DSC Envoy NT9010 User Manual

WARNING
This manual contains information on
limitations regarding product use and
function and information on the
limitations as to liability of the
manufacturer. The entire manual should
be carefully read.
User’s Guide
Quick Reference Guide
Away
Exit
The following chart lists the basic functions of your system, and the keys to press for each function. Refer to the listed page number for more information.
NOTE: Some functions may not be available on your system. Ask your installer for more information.
To Perform This Function: Enter: Page:
Turn on system (Away): ..................... [access code], leave through entry/exit door 9
OR press (if enabled)
Turn on system (Stay):........................ [access code], do not leave premises 12
OR press (if enabled)
Turn off system:................................. [access code] 10
*
Turn on system (No Entry Time): ........ [access code] 13
Turn on system (Quick, if enabled):.... (from Ready state) 12
Turn on rest of system (if Stay armed): OR press (if enabled) 12
Exit premises when system on: .......... OR press (if enabled) 14
Turn off zones (Bypass): ..................... [two-digit zone number(s)], to exit 18
9
*
0
*
1
*
0
*
1
Away
Stay
#
*
Test system ........................................ [master code] 20
6
4
Send Fire message: ............................ (press & hold for 2 seconds, if enabled) 17
Send Auxiliary message: .................... (press & hold for 2 seconds, if enabled) 17
*Send Medical message: ................... (press & hold for 2 seconds, if enabled) 17
Send Panic message: ......................... (press & hold for 2 seconds, if enabled) 17
Silence fire alarm: .............................. [access code] 15
Silence intrusion alarm: ..................... [access code] 16
*
Turn door chime on/off: ...................... to toggle on or off 22
Check alarm memory: ....................... 16
Check troubles .................................. 19
Set time and date: ............................. [master code]
*
If available
4
OR press (if enabled)
*
3
2
*
6
*
Chime
1
Table of Contents
Quick Reference Guide i
Table of Contents ii
Limited Warranty iii
About This Guide 1
NT9010 controller Features 2
Section 1: Introduction
How Your System Works ................................................4
IMPORTANT NOTICE.......................................................4
Fire Detection.................................................................5
Testing ...........................................................................5
Remote Monitoring ........................................................5
Maintenance ..................................................................5
Section 2: Using Your NT9010 System
Operating the System from the NT9010 controller.......... 6
Operating the System from a Telephone.........................6
Receiving Incoming Calls ................................................7
Recording and Playing Voice Memos on the NT9010 ......7
Recording and Playing Voice Memos from
a Remote Phone ............................................................. 8
Section 3: Turning Your System On (Arming) and Off (Disarming)
Turning On Your System.................................................9
Turning Off Your System ..............................................10
Other Ways to Turn Your System On ............................10
Turning On Your System When Everyone is Away
(Away Mode)................................................................11
What to do if the Siren Sounds Immediately
After You Exit...............................................................11
Turning On Your System While You Are At Home
(Stay Mode)..................................................................12
Turning On Your System With No Access Code
(Quick Arm)..................................................................12
Turing On Your System with No Entry Time ..................13
Turning On Your System Automatically
(Automatic Arming)......................................................13
Exiting When the System is On (Quick Exit)...................14
Section 4: Dealing With Alarms and Emergencies
Fire Alarms ...................................................................15
Intrusion (Burglary) Alarms............................................16
Central Station Talk/Listen-in........................................ 16
Checking Alarms in Memory ........................................ 16
Calling for Help............................................................ 17
Section 5: Using Advanced Functions
Turning Off Part of Your System (Bypassing Zones)...... 18
Checking Trouble Conditions ....................................... 19
Testing Your System.....................................................20
Allowing Computer Access to Your System .................. 20
Section 6: Customizing Your System
Programming Access Codes......................................... 21
Setting the Time and Date............................................ 21
Turning the Door Chime On or Off............................... 22
Changing NT9010 Speaker Volume.............................. 22
Changing Telephone Prompt Volume........................... 22
Section 7: Fire Safety
Household Fire Safety Audit ......................................... 23
Fire Escape Planning..................................................... 23
Section 8: Guidelines for Locating Smoke Detectors 24
Section 9: Replacing Batteries
Tips for Buying Batteries............................................... 26
Door/Window Contacts................................................ 27
Motion Detectors......................................................... 27
Glassbreak Detectors.................................................... 27
Smoke Detectors.......................................................... 28
Wireless Keys ............................................................... 28
After Installing New Batteries ....................................... 28
Glossary 29
System Information
For Service ................................................................... 31
Access Codes............................................................... 31
System Information...................................................... 31
Zone Information .........................................................32
Index 33
Warning 34
i
Limited Warranty
Digital Security Controls Ltd. warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use. During the warranty period, Digital Security Controls Ltd. shall , at its optio n, repair or replace any defective product upon return of the product to its factory, at no charge for labour and materials. Any replacement and/or repaired parts are warran ted for the remainder of the original warranty or ninety (90) days, whichever is longer. The original owner must promptly notify Digital Security Controls Ltd. in writing that there is defect in material or workmanship, such written notice to be received in all events prior to expiration of the warranty period .
International Warranty
The warranty for international customers is the same as for any customer within Canada and the United States, with the exception that Digital Security Controls Ltd. shall not be responsible for any customs fees, taxes, or VAT that may be due.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in question to th e point of purchase. All authorized distributors and dealers have a warranty pro­gram. Anyone returning goods to Digital Security Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will no t accept any ship­ment whatsoever for which prior auth orization has n ot been obtaine d.
Conditions to Void Warranty
This warranty applies only to defects in pa rts and workmanship relating to normal use. It does not c over:
•damage incurred in shipping or handling;
•damage caused by disaster such as fire, flood, wind, earthquake or lightning;
•damage due to causes beyond the control of Digital Security Controls Ltd. such as excessive voltage, mecha nical shock or water damage;
•damage caused by unauthorized attachment, alterations, modificatio ns or foreign objects;
•damage caused by peripherals (unless such per ipherals were su pplied by Digita l Security Controls Ltd.);
•defects caused by failure to provi de a suitable in stallation environm ent for the products;
•damage caused by use of the products for purposes other than those for which it was designed;
•damage from improper maintenance;
•damage arising out of any other abuse, mishandling or improper application of the products.
Digital Security Controls Ltd .’s liability for failu re to repair the pr oduct under this warranty after a reasonable number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach of warranty. Under no circum­stances shall Digital Security Controls Ltd. be liable for any special, incidental, or consequential damages base d upon breach of warranty, breach of contract, negli­gence, strict liability, or any other legal theory. Such damages include, but are not limited to, loss of pr ofits, loss of the prod uct or any associated eq uipment, cost of capital, cost of substitute or replacement equipment, facilities or services, down time, purchaser’s time, the claims of third parties, including customers, and injury to property.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed or implied (including all implied warranties of mer­chantability or fitness for a particular purpose) And of all other obligations or lia­bilities on the part of Digital S ecurity Contro ls Ltd. Digital Security Controls Ltd. neither assumes nor author izes any other pe rson purporti ng to act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or lia­bility concerning this product. This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario, Canada. WA R N IN G : Digital Security Controls Ltd. reco mmends that th e entire system be completely tested on a regula r basis. However, despite fre quent testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possibl e for this product to fail to perform as expe cted.
Installer’s Lockout
Any products returned to DSC w hich have the Insta ller’s Lockout option enabled and exhibit no other problems will be subject to a service charge.
Out of Warranty Repairs
Digital Security Controls Ltd. will at its option repair or replace out-of-warranty products which are returned to its fact ory according to th e following conditio ns. Anyone returning goods to Digital Security Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment whatsoever for which prior authorization has not been obtained.
Products which Digital Securi ty Controls Ltd . determines to be repairable wi ll be repaired and returned. A set fee which Digital Security Controls Ltd. has predete r­mined and which may be revised from time to time, will be charged for each unit repaired. Products which Digital Sec urity Control s Ltd. determines not to be repairable wi ll be replaced by the nearest equivalent product available at that time. The current market price of the replacement product will be charged for eac h replacement u nit.
ii
About This Guide
This NT9010 User’s Guide is designed for anyone using a NT9010 Security System. The NT9010 has many useful features. Read this guide thoroughly to learn how to use your security system. Ensure that all users of this system are fully instructed in its use.
Important information about fire and burglary alarms is in Section 4: Deal­ing With Alarms and Emergencies begining on page 15. Read this section carefully!
This guide provides step-by-step instructions for each function. Each key you need
*
to press will be indicated by its symbol (e.g. To turn Door Chime On/Off). For some functions, you will need to enter your access code (indicated by [access
code]). To program other access codes, or to perform advanced functions, you will need to enter your master code (indicated by [master code]). You can also use the master code to turn the system on and off.
The NT9010 controller and its lights and functions are described on pages 2 and 3. The
Quick Reference Guide
required to access basic system functions, and the page number each function is described on.
See the
Fill out the System Information on page 31 with all of your zone informa­tion and access codes, and store this manual in a safe place for future refer­ence.
Glossary
on page 29 to learn more about words used in this manual.
inside the front cover shows you the commands
4
1
NT9010 Controller Features
This is the NT9010 controller. It controls and monitors all devices on your NT9010 security system. You can access all system functions using the buttons on the NT9010. In addition, the NT9010 provides easy to understand voice prompts to help you use the system. Please familiarize yourself with your new system console and its features.
™™
2
Microphone
You can use the microphone to record a voice memo on the NT9010. To record a memo, press the Record button, then talk into the micro­phone. When you are finished recording, press
#
. To play the memo, press the Playback but-
ton. If central station talk/listen-in is enabled on your
system, the microphone will also allow you to talk to your central station operator.
Siren
The NT9010 uses the siren to warn you about fire and burglary alarms.
Speaker
The NT9010 uses the speaker to broadcast sys­tem announcements, instructions, recorded memos, and alarms.
Status Lights
The NT9010’s “Ready”, “Armed” and “System” status lights provide instant visual feedback on the status of your security system.
Green “Ready” Light
If the Ready light is ON, the system is ready to be turned on. You will not be able to turn the sys­tem on unless the Ready light is ON (see
ing On Your System
If the Ready light is flashing, someone has recorded a voice memo on the NT9010. Press the Playback button to listen to the recording.
Red “Armed” Light
If the Armed light is ON, the system has been turned on successfully.
Yellow “System” Light
If the System light is ON, one or more of these conditions could be present on the system:
System Troubles (See
on page 19).
tions
Alarms in Memory (See
on page 10).
tem
on page 9).
Checking Trouble Condi-
Turning Off Your Sys-
Turn -
Zones Bypassed (turned off) (See
Part of Your System (Bypassing Zones)
page 18).
Programming
you are programming access codes, or perform­ing other programming functions.
. The System light will flash when
Turning Off
on
Emergency Keys:
In an emergency, you can use these keys to instantly contact your central station:
Press both * keys for two seconds to send a Fire message.
Press both * Keys for two seconds to send an Auxiliary message.
Press both ** Keys for two seconds to send a Medical message.
Press both * Keys for two seconds to send a Panic message.
IMPORTANT NOTE:
Medical, and Panic keys will NOT function unless programmed by the installer. If these keys are in service and the installer has enabled audible feedback, holding down both keys for two seconds will cause the keypad sounder to beep indicating that the input has been accepted and sent.
** Medical keys are available only on units intended to be monitored for medical applications.
Number Pad
Use the number pad to enter your access code and system commands. To select a function press . To exit a function press .
If your installer has enabled them, you can use the function buttons to access the stay, away, door chime, quick exit, status, volume control, memo record, and memo playback features. To use a feature, press and hold one of the buttons for two seconds. Refer to this information on these features.
*
Function Buttons
*The Fire, Auxiliary or
#
for more
Guide
3
Section 1: Introduction
Your installer has set up your system with your home or business in mind. You may not need all of the features described in this manual. Your installer will only turn on the features that you need, and should explain all the active features to you. If you have any questions about which features are included on your system, please ask your installer.
How Your System Works
Ready
Armed
System
Sta y
3
1
Away
2
Chime
5
4
6
Exit
Status
8
7
9
Volume
Recor d
*
#
0
Playback
™™
IMPORTANT NOTICE
Your security system consists of a DSC NT9010 controller, and various detectors and wireless devices.
The controller is the “brain” of your security system. It controls and checks all the detectors, and communicates with the central station (if remote monitoring is enabled). You will access system functions with your NT9010 controller, which is described on pages 2 and 3 of this manual. Each NT9010 has a microphone, siren, speaker, number pad, emergency keys, and eight function keys.
Using the NT9010 you can send commands to the system and check the current system status. Your installer will mount the NT9010 in a convenient location inside your premises.
Your security system can provide monitoring of intrusion, fire, and emergency. The security system has several zones (monitored areas). Each of these zones will
be connected to a detector (motion detector, glassbreak detector, door contact, etc.). If a detector goes into alarm, the NT9010 will sound an alarm and may announce the specific zone that caused the alarm (depending on how your installer has programmed the system).
A security system cannot prevent emergencies. It is only intended to alert you and – if the system is remotely monitored – your central station of an emergency situation. Security systems are generally very reliable but they may not work under all conditions and they are not a substitute for pru­dent security practices or life and property insurance. Your security system should be installed and serviced by qualified security professionals who should instruct you on the level of protection that has been provided and on system operations. For important warnings and cautions, please see page 34.
4
Introduction
Fire Detection
Te s ti n g
Remote Monitoring
Maintenance
This NT9010 controller is capable of monitoring fire detection devices such as smoke detectors and providing a warning if a fire condition is detected. Good fire detection depends on having an adequate number of detectors placed in appro­priate locations. The system must be installed in accordance with NFPA 72 (N.F.P.A., Batterymarch Park, Quincey MA 02269). Carefully review
Fire Safety
on
page 23.
NOTE:
Your installer must enable the fire detection portion of this equip-
ment for it to work.
To make sure your system continues to work as intended, you must test your sys­tem weekly. Please refer to
Testing Your System
on page 20. If your system does
not work correctly, call your installer for service.
This system can send alarms, troubles and emergency messages over telephone lines to a central station. If you accidentally initiate an alarm, immediately call the central station to prevent an unnecessary response.
NOTE:
Your installer must enable remote monitoring for it to work.
With normal use, the system requires minimum maintenance, but please note the following points:
1. Do not wash the security equipment with a wet cloth. Light dusting with a slightly moistened cloth should remove normal dust accumulations.
2. Use the system test described in
Testing Your System
on page 20 to check the battery condition of the NT9010 controller. We recommend that the stand­by battery be replaced every three years.
3. Consult the manufacturer’s literature for testing and maintenance instructions for other system devices such as smoke detectors, motion detectors, and glass­break detectors. For instructions on replacing detector batteries, see
Batteries
NOTE:
on page 26.
The NT9010 is only compatible with DSC wireless devices.
Replacing
5
Section 2: Using Your NT9010 System
Operating the System from the NT9010 controller
Operating the System from a Telephone
The NT9010 controller provides easy to understand voice prompts to help you to use your system.
You can check the current status of your system by pressing the Status button. The NT9010 will announce the time, whether the system is currently on (armed) or off (disarmed), if any zones are currently open or bypassed (turned off), and if there are any trouble conditions currently present on the system. Pressing the Status button while the NT9010 is speaking will cause it to stop.
If your installer has connected your NT9010 system to an incoming telephone line, you can access the system using a local telephone (a telephone on your premise). You may also be able to use the system from a remote telephone (a telephone not on your premise), if your installer has turned on this feature.
Even though you can use a telephone to operate your system, the telephone can not display or indicate system status or zones in alarm. Therefore, it is essential that you check the NT9010 controller regularly for any changes in system status.
CAUTION:
redial button to arm or disarm your system.
NOTE:
not from a local or a remote telephone.
Local Telephone Access
Use this procedure to call your NT9010 system within your home from a telephone that is on the same telephone line. No dial-in is necessary.
1. Pick up the telephone handset - you will hear a dial tone.
2. Enter your 3-digit Telephone Access Code. The dial tone will stop and the sys­tem will announce:
“Hello.”
3. The system may also say: “Enter your access code.” If so, enter your [access code].
4. The system announces one or more messages to advise you of its status. Follow the voice prompts to use the system functions.
For the security of your codes, DO NOT use a telephone with a
The Duress Code should only be used from the local controller and
6
Using Your NT9010 System
Remote Telephone Access
NOTE:
Pause for one second between key presses when entering access
codes or commands on a remote Phone
1. From any touch-tone telephone, dial number of the line on which your NT9010 has been installed.
2. After one ring, hang up. Wait 10 seconds then call again. On the second call, the system will answer after one or two rings and announce:
“Hello.”
3. Enter your 3-digit Telephone Access Code within 10 seconds. If you wait longer than 10 seconds, the system will automatically hang up.
4. The system will then prompt: “Enter your access code.” Enter your [access code] within 20 seconds. If you wait longer than 20 seconds,
the system will hang up. The system will also hang up if 3 incorrect access codes are entered.
5. Once you have entered an access code, the system will announce one or more messages to advise you of its status. Follow the voice prompts to use the sys­tem functions.
NOTE:
There is only one “Telephone Access Code”. It is programmed by your installer. It is not the same as your 4- or 6-digit system access code. More than one system access code can be programmed for use by different users of your system (see Programming Access Codes on page 21).
Receiving Incoming Calls
Recording and Playing Voice Memos on the NT9010
If you are accessing the NT9010 system over a local telephone at the same time as someone calls you, the system will announce:
“Attention, you have an incoming call. To receive the call, press pound now.” To answer the incoming call, press . If you do not press , you can continue
# #
to use the system.
You can record a voice memo on the NT9010 controller to be listened to at a later time. To record a voice memo:
1. Press the Record function button. The NT9010 says “Record memo now, To
complete press [#]“. The maximum memo length is 20 seconds.
2. Speak into the microphone (located in the top left corner of the unit). When
you have finished recording, press . The green Ready light flashes to indicate
#
a new memo has been recorded.
To listen to a voice memo:
1. Press the Playback function button. Once the memo has been played, the green
Ready light stops flashing, but the memo remains in memory until a new one is recorded, or until the NT9010 loses all power.
2. If the memo is not for you, you can press to stop the playback. If you press
#
before the playback finishes, the Ready light will continue to flash.
#
7
3. When the playback is finished, the NT9010 will say “Press [✱] to erase. Press [#] to save”.
Recording and Playing Voice Memos from a Remote Phone
To record a voice memo from a remote phone:
*
7
1. Press .
• Press , the NT9010 will say “For memo functions, press [7]“, then
• Press , the NT9010 will say “To record memo, press [1]. To playback
1
*
7
memo, press [2]“, then
• Press , the NT9010 will say “Record memo now. To complete press [#]“.
2. Speak into the telephone. When you have finished recording, press . The
1
#
NT9010 will say “To record memo, press [1]. To playback memo, press [2]“.
3. Press to exit this function.
#
To listen to a voice memo from a remote phone:
*
1. Press .
• Press , the NT9010 will say “For memo functions, press [7]“, then
• Press , the NT9010 will say “To record memo, press [1]. To playback
27
*
7
memo, press [2]“, then
• Press , the NT9010 beings to playback your voice memo.
• Press will cancel the playback.
2. When the playback is finished, the NT9010 will say “Press [
2
#
] to erase. Press [#]
to save”.
NOTE:
Press [
] will only erase the notification of the memo, not the memo itself. After the notification has been erased, press [#] will not restore the notification. But you will still be able to listen to the memo by press Play­back.
• Once you made your choice, the NT9010 will say “To record memo, press [1]. To playback memo, press [2]“.
3. Press to exit this function.
#
8
Section 3: Turning Your System On
(Arming) and Off (Disarming)
This section describes how to turn your system on and off. Read this section care­fully.
Tur n ing O n Your System
1. Before you turn on your system, make sure that it is Ready. You can tell that the system is ready when the green (Ready) light is ON.
see the Note below
2. Enter your access code on the keypad. If you have entered the wrong code, the keypad will sound one long beep - try again to enter the correct code.
When you enter a valid access code:
• The keypad sounds fast beeps.
• The red (Armed) light turns ON.
• The keypad starts to beep once every second. This tells you that the system is turning on (Audible Exit Delay).
3.
If you will be leaving
tem that you are away, and the system turns on completely.
If you will be staying
you are staying, and the system turns on only the perimeter areas.
NOTE:
If the green (Ready) light is
• Close all doors and windows
• Stop motion in all areas with motion detectors
If the yellow (System) light is ON, check for possible trouble conditions (see
Checking Trouble Conditions
turned off unintentionally (see
Zones)
on page 18).
.
, go out through the entry/exit door. Doing this tells the sys-
, do not open the entry/exit door. This tells the system that
not on
on page 19), and check that no zones are
Turning Off Part of Your System (Bypassing
:
If the green light is not on,
9
Tur n ing O ff Your System
1. If you are outside, enter through the entry/exit door. The keypad beeps to remind you to turn off the system.
NOTE:
Entering by any other door will immediately cause an alarm.
If you are inside, go to the keypad (the keypad will not beep).
2. Enter your [access code]. If you have entered from outside, you must enter the correct access code before the keypad stops beeping. If you do not enter a valid access code during this time, the system will sound an alarm.
NOTE:
If you have entered the wrong code the keypad will sound one long
beep - try again to enter the correct code.
As soon as you enter the correct code, the red (Armed) light turns OFF and the keypad stops beeping.
3. If an alarm occurred while the system was on, the NT9010 will announce: “Sys­tem is off. There are (number) alarms in memory: {Zone XX}.” See
Alarms in Memory
CAUTION:
If you return and find that an alarm has occurred while you
on page 16.
Checking
were away, it is possible that an intruder may still be on the premises. Go to a nearby safe location, and call your central station or the local authorities to investigate. The alarm memory is cleared each time the system is turned on, so any alarms showing have occurred only during the last time the sys­tem was on.
Other Ways to Tur n You r System On
10
There are two basic methods for turning on your security system.
: Use this method when everyone will be away from the premises. See
Away
page 11.
: Use this method when one or more people will stay on the premises. See
Stay
page 12.
You can also use any of the following methods to turn on your system (see pages 10 to 11):
Quick Arming:
Turn on your system without having to enter an access code.
Your installer must turn on this feature before it will work.
“No Entry” Arming:
Turn on your system with no entry time - use this method
when no one else will be entering the premises.
Automatic Arming:
The system will turn itself on at pre-set times.
Your
installer must turn on this feature before it will work.
NOTE:
will automatically be in Stay mode. (See
You Are At Home (Stay Mode)
When turning on your system from a remote telephone, the system
Turning On Your System While
on page 12.)
Turning Your System On (Arming) and Off (Disarming)
Tur n ing O n Your System When Everyone is Away (Away Mode)
When you turn on your system using the Away method, both interior zones (e.g. motion detectors) and perimeter zones (e.g. door and window contacts) will be active and will cause an alarm if they are opened.
1. Check that your system is ready (green Ready light is ON).
2. Enter your [access code]. As you enter each digit, the keypad sounder beeps. If you entered the access code incorrectly, the keypad sounder buzzes steadily for two seconds. Re-enter your access code correctly.
When you enter a valid access code:
• The keypad sounds fast beeps.
• The red (Armed) light turns ON.
• The exit time begins and the keypad beeps once every second. The keypad beeps quickly for the last 10 seconds of the exit time.
3. Exit the premises through the entry/exit door. Doing this tells the system that you are away, and the system turns on all the interior zones.
At the end of the exit time, all keypad lights, except the red (Armed) light, turn OFF. The system is now on.
NOTE:
not turned on. See
If the yellow (System) light is ON, there could be one or more zones
Turning Off Part of Your System (Bypassing Zones)
on page 18. If you turn on the system with a zone bypassed or a trouble present, your security protection is reduced.
Away Button
You may also be able to quickly turn on your system in Away mode using the “Away” button on your keypad. Press and hold it for two seconds to turn on the system in Away mode. Your installer will tell you if this feature has been enabled on your system.
What to do if the Siren Sounds Immediately After You Exit
Your installer will tell you if this feature has been enabled on your system. In order to reduce false alarms, the system can notify you of an improper exit
when turning on the system in the Away mode. If you do not securely close the entry/exit door during the exit time, the keypad will emit one continuous beep and the siren will sound.
If this occurs:
1. Re-enter the premises.
2. Enter your [access code] to turn off the system. You must do this before the
entry time ends.
3. Turn the system on again, making sure to close the entry/exit door properly.
(See
Turning On Your System When Everyone is Away (Away Mode)
.)
11
Tur n ing O n Your System While You Are At Home (Stay Mode)
Use the Stay mode when you want to stay on the premises, and also want to pre­vent unauthorized entry from outside. The system will only turn on the perimeter zones (e.g. door and window contacts), and will leave the interior zones off (e.g. motion detectors) so that you will be free to move around inside.
1. Check that your system is ready (green Ready light is ON)
2. Enter your [access code]. As you enter each digit, the keypad sounder beeps. If you entered the access code incorrectly, the keypad sounder will buzz steadily for two seconds. Re-enter your access code correctly.
When you enter a valid access code:
• The keypad sounds fast beeps.
• The red (Armed) light turns ON.
• The exit time begins and the keypad beeps once every second. The keypad will beep quickly for the last 10 seconds of the exit time.
3. DO NOT leave through the entry/exit door. This tells the system that you are not leaving, and the system automatically turns off the interior zones.
At the end of the exit time, all keypad lights, except the red (Armed) and yellow (System) lights, turn OFF. The system is now on.
Re-activate bypassed zones
To turn on the rest of the system when it is in Stay mode:
*
1. Press . The interior zones are now on.
NOTE:
1
When you have turned on the interior zones, you will not be able to enter areas protected by motion detectors, or open doors and windows. To access these areas, you must enter your [access code] and turn off the sys­tem.
Stay Button
You may also be able to quickly Stay arm your system using the “Stay” function button on your keypad.
If your installer has programmed this button
, press and
hold it for two seconds to turn your system on in Stay mode.
Tur n ing O n Your System With No Access Code (Quick Arm)
12
Your installer will tell you if the Quick Arm method is enabled on your system. Using the following method, you can quickly turn on your system without having to enter an access code.
1. Check that the system is ready (green Ready light is ON)
*
2. Press .
0
• The keypad sounds fast beeps.
• The red (Armed) light turns ON.
• The exit time begins and the keypad beeps once every second until the end of the exit time.
3. Go out through the entry/exit door. The system will be in Away mode. If you do not exit, the system will be in Stay mode.
Turning Your System On (Arming) and Off (Disarming)
#
#
*
NOTE:
Pressing will only turn on the system. To turn the system off,
0
you must enter a valid [access code]. See
10.
Turning Off Your System
on page
Turi n g On Your System with No Entry Time
Tur n ing O n Your System Automatically (Automatic Arming)
If you want to turn on the system, and no one else will be entering, you can remove the entry time from zones that normally have one. If somebody enters through any zone, the system will sound an instant alarm.
1. Check that your system is ready (green Ready light is ON)
*
2. Press , then your [access code].
9
• The red (Armed) light flashes as a reminder that the system is on and has no entry time.
• The keypad sounds fast beeps.
3. The system is now in Stay mode.
Your installer may have set up your system to turn on at a pre-set time. If auto­matic arming has been set up, when the system reaches the pre-set autoarm time, the keypad buzzers will sound for one minute.
During this one-minute warning time, you may be able to stop automatic arming by entering your [access code]. Ask your installer for more information.
Your installer may have set up the system so that users with a master code can change the autoarm time at the keypad. If so, master users will be able to turn the automatic arming function on or off, and program the time at which the system will automatically turn on each day.
To turn automatic arming on or off:
*
1. Press , then [master code].
2. Press to turn automatic arming on or off. The keypad will beep 3 times
6
2
when auto-arm is turned ON, and once when it is turned OFF.
3. When you are finished, press .
To change the autoarm time:
*
1. Press , then [master code].
2. Press .
6
3
3. Enter the autoarm time using the 24Hr format (0000 - 2359). For example, to set the time for 1:00pm, enter (1300).
5. When you are finished, press twice.
NOTE:
autoarm feature to work. Please see
The system must have the correct time and date in order for the
Setting the Time and Date
on page 21.
13
Exiting When the System is On (Quick Exit)
Your installer will tell you if the Quick Exit feature will work on your system. You can use the quick exit feature to leave the premises while the system is on, without having to turn your system off and on again.
To use the quick exit feature:
*
1. While the system is on, press .
0
2. The system will start a two-minute countdown, during which you may leave through the entry/exit door.
NOTE:
During this time, you may only open and close the entry/exit door once. Once the door is closed the system will end the two-minute quick exit time. If the door is opened again, or is not closed before the two-minutes are up, or if another entry/exit door is opened, the entry delay time will begin. The system must then be turned off so that an alarm is not gener­ated.
Exit Button
If your installer has programmed the “Exit” function button, press and hold the button for two seconds to activate the quick exit feature.
14
Section 4: Dealing With Alarms and
Emergencies
Read this section carefully so that you will know what to do if your system goes into alarm.
If you return to your premises and the siren is on. Contact the local authorities from a nearby safe location.
Your installer will tell you if fire detection equipment has been installed and enabled on your system.
NOTE:
A fire alarm always has priority over an intrusion (burglary) alarm.
Fire Alarms
A pulsing siren means a fire alarm.
low your evacuation plan immediately (see Fire Escape Planning
23
The system may also announce the label for the zone(s) that triggered the
).
alarm, if programmed by the installer. If remote monitoring is enabled, the system will send a fire message to the central
station. Your installer may have set up the keypad Fire keys and other fire equip­ment to send a fire alarm message to the central station as soon as they are acti­vated.
Your installer may have set up other equipment (e.g. smoke detectors) to have a 30 second delay before sending the alarm message to the central station. Your installer will inform you how the equipment on your system operates. Equipment that has been set up with a 30 second delay (e.g. smoke detectors) gives you time to correct the problem before a false alarm is sent to the central station.
If there is no fire condition, to silence the fire alarm:
1. Press within 30 seconds of the beginning of the alarm. The fire alarm and
2. If the detector still detects smoke after 90 seconds, the alarm will sound again.
3. If you do not press within the 30 second delay time, the system will send a
NOTE:
no fire condition, call the central station to avoid an unnecessary response.
NOTE:
ently than described above. Ask your installer for more information regarding your system’s operation.
#
communication to the central station will be delayed for 90 seconds to give you time to clear the smoke detector.
If there is no smoke, the system will return to normal.
#
fire message to the central station (if remote monitoring is enabled on your sys­tem). To silence the fire alarm after the 30 second delay has expired, enter your [access code].
If you suspect that a fire message has been transmitted, but there is
Your installer may have programmed the system to operate differ-
If there is a fire, or if you are not sure, fol-
on page
15
Intrusion (Burglary) Alarms
A steady siren means an intrusion alarm. The system may also announce the label for the zone(s) that triggered the alarm, if programmed by the installer.
To silence the alarm:
1. Enter your [access code].
2. If the alarm was unintentional, call your central station immediately to avoid an
unnecessary response.
3. Check the alarm memory to see which zone caused the alarm.
Once the source of the alarm has been corrected, the system will return to the Ready state.
Central Station Talk/ Listen-in
Checking Alarms in Memory
If your installer has set up remote monitoring on your system, the talk/listen-in fea­ture may also be available. If an alarm, or other programmed event, occurs on your system, this feature allows a central station operator to listen to what is hap­pening on the premises. The operator may also be able to talk to whoever is present, depending on the type of event that has occurred. Ask your installer for more information on this feature and how it works.
The alarm memory announcement tells you which zone (detector) caused the alarm. The alarm memory is cleared each time the system is turned on. Any alarms announced by the system have only occurred the last time the system was on.
CAUTION:
If you return and find that there was an alarm while you were away, it is possible that an intruder may still be on the premises. Go to a nearby safe location, and call your central station or the local authorities to investigate.
If an alarm occurred while the system was turned on, the NT9010 will announce: “There are (number) alarms in memory: {Zone XX}.”.
1. To cancel the alarm memory announcement, press .
#
2. After the announcement is over, the system will return to the Ready state, but
the yellow (System) light will be ON. To listen to alarms in memory again, press
. The NT9010 will announce the zones that were in alarm.
*
3
16
Dealing With Alarms and Emergencies
Calling for Help
The NT9010 has three pairs of emergency keys. Using these keys you can send an immediate Fire, Auxiliary or Medical, and Panic messages to your central station.
IMPORTANT:
The Fire, Auxiliary or Medical and Panic keys will NOT func­tion unless they have been turned ON by the installer. If your installer has turned these keys ON, and enabled audible feedback, holding down the keys for two seconds will cause the keypad sounder to beep indicating that the alarm input has been accepted and transmission to the central station is underway.
From the NT9010 controller
Press both keys for two seconds to send a Fire message, and to trigger a fire alarm on the system.
Press both keys for two seconds to send an Auxiliary message.
Press both keys (if available) for two seconds to send a Medical message.
Press both keys for two seconds to send a Panic message.
NOTE:
In the U.S.A., do not program the Aux keys for use in medical emer-
gencies as per UL requirements.
17
Section 5: Using Advanced Functions
This section describes how to perform more specialized functions: turning off spe­cific detectors (bypassing zones), turning the door chime on or off, checking sys­tem troubles, and testing your system.
Tur n ing O ff Part of Your System (Bypassing Zones)
Sometimes, you may need to temporarily turn off a detector:
• if you need to go into a protected area while the system is turned on
• or, if a detector is temporarily out of service but you need to turn on the system This is called “bypassing”. When you bypass a detector, it
time you turn on your system. Detectors (zones) cannot be bypassed once the system is on. Bypasses on detec-
tors are automatically cancelled each time the system is turned off. You must bypass the detectors again, if required, before you turn the system on again.
*
1. Start with the system turned off. Press .
2. If the system asks for your [access code], enter it now.
3. Enter the two-digit number (01-32) of the detector you want to turn off (bypass). The system will announce the zones (detectors) that are bypassed: “There are (number) zones bypassed: {Zone XX}, etc...To exit, press [#].”
To find out the number of a detector, check in
TIP:
32.
4. To turn a detector back on, enter the two-digit number of the zone (01-32). The system will return the zone to normal status and the zone will be ON when the system is next armed.
The system will announce any other zones (detectors) which are bypassed: “There are (number) zones bypassed: {Zone XX}, etc...To exit, press [#].”
5. When you are finished turning off detectors, press .
6. The next time you turn on your system, the bypassed detectors on. When you turn your system off again, all zones will return to normal (they will not be bypassed).
NOTE:
your level of security. If a detector is not working, call a service technician immediately so that the problem can be resolved and your system returned to proper working order.
NOTE:
vent you from turning off certain detectors (for example, smoke detectors).
NOTE:
until you turn off the bypass using the steps above (ask your installer for more information).
Bypassed detectors will not be able to sound an alarm - this reduces
For security reasons, your installer may program the system to pre-
If you have 24-hour zones on your system, they will stay bypassed
1
will not
Zone Information
#
turn on the next
on page
will not
turn
18
Using Advanced Functions
Checking Trouble Conditions
Your system continuously checks for a number of possible trouble conditions. If one of these trouble conditions occur:
• the yellow (System) light will be ON until the trouble is fixed
• the keypad will beep twice every 10 seconds until it is acknowledged by press­ing any key
• the NT9010 will say “System Trouble” when announcing the status of the system
NOTE:
A Trouble condition reduces the level of security your system pro-
vides. Call your installing company for service.
*
To listen to an announcement of the troubles that are present, press . To exit the trouble announcement, press .
#
2
Here is a list of the various trouble conditions that your system might announce:
Announcement: Problem and how it should be addressed:
“Service is required, press [1].”
“Low Battery”
“Remote Bell Trouble”
“Bad Module Placement”
“System Fault”
“AC Power Trouble.” Electrical power to the system has been interrupted. Check your
“Phone line trouble.” Your system has detected a problem with the telephone line. If
“Communication trouble.”
“ Zone Fault, press [5].”
“Zone tamper, press [6].”
If this message is announced, call for service. When the system announces this message, one or more of the following troubles may then be announced.
“Low Battery” means the battery voltage has fallen below the normal operating voltage.
“Remote Bell Trouble” means the system is having a problem communicating to the remote bell.
“Bad Module Placement” means during the installation, not all of the devices on your system were properly tested for commu­nication integrity.
“System Fault”means there is an internal system error.
fuse box or circuit breaker to ensure that the electricity supply for the system is on. If this does not correct the problem, call for service. The NT9010 may go to sleep to conserve the backup battery if the AC power is out for more than 30 seconds. If this happens, you can “wake up” the unit by pressing and holding
#
for 2 seconds.
this problem does not correct itself, or happens frequently, call for service.
Your system has been unsuccessful in communicating an event to your central station. If you hear this message, call for service immediately.
Your system has detected a fault on one or more zones (detectors).
5
Press , and the system will announce which zones have a fault. If you are unsure of how to clear a zone fault, call for service.
Your system has detected a tamper on one or more zones (detectors). Press and the system will announce which
6
zone(s) have tampers. If you are unsure how to clear the zone tamper, call for service.
19
Announcement: Problem and how it should be addressed:
“Device low battery, press [7].”
“The time and date are incorrect.”
Your system has detected that one or more of the wireless detectors on the system has a low battery. Press , and the sys­tem will announce which devices have a low battery. Change the relevant batteries. See page 26 for instructions. If this does not correct the problem, call for service.
If all power to the system is interrupted (AC and battery), the system clock and date will need to be reset. See
Time and Date
the system power failure, call for service.
on page 21. If you are unsure of the cause of
7
Setting the
Te st in g Yo u r System
Test your system every week. Report any problems immediately to your installation company.
NOTE:
Perform system tests during off-peak hours, such as early morning
or late evening.
1. If your system has remote monitoring, call the central station to tell them that you are testing your system.
6
2. Begin with the system turned off. Press [Master Code] . The system
*
4
sounds the siren and turns on all keypad lights for two seconds. When the sounder and keypad test is complete, press .
#
3. To test each area of your system, open each door and window in turn, or walk in motion detector areas.
4. Press the Status button. The system will announce all open zones.
5. If the system has any fire zones, activation will cause the alarm to sound in a pulsed mode. To silence the alarm, press .
CAUTION:
Do not use an open flame or burning materials to test a smoke
#
or heat detector. Contact your installer for information on safe methods of testing detectors.
6. When you are finished testing the system, inform your central station. If the system did not work properly, contact your installer.
NOTE:
Some features described above will not be functional unless enabled by your installer. Ask your installer which features are functional on your system.
Allowing Computer Access to Your System
20
From time to time, your installer may need to send information to, or retrieve information from your security system. Your installer will call your system over the telephone line using a computer. You may need to prepare your system to receive this “downloading” call. To do this:
6
1. Press [Master code] . This allows downloading for 1 or 6 hours
*
5
depending your installer’s set up. During this time, the system will answer incoming downloading calls.
For more information on this feature, please ask your installer.
Section 6: Customizing Your System
*
#
This section describes how to customize your system to suit your needs. Refer to this section for detailed instructions on: programming access codes and setting time and date.
Programming Access Codes
The master code (code 40) can be used to program system options, arm and dis­arm the system and program other access codes. You can program up to 32 addi­tional access codes (01 through 32). Other access codes, such as system supervisory and duress codes, are available. Contact your installer for more infor­mation.
*
1. Press [Master Code]. The red (Armed) light turns on and the yellow (Sys-
5
tem) light flashes.
2. Enter the two-digit number of the access code you want to program (01-32 for access codes, 40 for master code). If an access code already exists for the code number you have selected, it will be replaced by the new code.
3. Enter the new [code]. Access codes must be four digits unless otherwise indi­cated by your installer.
such as [1111] or [1234].
4. To exit access code programming, press .
NOTE: Do not use the factory default or obvious codes
#
5. Record your new codes on the “System Information” on page 31 in this book­let.
Erasing a code:
1. Press [Master Code]
*
5
2. Enter the number of the code you want to erase [01 to 32]. The Master code cannot be erased.
3. To erase the code, press .
4. To exit access code programming, press .
*
#
Setting the Time and Date
You should make sure that your system has the correct time and date. This is important for the auto-arm feature to function correctly, and for accurate report­ing of events.
1. To select time and date, press [Master Code] .
6
1
2. The system announces the current time and date. To change the time, press
1
, then enter the Time in Hours and Minutes using the 24-Hour format
(00:00 to 23:59).
3. To change the date, press , then enter the Date in Months, Days and Years
2
(MMDDYY) (November 26, 2000 = 112600).
4. To exit programming, press .
21
Tur n ing t he Door Chime On or Off
If your installer has enabled the door chime feature, your NT9010 will beep when­ever designated doors or windows are opened or closed. The NT9010 may also announce the zones that were opened or closed, if programmed. Your installer has programmed which doors and windows will activate the door chime.
*
1. Press to turn the door chime feature ON
4
The keypad will beep 3 times.
*
2. Press again to turn the door chime feature OFF
4
The keypad will sound one long beep. The function button labeled Chime can also perform the same function if it is
pressed and hold for 2 seconds. When door chime is enabled the keypad will beep 3 times. When door chime is disabled the keypad will sound one long beep.
Changing NT9010 Speaker Vol u me
Changing Telephone Prompt Vol u me
You can select from 3 different volume levels for NT9010 announcements - low, medium, and high.
1. Press the Volume function key. The NT9010 volume increases to the next level and will announce the volume level it is at.
2. Repeat step 1 until you find a volume setting you like.
3. When you have selected the volume level you want, press to exit.
#
If you will be using a telephone to access your system, you can change the volume of the telephone prompts. You can select from three different telephone volume levels, low, medium and high.
*
1. Press [Master Code] . The NT9010 announces the telephone volume
6
7
level: “Phone volume is low.”
2. To change the volume, press .
1
3. Repeat step 2 until you find a volume setting you like.
4. When you have selected the volume level you want, press to exit.
#
22
Section 7: Fire Safety
Read this section carefully. It contains important information about fire safety.
Household Fire Safety Audit
Fire Escape Planning
Most fires occur in the home. To minimize this danger, we recommend that a household fire safety audit be done and a fire escape plan be created.
1. Are all electrical appliances and outlets in a safe condition? Check for frayed cords, overloaded lighting circuits, etc. If you are uncertain about the condition of your electrical appliances or household service, have a professional evaluate these units.
2. Are all flammable liquids stored safely in closed containers in a well-ventilated, cool area? Cleaning with flammable liquids should be avoided.
3. Are fire hazardous materials (e.g., matches) well out of reach of children?
4. Are furnaces and wood burning appliances properly installed, clean and in good working order? Have a professional evaluate these appliances.
There is often very little time between the detection of a fire and the time it becomes deadly. Therefore it is very important to develop and rehearse a family escape plan.
1. Every family member should participate in developing the escape plan.
2. Study the possible escape routes from each location within the house. Since many fires occur at night, special attention should be given to the escape routes from sleeping quarters.
3. Escape from a bedroom must be possible without opening the interior door.
Consider the following when making your escape plans:
• Make sure that all exterior doors and windows are easily opened. Ensure that they are not painted shut, and that their locking mechanisms operate smoothly.
• If opening or using the exit is too difficult for children, the elderly, or the hand­icapped, plans for rescue should be developed. This includes making sure that those who are to perform the rescue can promptly hear the fire warning signal.
• If the exit is above the ground level, an approved fire ladder or rope should be provided as well as training in its use.
• Exits on the ground level should be kept clear. Be sure to remove snow from exterior patio doors in winter. Outdoor furniture or equipment should not block exits.
• Each person should know of a predetermined assembly point where everyone can be accounted for (e.g., across the street or at a neighbor’s house). Once everyone is out of the building, call the Fire Department.
23
• A good plan emphasizes a quick escape. Do not investigate or attempt to fight the fire, and do not gather belongings or pets as this wastes valuable time. Once outside, do not re-enter the house. Wait for the fire department.
• Write the fire escape plan down and rehearse it frequently so that should an emergency arise, everyone will know what to do. Revise the plan as conditions change, such as the number of people in the home, or if there are changes to the building’s construction.
• Make sure your fire warning system is operational by conducting weekly tests (see
Here is a list of the various trouble conditions that your system
might announce:
on page 19). If you are unsure about system operation, con-
tact your installing dealer.
• We recommend that you contact your local fire department and request further information on fire safety and escape planning. If available, have your local fire prevention officer conduct an in-house fire safety inspection.
24
Section 8: Guidelines for
Locating Smoke Detectors
Research has shown that all hostile fires in homes gen­erate smoke to a greater or lesser extent. Experiments with typical fires in homes indicate that detectable quantities of smoke precede detectable levels of heat in most cases. For these reasons, smoke alarms should be installed outside of each sleeping area and on each sto­rey of the home.
The following information is for general guidance only and it is recommended that local fire codes and regula­tions be consulted when locating and installing smoke alarms.
It is recommended that additional smoke alarms beyond those required for minimum protection be installed. Additional areas that should be protected include: the basement; bedrooms, especially where smokers sleep; dining rooms; furnace and utility rooms, and any hall­ways not protected by the required units.
On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the pres­ence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-M86 or other appropriate national standards for installation recom­mendations.
Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may prevent the unit from detecting smoke.
Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the unit.
BedroomBedroom
Bedroom
LivingRoomKitchen
Figure 1
Bedroom
Living Room
Basement
Figure 3
Bedroom
Dining Room
Do not locate detectors in areas of high humidity. Do not locate detectors in areas where the temperature
oC
rises above 38
(100oF) or falls below 5oC (41oF).
Smoke detectors should always be installed in accor­dance with NFPA 72, the National Fire Alarm Code. Smoke detectors should always be located in accor­dance with:
• Paragraph 2-2.1.1.1 of NFPA 72, Chapter 2.:
“Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bed­rooms and on each additional story of the family liv­ing unit, including basements and excluding crawl spaces and unfinished attics. In new construction, a smoke detector also shall be installed in each sleep­ing room.”
• Paragraph 2-2.1.1.2 of NFPA 72, Chapter 2.:“Split level arrangement. Smoke detectors are required where shown. Smoke detectors are optional where a door is not provided between living room and recreation room.”
25
Section 9: Replacing Batteries
From time to time, the batteries in the detectors and other components on your system will need to be changed. If a device has a low battery, your system will announce a “Device Low Battery” trouble message (see
ditions
When the batteries in one device need to be replaced, it is suggested that the bat­teries in all system devices be replaced at the same time. The batteries used in the devices are Eveready Alkaline Energizer or Energizer Lithium batteries.
NOTE:
your central station.
on page 19).
Before changing the batteries in the detectors, you should inform
Checking Trouble Con-
Tips for Buying Batteries
• Your system is designed to work with either Eveready Alkaline Energizer or Lith­ium batteries according to individual device. When replacing batteries, be sure to buy the same brand and type. Do not replace the batteries with any other type. The reliability of your security system depends on its batteries, and “no name” or generic brand batteries may not provide the best quality and dependability.
• Use fresh batteries. Most batteries have a “best before” date printed on their packaging or on the batteries themselves. Buy batteries that have a “best before” date of two years or more from your purchase date.
• When disposing of used batteries, follow the instructions and precautions printed on the batteries. Many cities and communities have collection sites or disposal services. Contact your municipal offices for more information.
• If in doubt about the batteries used in your system, or if you have trouble installing them, contact your installer for assistance.
Required Batteries
WLS904-433 Motion Detector Four AAA batteries WLS904P-433 Pet Immune Motion Detector Four AAA batteries WLS906-433 Wireless Smoke Detector Six AA batteries. WLS919-433 Wireless Key Two CR2032 lithium
batteries. WLS912-433 Wireless Glassbreak Detector Three AA batteries WLS914-433 Pet Immune Motion Detector Four AA batteries WLS925L-433 Universal Transmitter One Lithium Energizer No.
EL123AP battery.
. .
.
.
26
Replacing Batteries
Door/Window Contacts
Motion Detectors
WLS925L-433
To remove the cover of the universal trans­mitter, squeeze both sides of the unit where the notches are. Pull to release the cover.
Use care when installing the battery and observe the correct polarity (see diagram). Use only an Eveready Lithium Energizer No. EL123AP battery.
WLS904-433/WLS904P-433
Remove the motion detector from its mounting plate by holding the detector by its sides and pushing up. Remove the old batteries and install four fresh Eveready Alkaline Energizer AAA batteries. Be sure to observe cor­rect polarity when inserting the batteries. Replace the detector on its mounting plate, making sure it snaps into place.
WLS914-433
Remove the motion detector from its mounting plate by holding the sensor by its sides and pushing up. Install four fresh Eveready Alka­line Energizer AA batteries. Be sure to insert the batteries in the proper orientation. Replace the sensor on its mounting plate, making sure it snaps into place. After the batteries are installed, the detector will take 60 seconds to warm up. During this time the LED will flash.
Glassbreak Detectors
WLS912-433
Remove the detector from its mounting plate by pushing the detector in the direction shown at right.
Install the three Eveready Alkaline Energizer bat­teries, with the correct polarity, as shown at right.
27
Smoke Detectors
WLS906-433
The WLS906-433 requires six Eveready Energizer AA batteries. To replace the batteries, remove the detector from the mounting plate by pushing the locking tab and turning the detector counter-clockwise.
Hold the unit with the battery compartment facing you, and the imprinted wording right-side up. Install the first two batteries in the row nearest to you, with the + terminals facing left. Next, install the middle two batteries with the + terminals facing to the right. Place your thumb over the centre of these four batteries to keep them in place. Install the last two batteries, with their + terminals facing to the left, by snapping them past the nylon retainer.
Wireless Keys
After Installing New Batteries
WLS919-433
The WLS919 wireless key requires two lithium CR2032 batter­ies. To replace the batteries, open the key’s plastic housing by inserting a flathead screwdriver along the side of the unit;
+
+
carefully twist the screwdriver to separate the top and bottom plastic. Remove the old batteries. Insert the new batteries according to the diagram at right and reassemble the key’s plastic housing.
NOTE:
The polarity of the batteries must be observed.
After you change the batteries on your system, the system may announce trouble conditions. A zone tamper should be displayed for each detector that had batter­ies changed. A zone fault may also be displayed and announced for these detec­tors. Refer to
Checking Trouble Conditions
on page 19 for information on
checking Zone Faults and Zone Tampers. Be sure to perform a complete test of your system after new batteries are installed
to ensure that all detectors are working properly (see
Testing Your System
on
page 20).
28
Glossary
Glossary
Access code
Alarm
Announce
Audible exit fault
Away arming
Bypassing a zone
A 4- or 6-digit code you enter on the keypad to turn your system on or off, or to use other system features.
When a zone is violated (e.g., a smoke detector detects smoke, a motion detector senses movement, a door with a contact is opened), it will trigger an alarm.
Intrusion (burglary) alarm:
motion detectors, glassbreak detectors, door/window contacts). Usually occurs when the system is on. Intrusion alarms sound with a steady siren.
Fire alarm:
be triggered at any time, whether the system is on or off. Fire alarms sound with a pulsing siren.
Voice notification by the NT9010 of a variety of system conditions.
A feature that warns you of an improper exit (e.g. door not completely shut) when you attempt to turn on your system. Helps to prevent false alarms.
Turning on the system so that all the detectors (perimeter and interior) are on. (Used when everyone is away from the premises.)
Turning off a detector temporarily. When you bypass a zone, the detector for that zone will not monitor activity in the zone and will not be able to trigger an alarm, until the system has been turned off, then on again.
An alarm triggered by fire, smoke or heat detectors. Fire alarms may
An alarm triggered by an intrusion detector (e.g.
Central station
Detector
Emergency message
Entry time
If remote monitoring is enabled, your system will send alarms, troubles and emer­gency messages to the central station. If necessary, the central station will then notify authorities in your area.
A part of the system that can detect and report problems (e.g. a motion detector can tell if there is movement in a room).
A message sent to the central station when one of the 3 pairs of emergency keys ( ) is pressed and held for two seconds. Your installer must program these keys, or they will not work. Units will have either ( ) or ( ) keys.
A timer programmed by your installer. It starts when you enter an area of the sys­tem that is on. You must enter an access code to turn the system off before the timer runs out, or else an alarm will be triggered.
29
Entry/exit doors
Your installer will program the doors you usually use to enter or exit the premises as the entry/exit doors. These doors are programmed with entry and exit times so that you can turn the system on and off without causing a false alarm.
Exit time
Local telephone
Master code
Remote telephone
Stay mode
Tro uble
Zone
A timer programmed by your installer. It starts when you turn on your system to allow you a period of time to leave the premises. At the end of the exit time, the system will be on.
If your NT9010 system is connected to your home/office telephone line, you may be able to use a telephone key to access the system.
The master code is, a 4- or 6- digit access code, is used to set system options, to turn the system on and off, and to program other access codes.
If your NT9010 system is connected to your home/office telephone line, you may be able to use an off-premise (remote) telephone to access the system.
Turning on the system so that only the perimeter zones (see zone definitions, below) are on. (Use when one or more people will stay on the premises.)
The NT9010 controller continuously checks the system for problems. If the control­ler finds a problem (trouble), it will indicate this at the keypad. See
Trouble Conditions
on page 19 for a list of possible trouble conditions, and how
Checking
they are displayed or announced.
A limited area of the premises monitored by a detector (smoke detector, door/win­dow contact, motion detector, glassbreak detector, etc.).
Perimeter zone:
A zone that detects intrusion from outside the premises (e.g.,
door contact on an outside door, glassbreak detector).
Interior zone:
A zone that detects intruders who have already entered (e.g., a
motion detector).
Fire zone:
A zone that has a heat or smoke detector.
30
System Information
Fill out the following information for future reference and store this guide in a safe place.
For Service
Central Station Information:
Account #:_______________________________ Telephone #: ____________________________
Installer Information:
Company: _______________________________ Telephone #: ___________________________
Access Codes
Your Master Code is:
Additional Access Codes:
Code # Access Code Code # Access Code Code # Access Code Code # Access Code
01 09 17 25
02 10 18 26
03 11 19 27
04 12 20 28
05 13 21 29
06 14 22 30
07 15 23 31
08 16 24 32
____________________________
System Information
[F] FIRE _____________________________________
[A] AUXILIARY_______________________________ or Medical ___________________________
[P] PANIC ___________________________________
The Exit Time is______________________ seconds.
The Entry Time is ____________________ seconds.
31
Zone Information
There are ________ active zones on the system.
Zone Protected Area Zone Type Zone Protected Area Zone Type
01 17
02 18
03 19
04 20
05 21
06 22
07 23
08 24
09 25
10 26
11 27
12 28
13 29
14 30
15 31
16 32
32
Index
A
AC power trouble message 19 Access codes
adding 21 changing 21 defined 29 erasing 21 Master code 30 programming 21 telephone code 6
Alarm
checking 16 defined 29 false 15 fire 15 intrusion 16
memory 16 Answering the telephone 7 Armed light 3
turning off system 10
turning on system 9 Arming
automatic 13
away 11
basic 9
no entry delay 13
quick 12
stay 12 Automatic arming 13 Auxiliary keys 17 Away 11
B
Batteries 26–28 Burglary alarm 16 Buttons
see Function buttons Bypassing zones 18
C
Central station 5
defined 29
talk/listen-in feature 16 Checking
alarms 16
troubles 19 Chime 22
Cleaning the system 5 Codes See Access codes Communication trouble mes­sage 19 Computer access to system 20
D
Date
setting 21
Detectors
defined 29
See also Zones Device low battery message 20 Disarming 10 Door
chime 22
entry/exit 9, 11, 30 Door/window contacts 27 Downloading 20
E
Emergency keys 17 Entry time 10
defined 29 Entry/exit door
defined 30 Exit 14 Exit time 11
defined 30
F
False alarm 15 Fire
alarm 15
detection 5
escape planning 23
keys 17
safety 23 Function buttons 3, 11, 12
G
Glassbreak detectors 27
I
Intrusion alarm 16
L
Local telephone access 6
M
Maintenance of system 5 Master code 30 Medical keys 17 Memos 7, 8 Microphone 3 Monitoring station 5 Motion detectors 27
O
Operating the system
using a telephone 6 using WLS9001 6
P
Panic keys 17 Phone line trouble message 19 Playback 7, 8 Problem, See Trouble Programming
automatic arming 13 codes 21 time and date 21
Q
Quick
arming 12 exit 14
R
Ready light 3
turning on system 9 Record 7, 8 Remote monitoring 5 Remote telephone access 7 Replacing batteries 26–28
S
Service is required message 19 Smoke detectors 28 Speaker 3
loudness 22 Status 6 Stay 12
System
how it works 4 maintenance 5 operating 6 testing 5, 20 trouble 19 turning off 10 turning on 9
System light 3
alarm in memory 16 programming codes 21 trouble 19 turning on system 11
T
Telephone calls
calling the system 6 receiving while using
system 7 Testing 5, 20 Time
setting 21 Time and date incorrect mes­sage 20 Trouble
defined 30
messages 19 Turning off system
See Disarming Turning on system
See Arming
V
Voice memos 7, 8 Volume 22
W
Wireless keys 28
Z
Zone fault 28
message 19 Zone tamper 28
message 19 Zones
bypassing 18
defined 30
testing 20
33
WARNING
Note to Installers
This warning contains vital inf ormation. As the only individual in contact with sys­tem users, it i s your responsibility to b ring each item in this warnin g to the attention of the users of this system.
System Failures
This system has been careful ly designed to be as effective as poss ible. There are circumstances, however, involving fire, burglary, or other types of emergencies where it may not provide protection. Any alarm system of any type may be com­promised deliberately or may fail to operate as expected for a variety of reasons. Some but not all of these reasons m ay be:
Inadequate Installation
A security system must be installed properly in order to provide ad equate protec­tion. Every installation should be evaluated by a security professional to ensure that all access points and areas are covered. Locks and latches on windows and doors must be secure and operate as intended. Windows, doo rs, walls, ceil ings and other building materials must be of s ufficient strength a nd construction to provide the level of protection expected. A reevaluation must be done during and after any con­struction activity. An evaluation by the fire and/or police department is highly rec­ommended if this service is availabl e.
Criminal Knowledge
This system contains security features which were kn own to be effective at the time of manufacture. It is possible for persons with criminal intent to develop techniques which reduce the effectiveness of these feat ures. It is important that a security sys­tem be reviewed periodically to ensure that its featu res remain effective and that it be updated or replaced if it is found that it does not provide the protection expected.
Access by Intruders
Intruders may enter through an unprotected a ccess point, c ircumvent a sensi ng device, evade detection by moving th rough an area of insufficient coverage, disco n­nect a warning device, or interfere with or prevent the proper operation of the sys­tem.
Power Failure
controllers, intrusion detectors, smoke detectors and many other security devices require an adequate power supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail. Even if the batteries have not failed, they must be charged, in good condition and installed correctly. If a device operates only by AC power, any interrupti on, however brief, will render that device inopera­tive while it does not have power. Power interruption s of any length are often accompanied by voltage fluctuations which may dam age electronic equipment such as a security system. After a power interruption has occurred, immediately conduct a complete system test to ensure that the system operates as intended.
Failure of Replaceable Batteries
This system’s wireless transmitte rs have been desi gned to provide several years of battery life under normal con ditions. The expected battery life is a function of the device environment, usag e and type. Am bient conditi ons such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the expected battery life. While each transmitting device has a low battery monitor which identifies when the batter ies need to be rep laced, this monitor may fail to operate as expected. Regular testing and maintenance will keep the system in good operating condition.
Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the radio path or deliberate jamming or other inad­vertent radio signal interference.
System Users
A user may not be able to operat e a panic or emergen cy switch possib ly due to per­manent or temporary physical disability, inability to reach the device in time, or unfamiliarity with the corre ct operation. It is important that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm.
Smoke Detectors
Smoke detectors that are a part of this system may n ot properly alert occupants of a fire for a number of reasons, some of which follow. The smoke detectors may h ave been improperly installed or positioned. Smoke may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roo fs, or on the other side of closed doors. Smoke detectors m ay not detect smoke from fires on another level of the residence or building.
Please Read Carefully
Every fire is different in the amount of smoke pro duced and the rate of burning. Smoke detectors c annot sense all typ es of fires equally we ll. Smoke detecto rs may not provide timely warning of fire s caused by carel essness or saf ety hazards such as smoking in bed, viol ent explosions, es caping gas, improper storage of flammable materials, overload ed electrical circuits, chi ldren playing w ith matches or a rson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warning to allow all occupants to escape in time to avoid injury or death.
Motion Detectors
Motion detectors can only detect mo tion within the de signated areas as shown in their respective installation instr uctions. They cannot discriminate between intru d­ers and intended occupants. Motion detectors do not provide volumetric area pro­tection. They have mul tiple beams of detection and motion can only be detected in unobstructed areas covered by these beam s. They cannot detect motion which occurs behind walls, ceilings, floor, closed doors, glass part itions, glass doors or windows. Any type o f tampering whether intentional or unintentional such as masking, painti ng, or spraying of any material on the lense s, mirrors, windows or any other part of the detection sy stem will impa ir its proper op eration.
Passive infrared motion detectors o perate by sensin g changes in t emperature. How­ever their effectiveness can be reduced when the ambi ent temperature rises near or above body temperature or if there are intentional or unintentional sources of heat in or near the detection area. Some of these heat sources could be heaters, radi ators, stoves, barbeques, fireplaces, sunlight, steam vents , lighting and so on.
Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if th ere is an inte rvening wall or door. If warning devices are located on a different level of the residen ce or premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may be inter­fered with by other noise sources such as stereos, radios, televisions, air condition­ers or other appliances, or passing traffic. Aud ible warning device s, however loud, may not be heard by a hearing-impa ired person.
Telephone Lines
If telephone lines are used to t ransmit alarms , they may be out of service or busy for certain periods of time. Also an intruder may cut the telephone line or defeat its operation by more sophisticate d means which ma y be difficult to detec t.
Insufficient Time
There may be circumstances when the system will operate as intended, yet the occupants will not be protected from the emergency du e to their inability to respond to the warnings in a timely manner. If the system is monitored, the response may not occur in time to protect the occupants or their belongings.
Component Failure
Although every effort has been made to make this system as reliable as possible, the system may fail to function as intended due to t he failure of a com ponent.
Inadequate Testing
Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance. The complet e system shou ld be tested weekly and immediately after a br eak-in, an attempted break-in, a fire, a storm, an earthquake, an acci dent, or any kind of construction act ivity inside or outsi de the premises. The testing should include all sensing devices, keypads, c onsoles, alarm indicating devices and any other ope rational devices t hat are part of t he system.
Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An ala rm system also is not a substitute for property owners, r enters, or other occupants to act prudently to prevent or minimize the harmfu l effects of an emergency situation.
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your authority to use this equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interfer­ence in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be deter­mined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Re-orient the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/television technician for help. The user may find the following booklet prepared by the FCC useful: How to Identify and Resolve Radio/Television Interference Problems”. This booklet is available from the U.S. Government Printing Office, Wash­ington D.C. 20402, Stock # 004-000-00345-4.
IMPORTANT INFORMATION
This equipment complies with Part 68 of the FCC Rules. On the side of this equipment is a label that contains, among other information, the FCC registration number of this equipment. Notification to Telephone Company The customer shall notify the tele­phone company of the particular line to which the connection will be made, and provide the FCC registration number and the ringer equiva­lence of the protective circuit. FCC Registration Number: F53CAN-34664-AL-E Ringer Equivalence Number: 0.4B USOC Jack: RJ-31X
Telephone Connection Requirements
pany provided ringers, all connections to the telephone network shall be made through standard plugs and telephone company provided jacks, or equivalent, in such a manner as to allow for easy, immediate discon­nection of the terminal equipment. Standard jacks shall be so arranged that, if the plug connected thereto is withdrawn, no interference to the
Except for the telephone com-
operation of the equipment at the customers premises which remains connected to the telephone network shall occur by reason of such with­drawal.
Incidence of Harm
cause harm to the telephone network, the telephone company shall, where practicable, notify the customer that temporary disconnection of service may be required; however, where prior notice is not practicable, the telephone company may temporarily discontinue service if such action is deemed reasonable in the circumstances. In the case of such temporary discontinuance, the telephone company shall promptly notify the customer and will be given the opportunity to correct the situation.
Additional Telephone Company Information
must be properly connected to the telephone line with a USOC RJ-31X telephone jack. The FCC prohibits customer-provided terminal equipment be connected to party lines or to be used in conjunction with coin telephone service. Interconnect rules may vary from state to state.
Changes in Telephone Company Equipment or Facilities
phone company may make changes in its communications facilities, equipment, operations or procedures, where such actions are reason­ably required and proper in its business. Should any such changes ren­der the customers terminal equipment incompatible with the telephone company facilities the customer shall be given adequate notice to the effect modifications to maintain uninterrupted service.
Ringer Equivalence Number (REN)
quantity of devices that you may connect to your telephone line and still have all of those devices ring when your telephone number is called. In most, but not all areas, the sum of the RENs of all devices connected to one line should not exceed five (5.0). To be certain of the number of devices that you may connect to your line, you may want to contact your local telephone company.
Equipment Maintenance Facility
phone equipment, please contact the facility indicated below for informa­tion on obtaining service or repairs. The telephone company may ask that you disconnect this equipment from the network until the problem has been corrected or until you are sure that the equipment is not mal­functioning. Digital Security Controls Ltd. 160 Washburn St., Lockport, NY 14094
Should terminal equipment or protective circuitry
The security control panel
The tele-
The REN is useful to determine the
If you experience trouble with this tele-
©2001 Digital Security Controls Ltd. Toronto • Canada Printed in Canada 29005928 R001
Loading...