Installation Instructions for
300 Watt Recessed Magnetic Transformer
120 Volt Input to 12 Volt Single Feed Output
SAVE THESE INSTRUCTIONS!
GENERAL INFORMATION IMPORTANT SAFETY INSTRUCTIONS
- RISK OF FIRE: This product must be installed by a qualified electrician. Turn the power to the electrical box off during installation. Read the "Important Safety Instructions" before installation.
- This product is suitable only for indoor dry locations and approved for the use at any height above the finished floor.
- This product may be dimmed only with a low voltage magnetic dimmer. Using a dimmer other than specified may work initially, but will eventually cause transformer failure and void the warranty. The dimmer must be derated as indicated by the dimmer manufacturer.
- Do not install this lighting system in a damp or wet location.
- Do not conceal or extend bus bar conductor through building wall.
- To reduce the risk of fire and burns, do not install this lighting system where the insulated open bus bar conductors can be shorted or contact any conductive materials.
- To reduce the risk of the system overheating and possibly causing a fire, make sure all the connections are tight.
- A typical installation is shown. Specific installation must be in accordance with the local electrical codes.
- TO REDUCE RISK OF FIRE, it is important to wire the recessed transformer for the system as described in this installation instruction.
- Load the circuit of the recessed transformer to MAXIMUM 300 Watt.
- This product may require some modification (remodeling) to existing wall where the transformers is to be mounted. The wall studs should be 16" apart.
- Do not install fixture assemblies closer than six inches, or as specified in the fixture installation instructions, to curtains or similarly combustible materials.
- Turn the electrical power off before modifying the lighting system in any way.
- The fixtures used with the Edge Lighting systems must be identified for use with the corresponding Edge Lighting systems.
- Minimum volume of the electrical box must be 6 cubic inches (98 cubic centimeters).
- The system is "ETL" listed for USA and Canada only when all the products used are supplied by Edge Lighting.
1
Install the Transformer
A
STUD
BRACKET
SCREW
T4T1
T3
COM T2
2
1: Install two THHN low voltage wires from the transformer
to the electrical box to which the power feed canopy will be attached. Run the proper size wire using the "Low Voltage Wire Size" chart below.
NOTE: Smaller wire sizes other than specified will result in an increase voltage drop and will reduce the lamp intensity.
NOTE: The THHN wire sizes specified in "Low Voltage Wire Size Chart" are for 3% or less drop in voltage based on 300 watt
loads. Lengths are the distance from the recessed transformer to the system power feed connector, or power feed canopy.
2: Insert one low voltage wire into the secondary terminal marked "COM" and tighten the screw firmly.
3: Insert the second low voltage wire to the "T2" tap terminal (default) and tighten the screw firmly.
4: Measure the voltage at the primary power line coming into the transformer. If the voltage is not in the range of 115-120 volt, then pick the proper terminal tap using the "Terminal Tap Chart" to reconnect the second low voltage wire.
1: Select the location between the wall studs (16" apart) where the transformer is to be mounted.
2: Place the transformer between the studs and fasten it to the studs through the bracket holes with four #8 or #10 screws (not provided).
Connect the 12 Volt Low Voltage Wires
B
ELECTRICAL BOX
LOW VOLTAGE WIRES
1
T4T1
3
T3
COM T2
2
5: Install drywall.
LOW VOLTAGE WIRE SIZE CHART
TRANSFORMER WATTAGE
WIRE SIZE FOR 5 FT
300 WATT #10 GA #6 GA #4 GA #1 GA
WIRE SIZE FOR 6-15 FT
WIRE SIZE FOR 16-20 FT
WIRE SIZE FOR 21-40 FT
TERMINAL TAP CHART
PRIMARY POWER INPUT VOLTAGE
105-109 T4
110-114
115-120
121-125
TERMINAL TAP TO BE USED
T3
T2
T1