Edge Lighting Magnetic Remote Transformer User Manual

© 2009 Edge Lighting. All Rights Reserved.
1718 W. Fullerton Ave
Chicago, IL 60614
Fax: 773-935-5613 www.edgelighting.com info@edgelighting.com
904-T-150-12-03
T-150-12
Installation Instructions for
150 Watt Remote Magnetic Transformer
120 Volt Input to 12 Volt Single Feed Output
SAVE THESE INSTRUCTIONS!
GENERAL INFORMATION IMPORTANT SAFETY INSTRUCTIONS
- RISK OF FIRE: This product must be installed by a qualified electrician. Turn the power to the electrical box off during installation. Read the "Important Safety Instructions " before installation.
- This product is suitable only for indoor dry locations and approved for the use at any height above the finished floor.
- This product may be dimmed only with a low voltage magnetic dimmer. Using a dimmer other than specified may work initially, but will eventually cause transformer failure and void the warranty. The dimmer must be derated as indicated by the dimmer manufacturer.
- Do not install this lighting system in a damp or wet location.
- Do not conceal or extend bus bar conductor through building wall.
- To reduce the risk of fire and burns, do not install this lighting system where the insulated open bus bar conductors can be shorted or contact any conductive materials.
- To reduce the risk of the system overheating and possibly causing a fire, make sure all the connections are tight.
- A typical installation is shown. Specific installation must be in accordance with the local electrical codes.
- TO REDUCE RISK OF FIRE, it is important to wire the remote transformer for the system as described in this installation instruction.
- Load the circuit of the remote transformer to MAXIMUM 150 Watt.
- Do not install fixture assemblies closer than six inches or as specified in the fixture installation instructions to curtains or similarly combustible materials.
- Turn the electrical power off before modifying the lighting system in any way.
- The fixtures used with the Edge Lighting systems must be identified for use with the corresponding Edge Lighting systems.
- Minimum volume of the electrical box must be 6 cubic inches (98 cubic centimeters).
- The system is "ETL" listed for USA and Canada only when all the products used are supplied by Edge Lighting.
1
Install the Remote Transformer
A
1
TRANSFORMER BRACKET
NOTE: In order to use small gauge wires from the transformer to the electrical box, it is recommended to install the remote transformers as near as possible to the electrical box. See "Low Voltage Wire Size Chart" below.
1: Use the transformer brackets to secure the transformer in place (hardware not included).
2: Loosen and remove the two Phillips screws on the sides of the transformer to remove the transformer cover.
COM T1 T2 T3 T4
PHILLIPS SCREW
2
2
B
TRANSFORMER COVER
1
TRANSFORMER BRACKET
3: Install a conduit and power wires from the panel to the transformer.
4: DO NOT connect the power wires to the panel at this time.
5: Connect the 120V black transformer wire to the hot power
with a wire nut.
6: Connect the 120V white transformer wire to the neutral power with a wire nut.
LOW VOLTAGE WIRE SIZE CHART
TRANSFORMER WATTAGE
WIRE SIZE FOR 5 FT
WIRE SIZE
FOR 6-15 FT
NEUTRAL POWER WIRE
3
WIRE SIZE FOR 16-20 FT
COM T1 T2 T3 T4
6
5
HOT POWER WIRE
CONDUIT
WIRE SIZE FOR 21-40 FT
150 WATT #12 GA #8 GA #6 GA #4 GA
2