Technical Data
Technical Data
Effective March 1, 2018
VNW-D – NeoSwitch Dual Tech/Single Level
Wall Switch Vacancy Sensor (Ground Required)
Catalog# Prepared by
Project Date
Comments Type
Overview
The Dual Technology Single Level Vacancy Sensing Wall Switch is
a motion sensing lighting control and conventional wall switch allin-one that is used to for energy savings and convenience. It does
not require a neutral wire for installation making it ideal for retrofit
applications.
Features
Requires Manual On for activation
Air-gap switch ensures no leakage current to load
Selectable built-in light level sensor
Products tested to NEMA WD 7 - 2011 Occupancy Motion
Sensors Standard
LED Rated
PIR
Activated
Ultrasonic
Activated
Self-Adjusting
Technical Data
March 2018
VNW-D – NeoSwitch Dual Tech/Single Level Wall Switch Vacancy Sensor (Ground Required)
Specifications
Technology Passive Infrared (PIR) and Ultrasonic (US)
Electrical
Ratings
(Per Relay)
Ballast
Compatiblity
Time Delays Self-Adjusting, 15 seconds/test (10 min. Auto)
Coverage Major motion - 36’ x 30’
Light Level
Sensing
Operating
Environment
Housing Durable, injection molded housing. ABS resin
Size Mounting Plate/Strap Dimensions:
LED Indicators Red LED for PIR detection; Green LED for
Standards FCC Compliant
120 VAC:
Incandescent/Tungsten –
Max. load: 6.7 amps, 800W, 50/60 Hz
Fluorescent/Ballast –
Max. load:10 amps, 1200W, 50/60 Hz
Electronic Ballast (LED) 3A
Motor Load: ¼ HP @ 125 VAC
277 VAC:
Fluorescent/Ballast –
Max. load: 9.8 amps, 2700W, 50/60 Hz
Electronic Ballast (LED) 3A
Compatible with LED loads, magnetic and
electronic ballasts
Selectable 5, 15, 30 minutes
Minor motion - 20’ x 16’
0 to 200 foot-candles
Temperature: 32°F - 104°F (0°C - 40°C)
Relative humidity: 20% to 90% non-condensing
For indoor use only
complies with UL 94V-0
4.195”H x 1.732”W (106.55mm x 44mm)
Product Housing Dimensions:
2.618”H x 1.732”W (110.49mm x 44mm)
Ultrasonic detection
cULus Listed
RoHS Compliant
Description/Operation
The VNW-D-1001-MV combines Ultrasonic (US) and Passive Infrared
(PIR) sensor technologies to monitor a room for occupancy to
deliver maximum energy savings and ensure the greatest sensitivity
and coverage for tough applications without the threat of false
triggers. Manual On switch is used to turn the lights ON and then
either or both technologies are used to keep the lights ON. The
lights are turned ON by pressing the universally recognized light
icon pushbutton. The sensor includes self-adaptive technology that
continuously self-adjusts sensitivity and time delay in real-time,
maximizing the potential energy savings that are available in the
particular application.
Applications
Private Offices
Small Conference Rooms
Lunch/Break Rooms
Small Classrooms
Small Restrooms (1-2 Stalls)
Small Lounges
Small Waiting Rooms
Small Closets
Small Storage Areas
2