Eberle INSTAT 868-a4 User guide

Contents:
1. Application
2. Features
3. Function description
3.1 Function – Switching mode –
3.2 Function – Pump logic –
3.3 Function – Time switch function –
3.5 Heating/Cooling changeover
3.6 Deleting the radio link
3.7 Testing the radio distance
3.8 Identifying active radio links
3.9 Lamp function
3.10 Bridge function
4. Installation
5. Commissioning
5.1 Establishing the radio link
5.2 Valve test
5.3 Power failure
5.4 Quit/Reset
5.5 Faults
5.6 Troubleshooting
6. Technical data
7. Dimensions
8. Wiring diagrams and examples
9. Brief operating instructions
1. Application
This module of the INSTAT 868-family converts the informa- tion from a transmitter, e.g. INSTAT 868-r…, into control signals for the loads.
2. Features
• Ready to plug-in, for immediate connection to a 230 V conduit box
• 230 V actuators can be directly connected
• 24V actuators switchable via volt free contacts (separate transformer required)
• 4 receive channels in one housing
• or 3 receive channels and one output for pump logic, e.g. for switching off the circulating pump when all valves are closed
• or 2 receive channels, each with one associated time switch output
• Master /slave function (master dictates switching times)
• Changing Heating /Cooling mode
• Valve test function
• Radio link test and system demonstration
• One transmitter can control several receive modules
• Self-learning address setting due to ”Learning mode“ in the transmitter
• One push-button per output for setting functions
• One signal lamp per output to indicate relay status, faults, etc.
• One reset button
• Acoustic signal in case of faults
• Monitoring valid addresses
• Monitoring the transmitter (if no signal has been received from the transmitter for an extended period of time, for in­stance, when the battery is empty, the output is switched on for 30% of the time and the signal lamp flashes).
Warning!
This unit must not be opened and installed except by au­thorized persons and in compliance with the circuit dia­gram provided on the pcb. It is mandatory in all work on the unit to observe the current safety regulations. In order to classify for protection class II it is necessary to take adequate installation measures. This separately mounted unit is designed for temperature control exclusively in dry and closed rooms with standard environment. This electronic device is created according EN 60730, it is working according operation principle 1C.
3. Function description
The INSTAT 868-a4 receiver converts radio signals from a transmitter, for instance, INSTAT 868-r, into control signals for loads. The loads are switched by means of a relay with changeover contacts. The switching condition is indicated by the respective signal lamp.
For relay switching characteristics, see Installation instruc­tions for the transmitter under Item “Function description“.
For controlling loads, the output can be configured in differ­ent ways. The functions subsequently listed can be combined in an INSTAT 868-a4.
3.1 Function – Switching mode – “One transmitter controls one switching output“
Up to 4 transmitters control one output each (channels 1…4) for heating ON/OFF (possibly, channel 4 lights up, see Sec­tion 3.2). One or more actuators can be connected to each output. For example, see Fig. 1.
3.2 Function – Pump logic –
Up to 3 transmitters control one output each (channels 1…3) for heating ON/OFF. Channel 4 output serves as a common pump logic output. The pump is switched off, LED 4
extinguishes (if none of the available transmitters has not called for heat (for more than approx. 10 minutes). The pump is switched by the break contact of the relay. This means that “emergency operation” of the heating system is possible in the event of a power fail­ure if ”normally open” actuators are used. By parallel connection of the channel 4 outputs, the pump logic can be extended to several receiving modules. To avoid short circuits in the slave units, remove bridges BR 4, BR 5. Supply slave units via terminal 7, 8 of the master unit, see Fig. 2. This function is always activated, as long as channel 4 is not pro
grammed to a transmitter.
Reactivation is possible only via Item 3.6 ”Delete radio links”.
3.3 Function – Time switch output – ”One transmitter controls one switching and an associated time switch output”
(Not possible with INSTAT 868-r1) One transmitter controls one output for heating ”ON/OFF”
and one time switch output for temperature setback. Two adjacent outputs respectively are combined to form pairs, the one with the lower number switches the actuator, the one with the higher number serves as a time switch output, see Fig. 3.
The time switch output switches ”ON” if the controlled tem­perature t3(night) is active on the transmitter and the warm­up period has not yet started.
This output can, for instance, be used to control the tempera­ture setback input for other controllers. Outputs which are not used for temperature setback, can be freely assigned to other transmitters. The time switch function is independent of the transmitter operating mode.
For ‘party’ and ‘manual operation’ in the transmitter, the switching times of the weekly program apply. In frost protec­tion the time-switching output is always active If the daily program is active, its respective switching times apply.
3.4 Function – Master/Slave –
In the case of this function, the slaves follow the master switching times.
Master/Slave is activated, if:
Channel 1 = Master
(INSTAT 868-r, clock thermostat)
Channels 2…4 = Slave (INSTAT 868-r1) Only slaves in the automatic mode follow the master. Only one master is possible. It must always be assigned to
channel 1
. If other INSTAT 868-r are assigned to higher chan- nels, these do not follow the master (the slaves do). In case of masters failing, the slave receive channels provide control to the comfort temperature, set on the slave controllers. For ex­ample, see Fig. 4. Party- and manual mode of the master has no influence to the slaves
3.5 Changing Heating/Cooling mode
With this function the INSTAT 868-a4 can be used for heating or for cooling. The switching behaviour of all outputs will be reversed (in case activated pump logic will be maintained without reverse). The function ”time switch“ ist not reversed.
For cooling mode (summer time)
1. Button at channel 3 and ”reset“ button pressing at the same time.
2. At first release button ”reset“ then button ”channel 3“
For heating mode (winter time) (as delivered condition)
1. Button at channel 4 and ”reset“ buttton pressing at the same time.
2. At first release button ”reset“ and then button ”channel 4“
3.6 Deleting the radio link
To delete all radio links:
1. press push-button at channel 1 and reset button simulta-
neously.
2. release reset button first, then channel 1 push-button.
This deletes all radio links. Any necessary links must be established new (see Item 5.1). Now, after having pressed the reset button, none
of the
lamps must light up briefly see 3.8..
3.7 Testing the radio distance
To determine the distance of the radio link, the following pro­cedure has to be followed:
On the transmitter:
Set the transmitter to Learning mode
Then on the receiver:
1. Press the channel 2 push-button and reset button simulta-
neously.
2. Release the reset button first, then the channel 2 push-
button.
Channel 2 signal lamp lights up. The signal tone and the
relay operate in the switching mode., approx. 2 sec. ”ON”,
approx. 8 sec. ”OFF”.
Now, while holding the transmitter in your hand, walk
away from the receiver until you reach the point where
the signal tone can no longer be heard and the relay is
about to stop operating. This is the maximum possible ra-
dio link distance. After a certain period, the transmitter automatically ceases to
operate in the ”Learning mode”. Always terminate the radio link test in the receiver by pressing the reset button.
Any other channels are not affected by the radio test.
3.8 Identifying active radio links
Having pressed the reset button, the programmed channels are indicated by the respective channel lamps briefly lighting up.
3.9 Lamp function
The signal lamps provide information about the respective channel:
• Heating ”ON/OFF” In normal operating mode, steady
light is possible
• Faults Flashing, 1 sec. interval, number varies
depending on type of fault s. 5.5
• Learning mode Permanently ”ON”
• Valve test ”ON” until push-button is pressed
• Radio test Flashing, 10 sec. interval
3.10 Bridge function
BR 1: Opening for switching beeper OFF (single-pole
plugging prevents loss of bridge)
BR 4, 5: Opening for double-pole insulation of the supply
voltage from the switching voltage
see wiring diagram
4. Installation
Mounting: for instance
• In the distribution board on DIN rail
• In the heating circuit distributor on DIN rail
• Mounting position: any
• The unit must not have contact with water.
Electrical connection of operating voltage:
Insert plug into conduit box. If a direct connection is re­quired, cut the plug off and clamp the wires.
Connecting the actuators:
Before inserting the cables, make a hole in the nipple using a round, pointed object.
Electrical connection:
(switch off mains supply)
See diagram on the printed circuit board and Item 8. In the as-supplied condition, the unit is designed for switching 230 V actuators. The actuators are simply connected to the terminals (a-c [normally-open] and b-c [normally-closed]) of the respective channels by means of both leads (terminals 7, 8 are not connected).
For switching a second voltage of up to 230/400V max. (also for 24 V actuators):
Remove bridges BR 4 and BR5 com
pletely.
The second voltage is fed via terminals 7, 8 (between chan­nels 2 and 3). Example, see Fig. 3.
By removing bridge BR 3, channels 3/ 4 can be operated with a voltage different from that of channels 1/ 2 (via terminals 7, 9).
Note:
Having removed
bridge BR 3 channels 3/4 remain connected as a single-pole connection to channels 1/2. Volt free contacts with the required safety clearance can only be obtained after com
plete removal of bridges BR4, 5
A suitable transformer is required for 24 V.
5. Commissioning
Delete all channels before commissioning, see Section 3.6.
5.1 Establishing the radio link
On completion of the installation work, a link between the INSTAT 868-r… transmitter and the respective output (chan­nels 1…4) must be established. This must be carried out in the following sequence: a) Set the transmitter to learning mode (see Transmitter
operating instructions)
b) 1. For function – switching mode –.
Set the required switching output of the receiver to learning mode. To do this: Briefly press the push-button for the desired output. A signal sounds, the associated signal lamp lights up and the output switches ON briefly. When the transmitter is identified, the signal tone ceases to sound and the associated signal lamp switches off.
2. For function – pump logic – As with b1, however, a transmitter
must not be assigned
to channel 4.
3. For function – time switch output – Set the desired switching output of the receiver and the as­sociated time switch output to learning mode. To dothis: press both the push-button for the desired switching output (channels 1,3) and the push-button for the time switch output (channels 2,4) (e.g. press 1, 2). A signal sounds, the associated two signal lamps light up and the two outputs switch on briefly.
c) When the transmitter is identified, the signal tone ceases
to sound and the associated signal lamps extinguish.
d) T
erminate the learning mode on the transmitter
e) Testing the established radio link, see Section 3.8. It is not possible to assign one transmitter to several outputs
in the same unit. However, one transmitter can control sever­al outputs in different receiving modules. To establish the ra­dio link, only one transmitter must be in the learnin
g mode.
5.2 Valve test
When the push-button of an associated output is pressed:
• the associated output switches ON (as long as the push-but­ton is pressed),
• the signal lamp lights up,
• the signal tone sounds.
After releasing the output button, the reset button must be pressed within 10 sec. As a result of this, the signal lamp extinguishes and the signal tone ceases to sound. After 10 sec., the learning mode starts; a link would be established to a transmitter which happens to be in the learning mode.
5.3 Power failure
If there is a power failure in the transmitter or in the receiver, all data will be saved. When power supply is restored, normal operation is resumed.
5.4 Quit/Reset
To • quit the learning mode or
• acknowledge a failure or
• terminate the radio link distance test or
• terminate the valve test or
• in the event of any other inexplicable phenomena
Mount cover in volt free condition only
Installation and Operating Instructions Radio frequency receiver
INSTAT 868-a4…
U 468 931003 267-1
This thermostat can be used in all EU and EFTA countries.
The manufacturer hereby declares that this device con­forms with the basic and other relevant requirements laid down by directive R&TTE 1999/5/EC.
The declaration of conformity can be downloaded from „www.funk868MHz.de“.
8. Wiring diagrams and examples
Fig. 1
Each transmitter controls a switching output for heating ON/OFF. No master/slave. Graphical representation of 230 V actuators.
Fig. 2
Each transmitter controls a switching output for heating ON/ OFF. Additional pump logic. No master/slave. Graphical representation of 230V actuators/pump.
Extension of pump logic to two receiving modules
Fig. 3
Each master controls one switching output (channel 1) and an associated time switch output (channel 2) for temperature setback of other controllers. Slaves on channels 3, 4. Graphical representation of 24 V actuators
Fig. 4
One master (channel 1) with 2 slaves (channel 2, 3). Additional pump logic (channel 4). A third slave can be programmed at channel 4. Connect a valve instead of a pump. Graphical representation 230 V actuators
9. Brief operating instructions for the INSTAT 868-a4 radio frequency receiver
Deleting the radio links 3.6 • Press the channel 1 button + the reset button simultaneously
• Release the reset button, then the channel 1 button
Testing the radio distance 3.7 • Set transmitter to Learning mode
• Press the channel 2 button + reset button simultaneously
• Release the reset button, then the channel 2 button
• Channel 2 signal lamp lights up
• Signal tone + relay are operating in the switching mode (brief ON - extended OFF)
• When the switching mode ceases to operate, the radio distance is exceeded
• Press the reset button for termination
• Transmitter: switch off Learning mode
Establishing the radio link 5.1 • Set transmitter to Learning mode
Function or 3.1 • Briefly press the channel button! ”Switching mode” • Signal lamp lights up + signal tone sounds
• When transmitter is identified, signal lamp + tone will stop
• Transmitter: switch off Learning mode - press the OK button Function 3.2 • Channels 1, 2, 3 Switching mode - Channel 4 Pump logic pump logic • Function is active, as long as channel 4 is not programmed
• Like function "Switching mode"
Function 3.3 • Set Transmitter to Lerning mode
• Briefly press channel 1 + 2 or channel 3 + 4 buttons
Switching and time switch output • Signal lamps light up + signal tone sounds
• When transmitter is identified, signal lamp extinguishes and signal tone ceases to sound
• lower number = switching output (actuator)
• higher number = time switch output
• Transmitter: switch off Learning mode Function 3.4 • Slaves follow master switching times Master/slave • Assign master to channel 1, program slaves to following channels
Changing Heating/Cooling mode 3.5
Heating • Winter mode (as-delivered condition)
• Press the channel 4 + the reset button simultaneously
• Release the reset button, then the channel 4 button
Cooling • Summer mode
• Press the channel 3 button + the reset button simultaneously
• Release the reset button, then the channel 3 button
Displaying programmed channels 3.8 • Press the reset button – programmed channels will be briefly displayed Valve test 5.2 • Press the channel button
• As long as the channel button is pressed, the output switches On
• Press the reset button within 10 sec. after releasing the channel button
Signal lamp - Fault messages 5.5
– Brief double flash • Double addressing - reprogramming the transmitter – Brief single flash +
no signal tone • Brief losses of transmitter signal (1h up to 10 h) with signal tone • Extended losses of transmitter signal (more than 10 h)
Output receives 30% of the manipulated variable (3 min. ON - 7 min. OFF)
press the reset button. This switches the relays to the OFF status. When new actuating signals are received (possibly after 10-20 min.), they will continue to work. Any existing radio link will be maintained.
5.5 Faults
If faults occur, an alarm is triggered. In this case, the signal lamp flashes
with varying duration, if necessary, a signal tone
sounds.
5.5.1 Double addressing
In this case the signal lamp flashes permanently two times short one after the other. The signal sounds be cancelled by re-learning one of the both transmitters. The output is switched with 30% capacity (3 minutes ON, 7 minutes OFF).
5.5.2 Brief losses of the transmission signal
If the transmitter fails to receive an actuating signal within a period of 1 and up to ~10 hours, the signal lamp shows a per­manent one brief flash
. No signal tone sounds. The output is switched with 30% of the manipulated variable (3 min. ON, 7 min. OFF). Upon the transmission signal recurring, the alarm automati­cally ceases.
5.5.3 Longer losses of the transmission signal
If the transmitter has not received an actuating signal for more than 10 hours, the signal lamp shows permanent one short flash. The signal tone sounds. The output is switched with 30% of the manipulated variable (3 min. ON, 7 min. OFF). Upon the transmission signal recurring, the alarm automati­cally ceases.
Note:
• In the case of heating systems that are in stand-by mode
even in the summer, e.g. electric heaters, the valve protec­tion (in the transmitter) must be switched off. In the other case the output would be switched On for 3 minutes each day!
• The signal tone can be switched off permanently by remov-
ing bridge BR 1.
For all t
ypes of faults, the following a
pplies:
• Function – Switching mode – A fault at one output will not
affect the other outputs.
• Function – Pump logic – A pump keeps ON operating in the
alarm mode (already after one transmitter has failed).
• Function – Time switch output –: The faulty behaviour also
applies to the associated time switch output.
• Function – Master/Slave – In the case of the master failing,
the slaves are switched to comfort mode.
• A flashing signal lamp indicates the alarm status, not the
switching status of the output.
• After a power failure in the transmitter or in the receiver,
normal operation is resumed.
• Under unfavourable local conditions it is possible that the
radio link between the transmitter and the receiver is insuf­ficient, for instance, if the receiver is installed in an inter­ference-proof metal housing. Please check whether the sit­uation improves when the transmitter is arranged in a dif­ferent position. For checking the radio link, see Section 3.7.
Table 1: When the radio link does not work…
Check the following: Yes No
1. Receiver: Is signal lamp ‘Power’ lighting up? Continue with 2 Check power supply possibly the unit is defective
2. Receiver: Is a channel 1…4 signal lamp flashing? Double addressing see Section 5.5.1 Continue with 5
Can the warning tone be heard? or transmission signal is missing (possibly only after one hour) Continue with 3
3. Press the reset button Continue with 4 Transmitter not programmed
Are the required channel signal lamps lighting up briefly? Reprogram, see Section 5.1 See Item 3.8
4. Transmitter: Is the battery OK? Continue with 5 Insert new batteries
5. Transmitter: Adjust to 30°C. Is the relay switched on after Continue with 6 Relay was already switched on
~30 sec? (signal lamp lights up). . Continue with 6 or transmission
signal is missing, continue with 7
6. Transmitter: Adjust to 5°C. Is the relay switched off Everything OK Transmitter signal is missing,
after ~30 s (signal lamp does not light up) continue with 7
7. Transmitter-receiver-actuator: Check wiring, if Everything OK Continue with 8, if necessary,
necessary, reprogram connection to radio receiver. check radio link distance,
see Section 3.7
Are Items 5 and 6 now successful? “Testing the radio link distance“
8. Reduce distance between receiver and transmitter Transmitter and receiver are Transmitter or radio receiver are
to ~2 m (not less). Are Items 5 and 6 working properly defective now successful?
7. Dimensions (for INSTAT 868-a4)
Base Unit Extension Unit
5.6 Troubleshooting
1. Valve does not open:
Has it been properly wired up?Has the radio link been established? (see Section 5.1)See table 1 up from item 3.Press the reset button (see Section 5.4)!
2. The signal lamp for a radio channel flashes and possi­bly a beeper is sounding
For basic fault procedures, see Section 5.5Learning mode, valve test, radio range test have not
been interrupted (see Sections 5.1, 5.2, 3.7, 5.4)!
Two transmitters are transmitting with the same ad-
dress; reprogram the associated radio link (see Sec­tion 5.5.1)!
No radio link, see Item 7 in the Table1 !One or more channels which are not in use are flashing.
These channels have lost their transmitter. Proceed as described under Section 3.6 ‘Deleting the radio link’. Re-lern needed links.
3. The channel 4 signal lamp lights up, although no transmitter has been programmed.
• Channel 4 serves as a pump logic, see Section 3.2.
In the case of inexplicable faults it is recommended to press the reset button on the receiver and, if necessary, on the transmitter.
6. Technical data
Type INSTAT 868-a4 Article-No. 0536 40 140 … Operating voltage 230 V (195…253V) 50 /60 Hz Power consumption < 3VA Ambient temperature 0…+50 °C
(without condensation) Storage temperature –20…+60°C Aerial Internal Push-button: for programming 4
for reset 1
Lamps: for programming 4
for operating volt. 1
Load circuit: 4 changeover contacts,
6A cosϕ =1; 2A cosϕ = 0.6
**
24 ... 230 V AC volt free* Number of actuators per contact:***
3 W each electrothermal
230 V 10*** max.
24 V 4*** max. Double-pole insulation voltage when bridges BR 4,5 are opened 400 V* max. Single-pole insulation voltage when bridge BR 3 is opened 230 V* max. Protection class of housing IP 40 / insulated Software class A Rated impulse voltage 2.5 KV Brinell test temperature 75°C Voltage and current for EMC 230 V, 6 A emitted interference testing Weight ~530 g
*) After complete removal of bridges BR 4, 5, a creepage distance and clear-
ance of 8 mm between the operating voltage and the relay terminals is guaranteed. The unit is therefore suitable for switching safety extra-low voltage (SELV). After removal of bridge BR 3, the two switching units (channels 1/2 against channels 3/4) show a 230 V basic insulation.
**) Total of all currents <= 10 A With a total of all currents of >2 A, install as
described under ”Switching a second voltage” (see Item 4, Installation).
***) A maximum of 10 x 4 = 40 (230 V) actuators or 4 x 4 = 16 (24 V) actuators
respectively can be controlled by an INSTAT 868-a4 at one time. Four actuators can be mechanically connected to the six-point terminal. If there are more actuators, provide external terminal points.
Note: In individual cases it may not be possible to establish a permanent radio link between radio transmitter and radio receiver. The rea­son for this is not to be attributed to our radio control, but to the radio distance to be used. Therefore, we recommend checking its prop­er functioning at the respective place of installation.