WARNING: Please refer to the System Installation Manual for information on limitations regarding product use
and function and information on the limitations as to liability of the manufacturer.
NOTE: These instructions shall be used in conjunction with the system Installation Manual of the Control Panel
with which this equipment is intended to be used.
9
0
#
Page 2
The PK5500 keypad can be used on security systems with up to 64
Knock Out
Knock Out
Knock Out
Wiring Slot
Tamper
Hooks
zones. These keypads are compatible with the latest version of the
folllowing DSC security systems:
•PC580•PC585•PC1555MX •PC1565
•PC1616•PC1832•PC1864•PC5005
•PC5008•PC5010•PC5015•PC5016
•PC5020
Specifications
• Temperature range: -10°C to +55°C (14°F to 131°F)
• Humidity (MAX): 93%R.H.
• Plastic enclosure protection degree: IP30, IK04
• Voltage rating: 12V
• Connects to control panel via 4-wire Keybus
• 1 keypad zone input/PGM output*
• PK5500 Current Draw: 50mA (standby)/125mA (maximum)
• Wall mount tamper
• 5 programmable function keys
• Ready (Green LED), Armed (Red LED), Trouble (Yellow LED), A C (Green LED)
•Low temperature sensor: Alarm 6°C (43°F)/Restore 9°C (48°F)
NOTE: * Zone not to be programmed as Fire type or 24h type.
Unpacking
The Power keypad package includes the following parts:
Mount the keypad where it is accessible to designated points of entry
and exit. Once you have selected a dry and secure location, perform
the following steps to mount the keypad.
Disassemble Keypad
1. I nsert a flat head screwdriver into the provided slot (first of two).
2. Move screw driver toward the back plastic and lift as in the following
diagram. This will unhook one side of the front plastic.
3. Repeat step # 1 and 2 on the second provided slot to disconnect
the front plastic and allow access for wiring.
DC nominal
1
Mount and Wire Keypad
1.
3.
Hooks
Tam p e r
2.
4.
2
Press to Snap
3
Swing
to engage
1. Secure Keypad to wall using mounting holes. Use all 4 screws provided
unless mounting on a single gang box.
2. Place keypad into hooks on the backplate and swi ng down to engage.
3. Run wire through wiring slot or knockouts. Connect Keybus and PGM/Zone
wiring to keypad. Place tamper switch into tamper hole on backplate.
4. Remove keypad from hooks. Place keypad into back plate, ensure the wire
is pushed back into the wall as much as possible. Route the wire inside
the keypad ensuring high components are avoided. Snap the front assembly closed, ensuring there is no pressure to the keypad from the wire
below.
NOTE: If any tension found between the front keypad assembly
and wiring, please open the keypad reroute the wire and close
again. Repeat these steps until the keypad is closed properly.
Wiring
1. Before wiring the unit, ensure that all power (AC transformer and battery)
is disconnected from the control panel.
2. Connect the four Keybus wires from
the control panel (red, black, yellow
and green) to the keypad terminals.
Refer to diagram.
3. If programmed as an input, you can
connect a device - such as a door
contact - to the ‘P/Z’ terminal of the
keypad. This eliminates the need to
run wires back to the control panel for
the device. To connect the zone, run one wire from the device to the ‘P/Z’
terminal and the other wire from the device to the B (black) terminal. For
powered devices, run the red wire to the R (positive) terminal and the
black wire to the B (negative) terminal. When using end of line supervision, connect the zone according to one of the configurations outlined in
your system’s Installation Manual.
4. If the ‘P/Z’ terminal is programmed as an output, the output follows the
PGM programmed in Section [080]. A small relay, buzzer or other DC
operated device may be connected between the positive supply voltage
and the ‘P/Z’ terminal (maximum load is 50mA).
Applying Power
Once all wiring is complete, and the equipment is secured to the building
structure with at least two screws apply power to the control panel:
1. Connect the battery leads to the battery.
2. Connect the AC transformer.
For more information on control panel power specifications, see the control
panel Installation Manual.
PK5500
RED
BLK
YEL
GRN
To zone or
PGM output
Page 3
Programming the Keypad
Toggle Option
1 _ _ 4 _ _ _ _
There are several programming
options available for the keypad.
These are described below. Programming the keypad is similar
to programming the rest of the system. When you are in the keypad programming sections, the keypad will display which options are turned on
along the top of the display. To turn an option on or off, press the number
corresponding to the option on the number pad. The numbers of the options
that are currently turned ON will be displayed. For example, if options 1
and 4 are on, the display will look like diagram shown on the different keypad displays.
For information on programming the rest of your security system, please
refer to your system’s Installation Manual.
Broadcasting LCD Labels
All LCD programming is done per keypad. If more than one LCD keypad is
present on the system, labels programmed at one keypad can be broadcast
to all other LCD keypads. Perform the following procedure in order to broadcast labels:
Step 1 - Program one LCD keypad completely.
Step 2 - Make sure all LCD keypads are connected to the Keybus.
Step 3 - Enter keypad programming by pressing [,][8][Installer
Code][,], then enter section [998] at the keypad that was programmed.
The keypad will now broadcast all the information programmed to all the
other LCD keypads on the system.
Step 4 - When the keypad is finished press the [#] key to exit.
NOTE: LCD Label broadcast from this keypad is only compatible
with other PK5500 keypads.
Language Programming
Hold (<>) keys for 2 seconds to enter language programming, scroll to
the desired language and Press [,] to select.
NOTE: If section [077] option 4 is OFF, language programming
can only be performed while in installers programming.
Enrolling the Keypad
The keypad will need to be assigned to a partition and slot if supervision or
keypad zones are being used. Keypad assignments and keypad option programming must be done at each keypad individually.
The 1st digit of keypad assignment is used to determine partition assignment (1 to 8). If partitioning is not used, enter [1]. For Global Keypads,
enter [0].
The 2nd digit of keypad assignment is used to determine slot assignment
for keypad supervision. Each keypad will be assigned a different slot number from 1 to 8. PK5500 LCD keypads come defaulted in slot 8. If LCD keypads are used one LCD keypad must remain in slot 8.
Enter the following at each keypad installed on the system:
1. Enter Installer Programming by pressing [,][8][Installer’s Code]
2. Pres s [000] fo r Keypad Pr ogrammin g
3. Press [0] for Partition and Slot Assignment
4. Enter the 1st digit (0 to 8 for partition assignment)
5. Enter the 2nd digit (1 to 8 for slot assignment supervision)
6. Press the [#] key twice to exit programming.
7. After assigning all keypads, perform a supervisory reset by entering
[,][8][Installer’s Code][902] and wait for 60 seconds.
8. Press the [#] key to exit programming after 60 seconds.
Programming Labels
1. Enter keypad programming by pressing [,][8][Installer Code][,]. Enter
the 3-digit section number for the label to be programmed.
2. Use the arrow keys (<>) to move the underline bar underneath the letter to be changed.
3. Press the number keys [1] to [9] corresponding to the letter you require.
The first time you press the number the first letter will appear. Pressing the
number key again will display the next letter
.
[1] - A, B, C, 1 [4] - J, K, L, 4 [7] - S, T, U, 7 [0] - Space
[2] - D, E, F, 2 [5] - M, N, O, 5 [8] - V, W, X, 8
[3] - G, H, I, 3 [6] - P, Q, R, 6 [9] - Y, Z, 9,0
4. When the required letter or number is displayed use the arrow keys
(<>) to scroll to the next letter.
5. When you are finished programming the Zone Label, press the [,] key,
scroll to “Save,” then press [,].
6. Continue from Step 2 until all Labels are programmed.
ASCII Characters
Changing Brightness/Contrast
1. Press [,][6][Master code].
2. Use the [<][>] keys to scroll to either Brightness Control or Contrast
Control.
3. Press [,] to select the setting you want to adjust.
4. a) ‘Brightness Control’: There are multiple backlighting levels. Use the
[<][>] keys to scroll to the desired level.
b) ‘Contrast Control’: There are 10 different display contrast levels. Use the
[<][>] keys to scroll to the desired contrast level.
5. To exit, press [#].
Changing the Buzzer Level
1. Press [,][6][Master Code].
2. Use the [<][>] keys to scroll to Buzzer Control.
3. There are 21 different levels, use the [<][>] keys to scroll to the
desired level.
4. To exit, press [#].
Emergency Keys
Press the () key for 2 seconds to send a Fire transmission.
Press both () keys simultaneously for 2 seconds to send a
Panic transmission.
Broadcasting Door Chime
All door chime programming is done per keypad. If more than one keypad is present on the system, door chime programmed at one keypad can
be broadcast to all other keypads. Perform the following procedure in
order to broadcast door chime:
Step 1 - Program one keypad completely.
Step 2 - Make sure all keypads are connected to the Keybus.
Step 3 - Enter keypad programming by pressing [,][8][Installer
Code][,], then enter section [994] at the keypad that was programmed. The keypad will now broadcast all the door chime information programmed to all the other keypads on the system.
Step 4 - When the keypad is finished press the [#] key to exit.
Page 4
Limited Warranty
Digital Security Controls warrants that for a period of 12 months
from the date of purchase, the product shall be free of defects in
materials and workmanship under normal use and that in fulfilment of any breach of such warranty, Digital Security Controls
shall, at its option, repair or replace the defective equipment
upon return of the equipment to its repair depot. This warranty
applies only to defects in parts and workmanship and not to
damage incurred in shipping or handling, or damage due to
causes beyond the control of Digital Security Controls such as
lightning, excessive voltage, mechanical shock, water damage,
or damage arising out of abuse, alteration or improper application of the equipment.
The foregoing warranty shall apply only to the original buyer,
and is and shall be in lieu of any and all other warranties,
whether expressed or implied and of all other obligations or liabilities on the part of Digital Security Controls. Digital Security
Controls neither assumes responsibility for, nor authorizes any
other person purporting to act on its behalf to modify or to
change this warranty, nor to assume for it any other warranty or
liability concerning this product.
In no event shall Digital Security Controls be liable for any direct,
indirect or consequential damages, loss of anticipated profits,
loss of time or any other losses incurred by the buyer in connection with the purchase, installation or operation or failure of this
product.
WARNING: Digital Security Controls recommends that the entire
system be completely tested on a regular basis. However,
despite frequent testing, and due to, but not limited to, criminal
tampering or electrical disruption, it is possible for this product to
fail to perform as expected.
Important Information: Changes or modifications not expressly
approved by Digital Security Controls could void the user’s
authority to operate this equipment.
EN50131-1 Grade 2, Class II
Operating Instructions shall be made available to the end user.
ONI____I1Hold [P]anic Key prompt ONHold [P]anic Key prompt OFF
ONI____I2Auto-arm Control/Time prompt ONAuto-arm Control/Time prompt OFF
ONI____I3Quick Arm prompt ONQuick Arm prompt OFF
ONI____I4Interior Arm prompt ONInterior Arm prompt OFF
OFFI____I5Quick Exit prom pt ONQuick Exit prompt OFF
OFFI____I6Thermostat Control prompt ONThermostat Control prompt OFF
OFFI____I7ACK All Trouble Prompt ONACK All Trouble Prompt OFF
OFFI____I8Music Input prompt ONMusic Input prompt OFF
[072] Second User Display Mask
DefaultOptionONOFF
ONI____I1User-initiated Call-up prompt ONUser-initiated Call-up prompt OFF
OFFI____I2For Future Use
OFFI____I3Walk Test prompt ONWalk Test prompt OFF
ONI____I4Command Output#1 prompt ONCommand Output#1 prompt OFF
ONI____I5Command Output#2 prompt ONCommand Output#2 prompt OFF
OFFI____I6Command Output#3 prompt ONCommand Output#3 prompt OFF
OFFI____I7Command Output#4 prompt ONCommand Output#4 prompt OFF
OFFI____I8For Future Use
[073] Download LCD Message Duration
Default: 003 I_______I_______I_______I (Valid entries are 000-255), 000=Unlimited Message Disp.
This number represents the number of times the downloaded message is cleared by pressing any key while the message is up after timeout).
Page 7
[074] Key Options
DefaultOptionONOFF
ONI____I1[F]ire Key Enabled[F]ire Key Disabled
ONI____I2For Future Use
ONI____I3[P]anic Key Enabled[P]anic Key Disabled
OFFI____I4-8For Future Use
[076] First Keypad Options
DefaultOptionONOFF
ONI____I1Display Code when ProgrammingDisplay “Xs” when Programming
ONI____I2Local Clock Display ONLocal Clock Display OFF
OFFI____I3Local Clock Displays 24-hr TimeLocal Clock Displays AM/PM
ONI____I4Auto Alarm Memory Scroll EnabledAuto Alarm Memory Scroll Disabled
OFFI____I5Local Display of Temperature ONLocal Display of Temperature OFF
ONI____I6Bypass Options prompt ONBypass Options prompt OFF
OFFI____I7For Future Use
OFFI____I8Auto-Scroll Open Zones ONAuto-Scroll Open Zones OFF
[077] Second Keypad Option
DefaultOptionONOFF
ONI____I1Chime Enabled for Zone OpeningsChime Disabled for Zone Openings
ONI____I2Chime Enabled for Zone ClosingsChime Disabled for Zone Closings
OFFI____I35th Terminal is Keypad PGM Output5th Terminal is Keypad Zone Input
ONI____I4Language Selection EnabledLanguage Selection Disabled
OFFI____I5Power LED EnabledPower LED Disabled
ONI____I6Power LED indicates AC presentPower LED indicates AC absent
ONI____I7Alarms always Displayed When ArmedAlar ms not Displayed When Armed
OFFI____I8*Low Temperature Warning EnabledLow Temperature Warning Disabled
*The Low Temperature Warning is violated at 6°C (43°F) and restored at 9°C (48°F).
[080] PGM Terminal 1
Default: 01
I_______I _______I 1-14 Follow PGM Output Number, 15 Local PGM Pulse , 16 Local PGM Toggle
[082] Local PGM Output Pulse Activation Time
Default: 00
I_______I _______I Minutes (Valid Range 00-99)
Default: 05 I_______I _______I Seconds (Valid Range 00-99)
[101]-[108] Partition Labels
s
ex. For Partition 1 enter section [101], for Partition 2 enter section [102] etc.
NOTE: Partition 1 Label is also used as the System Labe l.
Page 8
[120]-[151] Command Output Labels
12
9
10
11
12
7
8
Default: “Command_O/P_1” - “Command_O/P_4”
For Partition 1 Command O/P 1 to 4 enter [120] to [123]For Partition 5 Command O/P 1 to 4 enter [136] to [139]
For Partition 2 Command O/P 1 to 4 enter [124] to [127]For Partition 6 Command O/P 1 to 4 enter [140] to [143]
For Partition 3 Command O/P 1 to 4 enter [128] to [131]For Partition 7 Command O/P 1 to 4 enter [144] to [147]
For Partition 4 Command O/P 1 to 4 enter [132] to [135]For Partition 8 Command O/P 1 to 4 enter [148] to [151]
SectionPart
[120]-[151]1to81to4
[201]-[264] Door Chime Sound Programming
You can program the keypad to make up to four different door chime sounds for individual zones.
ex. For Zone 1 enter section [201], for Zone 2 enter section [202] etc.
[994][,] Initiate Global Keypad Chime Br oadcast
[995][,] Reset Keypad Options to Factory Default
[996][,] Label Default
[997] View Software Version
[998][,] Initiate Global Label Bro adcast
[999][,] Reset Keypad EEPROM to Facto ry Defaults
Keypad Display Symbols
2
1
3
4
5
6
8
1 Fire – Indicates that there are fire al arms in memory.
2 Memory – Indicates that there are alarms in memory.
3 Ready Light (green) – If the Ready light is on, the system is ready for arming.
4 Armed Light (red) – If the Armed light is on, the system has been armed successfully.11
5 System Trouble – Indicates that a system trouble is active.
6 AC – Indicates that AC is present at the main p anel.
7 Program – Indicates that the system is in Installer’s Programming, or the keypad is busy.
7
8 Bypass – Indicates that there are zones automatically or manually bypassed.
9 For Future Use
10 Arm Mode – Indicates the mode the panel is armed in.
Stay – Indicates that the panel is armed in the Stay Mode. It wil l turn on at the beginning of the Exit
Delay
Away – Indicates that the pane l is armed in the Away Mode. It will turn on at the beginn ing of the
Exit Delay
Chime – This icon turns on when Door Chime is enabled on the system and will turn off when Do or
Chime is disabled.
Open – When zones are opened, this icon will turn on, and 7 segment displays 1 and 2 will scroll
12
through the open zones.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.