Dynalco SW-200B User Manual

Installation and Calibration Instructions
SW-200B Speed Switch
1. Installation: Mount the SW-200B to a secure bracket off the engine. If
on-engine mounting is necessary , shock mounts are recommended. Wire according to connection diagram on reverse. Shielded cable is recommended. Shield should be brought to ground directly . The SW-200B will work with most magnetic pickups provided the signal amplitude is greater than 50 mVrms and less than 70 V rms. Mount pickup according to manufacturers instructions.
2. Calibration: Determine the setpoint frequencies from an RPM value using the following formula:
Frequency =
A. Verify the current calibration: use a signal generator . Connect it to the
SW-200B magnetic pickup input.
B. Confirm the DIP switches are properly set for the frequency range and
overspeed relay logic desired. (See chart below.)
C. Set the signal generator output to at least 10% below the lowest setpoint.
Slowly increase the frequency. Using an ohmmeter across the relay contacts, determine the frequency at which each relay changes state.
a. Change a setpoint: remove the appropriate access hole screw to reach
the setpoint's relay adjustment trim pot.
b. Set the signal generator to the frequency at which the relay should change
state. Connect it to the SW-200B magnetic pickup input.
c. Using a small, flat screwdriver, adjust the trim pot for the appropriate
relay until the relay changes state.
d. Decrease the frequency, then slowly increase it to verify that the relay
trips at the appropriate point.
RPM x No. of Teeth (Holes)
60
Replace the access hole screw
.
DIP SWITCH SETTINGS
Switches 1 & 2 set the
DIP
SW 1
OFF OFF = 0 – 11,200 Hz ON N/A =
OFF ON = 0 – 5,000 Hz OFF N/A =
ON ON = 0 – 1,000 Hz N/A ON = Latches
DYNALCO CONTROLS RESERVES THE RIGHT TO CHANGE THESE SPECIFICATIONS WITHOUT NOTICE.
(
© 2002 Azonix-Dynalco 145F-12044, Rev 0
DIP
SW 2
Azonix-Dynalco, 3690 N.W. 53rd Street, Fort Lauderdale, FL 33309 U.S.A.
954) 739-4300 • Fax (954) 484-3376 • www.dynalco.com • mailbox@dynalco.com
Full-Scale
Range
SW-200B is a trademark of Dynalco Controls
Switches 3 & 4 set the
overspeed relay logic
DIP
SW 3
N/A OFF =
DIP
SW 4
Relay Logic
Energizes
Above
Setpoint
De-Energize
Above
Setpoint
Does not
Latch
CONNECTION DRAWINGS