Dsc PC585 INSTALLATION

WARNING
This manual contains information on limitations regarding product use and function and information on the
limitations as to liability of the manufacturer. The entire manual should be carefully read.
Installation
Manual
Software Version 2.3 / DLS-1 v6.7 and up
See Back Cover for New Features in Version 2.3
WARNING Please Read Carefully
This warning contains vi tal infor mation. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system.
System Failures
This system has been carefully designed to be as e ffective as possible. There are circu mstances, however, involving fire , burglary, or other types of emergencies where it may not provide prote ction. Any alar m sys­tem of any type may be compromised deliberately or may fail to opera te as expected for a variety of reasons. Some but not all of thes e reasons may be:
Inadequate Installation
A security system must be installed properly in order to provide adequate protection. Every i nstallation should be evaluat ed by a secu rity profes sional to ensure that all access points an d areas are covered. Locks and latches on windows and doors m ust be sec ure and op erate as i ntended. Windows, doors, walls, ceilings and other building materials must be of sufficient strength and construction to provide the level of protection expected. A reevaluation must be done during and after any construction activity. An evaluation by the fire and/or police department is highly recommended if this ser vice is available.
Criminal Knowledge
This system co ntains security features which were known to be effective at the time of manufactu re. It is pos­sible for persons with criminal intent to develop techniques which reduce the effectiveness of these features. It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it does not provide the protection expected.
Access by Intruders
Intruders may enter through an unprotected acces s point, c ircumvent a sensing device , evade detection by moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent the proper op eration of the system.
Power Failure
Control units, intrusion detectors, smoke detectors and many other security devices require an adequate power supply for proper operation . If a device operates from batteries , it is pos sible for the batteries t o fail. Even if the batt eries have not failed, they must be charged, in good condition and installed correctly. If a device operates only by AC power, any inter ruption , however brief, will render that device inoperative while it does not have power. Power inter ruptions of any length are often accompanied by voltage fluctuatio ns which may damage electronic equipment such as a security system. After a power interruption has occurred, immediately conduct a compl ete system test to ensure that the system oper ates as intended.
Failure of Replaceable Batteries
This system’s wireless transmitters have been designed to provide several years of battery life under normal conditions. The expected battery life i s a function o f the device environment, usage a nd type. Ambient con­ditions such a s high humidity, high or low temperatures, or large temperature fluctuations may red uce the expected battery life. While each tr ansmitting device has a low battery monitor which iden tifies when the batteries nee d to be replaced, this monito r may fail to operate as expected. Regu lar testing and mainte nance will keep the system in good operating condition.
Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver und er all circumstances which could include metal objects placed on or near the radi o path or d eliberate ja mming or other inadvertent radio s ignal interference.
System Users
A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physical disabili ty, inability to reach the d evice in time, or unfamiliari ty with the cor rect operat ion. It is important that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm.
Smoke Detectors
Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of rea­sons, some of which follow. The smoke detec tors may have been improperly installed or positioned. Smoke may not be able t o reach the smoke dete ctors, such as when the fire is in a chimney, walls or roofs , or on the other side of c losed doors. Smoke detectors may not detect smoke from f ires on ano ther level of the resi­dence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot sense all types of f ires eq ually well. Smoke detectors may not provide timely warning of fires caused by carelessness or safety hazards suc h as smoking in bed, violen t explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, chil dren playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insuff icient warn­ing to allow all occupants to escape in time to avoid injury or death.
Motion Detectors
Motion detectors can only detect motion within t he designate d areas as shown in their respective insta llation instructions. They cannot discriminate between intruders and intended occupants. Motion detectors do not provide volumetric area pr otection. They have multip le beams of detection and motion can only be detected in unobstructed areas covered by these beams. They cannot detect motion which occurs behind walls, ceil­ings, floor, closed doors, glass partitions, glass doors o r windows. Any type of t ampering whether intentional or unintentional such as masking, painting, or spraying o f any material on the lenses, mir rors, windows or any other part of the detection system will impair its proper operation. Passive infr ared moti on de tect ors opera te by se nsin g changes in tempera ture . However their effectiven ess can be reduced when the ambient t emperature rises near or a bove body temperature or if there are intention al or unintentional sources of heat in or near the det ection area. Some of these heat sourc es could be heaters, radiators, st oves, barbeques, firepl aces, sunlight, steam vents, lighting and so on.
Warning Devices
Warning devices such as sirens , bells, h orns, or strobes may not warn people or waken someone sl eeping if there is an intervening wall or door. If warning devices are located on a different level of the residence or premise, then it is less likely that the occupants w ill be alerted or awakened. Audible warning devices may be interfered wit h by other noise sources such as ste reos, radios, televisions, air conditioners or other appli­ances, or passi ng tr aff ic. Audible war ning devices, however lo ud, may not be heard by a hearing-im pair ed person.
Telephone Lines
If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time. Also an intruder may cut the te lephone line or defe at its op eration by mo re sophist icated mea ns which may be difficult to dete ct.
Insufficient Time
There may be circumstances when the sy stem will operate as intended, yet the occupants will not be pro­tected from the emergency due to their inability to respond to the warnings in a timely manner. If the system is monitored, the response may not occur in time to protec t the occupants or their belongings.
Component Failure
Although every effort has been made to make this system as reliable as possible, the system may fail to func­tion as intended due to the failure of a compo nent.
Inadequate Testing
Most problems that would prevent an alar m system from operating as inte nded can be found by regular test­ing and maintenance. The complete system shou ld be tested weekly and immediately after a break-in, an attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity insid e or outside the premises. The testing should include all sensing devices, keypads, consoles, alarm indicating devices and any other operational devices that are part of the system.
Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm sys­tem also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation.
Limited Warranty
Digital Security Controls Ltd. warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use. Dur­ing the war ranty perio d, Digital Securi ty Control s Ltd. shal l, at its option, re pair or replace any defe ctive product upon return of the product to its factory, at no charge for labour and materials. Any replacement and/ or repaired parts ar e warrante d for the remainder o f the original warranty or nine ty (90) days, whichever is longer. The original owner must promptly notify Dig ital Securi ty Controls Ltd. in wri ting that there is defect in material or workmanship , such wri tten notice to be re ceived in all events prior to expiration of the war­ranty period.
International Warranty
The warranty for international customers is the same as for any customer within Canada and the United States, with the exception that Digital Security Controls Ltd. shall not be responsible for any custo ms fees, taxes, or VAT that may be due.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in question to the point of purchase. All authorized distributors and dealers have a warranty program. Anyone returning goods to Digital Security Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment whatsoever for which prior authorization has no t been obtained.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:
• damage incurred in sh ipping or handling;
• damage caused by disaster such as f ire, flood, wind, earthquake or lig htning;
• damage due to causes beyond the control of Digital Security Controls Ltd. such as excessive voltage, mechanical shock or water damage;
• damage caused by unauthoriz ed attachmen t, alterations, modif ications or foreign objects;
• damage caused by peripheral s (unless such peripherals were supplied by Digital Security Controls Ltd.);
• defects caused by failure to provide a suitable installation environment for the products;
• damage caused by use of the products for purposes other than those for which it was designed;
• damage from improper maintenance;
• damage arising out of any other abuse, mishandling or improper application of the products.
Digital Securi ty Controls Ltd.’s liability for failure to repair the product under this warranty aft er a reason­able number of attempts will be limited to a replacement of the product , as the exclus ive remedy for breach of warranty. Under no circumsta nces shall Digital Security Controls Ltd. be liable for any special, incidental, or consequential damages based upon breach of warranty, breach of contract, negl igence, strict liability, or any other legal theor y. Such damages includ e, but are not limited to, loss of prof its, loss of the product or any associated equipment, cost of capital, cost of substitute or replacement equipm ent, facilit ies or services, down time, purchaser’s time, the claims of third parties, including customers, and injury to property.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed or implie d (including all implied warranties of merchantability or f itness for a par­ticular purpose) And of all oth er obligations or liabi lities on the part of Digital Security Controls Ltd. Digital Securi ty Controls Ltd. neit her assumes nor authorizes any other person purporting to act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or l iability concerning this product.
This disclaim er of warranties and limited warranty a re governed by the laws of the province of Ontario, Canada.
WARNING: Digital Securi ty Controls Ltd. recommends that the entire system be complet ely tested on a
regular basis . However, despite frequent te sting, and due to, but not limited to, crimi nal tamperin g or electri­cal disruption, it is possible for this product to fail t o perform as expected.
Installer’s Lockout
Any products returned to DSC which have t he Install er’s Lockout option enabled and exhibit no other prob­lems will be subject to a service charge.
Out of Warranty Repairs
Digital Security Controls Ltd. will at its opti on repair or replace o ut-of-warranty products which are returned to its factory according to the following conditions. Anyone returning goods to Digital Security Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment whatsoever for which prior authorization has not been obtained.
Products which Digital Security Controls Ltd. determines to be repairable will be repaired and returned. A set fee which Digital Security Controls Ltd. has predetermined and which may be revised from time to time, will be charged for each u nit repaired .
Products which Digital Security Controls Ltd . determines not to be repairable will be replaced by the near est equivalent product available at that time. The current market price of the replacement pro duct will be charged for each replacement unit.

Table of Contents

Section 1: System Introduction 1
1.1 Specifications ........................................................................1
1.2 Additional Devices ..............................................................2
1.3 Out of the Box .......................................................................2
Section 2: Getting Started 3
2.1 Installation Steps ..................................................................3
2.2 Terminal Descriptions .........................................................3
2.3 Keybus Operation and Wiring ...........................................4
2.4 Current Ratings – Modules and Accessories ...................4
2.5 Keypad Assignment ............................................................4
2.6 Supervision ...........................................................................5
2.7 Removing Modules ..............................................................5
2.8 Zone Wiring ..........................................................................5
2.9 Fire Zone Wiring ..................................................................6
2.10 LINKS Zone Wiring .............................................................6
2.11 Keypad Zones .......................................................................6
Section 3: Keypad Commands 8
3.1 Arming and Disarming .......................................................8
3.2 Auto Bypass – Stay Arming ...............................................8
3.3 Automatic Arming ...............................................................8
3.4 [*] Commands .......................................................................8
3.5 Function Keys .....................................................................11
3.6 Features Available for the LCD5500Z .............................12
Section 4: How to Program 13
4.1 Installer’s Programming ...................................................13
4.2 Programming Decimal Data .............................................13
4.3 Programming HEX Data ...................................................13
4.4 Programming Toggle Option Sections ............................14
4.5 Viewing Programming ......................................................14
Section 5: Program Descriptions 15
5.1 Programming Security Codes ..........................................15
5.2 Zone Programming ............................................................15
5.3 Zone Attributes ..................................................................16
5.4 Assigning Keypad Zones ................................................. 17
5.5 Communicator – Dialing .................................................. 17
5.6 Communicator – Account Numbers .............................. 17
5.7 Communicator – Telephone Numbers ........................... 17
5.8 Communicator – Reporting Codes ................................. 18
5.9 Communicator – Reporting Formats .............................. 19
5.10 Downloading ..................................................................... 20
5.11 PGM Output Options ....................................................... 21
5.12 Telephone Line Monitor (TLM) ...................................... 23
5.13 Bell ....................................................................................... 23
5.14 Test Transmission .............................................................. 23
5.15 Transmission Delay .......................................................... 23
5.16 Fire, Auxiliary and Panic Keys ........................................ 23
5.17 Arming/Disarming Options ........................................... 24
5.18 Entry/Exit Delay Options ................................................ 24
5.19 Swinger Shutdown ............................................................ 25
5.20 Event Buffer ....................................................................... 25
5.21 Keypad Lockout Options ................................................. 25
5.22 Keypad Blanking ............................................................... 25
5.23 Keypad Backlighting ........................................................ 25
5.24 Loop Response ................................................................... 25
5.25 Keypad Tampers ............................................................... 26
5.26 LINKS1000 Cellular Communicator ............................... 26
5.27 Additional System Modules ............................................ 26
5.28 Clock Adjust ....................................................................... 26
5.29 Timebase ............................................................................ 27
5.30 Resetting Factory Defaults ............................................... 27
5.31 Installer’s Lockout ............................................................. 27
5.32 Walk Test (Installer) .......................................................... 27
Section 6: Programming Worksheets 28
Appendix A: Reporting Codes 43
Appendix B: Programming LCD Keypads 45
i

PC585 Wiring Diagram

ii

Section 1: System Introduction

1.1 Specifications

Downloading Software Support
• PC585 v2.3 uses DLS-1 v6.7 and up.
Flexible Zone Configuration
• Four fully programmable zones
• System expandable to 32 zones using:
up to 8 keypad zone inputs and/or
up to 32 wireless zones with the PC5132 wireless expansion module
• 38 access codes: one master code, one maintenance code, two duress codes, two supervision codes and 32 general access codes
• 27 zone types; 8 programmable zone attributes
• Normally closed, single EOL and double EOL zone wiring
• 32 wireless zones with the PC5132 Wireless Receiver
Audible Alarm Output
• 700mA Supervised Bell Output (current limited at 3 amps),
DC
12V
• Steady or Pulsed Output
EEPROM Memory
• Does not lose programming or system status on complete AC and Battery failure
Programmable Outputs
• Two programmable outputs; 18 programmable options
• PGM1 = 50mA; PGM2 = 50mA
Powerful 1.5 Amp Regulated Power Supply
• 550 mA Auxiliary Supply, 12 V
• Positive Temperature Coefficient (PTC) components replace fuses
• Supervision for loss of AC power, low battery
• Internal clock locked to AC power frequency
Power Requirements
• Transformer = 16.5 V
• Battery = 12 volt 4 Ah minimum rechargeable sealed lead acid battery
Remote Keypad Specifications
• Keypads available:
- PC5509 eight zone LED keypad
- PC1555RKZ eight zone LED keypad with zone input
- PC5508Z eight zone LED keypad with zone input
- PC5516Z sixteen zone LED keypad with zone input
- PC5532Z thirty-two zone LED keypad with zone input
- LCD5500Z Alphanumeric keypad with zone input
• All keypads (except PC5509) have five programmable function keys
• Connect up to eight keypads
• 4-wire (Quad) connection to Keybus
• Built in piezoelectric buzzer
AC, 40VA
DC
Digital Communicator Specifications
• Supports major communication formats including SIA and Contact ID
• Event-initiated personal paging
• Three programmable telephone numbers
• Two account numbers
• Supports LINKS1000 cellular communication
• Supports LINKS2X50 long range radio transmitter
• DTMF and pulse dialing
• DPDT line seizure
• Anti-jam feature
• Split reporting of selected transmissions to each telephone number
System Supervision Features
The PC585 continuously monitors a number of possible trou­ble conditions including:
• AC power failure • AUX Power Supply Trouble
• Fault by zone • Loss of internal clock
• Tamper by zone • Bell output trouble
• Fire trouble • Telephone line trouble
• Failure to communicate • Low battery condition (panel)
• Low battery by zone (wireless)
• Module fault (supervisory or tamper)
False Alarm Prevention Features
• Audible Exit Delay • Quick Exit
• Audible Exit Fault • Cross Zone Burglary Alarm
• Communication Delay • Rotating Keypress Buffer
• Urgency on Entry Delay • One Restart of Exit Delay
Additional Features
• Auto Arm at specified time
• Keypad-activated alarm output and communicator test
• All modules connect to the system via a four wire Keybus up to 1000’/305m from main panel
• An event buffer which records the past 128 events with both the time and date at which they occurred; buffer can be printed using PC5400 serial interface module, or viewed with the LCD5500Z keypad and DLS-1 software
• Supports the addition of the PC5132 wireless receiver for integration of wireless devices
• Uploading and downloading capability
• Local downloading capability through the use of the PC-LINK adaptor
• Added Keybus fault protection: clock and data outputs have been programmed to withstand shorts to +12v to pre­vent control panel damage
1

1.2 Additional Devices

In addition to the information below, see the back cover for a DSC module compatibility table.
PC5132 Wireless Receiver
The PC5132 Wireless Receiver can be used to connect up to 32 wireless devices to the system. All devices are spread spectrum, 900 MHz, fully supervised devices which use stan­dard ‘AAA’ or ‘AA’ alkaline batteries. Seven devices are available. They are as follows:
WLS904 Wireless Motion Detector:
tection to your system
WLS905 Wireless Universal Transmitter:
or window contacts to your system.
WLS906 Wireless Smoke Detector:
your system.
WLS907 Wireless Slimline Universal Transmitter:
wireless door or window contact.
WLS908 Wireless Panic Pendant:
the system. When used, the unit will indicate a non-medical emer­gency to the central station.
WLS909 Wireless Key :
arming and disarming to the system, as well as one-button access to several programmable functions.
Adds a simple and mobile method of
WLS910 Wireless Hand held Keypad:
allows arming and disarming from anywhere on the premises.
PC5400 Printer Module
The PC5400 Printer Module allows the panel to print out all events that occur on the system to any serial printer. The print­out will contain the time, date and the event that occurred.
LINKS1000 Cellular Communicator
The LINKS1000 Cellular Communicator can be used three dif­ferent ways: as the sole communicator for the panel, as a backup for either or both telephone numbers or as a redun­dant backup to the land line communicator where the panel will call both the land line and via the LINKS.
LINKS2X50
Either the LINKS2150 or LINKS2450 may be used to transmit alarm information over a long range radio network.
Adds wireless space pro-
Adds wireless door
Adds smoke detection to
A smaller
Adds personal protection to
A portable keypad which
Cabinets
Several different cabinets are available for the PC585 mod­ules. They are as follows:
PC5003C Cabinet
Main control cabinet for the PC585 main panel. Dimensions 288mm x 298mm x 78mm / 11.3” x 11.7” x 3” approximately.
PC500 Cabinet with Removable Door
Main control cabinet for the PC585 main panel. Dimensions 213mm x 235mm x 78mm / 8.4” x 9.25” x 3” approximately.
PC5004C Cabinet
Cabinet to house the PC5400 Printer Module. Dimensions 229mm x 178mm x 65mm / 9” x 7” x 2.6” approximately.

1.3 Out of the Box

Please verify that the following components are included in your system:
• one PC5003C main control cabinet
• one PC585 main control circuit board
• one PC1555RKZ keypad with zone input
• one Installation Manual with programming worksheets
• one Instruction Manual for the end user
• one hardware pack consisting of:
- one mylar cabinet label
- four plastic circuit board standoffs
- ten 5600 (5.6K) resistors
- one 2200 (2.2K) resistor
- one 1000 (1K) resistor
- ground connection assembly
- one cabinet door plug
2

Section 2: Getting Started

The following sections provide a thorough description of how to wire and configure devices and zones.

2.1 Installation Steps

Read this section completely before you begin. Once you have an overall understanding of the installation process, carefully work through each step.
Step 1: Create a Layout
Draw a rough sketch of the building to get an idea of where all alarm detection devices, keypads and other modules are to be located.
Step 2: Mounting the Panel
Mount the panel in a dry area close to an unswitched AC power source and the incoming telephone line. Before attach­ing the cabinet to the wall, be sure to press the four circuit board mounting studs into the cabinet from the back. After you have attached the cabinet to the wall, stick the provided DSC logo sticker on the front of the cabinet.
NOTE:You must complete all wiring before connecting the bat­tery, or applying AC to the panel.
Step 3: Wiring the Keybus (Section 2.3)
Wire the Keybus to each of the modules following the guide­lines provided in Section 2.3 of this manual.
Step 4: Zone Wiring (Section 2.8)
You must power down the control panel to complete all zone wiring. Please refer to 2.8 necting zones using normally closed loops, single EOL resis­tors, double EOL resistors, Fire zones and Keyswitch Arming zones.
Step 5: Complete Wiring (Section 2.2)
Complete all other wiring including bells or sirens, telephone line connections, and ground connections following the guide­lines provided in Section 2.2 (“Terminal Descriptions”).
Step 6: Power up the Control
Once all zone and Keybus wiring is complete, power up the control panel. First, connect the red battery lead to the posi­tive terminal and the black lead to negative. Then, connect the AC.
NOTE: Connect the battery bef ore con nectin g the A C . You must apply AC power to the panel for at least 10 seconds, or the panel will not function. The panel will not power up on the battery connection alone.
Step 7: Keypad Assignment (Section 2.5)
In order for keypads to be properly supervised, each must be assigned to a different slot. Please follow the guidelines pro­vided in Section 2.5 when assigning keypads.
Step 8: Supervision (Section 2.6)
The supervision of each module by the panel is automatically enabled upon power up. Please verify that all modules appear on the system according to the instructions in Section 2.6.
Step 9: Programming the System (Sections 4 & 5)
Section 4 explains how to program the panel. Section 5 con­tains a complete description of the various programmable fea­tures, which options are available and how they function. Fill out the Programming Worksheets completely before attempt­ing to program the system.
“Zone Wiring”
on page 5 when con-
Step 10: Testing the System
Test the panel thoroughly to ensure that all features and func­tions are operating as programmed.

2.2 Terminal Descriptions

Battery Connection
A 12V 4Ah rechargeable battery is used as a backup source of power in the event of an AC power failure. The battery also provides additional current when the panel’s demands exceed the power output of the transformer, such as when the panel is in alarm. The High Current Charge/Standard Battery Charge option (section [701], option [7]) allows you to choose between a high current battery charge and the standard battery charge rate.
High Current/Standard Battery Charge. . . .Section [701]: [7]
NOTE:Do not connect the battery until all other wiring is com­plete. Connect the battery before connecting the AC.
Connect the RED battery lead to the positive battery terminal; connect the BLACK lead to negative.
AC Terminals – AC
The panel requires a 16.5VAC, 40VA transformer. Connect the transformer to an unswitched AC source and connect the transformer to these terminals.
The panel can be programmed to accept a power line fre­quency of either 50Hz AC or 60Hz AC in programming section [701], option [1].
NOTE:Do no t conn ec t the tr a nsf ormer until all ot her wiring is complete.
Auxiliary Power Terminals – AUX+ and AUX-
These terminals provide up to 550 mA of additional current at 12 VDC for devices requiring power. Connect the positive side of any device requiring power to the AUX+ terminal, the nega­tive side to AUX- (ground). The AUX output is protected. This means that if too much current is drawn from these terminals (such as a wiring short), the panel will temporarily shut off the output until the problem is corrected.
Bell Output Terminals – BELL+ and BELL-
These terminals provide up to 700 mA of continuous current at 12 V
DC for powering bells, sirens, strobes or other warning-
type equipment. Connect the positive side of any alarm warn­ing device to BELL+, the negative side to BELL–. Please note that the Bell output is protected: if too much current is drawn from these terminals (such as a wiring short), the Bell PTC will open. Three amps can be drawn for short periods only. The Bell output is supervised. If no alarm warning devices are in use, connect a 1000 resistor across BELL+ and BELL– to prevent the panel from displaying a trouble condition. For more information, please refer to page 9).
Keybus Terminals – AUX+, AUX-, YEL, GRN
The Keybus is used by the panel to communicate with mod­ules and vice versa. Each module has four Keybus terminals that must be connected to the four Keybus terminals on the panel. For more information, see section 2.3
tion and Wiring”
on page 4.
“[*][2] Trouble Display”
“Keybus Opera-
on
3
Programmable Output Terminals – PGM1 and PGM2
Each PGM output is designed so that when activated by the panel, the terminal will switch to ground
PGM1 can sink up to 50mA of current. Connect the positive side of the LED or buzzer to AUX+, the negative side to PGM1. PGM2 operates simi­larly to PGM1. If more than 50 mA of current are required, a relay must be used.
Please study PGM wiring in the accompanying diagram. For a list of the programmable output options, please see section 5.11
Options”
Zone Input Terminals – Z1 to Z4
Each detection device must be connected to a zone on the control panel. We suggest that one detection device be con­nected to each zone; wiring multiple detection devices to a single zone, however, is possible. For zone wiring specifics, please see section 2.8
Telephone Connection Terminals – TIP, RING, T-1, R-1
If a telephone line is required for central station communica­tion or downloading, connect an RJ-31X telephone jack in the following manner:
“Zone Wiring”
on page 5.
“PGM Output
on page 21.
NOTE:Please ensure that all pl ugs and jacks meet the dimen­sion, tolerance and metallic plating requirements of 47 C.F.R. Part 68, SubPar t F. For proper operation, no other telephone equipment should be connec te d betwe en th e contro l pa nel and the telephone company facilities. Do not connect the alarm panel communicator to telephone lines intended for use with a fax machine. These lines may incorporate a voice filter which disconnects the line if anything other than fax signals are detected, resulting in incomplete transmiss io ns.

2.3 Keybus Operation and Wiring

The Keybus is used by the panel to communicate with all con­nected modules and vice versa. The red (AUX+) and black (AUX-) terminals are used to provide power, while the yellow (YEL) and green (GRN) terminals are clock and data respec­tively.
NOTE: The four Keybus terminals of the panel must be con­nected to the four Keybus terminals or wires of all modules.
The following restrictions apply to Keybus wiring:
• Keybus should be run in minimum 22 gauge quad (0.5mm); two pair twist is preferred.
• The modules should be home-run to the panel but can be connected in series or T-tapped.
• Any module can be connected anywhere along the Key­bus. You do not need to run a separate Keybus wire for keypads, etc.
• No module can be more than 1,000'/305m (in wire length) from the panel.
• Shielded wire should not be used.
Example of Keybus Wiring
NOTE: Module (A) is correctly
wired within 1,000'/ 305m of wire from the panel. Module (B) is correctly wired within 1,000'/ 305m of wire from the panel. Module (C) is NOT wired correctly as it is further than 1,000'/ 305m from the panel, in wire distance.
2.4 Current Ratings – Modules and Acces-
sories
In order for the PC585 system to operate properly, the power output capabilities of the main control and the expansion devices must not be exceeded. Use the data presented below to ensure that no part of the system is overloaded and cannot function properly.
PC585 (12 V
AUX+: ........550mA: Subtract the listed rating for each key-
BELL: .........700mA continuous rating; 3.0A short term. Avail-
PC585 Device Ratings (at 12 V
• LCD5500Z Keypad: 85mA max.
• PC1555RKZ Keypad: 85mA max.
• PC5508Z, PC5516Z, PC5532Z Keypads: 85mA max.
• PC5509 Keypad: 85mA max.
• PC5400 Serial Module: 65mA
• PC5132 Wireless Receiver: 125mA
Other Devices
Please read the manufacturer’s literature carefully to deter­mine the maximum current requirements for each device— during activation or alarm—and include the proper values for loading calculations. Connected devices must not exceed system capabilities during any possible operational mode.
DC)
pad, expansion module and accessory con­nected to AUX+ or Keybus.
able only with standby battery connected.
DC)

2.5 Keypad Assignment

There are eight available slots for keypads. LED keypads by default are always assigned to slot 1. LCD5500Z keypads are always assigned to slot 8. You will need to assign each key­pad to its own slot (1 to 8). Keypad assignment is required, as it tells the panel which slots are occupied. The panel can then generate a fault when a keypad supervisory is not present.
NOTE: One LCD keypad must be assigned to slot 8 in order to upload keypad programming using DLS-1 so ftware.
NOTE: PC5509 keypads are always assigned to slot 1. They cannot be reprogrammed.
How to Assign Keypads
Do the following at each keypad installed on the system:
1. Enter [*][8][installer’s code] to go to installer programming
2. Enter [000] for Keypad Programming
3. Enter [0] for Slot Assignment
4. Enter a two digit number (11-18) to specify which supervi­sory slot the keypad will occupy.
4

Getting Started: 2.6 Supervision

5. Press [#] twice to exit installer programming. After assigning all keypads, perform a supervisory reset by entering section [902] in installer’s programming. The panel will now supervise all assigned keypads and enrolled modules on the system.
How to Program Function Keys
By default, the 5 function keys on each keypad are pro­grammed as Stay Arm (03), Away Arm (04), Chime (06), Sen­sor Reset (14) and Quick Exit (16). You can change the function of each key on every keypad:
1. Go to the keypad where you want to change the function key programming and enter Installer Programming.
2. Press [000] for Keypad Programming.
3. Enter [1] to [5] to select a function key to program.
4. Enter the 2 digit number, [00] to [17] to select the feature you want the function key to have. For a complete list of Function Key options see section 3.5 page 11.
5. Continue from step 3 until all function keys are pro­grammed.
6. To exit Installer Programming, press [#] twice.
“Function Keys”
on
2.6 Supervision
By default, all modules are supervised upon installation. Supervision is enabled at all times so that the panel can indi­cate a trouble if a module is removed from the system. To check which modules are currently connected and super­vised, enter programming section [903] from installer’s pro­gramming. The LCD keypad will allow you to scroll through the display of connected modules. A connected module which does not show as being present will appear as a trouble con­dition and the Trouble light on the keypad will turn ON. This condition may be due to one or more of the following reasons:
• the module is not connected to the Keybus
• there is a Keybus wiring problem
• the module is more than 1,000'/305m from the panel
• the module does not have enough power
For more information regarding module supervision troubles, please refer to
“[*][2] Trouble Display”
on page 9.

2.7 Removing Modules

The panel must be instructed to no longer supervise a module being removed from the system. To remove the module, dis­connect it from the Keybus and reset the supervision field by entering [902] in the installer’s programming. The panel will be reset to recognize and supervise all existing modules on the system.

2.8 Zone Wiring

For a complete description of the operation of all zone types, please refer to 5.2
There are several different ways in which zones may be wired, depending on which programming options have been selected. The panel can be programmed to supervise nor­mally closed, End of Line, or Double End of Line loops. Please refer to the following diagrams to study each type of individu­ally supervised zone wiring.
NOTE:An y z one pro gr am med for Fire or 24 Hour Supervisory must be wired with a single End of Line (EOL) resistor regard­less of the type of zone wiring supervision selected for the panel (section [013]: [1] -[2]). See 5.2 “Zone Programming” on page 15.
“Zone Programming”
on page 15.
NOTE:If y ou chang e the zone supervision options from DEOL to EOL or from NC to DEOL (section [013], options [1] or [2]), you should power down the system completely, and then power it back up. If you do not, the zones may not work cor­rectly.
Normally Closed (NC) Loops
To enable normally closed loops, programming section [013], option [1] must be ON.
NOTE:This option shou ld only be select ed if Normally Closed (NC) detection devices or contacts are being used.
Single End Of Line (EOL) Resistors (5600)
To enable panel detection of single end of line resistors, pro­gramming section [013], options [1] and [2] must be OFF.
NOTE:This option shoul d be selected if e ither Normally Closed (NC) or Normally Open (NO) detection devices or contacts are being used.
Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if the zone is in alarm, tampered or faulted. To enable panel detection of double end of line resistors, pro­gramming section [013], option [1] must be OFF and option [2] must be ON.
NOTE: If the Do ub le EOL su pervision o ption is en ab led, all hardwire zones on the main panel must be wired for Double EOL resistors, except for Fire and 24 Hour Supervisory zones.
NOTE:Do not wire DEOL resistors on keypad zones. NOTE: Do not use DEOL resistors f o r Fir e z ones o r 24 Hour
Supervisory zones. Do not wire Fire zones to keypad zone ter­minals if the DEOL supervision option is sel e cted.
NOTE: Thi s option can only be sele cted if Normally Clo sed (NC) detection devices or contacts are being used.
5
NOTE:Only one NC contact can be connected to each zone. Wiring multiple detection devices or contacts on a single loop is not allowed.
The following chart shows zone status under certain condi­tions:
Loop Resistance Loop Status
0 (shorted wire, loop shorted) Fault
5600 (contact closed) Secure
Infinite (broken wire, loop open) Tamper
11200 (contact open) Violated
End of Line Resistors. . . . . . . . . . . . . . . . . .Section [013]: [1]
Double End of Line Resistors . . . . . . . . . . .Section [013]: [2]

2.9 Fire Zone Wiring

NOTE:4-Wire Smoke Detectors
All fire zones must be wired according to the following dia­gram:
This type of zone always requires a single EOL resistor (5600). Wire this zone according to the above diagram.
LINKS Answer
When using the LINKS1000 cellular communicator, any main board zone may be configured for LINKS Answer. A zone configured for LINKS Answer allows downloading to be per­formed in the event of tele­phone line failure. When the LINKS receives a tele­phone call, it will activate the RING terminal on the LINKS circuit board. The zone programmed as LINKS Answer always requires a single EOL resis­tor (5600). Wire the LINKS Answer zone according to the above diagram.
NOTE: The LINKS Answer zone is only required for download­ing to the panel via the LINKS.
NOTE: When using the LINKS, Busy Tone Detection must not be used.
NOTE: Keypad zones cannot be used for 24 Hour Supervisory or LINKS Answer.

2.10 LINKS Zone Wiring

LINKS Support
When using the LINKS1000 cellular communicator, con­nect the LINKS to the main panel according to the fol­lowing diagram:
LINKS Supervision (24 Hour Supervisory)
When using the LINKS1000 cellular com­municator, any main board zone may be configured for LINKS Supervision. Pro­gram this zone as zone type [09], 24 Hour Supervi­sory in section [001]. With a LINKS Supervisory zone, if the LINKS1000 experiences a trouble, the zone will be violated, caus­ing the panel to report the event to the central station.

2.11 Keypad Zones

Each “z” keypad on the system has a zone input to which a device - such as a door contact - can be connected. This eliminates the need to run wires back to the control panel for every device. To install the keypad, open the keypad plastic by removing the screw at the bottom of the unit. Locate the five terminals on the keypad circuit board. Connect the four Keybus wires from the control panel: the red wire to R, the black to B, the yellow to Y and the green to G. To connect the zone, run one wire to the Z terminal and the other to B. For powered devices, use red and black to supply power to the device. Run the red wire to the R (positive) termi­nal and the black wire to the B (negative) terminal.
When using end of line supervision, connect the zone accord­ing to one of the configurations outlined in section
Wiring”
. End of line resistors must be placed on the device
end of the loop, not at the keypad.
NOTE: Keypad zones do not support DEOL resistors.
2.8 “Zone
6
Assigning Keypad Zones
When using keypad zone inputs, each input used must be assigned a zone number in Installer’s Programming. First, ensure that you have enrolled all installed keypads into the desired slots. (See 2.5
Next, enter programming section [020] to assign the zones. There are eight programming locations in this section, one for each keypad slot. Enter a 2-digit zone number for each of the keypad zones. This number must be entered in the location corresponding to the keypad to which each zone is con­nected. Example: The zone on an LCD5500Z keypad in slot 8 is to be assigned zone 3. In section [020], scroll to option [8] and enter (03).
“Keypad Assignment”
on page 4.)
NOTE:K e ypad zones 1-4 will replac e zone terminal s Z1-Z4 on the control panel.
NOTE: Once the keypad zones are assigned, you must also program zone definitions and zone attributes. (See also 5.4 “Assigning Keypad Zones” on page 17).
Getting Started: 2.11 Keypad Zones
7

Section 3: Keypad Commands

Use any system keypad to enter commands and/or program the PC585 security system. The LED keypad uses function and zone indicator lights to represent alarm functions and sta­tus. If you have a PC1555RKZ keypad, the System light acts as a Trouble, Memory, Program and Bypass indicator. Unlike other LED keypads, these conditions will only be represented by the System light. The LCD keypad provides a written description on the liquid crystal display and uses function indicator lights to communi­cate alarm status to the user. The PC585 Instruction Manual provides basic directions for arming and disarming the system, bypassing zones and per­forming user functions from the keypads. The following sec­tions provide additional details on these functions.

3.1 Arming and Disarming

For a description of basic arming and disarming, please see the PC585 Instruction Manual. For other methods of arming, please refer to
Delay”
and 3.5
“[*][0] Quick Arm”, “[*][9] Arming Without Entry
“Function Keys”
on page 11.
NOTE: The event buffer will log “Armed in Stay Mode” or “Armed in Awa y Mode” wh en ever the system is armed.
In an attempt to prevent false alarms, the Audible Exit Fault will notify the user of an improper exit when they arm their sys­tem. If a non force-arming Delay 1 or Delay 2 type zone is left open at the end of the exit delay, the entry delay will begin immediately and the bell or siren will sound a steady alarm for the entry delay period. At the end of the entry delay period, if the system has not been disarmed it will go into alarm. This feature can be turned OFF in programming section [013], option [6]. (See 5.17
24.)
“Arming/Disarming Options”
on page

3.2 Auto Bypass – Stay Arming

Stay arming allows the user to arm the system without leaving the premises. All zones programmed as stay/away will be bypassed when the user stay arms the system, so that the user does not have to bypass interior zones manually. (See
5.2
“Zone Programming”
When the system is armed using a valid access code, if any zones on the system have been programmed as stay/away zones, the Bypass light will turn ON. The panel will then moni­tor all zones programmed as Delay 1 and Delay 2 zones, such as designated entry/exit doors. If a delay zone is not violated by the end of the exit delay, the panel will bypass all stay/away zones. The Bypass light will remain on to inform the user that the interior zones have been automatically bypassed by the panel. If a delay zone is violated during the exit delay, the sys­tem will arm in Away mode and all stay/away zones will be active after the exit delay expires. The user can arm the stay/away zones at any time by entering the [*][1] keypad command. (See
vating Stay/Away Zones”
Stay arming can also be initiated by pressing and holding the Stay function key for two seconds on the PC5508Z and LCD5500Z keypads, if programmed by the installer. For more information regarding Stay arming, please see 3.5
Keys”
on page 11.
on page 15.)
“[*][1] Bypassing and Acti-
on page 8.)
“Function

3.3 Automatic Arming

The system can be programmed to Auto-Arm at a specific time every day if it is in the disarmed condition. In order for the Auto-Arm function to work properly, you must program the cor­rect Time of Day. For programming the clock and auto-arm times, see When the system’s internal clock matches the Auto-Arm Time, the panel will check the system status. If the system is armed, the panel will do nothing until the next day at the auto-arm time, when it will check the system again. If the system is dis­armed at the auto-arm time, the panel will sound the buzzer of all keypads for one minute. If the Bell Squawk During Auto Arm option is enabled (section [014], option [2]), the bell will squawk once every 10 seconds while the system is auto-arm­ing. If a valid access code is entered, auto-arming will be aborted.
“[*][6] User Functions”
on page 10.
NOTE: If auto-arm is canc elled , th e nu mber o f th e user who cancelled the auto-arm will be logged in the event b uffer.
If no code is entered, the panel will auto-arm. If a zone is vio­lated, the panel will transmit a Partial Closing Reporting Code – if programmed – to indicate to the central station that the system is not secure. If the zone is restored, the panel will add the zone back into the system.
NOTE: Auto arming can only be cancelled by entering a valid access code at any keypad.

3.4 [*] Commands

The [*] key commands provide an easy way for the user to access basic system programming – such as programming access codes or bypassing zones. The user can also use the [*] key commands to check on the system’s status, including viewing trouble conditions and displaying the event buffer on the LCD keypad.
The [*] key commands can be performed from both LCD and LED keypads. The LED keypad uses the zone indicator lights to display command information. The LCD display provides written information, guiding the user through each command. The commands in this section are explained as viewed from an LED keypad. When using an LCD keypad, use the arrow keys (< >) to scroll through information provided. Otherwise, the functions remain the same for both keypad types.
[*][1] Bypassing and Activating Stay/Away Zones
Use the [*][1] keypad command to bypass individual zones. A bypassed zone will not cause an alarm.
NOTE: Zones can only be b ypass ed whe n th e sys tem is not armed.
If the Code Required for Bypass option is enabled (section [015], option [5]), only access codes with the bypass attribute enabled will be able to bypass zones. (See 5.1
Security Codes”
If the Bypass Status Displayed While Armed option is cho- sen, the Bypass (or System) light will be ON while the system is armed to indicate any bypassed zones. (See 5.17
Disarming Options”
on page 15.)
on page 24.)
NOTE: When you disarm the s ystem, all man ually -bypa ssed zones will be unbypassed.
“Programming
“Arming/
8
Keypad Commands: 3.4 [*] Commands
Activate Stay/Away Zones
If the system is armed in stay mode, the [*][1] command can be used to activate the stay/away zones.
[*][2] Trouble Display
The panel constantly monitors itself for several different trou­ble conditions. If a trouble condition is present, the Trouble (or System) light will be on and the keypad will beep twice every 10 seconds. The trouble beep can be silenced by pressing any key on any keypad. If Bell Squa wk on Trouble is enabled (section [014], option [5]), the bell will squawk every 10 sec­onds when a trouble condition is present.
Light Trouble
1
Service Required: Press [1] to determine the specific trouble. Lights 1 - 5 will light up to indicate the trouble:
• Light [1] Low Battery: Main panel backup battery charge is low (below 11.5 volts under load).Trouble is restored
• Light [2] Bell Circuit Trouble: The bell circuit is open (see section 5.13
• Light [3] General System Trouble: The printer connected to the PC5400 Printer module has a fault and is off-line.
• Light [4] General System Tamper: Tamper has been detected in a module.
• Light [5] General System Supervisory: The panel has lost communication with a module connected to the Keybus
NOTE: NOTE:
2
AC Failure: AC power is no longer being supplied to the control panel. The Trouble (or System) light will flash if an AC
Failure is present, if the Trouble Light Flashes if AC Fails option is programmed (section [016], option [2]). This trouble will not be displayed if the AC Trouble Displayed option is disabled (section [016], option [1]). See section 5.8
municator – Reporting Codes”
3
Telephone Line Monitoring Trouble (TLM): There is a problem with the telephone line (See section 5.12
phone Line Monitor (TLM)”
4
Failure to Communicate (FTC): The communicator failed to communicate with any of the programmed telephone
numbers (see section 5.5
5
Zone Fault (including Fire Zone): A zone on the system is experiencing trouble, meaning that a zone could not
provide an alarm to the panel if required to do so (e.g. a fire zone is open, or there is a short on a DEOL zone, or a super­visory fault on a wireless zone). When a zone fault trouble condition occurs, the keypad(s) on the system will start to beep. Press [5] while in Trouble mode to view the affected zones.
NOTE:
6
Zone Tamper: A zone configured for Double End Of Line resistor supervision has a tamper condition, or the tamper
switch is open on a wireless device. When a tamper condition occurs, the keypad(s) will start to beep. Press [6] while in the Trouble mode to view the affected zones. If a zone is tampered or faulted, it must be fully restored to clear the trouble.
NOTE:
as open on the keypad, and will be hidden from the end user. If the option is disabled, Faults and Tampers will be dis­played on the keypad
NOTE:
7
Device Low Battery: A wireless device has a low battery condition. Press [7] one, two, or three times to view which
devices are experiencing battery failure. An LED keypad will indicate battery failure using zone lights 1 to 8. The follow­ing will occur:
Press [7] 1 Zones with low batteries (LED keypad - zone lights 1 to 32) Press [7] again 2 Handheld keypads with low batteries (LED keypad - zone lights 1 to 4) Press [7] again 3 Wireless keys with low batteries (LED keypad - zone lights 1 to 8)
8
Loss of System Time: When the panel is powered up, the internal clock needs to be set to the correct time. This
trouble is cleared when an attempt is made to reset the clock.
when the battery charges over 12.5 volts.
(see section 2.6
All tamper conditions must be physically restored before the trouble condition will clear.
Lights [6-8] – Not used
“Supervision”
on page 18 for information on AC trouble reporting.
on page 23.)
on page 5). The event buffer will log the event.
“Communicator – Dialing”
A Fire zone trouble will be generated and displayed in the armed state.
By enabling
Once a zone is tampered or faulted, it must be completely restored before the trouble condition will clear.
Tampers/Faults Do Not Show as Open
Keypad beeps: Keypad displays:
To view the battery conditions of wireless keys 9 through 16, you must use an LCD keypad.
To view trouble conditions from an LED keypad:
1. Press [*][2].
2. The keypad will flash the Trouble (or System) light. The zone indicator lights corresponding to the present trouble conditions will be ON.
When using an LCD keypad, the trouble conditions will be listed on the display. Use the arrow (< >) keys to scroll through the list of present trouble conditions.
NOTE:Troubles can be viewe d while armed using the LCD k e y ­pad, provided the keypad is version 2.0 or later. Older keypads will incorrectly display “Fire Trouble”. If using older LCD key­pads, progr amming se ction [01 3], opt ion [3] as OF F will ensure troubles are displayed correctly.
The various troubles are described below:
“Bell”
on page 23).
“Com-
“Tele-
on page 17).
in section [013], option [4], Faults and Tampers will not show
[*][3] Alarm Memory
The Memory (or System) light will be on if any alarm occurred during the last armed period or – in the case of 24 hour zones – if an alarm occurred while the panel was disarmed. To view alarm memory, press [*][3]. The keypad will flash the Memory (or System) light and the zone indicator lights corre­sponding to the alarm or tamper conditions which occurred during or since the last armed period. To clear the Memory (or System) light, arm and disarm the system.
[*][4] Door Chime On/Off
The door chime feature is used to sound a tone from the key­pad whenever a zone programmed as a chime zone is acti­vated. (See 5.3
“Zone Attributes”
on page 16.) If the door chime feature is enabled, the keypad will emit five short beeps whenever a chime zone is activated. Designated entry/exit doors are often defined as chime zones. The feature can be turned on or off while the system is armed or disarmed.
9
[*][5] Programming Access Codes
There are 37 access codes available to the user. They are:
Access code (40)..................... One master code
Access codes (01)-(32)............ 32 general access codes
Access codes (33)-(34)............ Two duress codes
Access codes (41)-(42)............ Two supervisor codes
All access codes have the ability to arm or disarm the system and can activate the PGM Outputs using the [*][7] com­mands. Access codes can be either four or six digits (See 5.1
“Programming Security Codes”
For a description of how to program access codes from LCD or LED keypads, see the PC585 Instruction Manual.
on page 15.)
Master Code – Access Code (40)
This code can be used to program all access codes. The Master code has all Access Code Attributes enabled by default, so that the Master code can be used to perform any keypad function. Master code attributes cannot be changed. If the Master Code N ot Changeable option is enabled, (sec- tion [015], option [6]) the Master Code can only be changed by the Installer.
General Access Codes – Access Codes (01) to (32)
General access codes can arm and disarm the system. When the Code Required for Bypassing option is enabled, users will need to enter a valid access code when bypassing zones. Individual access codes can have the Zone Bypassing attribute disabled under Access Code Attribute programming. For more information regarding access code options, please see 5.1
“Programming Security Codes”
on page 15.
Duress Code – Access Code (33) and (34)
Duress codes will send a duress reporting code to the central station when entered.
NOTE: If a duress c ode is prog ra mmed, whe n it is use d, the panel will always send a reporting code to the central station, even if the attributes of the duress code are turned off.
Supervisor Codes – Access Code (41) and (42)
These codes can be used to program general access and duress codes. The two supervisor codes have all attributes on by default. These settings can be changed.
Access Code Attributes
There are three access code attributes which can be pro­grammed for each code. To program each attribute, enter [*][5][Master Code][9] to enter the attribute programming mode. Then enter the code number [01-32,33,34,41,42]. Enter the attribute number:
Attribute [1].......... User enabled for arming, disarming, alarm
reset, [*][7][1-2] options, auto arm cancel-
lation
Attribute [2]..........Not used
Attribute [3]..........Zone bypassing enabled
Attribute [4]-[6].... Not used
Attribute [7]..........Bell squawk on access code entry
Example
have wireless key access codes squawk the bell, while other codes are silent. To do this, enable attribute [7] on all access codes associated with wireless keys.
: You can use the arm/disarm bell squawk attribute to
NOTE: If you enable the Bell Squawk on Arming/Disarming (section [014], option [1]), the bell will sound arm/disarm bell squawks for all access codes, regardless of the programming for attribute [7]. See 5.17 “Arming/Disarming Options” on page 24.
NOTE: Master code attributes cannot be changed.
[*][6] User Functions
This command can be used to program several different func­tions: To program User Functions:
1. Press [*][6][Master Code]. The Program (or System) light will flash.
2. Press the number [1] to [6] for the item to be programmed.
• [1] – Time and Date The time and date must be accurate for the auto-arm or test transmission functions to work properly and for the event buffer to time and date stamp all events.
- Enter the time (hour and minute) using 24hr format [HH MM] from 00:00 to 23:59.
- Enter the date by month, day and year [MM DD YY].
• [2] – Auto-Arm Enable/Disable To enable or disable auto-arming, press [2]. The keypad will sound three short beeps when auto-arm is enabled and one long beep when disabled. For more information, see 3.3
• [3] – Auto-Arm Time The system can be programmed to arm automatically at a pre-set time. When programming the auto-arm time, enter the time (hour and minute) using 24hr format [HH MM]. For more information, see 3.3
• [4] – System Test When [4] is pressed the panel will test the bell output, key­pad lights and the communicator for two seconds. The panel will also send a System Test Reporting code, if pro­grammed. (See 5.8 page 18.)
• [5] – Enable DLS (Downloading) When [5] is pressed, the panel will enable the downloading option for one hour or six hours depending on the option selected in programming section [702]: [7]. During this time, the panel will answer incoming downloading calls. (See 5.10
• [6] – User Initiated Call-Up When [6] is pressed, the panel will initiate a call to the downloading computer.
Additional Features Available from the LCD Keypad
Additional features, including access to the event buffer, are available using the LCD keypad. Use the arrow keys (< >) to scroll through the [*][6] menu and press the [*] key to select the following commands:
“Automatic Arming”
“Automatic Arming”
“Communicator – Reporting Codes”
“Downloading”
on page 20.)
on page 8.
on page 8.
on
Viewing the Event Buffer from an LCD Keypad
Select “View Event Buffer” from the [*][6] menu. The keypad will display the event, event number, time and date along with the zone number and access code, if applicable. Press [*] to toggle between this information and the event itself. Use the arrow keys (<>) to scroll through the events in the buffer. When you have finished viewing the event buffer, press [#] to exit.
Brightness Control
You can select from 10 different backlighting levels. Use the arrow keys (< >) to scroll to the desired backlighting level. Press [#] to exit.
Contrast Control
You can select from 10 different display contrast levels. Use the arrow keys (< >) to scroll to the desired contrast level. Press [#] to exit.
10

Keypad Commands: 3.5 Function Keys

Keypad Sounder Control
You can select from 21 different keypad tones. Use the arrow keys (< >) to scroll to the desired keypad sound level and press [#] to exit. This feature can be accessed on LED key­pads by pressing and holding the [*] key.
[*][7] Command Output Functions
The user can activate programmable output functions using the [*][7][1-2] commands. The outputs may be activated when the system is either armed or disarmed.
[*] [7] [1] – Command Output Option #1:
Press [*] [7] [1] [Access Code, if required] to activate outputs programmed as PGM output option [19]. This output can be used for operating devices such a garage door opener, light­ing or door strikes.
[*][7][2] – Command Output Option #2:
Press [*][7][2][Access Code, if required] to activate all outputs programmed as one of PGM output options [03] or [20].
Special Note:
resetting smoke detectors. Smoke detectors should now be programmed as output [03] “Sensor Reset” . If using output option [03], do not program [20] Command Output Option #2. Please see 5.11 information.
[*][8] Installer’s Programming
Enter [*][8] followed by the Installer’s Code to access Installer’s Programming. See sections 4 and 5 for more infor­mation.
[*][9] Arming Without Entry Delay
When the system is armed with the [*][9] command, the panel will cancel the entry delay. Delay 1 and Delay 2 type zones will be instant and Stay/Away zones will be bypassed as soon as the exit delay has ended (see section 5.2
ming”
on page 15). The user must enter a valid access code
after pressing [*][9].
[*][0] Quick Arm
If the Quick Arm option is enabled (section [015], option [4]), enter [*][0] to arm the panel without an access code. (See
5.17
“Arming/Disarming Options”
Arm option is disabled, users will need to enter an access code after pressing a function key.
Traditionally, [*][7][2] has been reserved for
“PGM Output Options”
on page 21 for more
“Zone Program-
on page 24.) If the Quick
NOTE: Quick Arm cannot be used to cancel auto arm.
[*][0] Quick Exit
The Quick Exit function, if enabled, will allow someone to leave an armed premises through a Delay type zone without having to disarm and re-arm the system. (See 5.17
Disarming Options”
When [*][0] is entered, the panel will provide a two minute win­dow for the user to exit the premises. During this time, the panel will ignore only one activation of a Delay zone. When the Delay zone is secured, the panel will end the two minute quick exit delay. If a second Delay zone is tripped, or if the zone is not restored after two minutes, the panel will begin entry delay 1.
on page 24.)
“Arming/
NOTE: If the Exit Delay is in progress, performing a Quick Exit will not extend the Exit Delay.
3.5 Function Keys
There are five function keys on each keypad labelled Stay, Away, Chime, Reset and Exit. Each of these keys is pro­grammed by default to perform one of the functions described
below. Press and hold the appropriate key for two seconds to activate a function. If the Quick Arm option is disabled (section [015], option [4]), users will need to enter an access code after pressing a func­tion key.
NOTE:On the PC1555RKZ k e y pad, us e nu mber k e ys 1 - 5 for the function ke y s.
“Stay” – (03) Stay Arm
The system will arm in the Stay mode (see 3.2
Stay Arming”
gramming section [015], option [4]) to have this key function without the need to enter an access code. If Quick Arm is not enabled, the user will have to enter an access code before the system will stay arm.
“Away” – (04) Away Arm
The system will arm in the Away mode (see 3.2
– Stay Arming”
gramming section [015], option [4]) to have this key function without the need to enter an access code. If Quick Arm is not enabled, the user will have to enter an access code before the system will away arm. When the panel is being Away armed, users can restart the exit delay once, by pressing the Away button before the exit delay expires. This will not work if the panel is being Stay armed.
“Chime” – (06) Door Chime On / Off
The Door Chime feature will turn ON or OFF. (See
Chime On/Off”
“Reset” – (14) Sensor Reset or [*][7][2]
The panel will activate all PGM outputs programmed as option [03] Sensor Reset or [20] Command Output Option #2. (See “[*][7] Command Output Functions” .)
“Exit” – (16) Activate Quick Exit
The panel will activate the Quick Exit feature (See
Quick Exit”
Additional Function Key Options
The programming of any function key on any keypad may be changed to one of the options listed below. (See 2.5
Assignment”
key programming.) Each option is listed according to the pro­gramming code, followed by the corresponding [*] key com­mand. For more information regarding each function, please refer to the appropriate part of Section 3.4, “[*] Commands”.
on page 8). Enable the Quick Arm feature (pro-
on page 8). Enable the Quick Arm feature (pro-
on page 9.)
on page 11.)
on page 4 for instructions on changing function
“Auto Bypass –
“Auto Bypass
“[*][4] Door
“[*][0]
“Keypad
NOTE: The PC5509 function keys cannot be ch anged from the defaults listed above.
[00] Null Key: The key is not used and will perform no
function when pressed.
[01]-[02] For future use [03] Stay Arm: As described above. [04] Away Arm: As described above. [05] [*][9] No-Entry Delay Arm: A valid access code
must also be entered.
[06] [*][4] Door Chime On / Off: As described above. [07] [*][6][----][4] System Test: A valid master code must
also be entered.
[08] [*][1] Bypass Mode: A valid access code may need
to be entered.
[09] [*][2] Trouble Display [10] [*][3] Alarm Memory
11
[11] [*][5] Programming Access Codes: A valid master
code must also be entered.
[12] [*][6] User Functions: A valid master code must also
be entered.
[13] [*][7][1] Command Output Option #1: A valid
access code may need to be entered.
[14] [*][7][2] Reset (Command Output Option #2): As
described above.
[15] For future use [16] [*][0] Quick Exit: As described above. [17] [*][1] Reactivate Stay/Away Zones [18] - [20] For future use

3.6 Features Available for the LCD5500Z

These features are only available for LCD5500Z keypads with zone inputs:
Automatic Scrolling of Alarms in Memory
The LCD5500Z keypad allows automatic scrolling through alarms in memory while the keypad is idle. This feature, if enabled, will override the clock display. This option can be programmed in LCD programming section [66], option [4].
24 Hour Time Display Option
The LCD5500Z can be programmed to display time using a 24- hour clock, instead of a 12-hour, am/pm clock. This option can be programmed in LCD programming section [66], option [3].
Keypad Zones
See 2.11
Viewing Troubles While Armed
See to view troubles.
Backlighting Boost
The LCD5500Z, PC55XXZ and PC1555RKZ zone input key­pads will provide extra number pad lighting when any key is pressed. The backlighting boost will last for an additional 30 seconds after the last keypress.
“Keypad Zones”
“[*][2] Trouble Display”
on page 6.
on page 9 for information on how
12
Loading...
+ 36 hidden pages