DSC AMP-704 Installation Instructions Manual

AMP-704
Point Interface Module
INSTALLATION INSTRUCTIONS
The AMP-704 Point Interface Module (PIM) allows for the connection of non-powered or ex­ternally powered hardwired devices to the Addressable Multiplex Loop (AML). The four in­puts and cover tamper can be individually enrolled as zones on the control panel. The module is jumper-selectable for either N/C loops, SEOL, or DEOL resistors .
The AMP-704 PIM uses a 2-wire connection for power and to communicate with the control panel. This, in combination with low power devices, simplifies wiring and reduces installation cost. The AMP-704’s low current draw also maximizes the number of modules that can be connected to an addressable loop. For additional information on AML wiring, please refer to the compatible panel’s Installation Manuals.
Voltage .................................................... 12V
Current Draw....... 3.4mA max (Burg Config.)
.............................. 6.7mA max (Fire Config.)
Loop resistance......................... 100ΩΩ (max.)
Normal loop response........................400ms.
Temperature............. 32º - 120º F (0º - 49º C)
Humidity................0 - 93%, non-condensing
Figure 1: AMP-704
SW1
Control Panel Compatibility
• PC4020/PC4020CF v3.0 and higher
• PC5010 v2.0 and higher*
• PC5015 v2.2 and higher*
• PC5020/PC5020CF v3.0 and higher*
*Requires PC5100 Addressable Expansion Module
NOTE: For Commercial Fire applications use the AMP-704 only in conjunction with models PC4020CF and PC5020CF control units.
IN G ND Z1 COM Z2 Z3 COM Z4
Mounting
Select a mounting location for the AMP-704. The module should be located in a dry location and as close as possible to the points to be protected. Alternatively to the method explained below, the PCB may be mounted in a metal cabinet using the standoffs provided with the unit, refer to Figure 3.
1. Remove the cover using a flat blade screwdriver to push in the tab at the bottom of the enclosure.
2. Pull the addressable loop and input wires through the wiring access holes located at the bottom of the backplate.
3. Mount the device securely to the wall using the two mounting tabs on the backplate or using the two mounting holes inside the backplate. To use the holes inside, the PCB must first be removed. To do this, remove the 3 screws holding the PCB and lift it out.
CAUTION: When replacing the PCB, do not over-tighten the screws, the PCB could be damaged.
NOTE: If the mounting tabs are not being used to mount the device, they can be broken off.
4. Wire the module and configure the EOL supervision jumper as per the instructions below.
5. Replace the cover and insert the cover screw.
Wiring
Connect the AMP-704 wiring as indicated below:
Loop Current vs. Wiring Distance
Figure 2: AMP-704 Wiring
(from PC4020/PC5100)
Total Loop
Current (mA)
10 2880/878 5143/1568 20 1620/494 3645/1111 30 1010/308 2520/768 40 771/235 1736/529 50 600/183 1250/768
70 400/122 800/244 100 200/61 310/95 120 135/41 155/47 150 100/30 124/37 170 96/28 120/35
22 AWG
distance (ft/m)
18 AWG
distance (ft/m)
SUPERVISED,
POWER LIMITED
PC4020: PGM1/PGM2
PC5100: STR+
PC4020: AUX-
PC5100: STR-
IN GND Z1 COM Z2 Z3 COM Z4
SUPERVISED,POWER LIMITED
Refer to EOL supervision for proper input connections Rating: 12V, 1mA
CAUTION: Connect only DSC addressable devices to the addressable loop connections. Connection of any other type of device will impair operation. Any devices other than addressable devices that require power to operate must be powered separately.
Figure 3: Power Limited and Non-Power Limited Wiring (this diagram is representative of
all compatible control panels)
POWER LIMITED
POWER LIMITED
Compatible
Control Panel
WARNING: Do not route any wiring
NON-POWER
LIMITED
Cable
Tie
Class2
Power
Limited
37VA
Voltage
Barrier
over circuit boards. Maintain at least 1" (25.4mm) separation.
KEYBUS
Power Limited
Cable Tie (not provided) To prevent wires from falling onto batteries, secure them to the enclosure or to the plastic standoff located under the control panel.
For fire installations,
Non-Power
Limited
-
+
lines come through
conduit connections.
-
+
7Ah7Ah
AMP-704
INSTALL BATTERY & AC WIRING AS SHOWN
IMPORTANT: A minimum 1/4" (6.4mm) separation must be main-
tained at all points between battery/primary AC wiring and all other wiring connections. The AMP-704 is mounted inside the compatible control unit's enclosure using 3 nylon spacers 3/8" (9.6mm).
Loading...
+ 2 hidden pages