Bulletin AV-2-DAFM
Series DAFM Duct Air Flow Measuring Probe
Specifications - Installation and Operating Instructions
1
[25.40]
1/8
[3.18]
[3.18]
1/2
[12.39]
1/8
1/2
[12.39]
1/4˝ BARB FITTINGS TO
BE CENTERED ON PLATE
1-7/19
[36.51]
6
[152.40]
Ø1/4
[6.35]
1-1/16
[52.39]
4X
1/2
L
[12.70]
5
[127.00]
Ø1/4
[6.35]
3/8
[9.52]
The DAFM Model Duct Air Flow Measuring Probe uses evenly
distributed total and static pressure measuring points to deliver an
accurate measurement of flows in a duct. The Air Flow Measuring Probe
can be completely installed from outside of the duct making it very easy to
install. With its lightweight and durable construction in addition to its ease
of installation, this product lends itself to being used in the HVAC industry.
These air flow measuring probes may be ordered to fit into either round or
rectangular duct installations.
INSTALLATION
When you unpack the Model DAFM Duct Air Flow Measurement Probe
ensure that there is no visible damage from shipping. Inspect each sensing
point on the probes to ensure that they are not filled with debris from
shipping. If there is obvious shipping damage, the probe must be replaced
prior to use in order to avoid inaccurate measurements. Please contact
Dwyer Instruments, Inc. if it is necessary to replace your air flow
measurement probe.
1/8
[3.18]
4
[101.60]
1/2
2X
[12.70]
[12.70]
1/2
2
[50.80]
6
[152.40]
Ø1/4
[6.35]
1-7/16
[36.51]
2-1/16
[52.39]
4X
L = Smallest Duct Diameter
or Length
L
1/2
[12.70]
5
[127.00]
Ø1/4
[6.35]
3/8
[9.52]
2X
SPECIFICATIONS
Wetted Materials: Aluminum with clear anodized finish.
Accuracy: ±2% (Note: Field Calibration May Be Required).
Max. T emperatur e:400ºF (204ºC).
Minimum Design Flow: 400 fpm (2.03 m/sec).
Maximum Design Flow: 12,000 fpm (60.96 m/sec).
Process Connections: 1/4˝ barb.
Straight Run Requirements: 5 diameters or longest side dimensions.
RECTANGULAR DUCT MODELS
Determining Probe Number and Placement for Rectangular Ducts
1. To determine the number of probes you need please consult the chart
below.
Example: You have a duct with a 24˝ side, and upon consulting the chart
Short Duct Dimension
Number of Probes
<12˝
1
12˝ - 23˝
2
24˝ - 35˝
3
36˝ - 59˝
4
60˝ - 89˝
5
>89˝
6
determined that you needed 3 probes for this size duct.
24 / 3 = 8
2. In order to determine where to place your probes, divide the short duct
dimension by number of probes.
3. Divide the result by two and this will be the distance from the side of
the duct to the first probe location.
4. The next probe will be placed two times the resulting distance from
step two from the first probe. So, if the first probe was placed 4˝ from
the side of the duct, your next probe would be placed 8” from the first
Therefore, the first probe is placed 4˝ from the side of the duct.
The second probe is placed 4˝ + 8˝ = 12˝ from the side of the duct.
8 / 2 = 4
probe, or 12˝ from the side of the duct.
5. Continue this pattern until you have determined all probe locations.
DWYER INSTRUMENTS, INC.
The third probe is placed 4˝ + (2 x 8˝) = 20˝ from the side of the duct.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
DAFM DAFM
4˝
12˝
20˝
AIR FLOW
DAFM
ROUND DUCT PROBE INSTALLATION
1. Cut 4˝ X 1˝ holes at locations calculated above in side of duct.
2. Place silicon bead around holes.
Long Duct Dimension
3. Slide DAFM into holes and screw four self drilling screws into duct to
attach DAFM.
4. Connect 1/4˝ OD plastic tubing to barb fittings on DAFM.
5. Check all fittings and tubing connections for leaks using a leak
detector.
6. Tee all high and low ports into one high and one low line and connect
to transmitter or gage.
7. The devices should be checked once a year for build-up of dirt of
debris common in an HVAC system.
24˝
Short Side Duct Dimension
Figure 1: Top view illustration of probe placement example.
Note: Illustration not to scale.
Please note that all probes should be installed vertically and
running parallel to each other if installed in a rectangular duct.
RECTANGULAR DUCT PROBE INSTALLATION
1. Cut 4˝ X 1˝ holes at locations calculated above in side of duct.
2. Place silicon bead around holes.
3. Slide DAFM into holes and screw four self drilling screws into duct to
attach DAFM.
4. Connect 1/4˝ OD plastic tubing to barb fittings on DAFM.
5. Check all fittings and tubing connections for leaks using a leak
detector.
6. Tee all high and low ports into one high and one low line and connect
to transmitter or gage.
7. The devices should be checked once a year for build-up of dirt of
debris common in an HVAC system.
CIRCULAR DUCT MODELS
Determining Probe Number and Location for Round Ducts
1. Note that in round ducts only two probes are needed. The quantity of
probes needed does not depend on size of the duct.
2. Locate probes 90 degrees apart. See Figure 2 for an example.
CALIBRATION
Sometimes field calibration may be required if the probe is installed in a bad
location i.e. immediately downstream of an elbow. In or der to calibrate, you
must either perform a traverse of the duct or a sum of the air registers and
compare this with the DAFM output. Then, you must make the correction
to the effective area in the computer to make up for the error.
MAINTENANCE
Upon final installation, the device should be checked once a year for a build
up of dirt or debris that can be common in an HVAC system. Also check
the mounting stability once a year. Other than this no routine maintenance
is required. The DAFM model is not field serviceable and should be
returned if repair is needed (field repair should not be attempted and may
void warranty). Be sure to include a brief description of the problem plus
any relevant application notes. Contact customer service to receive a
return goods authorization number.
D
A
90°
F
M
DAFM
Figure 2: Cross-sectional view of probe placement in a round duct.
©Copyright 2008 Dwyer Instruments, Inc. Printed in U.S.A. 10/08 FR# R1-443660-00