366 CIRCLE OF PROGRESS POTTSTOWN, PA 19464
(610)323-2250FAX: (610)323-0114
LP4310 IB.DOC
9/16/04
TABLE OF CONTENTS
CONTENTS
SECTION1.0DESCRIPTION.
SECTION2.0PREPARATION FOR USE
SECTION2.1RECEIVING INSPECTION
SECTION2.2SHIPMENT
SECTION2.3SITE SELECTION
SECTION2.4INSTALLING
SECTION2.5LEVELING
SECTION2.6HOOK-UP CABLE
SECTION3.0TROUBLE SHOOTING
SECTION4.0SERVICING
SECTION4.1CHECKING THE LOAD CELL
SECTION4.2REPLACING THE LOAD CELL
SECTION5.0SPECIFICATIONS
SECTION6.0SPARE PARTS LIST
LIST OF ILLUSTRATIONS
FIGURE 1LP4310
FIGURE 2LEVELING OPERATION
FIGURE 3RESISTANCE TABLES
FIGURE 4OUTPUT TABLES
FIGURE 5LP4310 OUTLINE and INTERCONNECT
TABLE 1CONNECTION COLOR CODE
SECTION 1.0 DESCRIPTION
The Eagle Microsystems Model LP4310 is a low profile industrial floor scale available in four sizes; 30" x
30", 36" x 36", 42" x 42" and 48" x 48".
LP4310 IB.DOC
9/16/04
Fig. 1: LP4310
The LP4310 was designed for easy installation and maintenance. All maintenance and calibration work is
performed from the top surface and does not require the removal of any decking or lifting the scale to
adjust the leveling
SECTION 2.0 PREPARAT ION FOR USE
2.1 RECEIVING INSPECTION
1. Upon receiving the scale, carefully inspect the condition of the crate including the banding
and any protective covering used for shipping. Report any damage to the shipper and to
Eagle Microsystems.
2. Remove the scale from crating and inspect for damage. Report any damage to the shipper
and to Eagle Microsystems.
3. The scale is shipped with one (1) leveling feet removed. The leveling foot is packaged and
Strapped to the cable. Keep this with the scale untill instllation time.
2.2 SHIPMENT
Should re-shipment of your scale become necessary.
1. Use a strong, well built crate. The crate must be larger than the outer dimensions of the
scale to protect it in shipping.
2. Make sure the hook-up cable is protected and secured in crate.
4. Use strong banding to secure scale in shipment.
2.3 SITE SELECTION
1. Line power devices causing large inductive currents should not run off the same circuit as
the scale. Fluctuations in line voltage caused by such devices may result in display instability.
LP4310 IB.DOC
9/16/04
2. The hook-up cable to the read-out should not run close to other unshielded cables. Display
instability may result.
3. For best accuracy, a flat, level, and rigid surface is recommended to support the scale.
5. The area should be accessible for periodic cleaning.
2.4 INSTALLING ( refer to LP4310 Outline & Interconnect Dwg. at the end of this manual)
1. Clean the site area of dirt and debris.
2. The scale should be oriented so that loading will be from the hinge side of the scale. Secure the 2
“hinge brackets” to the floor with four (4) appropriately selected 3/8” diameter anchor bolts.
3. With the bottom of the scale exposed, install the leveling foot in the load cell. Screw the foot all
the way untill it bottoms out on the load cell.
2.5 LEVELING
SLOT TYPE
SCREW DRIVER
ADJUSTMENT
ACCESS HOLE
FOOT
Fig. 2: Detail showing easy leveling adjustments
with scale in place. A screw driver is the only tool needed.
1. For best scale performance scale should be level within 1/2 degree.
.
2.6 HOOK-UP CABLE
Table 1 shows the wiring connections necessary to attach the platform to the read-out instrument. The
color code and function are as noted.
COLORFUNCTION
BLACK– EXCITATION
WHITE– SIGNAL
GREEN+ SIGNAL
RED+ EXCITATION
Table 1
SECTION 3.0 TROUBLE SHOOTING
The following is a list of potential problems and likely cures.
LP4310 IB.DOC
9/16/04
1. Inaccurate but repeatable weight readings:
a.Adjust span on read-out (see instrument manual)
2. Blank or drifting display:
a.Consult the instrument manual.
b. Look for loose connection in hook-up cable at the instrument.
c.Test for bad load cell (Section 4.1).
SECTION 4.0 SERVICING
4.1 Checking the load cell.
1. Load Cell resistance test:
a.Disconnect the load cells from the instrument and measure the resistance as shown in
Figure 3.
b. Any electrical leakage between the leads and the load cell case is usually caused by moisture
leakage into the load cell or by moisture in a damaged load cell cable.
c.If a load cell does not pass the above resistance tests, replace it with a known good one.
LOAD CELL WIRING
LOAD
CELL
LOAD CELL RESISTANCE CHECK
RED TO BLACK 360
GREEN TO WHITE 350 +/- 5
RED, BLACK, GREEN,
WHITE, OR YELLOW
TO CASE
* Using a portable Ohm meter on highest range you should read infinity
2. Load Cell zero shift test:
a.Remove all the weight from the load cell and measure the output as shown in
Figure 4.
b. Connect a DC power supply of 10 or 15 volts to the Red (+) and Black (-) excitation load cell
leads.
RED +EXT
BLK -EXT
GRN +SIG
WHT -SIG
YEL SHLD
Ω
Ω
GREATER THAN 200
MEGOHMS *
FIGURE 3
c.The measured output between the Green (+) and White (-) signal leads should be less
than 5 millivolts.
LP4310 IB.DOC
9/16/04
d. An output signal greater than 5 millivolts indicates a zero shift caused by mechanical
overload.
e. If the output signal is between 5 and 15 millivolts, the load cells zero has shifted but will
probably still continue to work.
f.If the output signal is greater than 15 millivolts, the load cell should be replaced with a
known good one.
LOAD CELL WIRING
RED +EXT
LOAD
CELL
LOAD CELL VOLTAGE CHECK (WITH 15V EXCITATION)
BLACK TO WHITE:+7.5V (EXCITATION / 2)
BLACK TO GREEN:+7.5V (EXCITATION / 2)
BLACK TO RED:+15V
LOAD CELL OUTPUT
GREEN TO WHITE:LESS THEN +/- 5 MILLIVOLTS (NO DEAD LOAD)
LESS THEN 25 MILLIVOLTS (EXACT OUTPUT
VOLTAGE DEPENDS ON DEAD LOAD WEIGHT)
NOTE:If the load cell's zero has shifted due to a mechanical overload, the reason for the
overload should be determined before a new load cell is installed.
4.2 REPLACING THE LOAD CELL
BLK -EXT
GRN +SIG
WHT -SIG
YEL SHLD
FIGURE 4
Call the factory to advise that the load cell is defective. Report model and serial numbers for both load cell
and scale.
1.Remove all weight from scale.
2.Stand the scale on its side. Use caution; make sure that the hook-up cable is not being damaged.
3.Disconnect the wires of defective load cell being replaced. Gently pull cable out of the frame.
4.Use 3/4 wrench to remove 2 hext head cap screws which secure load cell to frame.
5.Install new load cell using 35 ft. lbs. torque to screws.
6.Insert leads into terminal as before and tighten.
7.With a screw driver, adjust the leveling foot until scale is level.
SECTION 5.0 SPECIFICATIONS
PHYSICAL SIZE:Model LP4310
LP4310 IB.DOC
9/16/04
30" x 30", 36" x 36", 42" x 42", and 48" x 48".
WEIGHT:33" x30" = 96 lbs, 36" x 36" = 115 lbs
42" x 42" = 135 lbs, 48" x 48" = 162 lbs
CONSTRUCTION:Welded steel and formed plate.
FINISH:Primer and Poline paint
CAPACITY:1000, 2000 and 4000 LB cap.
SAFE OVERLOAD:200% of Rated Capacity.
ULTIMATE OVERLOAD:400% of Rated Capacity.
NOMINAL OUTPUT: 1.0 mV/V at full scale
OPERATING ACCURACY:0.5% of Capacity with repeatable load placement.
REPEATABILITY:0.2 % of Capacity with repeatable load placement.
LOAD CELL:1 stainless steel strain gage beam, 350 Ω.
HOOK-UP CABLE:15' of 4 conductor color coded shielded cable.
SECTION 6.0 SPARE PARTS LIST
PART DESCRIPTION MODEL/CAPACITY
S.S. Load Cell1,000 lbs F.S.
S.S. Load Cell3,000 lbs F.S.
S.S. Load Cell4,000 lbs F.S.
S.S. 1/2-20 live foot All sizes and capacities
LP4310 IB.DOC
9/16/04
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.