look at the condition of the oil in the sight-glass (Figure 1, item 7). If the oil is cloudy or discoloured, continue
with the procedure at Step 2 below.
2. Close the vacuum system isolation-valve.
3. Turn the gas-ballast control (Figure 9, item 4) fully anti-clockwise.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 29
A344-02-880 Issue J
4.6Unattended operation
The pump is designed for unattended operation under the normal operating conditions specified in Section 2.
However, we recommend that you check the pump at a regular interval of not more than 14 days. Check the pump
more frequently if you pump high volumes of gas or if you operate the pump with the gas-ballast control (Figure 9,
item 4) open.
4.7Shut-down
Note:If the gas-ballast control is open and the pump is switched off for any reason, the pump drive shaft may
rotate in the reverse direction, causing a system pressure rise. To prevent this, use a gas-ballast control
valve (refer to Section 7.4.10).
We recommend, as described in the procedure below, that you decontaminate the oil before you shut down the
pump. Decontamination of the oil will prevent damage to the pump by the contaminants in the oil.
1. Refer to Section 4.5 and decontaminate the oil, as required.
2. Close the vacuum system isolation-valve (if not already closed).
3. Turn gas-ballast control (Figure 9, item 4) clockwise to close.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 31
A344-02-880 Issue J
WARNING
5Maintenance
5.1Safety
Obey the safety instructions given below and take note of appropriate precautions. If you do not,
you can cause injury to people and damage to equipment.
Ensure that maintenance is done by a suitably trained and supervised technician. Obey your local and
national safety requirements
Ensure that the maintenance technician is familiar with the safety procedures which relate to the pump-oil
and the products processed by the pumping system
Check that all the required parts are available and of the correct type before you start work
Isolate the pump and other components from the electrical supply so that they cannot be operated
accidentally
Allow the pump to cool to a safe temperature before you start maintenance work
Maintenance
Do not re-use 'O' rings and seals if they are damaged
After maintenance is completed, recheck the direction of pump rotation if the electrical supply has been
disconnected
Do not touch or inhale the thermal breakdown products of fluorinated materials which may be present if the
pump has been heated to 310°C and above. Fluorinated materials are safe in normal use but can decompose
into very dangerous substances (which may include hydrofluoric acid) if they are heated to 310°C and above.
The pump may have overheated if it was misused or if it was in a fire. Health and Safety Data sheets for
fluorinated materials used in the pump are available on request; contact your supplier or Edwards
Leak-test the system after maintenance work is complete if you have connected or disconnected any vacuum
or exhaust joints; seal any leaks found.
The pump and the pump-oil will be contaminated with the process chemicals that have been pumped during
operation. Ensure that the pump is decontaminated before maintenance and that you take adequate
precautions to protect people from the effects of dangerous substances if contamination has occurred.
The plan shown in Table 4 details the routine maintenance operations necessary to maintain your pump in normal
use. Instructions for each operation are given in the section shown.
More frequent maintenance may be required if you use your pump with gas-ballast or to pump corrosive or abrasive
gases and vapours. If necessary, adjust the maintenance plan according to your experience.
When you maintain the pump, use Edwards spares and maintenance kits; these contain all of the components
necessary to complete maintenance operations successfully. The Item Numbers of the spares and kits are given in
Section 7.
Examine the condition of any external accessories, filters or traps (if fitted). Refer to the instructions supplied with
these accessories for maintenance procedures.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 33
A344-02-880 Issue J
5.3Check the oil-level
Note:If required, you can check the oil-level while the pump is operating, however you must switch off the pump
and isolate the pump and other components in the pumping system from the electrical supply before you
pour oil into the pump
Refer to Figure 1 for the items in brackets.
1. Check that the oil-level in the sight-glass (7) is between the MAX and MIN level marks on the bezel of the
sight-glass.
2. If the oil-level is near to or below the MIN level mark, remove the oil filler-plug (6) and pour more oil into the
reservoir until the oil reaches the MAX level mark. If the oil-level goes above the MAX mark, open the oil
drain-tap (8) and drain the excess oil from the pump. When the oil level falls to the MAX mark, close the oil
drain-tap (8). Refit the oil filler-plug.
3. Refit the oil filler-plug (6), tighten the plug firmly by hand. Do no over-tighten.
4. If the oil is contaminated, drain and refill the pump with clean oil as described in Section 5.4.
5.4Replace the oil
Maintenance
Refer to Figure 1 for the items in brackets.
1. Operate the pump for approximately tenminutes to warm the oil, then switch off the pump (this lowers the
viscosity of the oil and enables it to be drained from the pump more easily)
2. Isolate the pump from your electrical supply and disconnect it from your vacuum system.
3. Remove the oil filler-plug (6).
4. Place a suitable container under the drain-tap (8). Open the drain-tap and allow the oil to drain into the
container.
5. If the oil drained from the pump is contaminated, pour clean oil into the filler-hole and allow it to drain out of
the pump. Repeat this step until the oil reservoir in the pump has been thoroughly cleaned.
6. Close the drain-tap (8).
7. Fill a suitable container with clean oil and pour the oil into the filler hole until the oil-level reaches the MAX
level mark on the bezel of the sight-glass (7).
8. Allow a few minutes for the oil to drain into the pump. If necessary, add more oil. Refit the filler-plug.
9. Replace the fine oil-filter (see Section 5.5).
10. Replace the gas-ballast filter (see Section 5.6).
Figure 9 - Fine oil-filter and gas-ballast bearing-plate locations
You must replace the fine oil-filter every time you change the oil in the pump. See Figure 9.
1. Isolate the pump from your electrical supply.
2. Place a suitable container underneath the oil drain scoop (5) below and to the left of the fine oil-filter (1). This
will contain any oil spill from the filter when it is unscrewed. The filter capacity is about 400 ml.
3. Unscrew the filter (direction arrows shown in Figure 9) using a suitable strap-wrench. Clean off any oil-spillage
on pump and filter housing surfaces. Dispose of the filter and any oil-spillage according to local environment
regulations covering industrial waste.
4. Make sure that the filter sealing ring (supplied with the new filter) is seated correctly on the new filter. Screw in
the new filter and tighten
You must keep the motor fan-cover clean. Your pump may overheat if the air-flow over the motor is restricted.
1. Isolate the pump from your electrical supply.
2. Use a dry cloth and a brush to remove dirt and deposits from the fan-cover.
3. Reconnect the electrical supply to your pump.
5.10Clean and overhaul the pump
Clean and overhaul the pump as described in the instructions supplied with the clean and overhaul kit (see Section 7).
5.11Test the motor condition
Test the earth continuity and the insulation resistance of the pump-motor, in accordance with local regulations for
periodic testing of electrical equipment. We recommend that the earth continuity is less than 0.1 and the
insulation resistance is greater than 10 M. If the motor fails these tests, you must replace the motor.
5.12Fit new blades
Fit new blades to the pump as described in the instructions supplied with the blade kit (see Section 7).
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 39
A344-02-880 Issue J
5.13Basic fault-finding
A list of fault conditions and their possible causes is provided here to assist you in fault-finding. If you are unable to
rectify a fault when you use this guide, call your nearest Edwards Service Centre for help.
5.13.1The pump has failed to start
The electrical supply fuse is blown
The electrical supply voltage does not match the motor
The outlet pipeline or the outlet-filter (if fitted) is blocked
The oil temperature is below 12°C
The oil is too viscous
The oil is contaminated
The pump has seized after long storage
The pump has been left to stand after contaminants have been pumped and has seized
The motor is faulty.
Maintenance
5.13.2The pump fails to achieve its specified performance
(Failure to reach ultimate vacuum).
The measuring technique or gauge is unsuitable
Yo u ha ve fi ll ed th e pu m p wi th t he w ro ng ty pe o f o il
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 43
A344-02-880 Issue J
CAUTION
6Storage and disposal
6.1Storage
Observe the storage temperature limits stated in Section 2. Storage below -30°C will permanently damage the
pump seals.
Note:If you will store a new pump in conditions of high humidity, remove the pump from its cardboard packaging
box; dispose of the box (refer to Section 6.2).
Use the following procedure to store the pump:
1. Ensure that the pump has been shut-down as described in Section 4.
2. Isolate the pump from the electrical supply.
3. Purge your vacuum system and the pump with dry nitrogen and disconnect the pump from your vacuum system.
4. Replace the oil as described in Section 5.4, paragraphs 3 to 8.
Storage and disposal
5. Place and secure protective covers over the inlet and outlet-ports.
6. Store the pump in cool, dry conditions until required for use.
7. When required, prepare and install the pump as described in Section 3. If the pump has been stored for more
than a year, before you install the pump you must clean and overhaul it as described in the instruction supplied
with the clean and overhaul kit.
6.2Disposal
Dispose of the pump, cleaning solutions, deposits removed from the pump, used pump oil, coolant, grease and any
components safely in accordance with all local and national safety and environmental requirements.
Particular care must be taken with the following:
Fluoroelastomers which may have decomposed as a result of being subject to high temperatures.
Components and oil which have been contaminated with dangerous process substances.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 45
A344-02-880 Issue J
7Spares and accessories
7.1Introduction
Edwards products, spares and accessories are available from Edwards companies in Belgium, Brazil, Canada, France,
Germany, Hong Kong, Italy, Japan, Korea, Singapore, Switzerland, United Kingdom, U.S.A, and a world-wide network
of distributors. The majority of these centres employ Service Engineers who have undergone comprehensive Edwards
training courses.
Order spare parts and accessories from your nearest Edwards company or distributor. When ordering, please state
for each part required:
Model and Item Number of your equipment
Serial number (if any)
Item Number and description of part.
7.2Service
Edwards products are supported by a worldwide network of Edwards Service Centres. Each Service Centre offers a
wide range of options including: equipment decontamination; service exchange; repair; rebuild and testing to factory
specifications. Equipment which has been serviced, repaired or rebuilt is returned with a full warranty.
Spares and accessories
Your local Service Centre can also provide Edwards engineers to support on-site maintenance, service or repair of
your equipment.
For more information about service options, contact your nearest Centre or other Edwards company.
The following maintenance kits contain all of the parts you will need to maintain your pump. The maintenance kits
also include instructions for the use of the kits. Use the Clean and Overhaul Kit for routine maintenance operations.
Use the Blade Kit together with the Clean and Overhaul Kit when you must renew the blade assembly in the rotary
pump.
PumpKit DescriptionItem Number
E1M40 and E2M40Clean and Overhaul KitA344-01-131
E1M40Blade KitA344-01-050
E2M40Blade KitA364-01-050
E1M40Major Service KitA344-01-814
E2M40Major Service KitA364-01-814
E1M40Interior AssemblyA344-01-100
E2M40Interior AssemblyA364-01-100
E1M80Interior AssemblyA345-01-100
E2M80Interior AssemblyA365-01-100
E1M80 and E2M80Clean and Overhaul KitA345-01-131
E1M80Blade KitA345-01-050
E2M80Blade KitA365-01-050
E1M80Major Service KitA345-01-814
E2M80Major Service KitA365-01-814
All modelsFine oil-filterA223-04-041
All modelsCommon Seals KitA344-01-820
7.4Accessories
A range of accessories is available for the E1M40, E2M40, E1M80 and E2M80 pumps.
7.4.1Inlet dust-filter
The inlet dust-filter is a nylon-fibre filter-element which protects your pump against abrasive dust (see Figure 12,
item 1). You can check the filter element by looking through a glass cover at the top of the filter. The filter is supplied
with bolts, washers, 40 mm 'O' ring and centring ring.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 47
A344-02-880 Issue J
7.4.2Inlet catchpot
The inlet catchpot traps liquid droplets and prevents their entry into the pump (see Figure 12, item 1). You can check
the liquid level in the catchpot by looking through a glass cover at the top of the catchpot. The catchpot is supplied
with bolts, washers, 40 mm 'O' ring and centring ring.
ProductItem Number
ITO100 Inlet CatchpotA441-02-000
7.4.3High-capacity inlet dust-filter
The high-capacity inlet dust-filter (see Figure 12, item 1) is a wire mesh filter. You use this filter where you have fast
pump down times and where high levels of dust and grit are involved. You can check the filter element by looking
through a glass cover at the top of the filter. The filter is supplied with bolts, washers, 40 mm 'O' ring and centring
ring.
ProductItem Number
ITM100 High Capacity Dust FilterA443-02-000
7.4.4Inlet chemical-trap
Spares and accessories
The inlet chemical-trap (see Figure 12, item 1) protects your pump against chemically active gases which may attack
your pump or pump oil. You must provide the trapping material suitable for your application. The trapping material
is contained in a removable fine mesh container supplied with the inlet chemical-trap. You can check the
chemical-trap by looking through a glass cover at the top of the chemical trap. The chemical trap is supplied with
bolts, washers, 40 mm 'O' ring and centring ring
ProductItem Number
ITC100 Inlet Chemical TrapA444-02-000
7.4.5Outlet catchpot
If your pump outlet is piped for remote discharge, condensed pipeline vapour could drain back to your pump. The
outlet catchpot (see Figure 12, item 5) collects the liquid. You can see from a sight-glass indication when you need
to drain the catchpot. The catchpot is supplied with two NW25 'C clamps, NW25 elbow, two NW25 centring rings and
'O' rings, bolts, washers, mounting bracket and studs.
The outlet mist-filter (see Figure 12, item 5) collects the oil contained in the oil-mist forming part of the discharge
gases. You can monitor the level of oil trapped in the filter, through a sight-glass. This mist-filter must only be used
for clean applications, for other applications see Section 7.4.7. You can return the trapped oil to your pump using
the oil return kit. The mist-filter is supplied with two N W25 'C clamps, NW25 elbow, two N W25 centring rings and
'O' rings, bolts, washers, mounting bracket and studs.
ProductItem Number
MF100 Mist FilterA462-03-000
Clean Application Oil Return KitA500-04-000
7.4.7Outlet mist-filter (toxic applications)
The outlet mist-filter (see Figure 12, item 5) collects the oil contained in the discharge gases. You can monitor the
level of contaminants through a sight-glass. You must check that the specification of the mist-filter you choose is
suitable for your application. The mist filter is supplied with two NW25 'C clamps, NW25 elbow, two NW25 centring
rings and 'O' rings, bolts, washers, mounting bracket and studs.
ProductItem Number
MF100AE Mist FilterA462-11-000
7.4.8External oil filter
The external oil filter (see Figure 12, item 3 or 4) is a free-standing filter. You can choose between two types of
oil-filter. The 'A' series uses an activated earth cartridge which provides chemical cleaning of the oil by removing
acidic and other aggressive contaminants. The 'M' series uses a pleated paper cartridge which does not provide
chemical filtering but removes abrasive particles down to 0.5 microns. The series 'A' and series 'M' oil-filters are
available in two sizes; the EOF100 has a 6-litre capacity, the EOF300 has a 15-litre capacity. You must check that the
external oil filter you choose is suitable for your application.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 49
A344-02-880 Issue J
7.4.9Oil-level monitor
The oil-level monitor (see Figure 12, item 7) fits in place of the existing oil-level sight-glass and bezel. The monitor
provides a switching facility which you can use to activate an alarm or other device. You still have the normal visual
indication of the oil-level.
ProductItem Number
OLM100 Oil Level MonitorA504-33-000
7.4.10Solenoid-operated gas-ballast control valve
The solenoid-operated gas-ballast control valve (see Figure 12, item 2) gives you automatic or remote control of
gas-ballast. You can connect the valve to shut off gas-ballast when the pump is switched off and so prevent air from
returning to the system.
1. Inlet dust-filter or inlet catchpot or inlet chemical trap or high capacity inlet dust-filter
2. Solenoid-operated gas-ballast valve
3. External oil-filter (15-litre capacity)
4. External oil-filter (6-litre capacity)
5. Outlet catchpot or outlet mist-filter
6. Vibration isolator
7. Oil level monitor
Spares and accessories
7.4.11Vibration isolators
Use vibration isolators (see Figure 12, item 6) to reduce vibration and noise when the pump is floor or
frame-mounted. You must use flexible bellows or other flexible piping between inlet and outlet connections when
you fit vibration isolators.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 51
A344-02-880 Issue J
Appendix AE2M40S and E2M80S
(Superpumps)
A1Introduction
A1.1Scope of this appendix
This appendix provides additional information about the E2M40S and E2M80S. Read this appendix in conjunction with
the instructions in the main sections in this manual.
A1.2Description
A1.2.1Construction
The Superpump pumps differ from the standard pump models as follows:
Appendix A
Internal parts have been designed to ensure reduced maintenance time and an increase in the pump running
efficiency
There is no fine oil-filter element
The oil filler cap is replaced by a non-return valve and inlet union for use with dry nitrogen oil-box purge
The gas-ballast adjustor knob is replaced by a dry nitrogen inlet pipe union and solenoid valve assembly; see
Figure A2.
A1.2.2Purpose of dry nitrogen gas-ballast
Dry nitrogen is injected into the pump stator through the gas-ballast solenoid valve to prevent the majority of any
corrosive gases condensing during the compression cycle of the pump. This form of gas-ballast is also used to lightly
pressurise the void between the rotor and shaft seals and assists in preventing any leakage of pump oil. You can check
the condition of the shaft seals by reducing the dry nitrogen gas pressure to zero (at the gas-ballast flow regulator)
while the pump is operating. Any shaft seal oil leakage is indicated by the presence of oil in a clear section of the
gas-ballast external return pipe; see Section A2.
Dry nitrogen is also introduced through a pipe union and non-return valve into the oil-box. This oil-box purge is used
when pumping flammable or toxic gases, where large scale dilution in the oil-box is necessary for safety reasons.
The pumps are available with the three-phase motor specified in Table A1. The dual voltage motors can be manually
set-up to work with the nominal supplies of 220-240 V, 380-415 V, or 208-230 V (Refer to Section 3.7). Dual voltage
motors are supplied preset to the highest of the selectable voltages.
Tab le A 1 - El ect ri ca l da ta (t hr ee -p ha se mo to rs )
Pump
E2M40S
E2M80S
*Yo u m ay n ee d to u se a di ff er en t fu s e ra ti n g. U se th e information supplied with your circuit breaker or
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 57
A344-02-880 Issue J
A3.2Fill the pump with oil
WARNING
Prevent direct skin contact with the oils and greases in this pump. Use suitable protective clothing.
These oils can cause inflamation of the skin after prolonged contact.
Fill the pump with oil as described below. Refer to Figure A2 for the item numbers in brackets.
1. Unscrew and move aside the pipe on the dry nitrogen non-return valve (5) on top of the oil-box. Remove the
non-return valve.
2. Pour oil into the pump until the oil-level just reaches the MAX mark on the bezel at the top of the sight-glass. If
the oil-level goes above the MAX mark, open the oil drain tap and drain the excess oil from the pump. You will
need additional oil if an external oil nitration unit is fitted. Refer to the instructions supplied with your filter;
see Associated publications on contents page iv of this manual.
Appendix A
3. After a few minutes, recheck the oil-level. If the oil-level is now below the MAX mark, pour more oil into the
pump.
4. Screw the non-return valve (5) back into the oil-box and tighten down firmly; re-connect the pipe.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Page 59
A344-02-880 Issue J
A4Operation
The pumps are designed for continuous operation.
CAUTION
If the pump is stopped for any reason; the dry nitrogen supply to the regulators must be switched off. This
eliminates the need to reset the regulators and also prevents possible oil pump priming problems on re-start
when the system is under vacuum.
Note:Refer to Figure A3. If you wish to continue to purge the oil-box after the pump has stopped you need only
switch off the supply to the gas-ballast by closing the flow regulator (5) to the gas-ballast.