DSC FSA-210 Series Installation And Operating Instructions Manual

FSA-210 Series Smoke Detector
P P
A A
I I
N N
T T
Piezo Siren
Alignment Marks
LED / Test Button
Place magnet here
DO DO
N N
O O
T T
29006015R007
Installation and Operating Instructions
Read this instruction sheet thoroughly before installation and use of the FSA-210 2-Wire Smoke Detector. This instruction sheet is intended to be used with the Installation Manual of the alarm control panel. All the instructions spec­ified within that manual must be observed.
Introduction
The FSA-210 is a 2-wire photoelectric smoke detector with the following available options: fixed temperature heat detector, internal piezoelectric alarm, auxiliary form C relay, and/or remote LED output. Three versions are available: US version (UL), Canadian version (ULC) and an International version (EU).
NOTE: Heat detection based on rate of rise has not been investigated by UL/ULC.
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During this sequence the unit also performs self diagnostics, and checks for faults. During normal operation the LED will flash every 50 seconds and the siren will not sound.
Smoke Alarm
The smoke detector has a nominal fixed alarm sensitivity (refer to the Specifications on the last page) and it will go into alarm
Installer Instructions
1. Smoke Detector Placement
On smooth ceilings, detectors may be spaced 9.1M (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, Chapter 11 CAN/ULC-S553-02 or other appropriate national standards for installation recommendations.
and rate of rise
when the signal level exceeds the 'alarm' threshold and send the alarm signal to the control panel. During an alarm the LED will flash once per second and the siren will sound the evacua­tion temporal pattern (UL, EU) or continuous beeps (ULC).
Remote Alarm - Interconnection
Multiple detectors (with sirens) can be connected using the PRM-2W Polarity Reversal Module. When a fire alarm occurs, the panel will signal the PRM-2W to reverse the polarity of the 2-wire loop. This will activate the sirens of all units connected on the loop. Refer to the PRM-2W/4W Installation Instructions for installation details.
Smoke - Drift Compensation
The detector automatically compensates for long-term envi­ronmentally induced changes to maintain a constant smoke sensitivity. When the drift compensation has reached its high or low limit of adjustment, the detector will go into the trou­ble state.
Heat Alarm
The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold (135ºF/57ºC); and send the alarm signal to the control panel. The detector will also go into heat alarm if there is a rapid increase in the temperature over a short period of time. During an alarm the LED will flash once per second and the siren will sound the evacuation temporal pattern (UL, EU) or continuous beeps (ULC).
Alarm Indications
Condition LED siren Relay
Normal / Sensitivity in Production Range
Alarm Smoke/Heat Flash 1/1s
Alarm Restore Flash 1/1s
Remote Alarm Flash 1/50s
Low Power Trouble OFF OFF Deactivated No Other
Fault / Trouble Test Switch - Failed OFF CHIRP 1/50s Deactivated No
Test Switch - Pass Flash 1/1s
Flash 1/50s OFF Deactivated No
Temporal or
Steady
Temporal or
Steady
Temporal or
Steady
OFF CHIRP 1/50s Deactivated No
Temporal or
Steady
Activated Yes
Activated Yes
Deactivated No
Activated Yes
Alarm
Current
Do NOT locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may pre­vent the unit from detecting smoke. Avoid areas with turbulent air flow, (near doors, fans or windows). Rapid air movement around the detector may prevent smoke from entering the unit. Do NOT locate detectors in areas of high humidity. Do NOT locate detectors in areas where the temperature rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
Install smoke detectors in accordance with NFPA 72, Ch. 11: “Smoke detectors shall be installed outside of each
sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics.
In new construction, a smoke detector shall also be installed in
Mounting Holes
Locking
Tab
V+ V
9.35-30VDC
EOL Device
++
-
++
-
++
-
Relay
NO NC C
each sleeping room.”
2. Mount Smoke Detector Backplate
Mount backplate using screws pro­vided and the appropriate holes on the mounting plate.
NOTE: Install wiring in accordance with the appropriate national and local electrical codes. For UL/ULC Installations, the power supply must be supplied from a UL/ULC Listed alarm control unit.
CAUTION: The dust cover protects the unit when not in service. Remove dust cover before use. The EU and International versions, shall be powered from an acceptable to the local authorities alarm controller.
3. Wiring
Refer to the wiring diagrams in this installation sheet and those provided in the Installation Manual of the alarm control panel being used with the unit. Before connecting the unit, prepare the wires from the electrical box for connection; Do not use frayed or bent wire.
When wiring is completed, inspect it and correct any errors before applying power to the unit. When the wiring has been thoroughly reviewed, neatly insert the wires into the electrical box and secure the unit to the mounting plate. To connect this device use only wiring listed as fit for the pur­pose.
4. Mounting
Detector Installation
Position the detector on to the base plate using the detector and base plate alignment marks. Press the detector
Alignment
Marks
Mounting
Surface
Detector
CLOSE
gently in place while rotating the detec­tor clockwise until the detector snaps into place. Remove the side tab from the locking tab to lock in place (optional). Removal: If the side tab is removed to lock the detector, depress tab with a small flat blade screwdriver and rotate detector counter-clockwise until the alignment marks line up. Remove detector.
5. Test Unit
Initiate test for units without a siren by placing a magnet near the LED/Test Button for greater than 5 seconds. Initiate test for units with a siren by pressing the test button for greater than 5 seconds. Alarm activation is indicated by the LED, the siren, and the alarm reporting to the Control Panel. If the smoke detectors are inter-connected using model PRM-2W and a detector is tested, then all detectors will sound. The detector restores to
OPEN
Backplate
Tab s
normal when the test button is released or when the magnet is removed.
NOTES: Allow a minimum of 20 seconds between test activa­tions. If the detector is in one of the following states when a test is initiated; it will not enter an alarm state.
1. Compensation trouble.
2. Failure of heat or smoke detector.
3. Other internal faults that could prevent a smoke or heat alarm.
NOTE: Smoke sensitivity of installed detectors can be mea­sured without removal or an alarm being generated using the FSD-100 Smoke Detector Test Meter.
Test Unit with FSD-100 Smoke Detector Test Meter
To test the unit using the FSD-100, set the test meter up to read devices as per the instructions supplied with the test instrument. Depress the test button (or place the FSD-100 on the outside edge of the plastics beside the test button to acti­vate the reed switch on units without siren) on the smoke detector for 1 second and release.
NOTES: If the test button is held for 5 seconds or longer, an alarm will be generated. Move the test meter over the center of the detector, wait until you hear the test meter beep, remove the unit and the information can be immediately reviewed. Please see the instructions supplied with the FSD­100 Smoke Detector Test Meter for more information. Perform the tests one at a time. Performing simultaneous tests on multiple detectors may trigger an alarm at the control panel.
6. Removing the Chamber for Cleaning
To clean or replace the smoke chamber the detector must be opened.
1. Press the 3 tabs on the bottom of the detector outward to release.
2. Remove the bottom portion which contains the PCB and the chamber.
3. Place thumb and forefinger on the sides of the chamber in the locations indicated by the arrows on top of the cham­ber.
4. Squeeze gently inward and pull up and the chamber will separate.
5. The removable portion can now be replaced or cleaned. Cleaning can be done using compressed air. Do not use a cloth as it may leave particles on the inner wall.
6. Replace the new or cleaned chamber by pressing it down until it snaps into place. Locate and press the backplate into the housing making sure the 3 locking tabs are snapped into their locked position.
7. Compensation Reset
Cleaning, replacement of the smoke sensor, or other changes may change the background signal/noise of the detector; this requires the drift compensation be reset. Compensation trou­ble is one of the faults indicated when the LED indicator is OFF while the siren is chirping.
• Remove power from the unit, then press and hold the test button for 30 seconds to power down unit.
• Power up unit while pressing the test button.The LED will flash; when 5 seconds has elapsed. Release the test button within 1 second after the fifth LED flash.
• The LED will flash every 8 seconds for 1 minute. When the detector stops flashing test the detector to verify normal operation.
Loading...
+ 2 hidden pages