Eden HC/4S 33, CS/4S 23, CS/4S 24, HC/4S 31, HC/4S 32 Installation, Operation And Maintenance Manual

...
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
WATER CASSETTES
2009-3
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
N
USO E MAN
U
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
STALLAZIONE,
TENZIONE
Vers. 2009-3
FIRST PART: FOR THE INSTALLER
GENERAL DIMENSIONS FOR 2 PIPE WATER CASSETTES 4
GENERAL DIMENSIONS FOR 4 PIPE WATER CASSETTES 5
WORKING LIMITS 6
GENERAL FEATURES AND MAIN COMPONENTS 6
Structure 6
Heat exchanger 6
Air fi lter 6
Motor fan group 6
Décor panel 6
Elimination of condensation 6
Wall mounted control for panels with a control board that is managed onboard (accessory)
6
RECOMMENDATIONS FOR THE INSTALLER 6
Unit installation 6
RECEIVING, STORE AND MOVING THE UNITS 7
INSTALLATION ACCESSORIES 7
SELECTION OF CASSETTE INSTALLATION LOCATION 7
INSTALLATION 7
Fixing the cassette 7
Fixing the panel 7
CHANGE OF AIR AND RECIRCULATION SYSTEM 8
Fresh air renewal 8
Air supply to an adjacent room 8
EXTERNAL AIR INLET WIRING DIAGRAM for cassettes with a control board that is managed onboard
8
WATER CONNECTIONS 8
Standard water connection to heating/cooling system
8
Cassettes with a control board that is managed onboard
8
Cassettes with and without a control board that is managed onboard
8
INSTALLATION OF AUXILIARY DRAIN PAN 9
CONDENSATE DRAINAGE 9
ELECTRIC POWER CABLES AND VALVE PASSAGE 10
ELECTRICAL CONNECTIONS 10
Eccess to the control panel 10
WIRING DIAGRAM FOR CASSETTE:
2 PIPE SYSTEM WITH I.R. REMOTE CONTROL (CS/4S + HC/4S) 11
4 PIPE SYSTEM WITH I.R. REMOTE CONTROL (CS/4S + HC/4S) 11
2 PIPE SYSTEM WITH WALL MOUNTED CONTROL (CS/4S + HC/4S)
12
4 PIPE SYSTEM WITH WALL MOUNTED CONTROL (CS/4S + HC/4S)
12
2/4 PIPE SYSTEM WITH WALL MOUNTED CONTROL (CS/4S + HC/4S)
13
2 PIPE SYSTEM WITH I.R. REMOTE CONTROL (CS/4S + HC/4S - 2nd SERIES)
14
4 PIPE SYSTEM WITH I.R. REMOTE CONTROL (CS/4S + HC/4S - 2nd SERIES)
14
2 PIPE SYSTEM WITH WALL MOUNTED CONTROL (CS/4S + HC/4S - 2nd SERIES)
15
4 PIPE SYSTEM WITH WALL MOUNTED CONTROL (CS/4S + HC/4S - 2nd SERIES)
15
SECOND PART: FOR THE USER
RECOMMENDATION 17
WATER CASSETTE OPERATION 17
THE INFRARED REMOTE CONTROLLER 17
I.R. REMOTE CONTROL OPERATIONS 18
WALL MOUNTED CONTROL SAME FUNCTIONS AS THE REMOTE CONTROL
20
WALL MOUNTED CONTROL OPERATIONS 20
TROUBLESHOOTING 20
CONDENSATE DRAIN PUMP OPERATION SPECIFICATION 20
PRE-HEATING FUNCTIONS 20
OPERATING DETAIL 21
TIPS FOR THE BEST USE 21
ENERGY SAVING 22
ROUTINE MAINTENANCE 22
END OF SEASON MAINTENANCE 22
WHAT TO DO IF... 22
DISMANTLING THE APPLIANCE 22
INDEX
water cassettes
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2009-3
water cassettes
4
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pic. 01
CS/4S 21 - 22 - 23 - 24 HC/4S 31 - 32 - 33 - 34
GENERAL DIMENSIONS FOR 2 PIPE WATER CASSETTES
MOD. 21 22 23 24 31 32 33 34
Fans number 1 1 1 1 1 1 1 1
Coil numbers 1 1 1 1 1 1 1 1
General features
Rows number 1 2 2 2 1 2 2 2
Hydraulic fi tting (Ø female gas) Ø 3/4” 3/4” 3/4” 3/4” 3/4” 1” 1” 1”
Depth of the unit (Lu) mm 580 580 580 580 835 835 835 835
Lenght of the unit (Pu) mm 580 580 580 580 835 835 835 835
Height of the unit (Hu) mm 280 280 280 280 240 305 305 305
Depth of the panel (Lp) mm 720 720 720 720 953 953 953 953
Lenght of the panel (Pp) mm 720 720 720 720 953 953 953 953
Height of the panel (Hp) mm 65 65 65 65 80 80 80 80
Air supply in adjacent room (Ø) A mm 150 150 150 150 - - - -
Air supply in adjacent room (BxH) C mm 350x100 350x100 350x100 350x100 120x80 120x80 120x80 120x80
Fresh air intake (Ø) D mm 65 65 65 65 - - - -
Fresh air intake (BxH) E mm - - - - 120x80 120x80 120x80 120x80
B mm 225 225 225 225 180 325 325 325
X mm 65,5 65,5 65,5 65,5 70 73 73 73
Y mm 55,5 55,5 55,5 55,5 75 68 68 68
W mm 100 100 100 100 58 88 88 88
Z mm 146 146 146 146 117 160 160 160
Net weight kg 19,0 19,0
Condensate tting Ø 24
Condensate tting Ø 27
Vers. 2009-3
water cassettes
5
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Pic. 02
CS/4S 41 - 42 - 43 - 44 HC/4S 51 - 52 - 53 - 54
GENERAL DIMENSIONS FOR 4 PIPE WATER CASSETTES
MOD. 41 42 43 44 51 52 53 54
Fans number 1 1 1 1 1 1 1 1
Coil numbers 2 2 2 2 2 2 2 2
General features
Rows number (standard coil) 1 2 2 2 2 2 2 2
Hydraulic fi tting (Ø female gas) Ø 3/4” 3/4” 3/4” 3/4” 3/4” 1” 1” 1”
Rows number (auxiliary coil) 1 1 1 1 1 1 1 1
Hydraulic fi tting (Ø female gas) Ø 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 3/4” 3/4”
Depth of the unit (Lu) mm 580 580 580 580 835 835 835 835
Lenght of the unit (Pu) mm 580 580 580 580 835 835 835 835
Height of the unit (Hu) mm 280 280 280 280 240 305 305 305
Depth of the panel (Lp) mm 720 720 720 720 953 953 953 953
Lenght of the panel (Pp) mm 720 720 720 720 953 953 953 953
Height of the panel (Hp) mm 65 65 65 65 80 80 80 80
Air supply in adjacent room (Ø) A mm 150 150 150 150 - - - -
Air supply in adjacent room (BxH) C mm 350x100 350x100 350x100 350x100 120x80 120x80 120x80 120x80
Fresh air intake (Ø) D mm 65 65 65 65 - - - -
Fresh air intake (BxH) E mm - - - - 120x80 120x80 120x80 120x80
B mm 225 225 225 225 180 325 325 325
X mm 65,5 65,0 65,5 65,5 86 73 73 73
Y mm 55,5 55,5 55,5 55,5 75 68 68 68
Wmm8282828258888888
Z mm 100 100 100 100 117 160 160 160
M mm 146 146 146 146 - - - -
N mm 159 159 159 159 - - - -
Net weight kg
Lu
550
515
Pu
X
34.5
52
W
N
Lp
Pp
Hu
B
Hp
C
D
Y
42 23
785
Pp
Pu
512
Lp
65
57
B
Hu
Y
X
20 60
Lu
EC
Hp
A
W
Z
Z
M
Condensate tting Ø 24
Condensate tting Ø 27
Vers. 2009-3
water cassettes
6
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
WORKING LIMITS
RECCOMENDATIONS FOR THE INSTALLER
GENERAL FEATURES AND MAIN COMPONENTS
Maximum inlet water temperature 70°C
Minimum inlet water temperature +4°C
Maximal working pressure 8 bar
Maximal inlet air temperature 32°C
Minimal inlet air temperature +4°C
ATTENTION! Air stratifi cation increases with the raise of inlet water temperature!
1 Airfl ow direction louvers 2 Air intake grille with fi lter 3 Airfl ow direction louvers 4 Indicator lights (the only model with a control board that is managed on board) 5 Power 6 Sleep mode 7 Timer mode 8 Infrared remote control receiver 9 EMERGENCY switch (used to switch on the air conditioner manually, without using the remote control, following the order given below).
STRUCTURE
Made in heavy-gauge galvanised sheet, the structure comes complete with ex­ternal brackets on the 4 corners for easy fi xing to the ceiling. Thermal-acoustic insulation: lining (polystyrene), external cladding (closed cell). Set-up for di­stribution of air to adjacent rooms through knock-out holes, either circular Ø 150 mm or rectangular 350x100 mm (CS/4S), and rectangular 120 x 80 mm (HC/4S), located on two sides of the appliance. Set-up for external air intake through Ø 65 mm circular knock-out hole (CS/4S). Rectangular 120x80 mm knock-out (HC/4S). Located on a squared off corner of the appliance.
HEAT EXCHANGER
Coil in copper piping expanded into aluminium fi ns in continuous block. The headers have easily accessible female gas fi ttings and air vent/drainage valve located on the squared off corner of the appliance.
AIR FILTER
The fi lter comprises a plastic frame holding the fi ltering membrane. Inserted in the inner part of the front panel, it may be easily removed and cleaned using a vacuum cleaner followed by washing with water.
MOTOR FAN GROUP
Single-inlet centrifugal fan with statically and dynamically balanced plastic impeller. The 4-speed electric motor, made to international standards, has an overload cut-out and the run capacitor always connected. The motor is directly coupled to the fan and cushioned with fl exible mountings. It is particularly effi cient and low noise.
DÉCOR PANEL
The décor panel has an innovative design so that the appliance may be used in both dwellings and business premises. The white (RAL 9003) panel is made in lightweight but strong plastic. Fixing to the load-bearing structure is quick and easy. 4 adjustable louvers ensure best air distribution throughout the room. Central intake grille with fi lter for cleaning the air. The grille may be removed to access internal parts without having to remove the panel from the ceiling.
ELIMINATION OF CONDENSATION
Condensate collecting system comprising:
- internal plastic tray for collecting condensation coming from the heat exchanger;
- external auxiliary plastic tray for collecting condensation coming from the valves and connecting pipes. Electric pump, which is an integral part of the appliance and connected to the external fi tting.
WALL MOUNTED CONTROL FOR PANELS WITH A CONTROL BOARD THAT IS MANAGED ONBOARD (accessory)
Wall mounted control for the water cassette with a 10 m headed cable with a connector (it maintains the same functions as the remote control).
Upon receiving the unit check for any damage, which should be reported imme­diately. For the water cassette to operate correctly, it should be installed accor­ding to the instructions given in this manual. Removal of a water cassette after it has been installed is an operation that requires special training: if this is neces­sary, please consult your dealer. After installation, explain the correct operating procedure to the customer using the booklet as a reference. Leave this manual with the customer since it is part of the kit supplied with the appliance. Take care not to scratch the units when handling them.
UNIT INSTALLATION
- Read this instruction manual thoroughly before starting installation.
- This unit complies with the low-voltage (EEC/73/23) and electromagnetic com­patibly (EEC/89/336) directives.
- The installation should be carried out by a qualifi ed installer.
- Follow all current national safety code requirements. In particular ensure that a properly sized and connected ground wire is in place.
- Check that the voltage and frequency of the mains power supply are as requi­red for the unit to be installed; the available power source must be adequate to operate all other appliances connected to the same line.
- Ensure that national safety code requirements have been followed the main supply circuit.
- Where necessary, use fi eld-supplied 25 mm I.D. PVC pipe of appropriate leng- th and with the correct thermal insulation for the condensate drain extension.
- After installation thoroughly test system operation and explain all system fun­ctions to the owner.
- Use this only for factory approved applications: the unit cannot be used in laundry or stream pressing premises.
Pic. 03
Pic. 04
OFF COOL HEAT
ON OFF
CS/4S
POWER SLEEP TIMER EMERGENCY
OFF
COOL
HEAT
HC/4S
O
N O
F
F
Vers. 2009-3
water cassettes
7
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
B
A
C
D
>100
100 < H > 350
RECEIVING, STORE AND MOVING THE UNITS
INSTALLATION ACCESSORIES
SELECTION OF CASSETTE INSTALLATION LOCATION
At the moment of the delivery of the unit, make sure that it corresponds to the one indicated on the transport document. Check the integrity of the packing and the unit. Should there be any differences with the original order or any damages, anomalies, or incomplete supply, please point it out on the delivery note and inform the fi rm straight away. Never install or use damaged appara- tuses. The unit can be stored in room protected from bad weather with tempe­rature between the -20°C and the +55°C. Transport the packed unit near as possible to the installation place. To avoid any damage to the unit, the plastic part (frontal panel and grille) are furnished separately. The handling and the installation could be facilitated cy use of an elevator (Pic. 05).
Vengono inclusi nella fornitura i seguenti materiali per l’installazione:
- n. 1 Cardboard mounting template;
- n. 1 Secondary basin for the condensation to be collected in correspondence with the valves.
RECCOMENDATION!
- The unit must be installed in a solid and vibration-free ceiling.
- There should be no obstruction of the air fl ow into and out of the unit and the air should be evenly distributed throughout the whole room.
- Do not install the unit near sources of heat, steam or infl ammable gases.
- Install the unit near an electric socket or connect it directly to the power supply.
- Do not install the unit in a place, which is exposed to direct sunlight.
- The selected place should allow easy drainage of the condensed water.
- Periodically check appliance operation and leave suffi cient space for mainte- nance around the appliance, as shown in the picture 06.
- Install the unit so that the fi lter is easily accessible.
FIXING THE PANEL
After installation of the unit, mount the grille using the 4 screws provided (pic. 10).
ATTENTION: It is very important to fi x the grille in the right position for correct connection of the receiver panel to the unit.
Establish the position and size of the hole in the ceiling using the external dia­meter of the cardboard mounting template (pic. 07).
To fi x the unit to the ceiling, use the threaded bar and suitable screw anchors as shown in pic. 08 (material not included in the supply).
Use a spirit level (pic. 9) to make sure that the unit is level and check that it is securely fi xed to the ceiling. In high humidity environments, metal supports must be insulated using adhesive insulating material.
WARNING!
- Disconnect the mains power supply switch before servicing the system or handling any internal parts of the unit.
- The manufacturer declines any liability for damage resulting from modi­ cations or errors in the electrical or water connections.
- Failure to observe the installation instructions, or use the unit under conditions other than those indicated in table “Operating limits” of this manual, will immediately invalidate the unit warranty.
- Failure to observe electric safety codes may cause a fi re hazard in the event of short circuits.
- Do not install or use damaged units.
- In case of malfunction turn the unit off, disconnect the mains power sup­ply and contact a qualifi ed service engineer.
- Maintenance must only be carried out by qualifi ed personnel.
- All of the manufacturing and packaging materials used for this appliance are biodegradable and recyclable.
- Dispose of the packaging material in accordance with local require­ments.
Pic. 05
Pic. 06
Pic. 07
Pic. 08
Pic. 09
Pic. 10
ATTENTION!
Catch up the cassette on the four corners. Don’t lift or move the unit through the ex­changer pipelines or the exhaust pipe con­dense.
INSTALLATION
FIXING THE CASSETTE
Select a place of installation where there can be a clearance of a least 100 cm (see pic. 06) around the appliance. Make sure that the installation does not interfere with existing electric wiring or plumbing.
- to fi x the panel only use the four supplied screws. Do not use other kinds of screws or you could damage the condensate drain pan.
- Do not bend or narrow the unit piping.
- Do not remove the cap from the unit piping until immediately before connecting the pipes.
- To prevent deformation of the air intake grille, do not overtighten the screws.
Vers. 2009-3
water cassettes
8
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
CHANGE OF AIR AND RECIRCULATION SYSTEM EXTERNAL AIR INLET WIRING DIAGRAM
WATER CONNECTIONS
- Side knockouts allow connection of a duct for fresh air intake and for conditio­ning an adjacent room.
- Remove the external prepunched anti-condensate insulator and remove the knockout panels using a punch.
FRESH AIR RENEWAL
Remove the polystyrene partition and insert the baffl e plate. Use material purchased locally that is suitable for continuous operation with temperatures of 60°C. The ducts may be in fl exible polyester (with steel spiral core) or in corrugated aluminium lagged with anti-condensate material (fi bre- glass 12±25 mm thick). Upon completion of installation, surfaces that have not been insulated may be covered with anti-condensate insulating material (e.g.: 6 mm thick expanded neoprene).
Failure to comply with these instructions could cause dripping due to the condensate; the manufacturer cannot be held responsible for any damage.
Any additional fan for external air intake (installer’s responsibility) must be con­nected to the terminal block as per the enclosed diagrams. Fan operation is in parallel to the damper (electrothermal control valve), so that it stops when the valve closes. Install an air inlet grille on the outside, with an inspectable fi lter holding frame to prevent the entry of dust and leaves, which could irreparably obstruct the unit heat exchanger coil.
The following reasons explain why it is necessary to install the 3-way valve:
- Cassettes with a control board that is managed onboard
1) If the water fl ow is not closed via the valve when the room temperature is reached, the air sensor installed in intake mode is conditioned by the heat ex­changer that cools it or heats it via natural convection. The result is that the unit will not adjust the temperature correctly or it will not go on.
2) The unit has a protection system that intervenes by closing the water fl ow via the valve in cases such as: a) Where there is a condensate discharge problem (if the valve does not close the water fl ow, the battery will continue to condense, causing the condensation basin to overfl ow). b) The user inserts the incorrect function on the remote control: hot as op­posed to cold. c) The water temperature rises to 80 °C (which damages the main conden­sation basin)
3) The unit has been designed to have continuous ventilation and warm or cool the room by closing or opening the water fl ow: this allows for optimal adjustment inside the room where it is installed.
- Cassettes with and without a control board that is managed onboard
4) If the unit remains turned off for a long time in cooling mode and the water ow is not closed, droplets of condensation may form at the air outlets, which will subsequently lead to a dripping unit.
FOR CASSETTES WITH A CONTROL BOARD THAT IS MANAGED ONBOARD
STANDARD WATER CONNECTION TO HEATING/ COOLING SYSTEM
ATTENTION! IT IS COMPULSORY TO INSTALL THE VALVE!
AIR SUPPLY TO AN ADJACENT ROOM
Remove the polystyrene, taking care not to damage the behind heat exchanger coil to the rear. Do not use the two knockout side openings for air ducting to an adjacent room simultaneously.
ATTENTION!
1) Ducting air to an adjacent room requires the closure of at least the corresponding duct end.
2) When valves are installed, the air ducts to the “D” adiacent room are unusable (pict. 11).
Pic. 11
Pic. 12
Pic. 13
A Knockout for air supply to an adjacent room Ø 150 mm
B Knockout for air supply to an adjacent room 350x100 mm
C Knockout for fresh air intake Ø 65 mm
D Knockout for air supply to an adjacent room 120x80 mm
E Knockout for air supply to an adjacent room 120x80 mm
F Knockout for fresh air intake 120x80 mm
A Fan circuit breaker
B Fan control relay 230V
C Antifreeze fresh air protection
D Fresh air fan motor
PE
L N
C
N
L
B
D
A
C
M
Balancing valve
Shut off valve
3 way valve
A
B
AB
OUT
IN
OUT
IN
A
B
C
D
E
F
HC/4S
CS/4s