Dometic RM7030, RM7732 User Manual

Foreword
This service manual is the result of the
dedication of The Dometic Corporation and
its
engineers necessary instruction for making accurate analyses of certain conditions. Provided is a diagnostic chart leading a qualified mechanic into the service manual pages to
locate and solve symptoms which may occur. Dometic has continued its commitment in providing service people with this, the most up-to-date information about servicing Dometic RV accessories.
in giving
service people the
form No. 3 106938.008
2/96
(Replaces OS1 684)
.
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
CONTENTS
PAGE NO.
RM7030/RM7732 DIAGNOSTIC FLOW CHART ........................... 1
SECTION 1
OPERATION
1.1 RM7030 (Prod. #921890201 & 921890301)
Refrigerator Operation .......................................................... 5
1.2 RM7030 (Prod. #921890401) Refrigerator Operation ................ 6
1.3 RM7732 Refrigerator Operation ............................................. 7
SECTION 2
AC VOLTAGE
AC Voltage Requirements ..................................................... 9
SECTION 3
AC COMPONENTS
Heating Element .................................................................. 9
SECTION 4
DC VOLTAGE
DC Voltage Requirements ..................................................... 9
SECTION 5
DC COMPONENTS
5.1 Thermostat: RM7030 (Prod. No. 921890201 & 921890301) ....... 9
5.2 Thermistor: RM7030 (Prod. No. 921890401) & RM7732 .......... 10
5.3 Thermistor Adjuster: RM7030 (Prod.No. 921890401) & RM7732 10
5.4 Solenoid Valve ................................................................... 10
5.5 Igniter ............................................................................... 11
5.6 High Voltage Cable ............................................................ 11
5.7 Fuses ............................................................................... 12
5.8 Upper Circuit Board ............................................................ 12
5.9 Lower Circuit Board ............................................................ 15
5.10 Door Switch....................................................................... 17
5.11 Electrode .......................................................................... 18
5.12 Climate Control Heater ....................................................... 18
SECTION 6
LP GAS
LP Gas Requirements ........................................................ 18
SECTION 7
LP GAS COMPONENTS
7.1 Manual Gas Shutoff Valve ................................................... 19
7.2 Orifice .............................................................................. 20
7.3 Thermocouple ................................................................... 20
7.4 Burner .............................................................................. 21
7.5 Flue Baffle ........................................................................ 21
7.6 Flue Cap (RM7030 Only) .................................................... 21
37
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
CONTENTS
SECTION 8
WIRING
8.1 External Wiring .................................................................. 21
8.2 Internal Wiring ................................................................... 21
SECTION 9
OTHER
9.1 Leveling ............................................................................ 25
9.2 Ventilation ......................................................................... 25
9.3 Air Leaks .......................................................................... 25
9.4 Door Position ..................................................................... 27
9.5 Ambient Temperature ......................................................... 27
9.6 Cooling Unit ...................................................................... 27
9.7 Food Storage .................................................................... 27
9.8 High Humidity .................................................................... 27
9.9 Interior Liner Seal to Frame ................................................. 28
SECTION 10
ICE MAKER
Ice Maker Operation ........................................................... 29
PAGE NO.
SECTION 11
ICE MAKER COMPONENTS
11.1 Mold Heater ...................................................................... 29
11.2 Ice Ejector......................................................................... 29
11.3 Mold Thermostat ................................................................ 29
11.4 Shutoff Arm ....................................................................... 30
11.5 Mold Switches ................................................................... 30
11.6 Timing Motor ..................................................................... 30
11.7 Water Valve ...................................................................... 30
11.8 Ice Maker Assembly ........................................................... 31
SECTION 12
ICE MAKER  OTHER
12.1 Water Fill Adjustment.......................................................... 34
12.2 Wiring ............................................................................... 35
12.3 Water Supply ..................................................................... 35
36
DIAGNOSTIC SERVICE MANUAL
Diagnostic Service Manuals
DOMETIC® RM7030/RM7732
Refrigerators
This program will address the most common system problems associated with the Dometic RM7030/RM7732 refrigerators supplied by The Dometic Corporation. Our intent is to provide you with a guideline of checks to make, should you encounter one of the following symptoms.
RM7030 REFRIGERATOR SECTION: Product No. 921890201 & 921890301 SYMPTOM CAUSE REFER TO STEP
REFRIGERATOR SECTION
1. No operation  no panel lights
2. No operation  has panel lights
3. Operating OK  no panel lights
4. No AC operation  operates on gas
Operation 1.1 A DC Volts 4A Fuse 5.7 A Wiring 8.1, 8.2 Upper Circuit Board 5.8 A Lower Circuit Board 5.9 A ,D
Operation 1.1 A Thermostat 5.1 Upper Circuit Board 5.8 A Solenoid 5.4 A Wiring 8.2 Lower Circuit Board 5.9 B,C,D
DC Volts 4A Wiring 8.2 Upper Circuit Board 5.8 B through I Lower Circuit Board 5.9 D
Operation 1.1 A AC Volts 2 Heating Element 3 Upper Circuit Board 5.8 B,C Wiring 8.2 Thermostat 5.1 Lower Circuit Board 5.9 B
5. No Gas operation  operates on AC
6. Insufficient cooling on all modes.
7. Insufficient cooling on AC  cools properly on gas.
Operation 1.1 A LP Gas 6 Manual Gas Valve 7.1 Igniter 5.5 A High Voltage Cable 5.6 A Electrode 5.11 Solenoid 5.4 A Upper Circuit Board 5.8 B,D,E Wiring 8.2 Lower Circuit Board 5.9 C
Ventilation 9.2 Leveling 9.1 Ambient Temperature 9.5 Air Leaks 9.3 Thermostat 5.1 Cooling Unit 9.6
AC Volts 2 Heating Element 3
1
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
SYMPTOM CAUSE REFER TO STEP
8. Insufficient cooling on gas  cools properly on AC.
9. Freezes on all modes.
10. Changes preset mode.
11. Flame failure light within 10 seconds.
12. Flame failure light after 3 minutes.
LP Gas 6 Orifice 7.2 Flue Baffle 7.5 Flue Tube 7.7 Flue Cap 7.6 Burner 7.4
Thermostat 5.1 DC volts 4A
DC Volts 4A Wiring 8.1 Lower Circuit Board 5.9 A,B,C,D
Igniter 5.5 A High Voltage Cable 5.6 A Electrode 5.11 Wiring 8.2
LP Gas 6 Manual Gas Valve 7.1 Solenoid 5.4 A Orifice 7.2 Burner 7.4 Wiring 8.2 Thermocouple 7.3 A
13. Interior light ON when door is closed.
14. Rapid formation of frost.
15. Water on frame.
RM7030 (Prod. No. 921890401) & RM7732
16. No operation  no panel lights
17. No operation  has panel lights
Wiring 8.2 Door Switch 5.10 Door Position 9.4
Food Storage 9.7 Interior Liner to Frame 9.9 High Humidity 9.8 Air Leaks 9.3
Interior Liner to Frame 9.9 High Humidity 9.8 Air Leaks 9.3 Climate Control Heater 5.12
Operation 1.1B or 1.2 DC Volts 4B Fuse 5.7 B Wiring 8.1 & 8.2 Upper Circuit Board 5.8 J Lower Circuit Board 5.9 E
Operation 1.1B or 1.2 DC volts 4B Thermistor 5.2 Fuses 5.7 B Upper Circuit Board 5.8 J Wiring 8.2 Lower Circuit Board 5.9 E,F,G
2
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
SYMPTOM CAUSE REFER TO STEP
18. No AC operation  operates on gas.
19. No gas operation  operates on AC
20. Insufficient cooling on all modes.
Operation 1.1B or 1.2 AC Volts 2 Fuse 5.7 B Heating Element 3 Upper Circuit Board 5.8 J Wiring 8.2 Lower Circuit Board 5.9 E,F
Operation 1.1B or 1.2 LP gas 6 Manual Gas Valve 7.1 Igniter 5.5 B High Voltage Cable 5.6 B Electrode 5.11 Solenoid 5.4 B Upper Circuit Board 5.8 J Wiring 8.2 Lower Circuit Board 5.9 E,G
Ventilation 9.2 Leveling 9.1 Ambient Temperature 9.5 Air Leaks 9.3 Thermistor 5.2 Cooling Unit 9.6 Thermistor Adjuster 5.3
21. Insufficient cooling on AC  cools properly on gas.
22. Insufficient cooling on gas  cools properly on AC.
23. Freezes.
24. Changes preset mode.
25. Check light on.
AC Volts 2 Heating Element 3 Lower Circuit Board 5.9 E,F
LP Gas 6 Orifice 7.2 Flue Baffle 7.5 Flue Tube 7.7 Flue Cap (RM7030 Only) 7.6 Burner 7.4 Lower Circuit Board 5.9 E,G
Thermistor 5.2 Thermistor Adjuster 5.3 Lower Circuit board 5.9 E,F,G Upper Circuit Board 5.8 J
Operation 1.1B or 1.2 DC Volts 4B Wiring 8.1 Upper Circuit Board 5.8 J Lower Circuit Board 5.9 E
DC Volts 4 Wiring 8.2 LP Gas 6 Manual Gas Valve 7.1 Solenoid 5.4 B Orifice 7.2 Burner 7.4 Lower Circuit Board 5.9 E,G Thermocouple 7.3 B
3
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
SYMPTOM CAUSE REFER TO STEP
26. Interior light on when door is closed.
27. Rapid formation of frost.
28. Water on frame.
ICE MAKER SECTION
29. Ice Maker fails to start.
30. Ice Maker won't make ice.
Wiring 8.2 Door Switch 5.10 Door Position 9.4
Food Storage 9.7 Interior Liner to Frame 9.9 High Humidity 9.8 Air Leaks 9.3
Interior Liner to Frame 9.9 High Humidity 9.8 Air leaks 9.3 Climate Control Heater 5.12
Operation 10 Arm in UP Position 11.4 AC Voltage 2 Water Valve 11.7 Ice Maker Cycle 11.8
Blades frozen in ice 12.1 AC Voltage 2 Water Valve 11.7 Ice Maker Cycle 11.8
31. Keeps making ice and won't shut off.
32. Not making enough ice.
33. Too much water is coming out.
34. Ejector blade frozen into ice cubes.
35. Unit is hooked-up  no water comes in.
36. Ice maker is running but won't make cubes.
37. Ice maker will not eject ice.
Shutoff Arm 11.4
Operation 10 Mold Thermostat 11.3 Cube Size 12.1 Ice Maker Cycle 11.8
Water Fill Adjustment 12.1 Water Valve 11.7
Water Fill Adjustment 12.1 Water Valve 11.7
Water Supply 12.3 Water Valve 11.7
Water Supply 12.3 Shutoff Arm 11.4 Mold thermostat 11.3 Hold Switch 11.5
Ice Ejector 11.2 Mold Heater 11.1 Timing Motor 11.6
4
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
SECTION 1
1.1 OPERATION RM7030 (Product No. 921890201 & 921890301)
A
B
OFF
C
ON
D
AC
E
F
G
H
AES FULLY AUTOMATIC MODE
Turn switch "C" to the "ON" position. The bulb above push-button "A" will light up green, indicating that the control system is in the fully automatic mode. In this mode, 120 volts AC operation has first priority, meaning the refrigerator will operate on 120 volts AC whenever it is available. If 120 volts AC is not available, the system will automatically switch to LP gas operation. The thermostat inside the refrigerator cabinet cycles the element/burner as required to maintain the desired temperature.
NOTE: The AES controls will automatically go to the fully automatic mode each time switch "C" is turned "ON".
LP GAS OPERATION
When there is no electrical power available (120 volts AC) or if the indicator lamp above button "B" is ON, the AES system will switch to LP gas operation. When the thermostat in the refrigerator cabinet calls for cooling, the following sequence takes place: A. A high voltage spark is created above the burner. B. Power is sent to a solenoid which opens the gas
control, allowing LP gas to flow to the burner. The
spark ignites the LP gas and the small flame pro-
vides heat for the boiler. C. The electrode mounted above the burner tube
monitors the flame continuously. If the flame should
fail for any reason, the high voltage spark will start
immediately and relight the flame.
When the thermostat reaches the desired temperature, it will shut off the gas flame completely. The system will remain on standby until cooling is again required.
LP GAS ONLY OPERATION
Turn switch "C" to the "ON" position and press push- button "B". The green indicator lamp over push-button "B" will come on and the refrigerator will operate only on LP gas even if 120 volts are available. When the vehicle engine is turned "OFF", the AES system initiates a 25 minute delay, preventing the refrigerator from operating on LP gas.
LP GAS DELAY MODE
When the vehicle engine is turned off, the AES system initiates a delay cycle which prevents the refrigerator from operating on LP gas for 25 minutes. The purpose of the delay is to avoid having a gas flame burning dur­ing a refueling stop at a gas station (see WARNING).
If the vehicle engine is restarted during this delay pe­riod, the LP gas operation will not start until the delay period is over. This means each time the vehicle engine is stopped, the complete 25 minute delay cycle will take place. If 120 volt AC becomes available during this de­lay cycle, the AES system will start operation in the 120 volt AC mode immediately, unless the push-button "B" (LP gas only) has been pressed.
If the RV is stopped somewhere other than a gas sta­tion, you may wish to cancel the delay cycle. To do this, turn the main system switch to "OFF" for several sec­onds, then turn the main system switch back to "ON" and the system will immediately start operation in the LP gas mode.
Most LP gas appliances used in recreational ve­hicles are vented to the outside of the vehicle. When parked close to a gasoline pump, it is possible that the gasoline fumes could enter this type of appli­ance and ignite from the burner flame, CAUSING A FIRE OR AN EXPLOSION.
FOR YOUR SAFETY, it is recommended that all LP gas appliances which are vented to the outside should be shut off when refueling.
The AES system is designed to turn off the LP flame during refueling stops by the use of the delay cycle explained previously. However, you must remember that the delay cycle will be activated only if the refrigerator is properly connected to the vehicle engine electrical circuit.
If the refrigerator is not connected to the engine by the ignition lock wiring, the refrigerator must be shut off during refueling. To do this, turn the main system switch "C" to "OFF". Only after the vehicle has been moved away from the refueling area should the main system switch "C" be turned back ON.
5
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
FLAME FAILURE DURING LP GAS OPERATION
If the LP gas flame fails during the burner cycle, the high voltage spark will continue arcing for up to three minutes.
At the end of three minutes the gas control will stop the flow of LP gas to the burner, the sparking will stop and the red indicator lamp "H" will light up. LP gas operation will not be possible as long as this indicator is ON.
To restart LP gas operation, turn the main system switch "C" to "OFF" for five seconds and then back ON. This will reset the AES controls and turn off the flame failure indicator "H". The system will start another cycle for gas ignition.
If the refrigerator has not been used for a long time or the LP tanks have just been refilled, air may be trapped in the supply lines. To purge the air from the lines may require resetting (turning OFF and ON) the On/Off switch "C" three or four times.
If repeated attempts fail to start the LP gas operation, check to make sure that the LP gas supply tanks are not empty and all manual Shutoff valves in the lines are open.
NOTE: If you are in the AES mode when the flame failure light "H" comes on, the mode indicator lamp "A" (green light) will go out. If 120 volt AC power becomes available during this period, the mode indication lamp will come on showing that the refrigerator is operating on another energy source. The red lamp "H" will remain on until the AES system is reset with an OFF/ON operation of the main switch "C". If you have selected the LP gas only mode (control button "B"), the 120 volt function has been locked out. If the burner fails to light, the green lamp over button "B" will go out and the red lamp "H" will glow indicating flame failure. Even if 120 volts is available, the refrigerator cannot switch to electric operation and all cooling will stop. This fact must be considered when selecting "gas only" operation.
120 VOLTS AC OPERATION
Since 120 volt AC is usually the most economical source for operation of the refrigerator, the AES control system is designed to select this mode whenever it is available. The only exception to this is when push­button "B" (LP gas only mode) is selected. The 120 volt heating elements attached to the boiler provide the heat necessary to operate the cooling system. The thermo­stat controls the power ON and OFF to the elements and maintains the desired temperature.
LOW VOLTAGE MONITOR
The AES system requires 12 volts DC power at all times to operate properly. The DC power must be 9.5 volts DC or higher. If the DC voltage drops below 9.5 volts DC, the AES system will switch to an emergency cooling mode.
1. The mode indicator lamp will go off (green light);
2. The system will revert to continuous LP gas operation, with no thermostat control.
The refrigerator will continue to operate in the emer­gency mode until the DC power supply is increased to
10.5 volts DC. When 10.5 volts is reached, the mode indicator light (green) will come back on and normal operation will resume.
During the low voltage condition, the interior light will operate normally.
THERMOSTAT
The refrigerator is equipped with a thermostat that can be adjusted to maintain various temperatures. Turn the knob clockwise toward "MAX" for a lower temperature and for a warmer temperature  turn the knob counter­clockwise toward "MIN". Set the thermostat approxi­mately mid-range and adjust it toward "MIN" or MAX" to obtain the desired cabinet temperatures. Remember, at the "MAX" setting, the heating element/burner is running continuously and the lower cabinet temperatures are obtained.
1.2 RM7030 (Product No. 921890401)
AES DISPLAY PANEL
AES MODE
1. Move the AES mode selector button (2) to the DOWN position. If 120 volts AC is available, the AC mode indicator lamp "A" will illuminate indicating AC operation. If 120 volts AC is not available, the GAS mode indicator lamp "C" will illuminate and the control system will automatically switch to GAS operation.
2. If the CHECK indicator lamp "D" illuminates and the GAS mode indicator lamp "C" is off, the controls have failed to ignite the burner in the GAS mode. GAS operation may be reset by pressing main power ON/OFF button (1) to the OFF then ON position.
6
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
3. Press the TEMPERATURE SELECTOR button (3) until the lamp at the desired position is illuminated.
4. When operating in the AES mode, the AES mode indicator lamp "B" will illuminate. The control system will automatically select between AC and GAS operation with AC having priority over GAS. Either the AC indicator lamp "A" or the GAS indicator lamp "C" will illuminate depending on the energy source selected by the control system. If the control system is operating with AC energy and it then becomes unavailable, the system will automatically switch to GAS. As soon as AC becomes available again, the control will switch back to AC regardless of the status of GAS operation.
GAS MODE
1. Move the AES mode selector button (2) to the UP position. The GAS mode indicator lamp "C will illuminate. After 45 seconds the burner should be ignited and operating normally.
2. On the initial refrigerator start-up, it may take longer than 45 seconds to allow air to be purged from the gas line. If the gas does not ignite within 45 seconds, the CHECK indicator lamp "D" will illuminate and the GAS mode indicator lamp "C" will go off. To reset when the CHECK indicator lamp "D" is illuminated, press the main power ON/OFF button (1) to the OFF then ON position.
If the control is switched to AC operation while the CHECK indicator lamp is on, it will function properly, but the CHECK indicator lamp will not go off until the main power ON/OFF button is pressed to the OFF then ON position. NOTE: Do not continue to reset GAS operation if the CHECK indicator lamp continues to be illumi­nated after several tries. If repeated attempts fail to start the LP gas operation, check to make sure that the LP gas supply tanks are not empty and all manual shutoff valves in the lines are open.
3. Press the TEMPERATURE SELECTOR button (3) until the lamp at the desired position is illuminated.
THERMOSTAT
The thermostat on the refrigerator controls both the gas and electric operation, thereby eliminating the necessity of resetting each time a different energy source is employed.
After the initial start-up, the thermostat should be moved from "COLDEST" to the desired temperature setting, usually about mid-setting.
If for some reason the display module becomes non­functional, the control system will revert to fully auto­matic operation  selecting the best energy source available with AC and GAS priority. The temperature of the refrigerator will be maintained at the MID position within normal temperature tolerances. The power module will continually attempt to reestablish operation of the display module.
The second standby mode of operation will execute when a failure of the temperature sensing device or associated electronic circuitry occurs. If this should occur, the control system will operate on the energy source selected via the control panel. The cooling unit will run continuously on the selected energy source. The refrigerator will continue to operate in this mode indefi­nitely or until a new sensor is installed and the system is reset.
1.3 RM7732 REFRIGERATOR OPERATION
2-WAY DISPLAY PANEL
B
A
C
D
E
AUTO MODE
Press the AUTO mode selector button (2) to the DOWN position. If 120 volts AC is available, the AC mode indicator lamp (A) will illuminate indicating AC operation. If 120 volts AC is not available, the GAS mode indicator lamp (C) will illuminate and the control system will automatically switch to GAS operation.
If the CHECK indicator lamp (D) illuminates and the GAS mode indicator lamp (C) is OFF, the controls have failed to ignite the burner in the GAS mode. GAS operation may be reset by pressing the main power ON/ OFF button (1) to the OFF then ON position. (See GAS MODE.
Press the TEMPERATURE SELECTOR button (3) until the lamp at the desired position is illuminated.
STANDBY MODE OF OPERATION
This control system contains a feature where it will continue to operate the cooling system in the event of a failure of a major operating component. Two different modes of operation can occur in this category.
7
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
GAS MODE
Move the AUTO mode selector button (2) to the UP position. The GAS mode indicator lamp (C) will illumi­nate. After 45 seconds the burner should be ignited and operating normally.
On the initial refrigerator start-up, it may take longer than 45 seconds to allow air to be purged from the gas line. If the gas does not ignite within 45 seconds, the CHECK indicator lamp (D) will illuminate and the GAS mode indicator lamp (C) will go off. To reset when the CHECK indicator lamp (D) is illuminated, press main power ON/OFF button (1) to the OFF then ON position.
NOTE: DO NOT continue to reset GAS operation if the CHECK indicator lamp continues to be illumi­nated after several tries.
Press the TEMPERATURE SELECTOR button (3) until the lamp (E) at the desired position is illuminated.
THERMOSTAT
The thermostat on the refrigerator controls both the gas and electric operation, thereby eliminating the necessity of resetting each time a different energy source is employed.
After the initial start-up, the thermostat should be moved from "COLDEST" to the desired temperature setting is usually about mid-setting.
GAS MODE
When operating in the GAS mode, the AUTO mode indicator lamp (B) will be off and the GAS mode indica­tor lamp (C) will be illuminated. This mode provides LP gas operation only. The control system will activate the ignition system and will attempt to light the burner for a period of approximately 45 seconds. If unsuccessful, the CHECK indicator lamp (D) will illuminate and the GAS mode indicator lamp (C) will turn off.
To restart GAS operation, press the main power ON/ OFF button (1) to the OFF and then ON position. The control system will attempt a new 45 second ignition sequence.
If the refrigerator has not been used for a long time or the LP tanks have just been refilled, air may be trapped in the supply lines. To purge the air from the lines may require resetting the main power ON/OFF button (1) three or four times. If repeated attempts fail to start the LP gas operation, check to make sure that the LP gas supply tanks are not empty and all manual shutoff valves in the lines are open.
If the control is switched to AC or DC operation while the CHECK indicator lamp is on, it will function properly, but the CHECK indicator lamp will not go off until the main power ON/OFF button is pressed to the OFF then ON position.
TO SHUT OFF THE REFRIGERATOR
The refrigerator may be shut off while in any mode of operation by pressing the main power ON/OFF button (1) to the UP (OFF) position. This shuts off all DC power to the refrigerator, including the interior light.
DESCRIPTION OF OPERATING MODES
AUTO MODE
When operating in the AUTO mode, the AUTO mode indicator lamp (B) will illuminate. The control system will automatically select between AC and GAS operation with AC having priority over GAS. Either the AC indica­tor lamp (A) or the GAS indicator lamp (C) will illuminate depending on the energy source selected by the control system. If the control system is operating with AC energy and it then becomes unavailable, the system will automatically switch to GAS. As soon as AC becomes available again, the control will switch back to AC regardless of the status of GAS operation.
STANDBY MODE OF OPERATION
This control system contains a feature where it will continue to operate the cooling system in the event of a failure of a major operating component. Two different modes of operation can occur in this category.
If for some reason the display module becomes non­functional, the control system will revert to full automatic operation selecting the best energy source available with AC as first priority, and GAS as the second priority. The temperature of the refrigerator will be maintained at the MID position within normal temperature tolerances. The power module will continually attempt to reestablish operation of the display module.
The second standby mode of operation will execute when a failure of the temperature sensing device or associated electronic circuitry occurs. If this should occur, the control system will operate on the energy source selected via the control panel. The cooling unit will run continuously on the selected energy source. The refrigerator will continue to operate in this mode indefi­nitely or until a new sensor is installed and the system is reset.
8
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
SECTION 2
AC VOLTAGE REQUIREMENTS
The refrigerator is a 120 volt AC, 60 Hz appliance. The proper operating range is 100 to 132 volts. Check the AC volts at the receptacle where the refrigerator is attached. If voltage is outside of the proper operating range, correct the power source problem.
On RM7030 (Product No. 921890401) and RM7732, if voltage drops below 100 volts, cooling efficiency will decrease with voltage decrease. The refrigerator will not switch to another mode of operation until all AC power
is lost.
SECTION 3
AC COMPONENTS HEATING ELEMENT
The heating element is designed to deliver a predeter­mined amount of heat to the cooling unit. To check a heating element, remove the heater leads from the printed circuit board and measure for proper resistance across the two leads with a properly calibrated ohm meter. This check is to be done with the heating ele­ment at room temperature. The proper ohms for each of the two RM7030 and RM7732 heating elements is 69, with a tolerance of ten percent. If the resistance is outside the tolerance range, replace the heating ele­ment.
terminals at the back of the refrigerator. If power is outside the operational range, correct the power supply problem. The power supply to the refrigerator must be fused. Maximum fuse size: 5 amps.
With the refrigerator operating on AC or gas mode, if voltage to the refrigerator slowly drops to or below 9.5 volts DC, the gas flame will come on and will not be thermostatically controlled. Low DC volts (below 9.5) could cause over-cooling.
B. RM7030 (Prod. No. 921890401) & RM7732
For the refrigerator to operate on any mode, DC voltage must be supplied to the terminals at the rear of the refrigerator.
The operational range of the unit is a minimum of 9.6V DC to a maximum of 22V DC. The unit will automatically shut down until voltage has decreased to 18V DC. The refrigerator requires at least 9.6V DC for proper opera­tion; however, the panel lights will continue to illuminate until voltage has dropped to 4V DC or below.
Connecting the refrigerator to an unregulated converter can result in improper operation of the refrigerator. Do not use the body or chassis of the RV as a substitute for either of the two conductors. Proper polarity is crucial for refrigerator operation. Check for proper DC voltage at the positive and negative terminals at the back of the unit. If the voltage is outside the operational range, correct the power supply problem.
SECTION 5
SECTION 4
DC VOLTAGE REQUIREMENTS
A. RM7030 (Product No. 921890201 &
921890301)
For the refrigerator to operate on any mode, DC voltage must be supplied to the terminals at the rear of the refrigerator and must be connected directly to the battery of the RV. The operational range is 10.5 to 15 volts DC. Connecting the refrigerator to an unregulated converter can result in improper operation of the refrig­erator. Do not use the body or chassis of the RV as a substitute for either of the two conductors. Proper polarity is crucial for the operation of the refrigerator. Check for proper voltage at the positive and negative
DC COMPONENTS
5.1 THERMOSTAT RM7030 (Product No. 921890201 & 921890301)
The thermostat operates on DC volts and regulates the inside refrigerator temperature on all modes, by making and breaking the circuit to the printed circuit board. The internal mechanism breaks contact (continuity) when adequate cabinet temperature has been reached. Check the thermostat for continuity. This check should be made at room temperature with the thermostat turned all the way to MAX. Another check would be to use a jumper wire with insulated clips and bypass the thermostat.
NOTE: Use care when doing this test. Do not short to thermostat casing. Also remove jumper after testing is completed.
If the above test allows the refrigerator to operate and/ or the continuity test proves the thermostat to be defective, replace the thermostat. A defective thermo­stat would cause insufficient cooling, no cooling or freezing on all modes.
9
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
5.2 THERMISTOR RM7030 (Prod. No. 921890401) and RM7732
To determine if the temperature sensor is functioning properly, perform the following test.
Remove the cover from the lower circuit board. Discon­nect the thermistor harness from the P2, 2-pin terminal on the lower circuit board. Place thermistor in a glass of ice water. Wait 2 to 3 minutes. Using an ohm meter, place a probe on each terminal point. You should get a reading of approximately 7,000 to 10,000 ohms. Normal failure for this type of device is to have a very high resistance. A defective thermistor could cause an over­cooling condition on all modes.
P3
P1
P2
Thermi stor unplugged from PC Board
5.3 THERMISTOR ADJUSTER RM7030 (Product No. 921890401) and RM7732
The thermistor adjuster is a resistor-type component that attaches between the thermistor and the lower board. Its function is to allow the refrigerator to reach temperatures below the normal 46° to 35°F. range (setting 1 through 5 on upper circuit board).
To determine if the thermistor adjuster is operating properly, do an ohms resistance check across the terminals. Proper ohms reading is approximately 23,200 ohms ± 10%.
5.4 SOLENOID VALVE A. RM7030 (Product No. 921890201 & 921890301)
The solenoid valve assembly is a safety valve as well as a gas flow valve. When the AES selects LP gas opera­tion, DC volts are sent to the solenoid coil which opens the internal valve.
Check the solenoid coil with a properly calibrated ohm meter. Remove the connector from the solenoid and measure the resis­tance across the upper and lower terminals. The proper reading would be 20 ohms with a toler­ance range of ten percent. Once flame is lit, the thermocouple produces the voltage to keep the valve open. If for any reason the thermocouple does not provide enough current to the valve, it will close, stopping the flow of gas. To check this portion of the solenoid valve assembly, verify the thermocouple is good (see Sec. 7.3A), the tip is clean and the receptacle in the solenoid valve assembly is clean. If the thermo­couple checks good, then replace the solenoid valve assembly. NOTE: If the solenoid ohms check shows an open coil, the refrigerator will not operate on any mode.
THERMISTOR ADJUSTER
THERMISTOR ADJUSTER
TO THERMISTOR
NOTE: Dometic refrigerators do not come equipped with a
thermistor adjuster. This is an add-on component.
TO THERMISTOR
P2
10
B. RM7030 (Product No. 921890401) and RM7732
When the refrigerator selects LP gas operation, DC volts are sent to the solenoid coil which opens the internal valve.
Check the solenoid coil with a properly calibrated ohm meter. Remove the connector from the solenoid and measure the resistance across the terminals. The proper reading would be 49 ohms with a tolerance range of ten percent.
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
Next, hook up a manometer at the test port. Then check for DC volts at gas valve terminals while the unit is in trial-for-ignition. If DC volts are present and pressure is low, replace the valve. If DC volts are not present at the valve while unit is in trial-for-ignition, verify that the wires at Plug 3, Terminal 1 and 2 on lower circuit board have DC volts (9 or more). If the valve chatters, check for low input voltage to the valve (below 9V DC).
5.5 IGNITER
A. RM7030 (Product No. 921890201 & 921890301)
The igniter is an electronic device that produces high voltage to create a spark at the burner, only on gas mode. It also produces an increased DC voltage at the "L" terminal which is a signal to the circuit board that a spark has been produced. First verify proper voltage at the positive (+) and ground () terminals. The reading should be within one volt of incoming voltage at the main terminal block. A voltage drop of more than one volt would indicate a loose connection (see Sec. 8.2) or a circuit board problem (see Sec. 5.9A to 5.9D).
NOTE: If a spark is not produced within 10 seconds, the gas flame warning lamp will illumi­nate. If spark is produced it will take 3 minutes for lamp to illuminate. If all of the previous checks are correct, the igniter is good  do not replace.
B. RM7030 (Product No. 921890401) and RM7732
The igniter is an electronic device that produces high voltage to create a spark at the burner, only on gas mode.
First, verify proper voltage at the positive (+) and ground () terminals. The reading should be within one volt of incoming voltage at the main terminal block during trial-for-ignition. If no voltage is present, see Sec.
5.9E to 5.9G. Next, disconnect DC power
at refrigerator terminal block. Remove high voltage cable from igniter. Reconnect DC power, the igniter should produce a sparking sound during trial-for-ignition. If not, replace the igniter.
HIGH VOLTAGE
Next, disconnect DC power at refrigerator terminal block. Remove high voltage cable from igniter. Recon­nect DC power  the igniter should produce sparking sound. If not, replace the igniter. With the igniter pro­ducing spark, connect meter leads to "L" and ground () terminals on the igniter, with the meter set on 20 volts DC range or lower. The meter should read a pulsating voltage. If not, replace the igniter.
5.6 HIGH VOLTAGE CABLE A. RM7030 (Product No. 921890201 & 921890301)
Disconnect DC power at the refrigerator terminal block. Disconnect high voltage cable from electrode. Recon­nect DC power. If sparking starts, cable is good (see Sec. 5.11). If no sparking, disconnect DC power. If sparking sound from igniter, then replace high voltage cable.
B. RM7030 (Product No. 921890401) and RM7732
Disconnect DC power at the refrigerator terminal block. Disconnect high voltage cable from electrode. Recon­nect DC power. If sparking starts during trial-for-ignition, the cable is good (see Sec. 5.11). If there is no sparking during trial-for-ignition, disconnect DC power and disconnect high voltage cable at the igniter. Reconnect DC power. If there is a sparking sound from the igniter during trial-for-ignition, then replace high voltage cable.
11
DOMETIC® RM7030/RM7732
BROWN
RED
10 PIN
YELLOW
GREEN
10 PIN
Refrigerators
DIAGNOSTIC SERVICE MANUAL
5.7 FUSES A. RM7030 (Product No. 921890201 & 921890301)
The fuse is to protect the circuit board. To check the fuse, remove it from the holder and do a continuity check. If no continuity, replace it with a proper 3-amp time delay fuse.
B. RM7030 (Product No. 921890401) and RM7732
The fuses are to protect the circuit board and the integrity of the heater circuit(s) against shorts.
The 3-amp DC fuse is designed to protect the circuit board from internal shorts. The 5-amp AC fuse is designed to protect the integrity of the AC heater circuit from shorts.
To check the fuses, remove from the holder and do a continuity check. If no continuity, replace with a proper amperage fuse.
NOTE: Determine the cause of the fuse failure and correct before replacing fuse.
CONTINUITY should be indicated between the brown terminal to the red terminal on the 10-pin connector.
NO continuity should be indicated between the yellow terminal to the green terminal on the 10-pin connector.
NO continuity should be indicated
BLUE
between the red terminal on the 10­pin connector to the blue terminal on the 7-pin connector.
YELLOW
GREEN
10 PIN
RED
10 Pin7Pin
7-PIN
CONNECTOR
6-PIN
CONNECTOR
5.8 UPPER CIRCUIT BOARD RM7030 (Product No. 921890201 & 921890301) A. ON-OFF SWITCH NOTE: The following checks should be made on the
upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. The checks are to be done with the wiring harness REMOVED from the lower circuit board.
With the switch in the "ON" position:
CONTINUITY should be indicated be­tween the orange terminal to the yellow terminal on the 10-pin connector.
10-PIN
CONNECTOR
10 PIN
ORANGE
YELLOW
With the switch in the "OFF" position:
CONTINUITY should be indicated between the yellow terminal to the green terminal on the 10-pin connector.
CONTINUITY should be indicated between the red terminal on the 10­pin connector to the blue terminal on the 7-pin connector.
NO continuity should be indicated between the orange terminal to the yellow terminal on the 10-pin connector.
NO continuity should be indicated between the brown terminal to the red terminal on the 10­pin connector.
NOTE: If any of these checks on the ONOFF switch are not correct, verify the wire harness has continuity. If the wire harness is good, replace the upper circuit board.
BLUE
RED
10 Pin7Pin
ORANGE
YELLOW
10 PIN
BROWN
RED
10 PIN
12
DIAGNOSTIC SERVICE MANUAL
7PIN
10 PIN
VIOLET
BLUE
DOMETIC® RM7030/RM7732
Refrigerators
B. AES FUNCTION SWITCH
NOTE: The following checks should be made on the
upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. The checks are to be done with the wiring harness REMOVED from the lower circuit board, and the ON­OFF switch turned to "ON".
With the AES function switch manually depressed:
BLACK
CONTINUITY should be indicated between the blue terminal and the black terminal on the 7-pin connector.
With the AES function switch NOT depressed:
NO continuity should be indicated between the blue and black terminals on the 7-pin connector.
NOTE: If the check on AES function switch is not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
C. AES FUNCTION LAMP
NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. These checks are to be done with the wiring harness REMOVED from the lower circuit board and the ONOFF switch turned to "ON".
Measure resistance between the brown terminal on the 7-pin connector (positive [+] lead from meter) to the brown terminal on the 10-pin connector (negative [] lead from meter). The proper resistance is approximately 26,000 ohms.
NOTE: If the check on the AES function lamp is not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
BLUE
7Pin
BROWNBROWN
10 Pin7Pin
With the gas function switch manually depressed: CONTI-
NUITY should be indicated between the violet terminal on the 10-pin connector to the blue terminal on the 7-pin connector. With the gas
function switch NOT de­pressed: A reading would NOT be indicated.
NOTE: If the check on gas function switch is not
correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
E. GAS FUNCTION LAMP
NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. These checks are to be done with the wiring harness REMOVED from the lower circuit board, and the ONOFF
BROWN
switch turned to "ON". Measure resistance between the
brown terminal on the 10-pin connector (negative [] lead from meter) to the white terminal on the 10-pin connector (positive [+] lead from meter). The proper
10 PIN
ohms resistance is approxi­mately 26,000 ohms.
NOTE: If the check on gas function lamp is not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
F. AC MODE LAMP AND SWITCH
NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. These checks are to be done with the wiring harness REMOVED from the lower circuit board, and the ON­OFF switch turned to "ON".
WHITE
D. GAS FUNCTION SWITCH
NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. The checks are to be done with the wiring harness REMOVED from the lower circuit board and the ON­OFF switch turned to "ON".
With the mode switch (?) manually depressed: Resistance should be indicated between the brown terminal on the 10-pin connector (negative [] lead from meter) to the red terminal on the 7-
RED
BROWN
pin connector (posi­tive [+] lead from meter). The proper resistance is approxi­mately 26,000 ohms.
7PIN
10 PIN
13
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
With the mode switch (?) NOT depressed: A reading would NOT be indicated.
NOTE: If the check on AC mode lamp and switch is
not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
G. DELAY MODE LAMP AND SWITCH NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. The checks are to be done with the wiring harness REMOVED from the lower circuit board, and the OFF-ON switch turned to "ON".
With the mode switch (?) manually depressed: Resistance should be indicated between the brown terminal on the 10-pin connector (negative [] lead from meter) to the yellow terminal on the 7-pin connector (positive [+] lead from meter). The proper resistance is approximately 26,000 ohms.
YELLOW
With the mode switch (?) NOT depressed: A reading would NOT
be indicated. NOTE: If the check on the delay
mode lamp and switch is not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
H. GAS MODE LAMP AND SWITCH:
NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. The checks are to be done with the wiring harness REMOVED from the lower circuit board, and the ON­OFF switch turned to "ON".
With the mode switch (?) manually depressed: Resistance should be indicated between the brown terminal on the 10-pin connector (negative [] lead from meter) to the green terminal on the 7-pin connector (positive [+] lead from meter). The proper
GREEN
resistance is approximately 26,000 ohms.
BROWN
10 Pin7Pin
BROWN
I. GAS FLAME WARNING LAMP:
NOTE: The following checks should be made on the upper circuit board and harness assembly BEFORE replacing the upper circuit board or wiring harness. The checks are to be done with the wiring harness REMOVED from the lower circuit board, and the OFF-ON switch turned to "ON".
BLACK
BROWN
Measure resistance between the brown terminal on the 10-pin connector (negative [] lead from meter) to the black terminal on the 10-pin connector (positive [+] lead from meter). The proper resistance is approxi­mately 22,000 ohms.
10 Pin
NOTE: If the check on gas flame warning lamp is not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
J. RM7030 (Product No. 921890401) and RM7732 NOTE: The PAL tester will allow for proper testing of the
integrity of the upper and lower circuit boards. PAL is available from your Dometic parts distributor.
NOTE: Each of the following tests should be done according to pin locations. The wire colors may vary.
With main ON/OFF switch on display panel in OFF position:
Check for DC voltage at Plug 1, Terminal 4 and terminal 5 negative () DC on the lower circuit board. If no voltage, then check fuse condition. Replace if blown. Check for DC voltage between J4 and J10 terminals on the lower circuit board. If fuse is good and there is battery voltage at J4, remove and replace lower circuit board. Next, check for DC voltage at the upper circuit board between terminal 4 (orange or white wire) and terminal 3 (black wire) which is negative () DC. If no voltage, and your previous check proved voltage at the lower circuit board between these wires, replace the cable assembly. If DC volts are present, proceed to the next check.
UPPER CIRCUIT BOARD
With the mode switch (?) NOT depressed: A reading would NOT
be indicated.
NOTE: If the check on gas mode lamp and switch is not correct, verify the wire harness has continuity. If wire harness is good, replace the upper circuit board.
14
10 Pin7Pin
DIAGNOSTIC SERVICE MANUAL
6
DOMETIC® RM7030/RM7732
Refrigerators
With main ON/OFF switch on display panel in ON position:
Check for DC volts between terminal 3 (red wire), () negative and terminal 5 (green wire) and terminal 1 (black wire). If there is no voltage, the ON/OFF switch on upper circuit board is defective. Replace the upper circuit board. If voltage is present, the ON/ OFF switch is good.
Next, do the same voltage test at the lower circuit board. Negative () plug 1, terminal 5 (red wire), to plug 1, terminal 1 (green wire) and plug 1, terminal 3 (black wire). If there is no voltage and you had voltage on previous test, the cable assembly is defective and you must replace it. If voltage is present, the ON/OFF switch on the upper circuit board and cable assembly is good.
DIAGNOSTIC MODE
NOTE: The PAL tester will allow for proper
testing of the integrity of the upper and lower circuit boards. PAL is available from your Dometic parts distributor.
This control system has an integral Diagnostic/ Test sequence.
Access to the diagnostic sequence unit is by means of the ON/OFF Power Switch and the Temperature Selector Switch. With the Power Switch in the OFF position, hold the Temperature Selector Switch in the DOWN position. While keeping the Temperature Selector Switch in the DOWN position, move the main power ON/OFF Switch to the ON (DOWN) position. Hold the Temperature Selector Switch DOWN for three (3) seconds. The control will indicate that the diag­nostics have been entered by illuminating each of the Mode Indicator Lamps and the Temperature Indicator Lamps one at a time in sequence. Each lamp is illuminated twice. The Check Lamp will then flash ON and OFF and #1 position Tempera­ture Indicator will remain illuminated. The test sequence can be operated automatically or manually. For AUTO step sequence, press the AUTO/GAS Mode Selector Switch to the DOWN position. The AUTO Mode Indicator will illuminate.
If each lamp illuminates during the check, the display circuit board is good.
In automatic test mode, each load is activated for approximately four (4) seconds then released. The control system will automatically exit the diagnostic sequence in approximately four (4) minutes or when power is turned OFF.
The Temperature Indicator Lamps are used to indicate which part of the control system is being tested. When position #1 is illuminated, the control is in an idle position with all output loads off. To activate the first load simply push the Temperature Selector Switch.
All of the checks listed below are done on the lower circuit board.
The manual test sequence is as follows:
Position #1: Idle Position, all loads off. Position #2: Activate AC Heater. Check for AC volts
at terminals J7 and J8.
Position #3: Activate Gas Solenoid. Check for DC
volts at Gas Solenoid white wire (-) and
yellow wire (+). Position #4: Idle position. All loads OFF. Position #5: Activate spark ignition system. Check
for DC volts to (+) terminal of igniter
and ground.
If you experience a problem on any of the above checks, verify the fuses on the lower circuit board are good.
If all checks prove to be good, and the refrigera­tor does not operate on electric mode, replace the lower circuit board. It has been damaged by AC volts in excess of 180 volts.
5.9 LOWER CIRCUIT BOARD RM7030 (Product No. 921890201 & 921890301)
The circuit board controls all modes of operation.
A. DC VOLTS
THESE PROCEDURES MUST BE FOLLOWED IN SEQUENCE AND AT THE PROPER TERMINALS OR DAMAGE TO THE BOARD WILL RESULT.
Before any checks are to be done, be
YE L L O W
GREEN
sure proper DC volts are to the board. Measure volts between yellow terminal on the 6-pin connector (positive [+] lead from meter) to green terminal on 6-pin connector (negative [] lead from meter). Voltage should be the same as
PIN
at the positive (+) and negative () terminal block. If not, check the fuse and wiring.
15
DOMETIC® RM7030/RM7732
6
6
Refrigerators
DIAGNOSTIC SERVICE MANUAL
B. AC OPERATION
THESE PROCEDURES MUST BE FOLLOWED IN SEQUENCE AND AT THE PROPER TERMINALS OR DAMAGE TO THE BOARD WILL RESULT.
For AC heating element operation, check that voltage is present between the large black and large white wire at the circuit board. If voltage is below 100 volts, the circuit board will select another mode. If voltage is above 100 volts, check that AC volts are present at the heating element connection. If no voltage is present, change the circuit board.
NOTE: Before installing a new circuit board, correct the cause of the failure, most likely it is the heating ele­ments or wiring.
If voltage is present, DO NOT CHANGE THE CIRCUIT BOARD. Check the following components: heating elements, upper circuit board, thermostat and wiring.
C. GAS OPERATION
THESE PROCEDURES MUST BE FOLLOWED IN SEQUENCE AND AT THE PROPER TERMINALS OR DAMAGE TO THE BOARD WILL RESULT.
Before you check the circuit board for gas operation, verify these components are good:
Igniter (Sec 5.5A) High Voltage Cable (Sec. 5.6A) Electrode (Sec. 5.11) Solenoid (Sec. 5.4A)
Upper Circuit Board (Sec. 5.8A to 5.8I) Thermostat (Sec. 5.1)
Also be sure NO voltage is present at the IGN lock terminal, and delay mode is not
YE L L O W
activated. First, check that voltage in excess of 10.5 volts is between the yellow terminal on the 6-pin connector (positive [+] lead from meter) to the ground strip (negative [] lead from meter). If less than
10.5 volts, correct wiring and/or power source problem.
Pin
Next, check for the pulse voltage from the igniter at the orange terminal on the 6-pin connector (negative [] lead from meter) and the ground strip (positive [+] lead from meter). If there is no signal voltage, check the igniter (see Sec. 5.5A) and the orange wire and connections. If signal voltage is present, next check
for voltage on the solenoid wires at the
ORANGE
circuit board. Positive lead from meter to the gray wire and negative lead from the meter to the black wire. If voltage is 9.5 volts or more, the circuit board is good. Do not replace. If no voltage is present, replace the circuit board.
Pin
D. DC VOLTS TO UPPER CIRCUIT BOARD
THESE PROCEDURES MUST BE FOLLOWED IN SEQUENCE AND AT THE PROPER TERMINALS OR DAMAGE TO THE BOARD WILL RESULT.
This check is to determine if the lower circuit board is providing
BROWNBLUE
voltage to the upper circuit board. Measure between the brown terminal on the 10-pin connector (positive [+] lead from meter) to the blue terminal on the 7-pin connector (negative [] lead from meter). A voltage reading indi-
10 Pin7 Pin
cates the circuit board is good. If no voltage is present, replace the circuit board. NOTE: Before changing the circuit board, be sure all troubleshooting steps have been followed.
RM7030 (Product No. 921890401) & RM7732
E. DC VOLT: ALL TESTS ARE TO BE DONE WITH
THE REFRIGERATOR IN THE COOLING MODE.
Before any checks are made, make sure the board is receiving proper DC volts. Measure volts between terminal J4 and the ground strip. Voltage should be the same as at the positive (+) and negative (-) on the terminal block. If not, check for loose connec­tions.
F. AC MODE: NOTE: The PAL tester will allow for
proper testing of the integrity of the upper and lower circuit boards. PAL is available from your Dometic parts distributor.
ALL TESTS ARE TO BE DONE WITH THE REFRIG­ERATOR IN THE COOLING MODE.
For AC heating element operation, check that incoming AC voltage is present at terminals J5 and J6 on the circuit board. If voltage is below 100 volts, see Sec. 2.
16
DIAGNOSTIC SERVICE MANUAL
e
e
DOMETIC® RM7030/RM7732
Refrigerators
Check for voltage at the heating element connection terminals J7 and J8 on the circuit board. If no voltage is present, check the 5 amp AC and 3 amp DC fuses. If fuse is defective, replace the fuse. If fuses are good, replace the circuit board.
J1
J2
6 Brown
5 Red
4 Orange
4 Orange
or White
or White
J3
J4
J5
J6
J7
Open 3 Blue 4
J8
P3
FIVE AMP FUSE
J10
Black 3
Open 2
Green 1
P1
P2
3 AMP FUSE
G. GAS MODE: NOTE: The PAL tester will allow for
proper testing of the integrity of the upper and lower circuit boards. PAL is available from your Dometic parts distributor.
ALL TESTS ARE TO BE DONE WITH THE REFRIG­ERATOR IN THE COOLING MODE.
Before checking the circuit board for gas operation, verify that the following components are good: Upper Circuit Board, Thermistor and 3 Amp Fuse.
NOTE: Each of the following tests should be done according to pin locations. The wire colors may vary.
First, check for voltage during trial-for-ignition (approximately 45 seconds) at Plug 3, Terminals 1 (white wire) and 2 (yellow wire) to the solenoid. If no voltage is present, change the circuit board. If voltage is present, check for voltage at the solenoid. If voltage is not present, check the wires and con­nections.
Next, check for voltage to the igniter. If no voltage is present, check the wires. If good, then change the circuit board. If voltage is present, this portion of the board is good.
NOTE: When millivolts to the lower circuit board are 10 ± 3, the power to Plug 3, Terminal 4 (blue wire) will be shut off. If flame extinguishes during the cooling mode, the circuit board will not supply voltage to Plug 3, Terminal 4 (blue wire) again until the millivolts have decreased to 10±3. This process could take up to 15 seconds or longer.
1 Whit
1 Whit
2 Yellow
To check the flame sense circuit of the lower circuit board, operate the refrigerator on GAS mode, then measure the millivolts between J3 terminal and the other wire connection from the thermocouple. The millivolt meter should read between 25 to 35 milli­volts with the gas flame burning. Next, turn the manual shutoff valve to OFF and watch the millivolt reading as it drops. Note the millivolt reading when Plug 3, terminal 4 (blue wire) receives power. It should be 10±3 millivolts or 7 to 13.
Repeat this test several times. If the igniter fails to spark on any test sequence, it should be replaced.
If the millivolt readings vary more than 1 to 2 MV from one test to the other when power is supplied to Plug 3, terminal 4, replace the lower circuit board.
NOTE: Verify all connections are clean and tight before replacing either component.
5.10 DOOR SWITCH
The door switch is an open switch when the switch arm is depressed (interior light should be off). When the refrigerator door is open the switch is closed (interior light should be on). Check that the switch assembly is properly aligned and that it is not broken. Check the switch assembly for continuity.
NOTE: To do a continuity check, first be sure all power is disconnected or OFF to the refrigerator. Second, remove all wires from the switch assembly, then check the switch. After the check, be sure the switch assem­bly is wired properly per the wiring diagram.
When the switch arm is depressed, there should not be continuity. When the switch arm is NOT depressed, there should be continuity. If any of these checks are incorrect, replace the switch.
17
DOMETIC® RM7030/RM7732 Refrigerators
5.11 ELECTRODE
First, do a visual check for cracks or breaks on the ceramic insulator. Verify the mounting bracket is attached properly to the elec­trode. If
BURNER
either of the above is found, replace the electrode. The spark gap must be set at three sixteenths (3/16") of an inch and tip of electrode above the slots in the burner.
If igniter (see Sec. 5.5A or B) and high voltage cable (see Sec. 5.6A or B) are good and there is no spark at the tip of the electrode, replace the electrode.
5.12 CLIMATE CONTROL HEATER
The climate control is a switch operated DC electric heater. Its primary function is to warm the frame of the refrigerator during high temperature/high humidity conditions. This prevents the formation of condensation on the metal frame.
ELECTRODE TIP
3/16"
DIAGNOSTIC SERVICE MANUAL
To check the heater itself, do an ohms resistance reading on the heater wire by using a properly cali­brated ohm meter. The proper ohms reading is 34 ohms ± 10%. The approximate amp draw is less than .5 (1/2) amp.
NOTE: The climate control will draw DC power continu­ously. It should be turned off when charging source is not available.
SECTION 6
LP GAS REQUIREMENTS
The LP gas pressure to the refrigerator should be 11 inches water column with half of all BTU's of the RV turned on. With all other appliances off, the pressure to the refrigerator should not exceed 12 inches water column. To check the gas pressure when the refrigera­tor is operating, there is a pressure test port on the solenoid.
To check the switch, disconnect the wires and do a continuity check. In the OFF position, there should be no continuity. In the ON position, there should be a continuity reading.
RM7030 (Product No. 921890201 & 921890301)
RM7030 (Product No. 921890401) and RM7732
TEST PORT
SOLENOID VALVE
18
TEST PORT
DIAGNOSTIC SERVICE MANUAL
SECTION 7
LP GAS COMPONENTS
7.1 MANUAL GAS Shutoff VALVE
The manual gas shutoff valve is where the incoming LP gas supply is attached. To check the shutoff valve, remove and inspect for any obstructions. The valve must be turned to "ON" before any gas operation can occur.
RM7030 (Product No. 921890201 & 921890301)
DOMETIC® RM7030/RM7732
Refrigerators
MANUAL GAS Shutoff VALVE
RM7030 (Product No. 921890401) and RM7732
19
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
7.2 ORIFICE
The orifice is a small brass fitting that has a ruby membrane that is laserbeam drilled and is mounted on the gas line just prior to the burner. The orifice is cleaned by using an alcohol based solvent and allowing to air dry.
NEVER USE A DRILL BIT OR JET TIP CLEANER TO CLEAN ANY ORIFICE AS THESE DEVICES WILL DAMAGE THE FACTORY MACHINED PART AND CREATE A POTENTIALLY DANGEROUS CONDI­TION.
If there is lack of cooling on gas operation, verify the orifice is the proper size (#73).
7.3 THERMOCOUPLE A. RM7030 (Product No. 921890201 & 921890301)
The thermocouple is a component extending above the burner assembly so the tip is in the path of the flame. It will produce 14 to 30 millivolts DC in normal operation. To check the thermocouple, use a known good safety
valve and attach to the thermocouple. Next, supply flame to tip of the thermocouple for a few moments while depressing the safety valve. Remove the flame and release the safety valve.
The valve should hold for at least 30 seconds. If it does not hold the safety valve open for 30 seconds, replace the thermocouple. If it does hold for 30 seconds or more, the thermocouple is good  do not replace it. NOTE: Be sure the tip on the thermocouple is clean.
B. RM7030 (Product No. 921890401) & RM7732
The thermocouple is a component extending above the burner assembly so the tip is in the path of the flame. During normal gas operation, the thermocouple should produce 25 to 35 millivolts when connected to the lower circuit board. Any reading below 18 millivolts could cause erratic gas operation. NOTE: A reading of 18 or less could be caused by low gas pressure or improper thermocouple location.
THERMOCOUPLE
ELECTRODE
BURNER TUBE
RM7030 (Product No. 921890201 & 921890301)
ORIFICE
PRESSURE TEST PORT
RM7030 (Product No. 921890401) and RM7732
20
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
7.4 BURNER
The burner is a slotted metal tube located below the flue tube on the cooling unit. It should be level, and the slots in the burner should be directly below the flue tube. The burner should be cleaned periodically, at least once a year. To clean the burner, remove from the refrigerator and check for any foreign residue that could cause a deflection of the gas flow or the flame. Next, soak the burner in an alcohol based solvent and allow to air dry. After cleaning, reinstall in the refrigerator.
7.5 FLUE BAFFLE
The flue baffle is designed to concentrate the heat (from the gas flame) at a certain area of the flue tube. It should be cleaned periodically, at least once a year. To clean, remove from the flue tube and check for any damage, then clean thoroughly.
The length of the flue baffle assembly (flue baffle and wire) should be 39 inches on RM7030; 40 inches on RM7732. The flue baffle itself should measure 13/16 inch wide and 6 inches long on RM7030 and RM7732. The proper position of the baffle above the burner is 1 inch.
7.6 FLUE CAP (RM7030 ONLY)
The flue cap is located at the top of the flue tube and is attached with a screw. It must be properly attached or flame outage could occur.
B. 12 Volt DC Connection
Connection is made to the main terminal block. The refrigerator must be connected to the battery circuit with two wires of adequate capacity to avoid voltage drop.
The wire gauge should be a minimum of 14 gauge.
RM7030 (Poduct No. 921890201 & 921890301) C. Ignition Lock Connection
In order for the circuit board to perform certain functions, it must receive a signal when the vehicle engine is running. The signal wire (16 gauge mini­mum) should originate at the run terminal of the ignition switch and connect to the "IGN Lock" posi­tion on the refrigerator terminal block.
Do not use the body or chassis of the vehicle as a substitute for either of the two conductors. No other electrical equipment or lighting should be connected to the refrigerator circuit.
8.2 INTERNAL WIRING
Check all wires at the connectors to be sure of a proper and tight connection. Also verify the refrigerator is wired per the wiring diagram for the exact model you are working on. See the following typical wiring diagrams. NOTE: Improper wiring at the lower circuit board could cause erratic operation and lower circuit board failure.
7.7 FLUE TUBE
The flue is a component of the cooling unit. It must be cleaned
FLUE CAP
periodically, at least once a year. To clean, remove flue cap and flue baffle, then cover the burner and clean by using a flue brush, Domet­ic Part No. 0151404001. If the flue tube becomes coated with scale or residue from combustion of LP gas, the efficiency of gas operation decreases.
NOTE: After cleaning be sure to reinstall the flue baffle and flue cap.
SECTION 8
WIRING
8.1 EXTERNAL WIRING A. 120 Volts AC Connection
The refrigerator is equipped with a three-prong (grounded) plug for protection against shock hazards and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
FLUE TUBE
(Wiring diagrams continued on next page)
21
DOMETIC® RM7030/RM7732 Refrigerators
RM7030 (PRODUCT NO. 921890201 & 921890301)
DIAGNOSTIC SERVICE MANUAL
TYPICAL WIRING DIAGRAM FOR
22
DIAGNOSTIC SERVICE MANUAL
TYPICAL WIRING DIAGRAM FOR
RM7030 (PRODUCT NO. 921890401)
DOMETIC® RM7030/RM7732
Refrigerators
M
Q
R
2
L
6
C
1
S
B
BLACK BROWN RED ORANGE
GREEN
WHI T E WHI T E
A5 B5 C5
D5 E5
A2 B2
J3
J2
A
O
P
J6
J5
J4
1
7
+
-
12V DC
J
T
1
I
2
1
T
1
2
1
1
F
2
P3
1
WHI T E
A3
YEL LOW
B3
4
BLUE
C3
2
E
J7
J10
J8
2
1
T
4
5
U
3
2
2
G
120 VOLTS AC
N
K
A
CIRCUIT BOARD POWER
B
CIRCUIT BOARD DIS PLAY
C
THERMISTOR
D
GAS VALVE
E
REIGNITER
F
THERMOCOUPLE
G
ELECTRODE
H
D
N
1
WHI TE
BLACK
2
3
GREEN
4
GREEN/YELLOW
5
GREY
6
BROWN
7
BLUE
H
RETAINER FOR BURNER
I
TERMINAL BLOCK
J
TERMINAL STRIP
K
ABS ORPTI ON UNI T
L
SWITCH
M
LIGHT
N
HEATER 120V AC
O
FUSE 3A
P
FUSE 5A
Q
HEATING CABLE
R
SWITCH
S
TERMINAL BLOCK
T
TERMINAL BLOCK
U
RETAINER FOR CIRCUIT BOARD POWER
23
DOMETIC® RM7030/RM7732 Refrigerators
RM7732 TYPICAL WIRING DIAGRAM
DIAGNOSTIC SERVICE MANUAL
24
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
SECTION 9
OTHER
9.1 LEVELING
In an absorption refrigerator system, ammonia is liquefied in the finned condenser coil at the top of the refrigerator. The liquid ammonia then flows into the evaporator (inside the freezer section) and is exposed to a circulating flow of hydrogen gas, which causes the ammonia to evaporate, creating a cold condition in the freezer.
The tubing in the evaporator section is specifically sloped to provide a continuous movement of liquid ammonia downward by gravity through this section. If the refrigerator is operated when it is not level and the vehicle is not moving, liquid ammonia will accumulate in sections of the evaporator tubing. This will slow the circulation of hydrogen and ammonia gas, or in severe cases, completely block it, resulting in a loss of cooling.
Any time the vehicle is parked for several hours with the refrigerator operating, the vehicle should be level to prevent this loss of cooling. The vehicle needs to be leveled only so it is comfortable to live in (no notice- able sloping of floors or walls).
When the vehicle is moving, the leveling is not critical as the rolling and pitching motion of the vehicle will pass to either side of level, keeping the liquid ammonia from accumulating in the evaporator tubing.
9.2 VENTILATION
Ventilation is one of the requirements for proper cooling unit operation. The coach vent system must be able to provide a way to direct the hot air produced by the action of the cooling unit, out away from the installation of the refrigerator.
0" CLEARANCE FROM SIDE OF CABINET
CLEARANCE
FROM COMBUSTIBLE MATERIALS
PATH OF AIR FLOW
as little open space as possible surrounding the sides and top of the refrigerator to achieve proper air flow. All potential dead air pockets should be blocked or baffled to ensure that heat won't be trapped in these spaces and reduce efficiency.
NOTE: Refrigerators should be installed in accordance with appropriate installation instructions received with the refrigerator.
9.3 AIR LEAKS
Check the gasket on the doors to be sure of a positive air seal. A simple method to check gaskets is to close the door on a dollar bill, then pull the dollar bill out. If no resistance is felt, the gasket is not sealing properly. This should be done on all four sides of the door. If a gasket is not sealing properly, first warm the gasket material with a hair drier.
DO NOT OVERHEAT AS YOU CAN MELT THE MATERIAL.
Then close the door and the magnetic strip should pull the gasket to the metal frame. Leave door closed until the material has cooled. Then recheck for a positive seal. If a positive seal cannot be achieved, replace the gasket. Also check that the cooling unit is installed properly. The cooling unit's foam block, the portion that surrounds the evaporator coils, must be flush to the cabinet at the back of the refrigerator and have a positive seal. If the cooling unit is not installed properly, remove and install properly.
RM7030:
The refrigerator is secured in the enclosure with six screws and they must be installed in the following order:
First Two Screws installed on front base; Second Two Screws installed in the top frame; Third Two Screws installed in the rear base.
Failure to follow the sequence in securing refrigerator in enclosure can cause leakage between the frame and cabinet. NOTE: Air leaks will cause insuffi­cient cooling as well as rapid forma­tion of frost.
3RD
2ND
The refrigerator extracts heat from the interior of the refrigerator cabinet and dissipates the heat out through the vent system. In a proper installation there should be
1ST
25
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
RM7732: SECURING THE REFRIGERATOR:
After the refrigerator is mounted in place (ensuring a combustion seal at the front frame), the refrigerator is to be secured in the enclosure with six screws. The screws have to be installed in the following order:
STEP 1: Two screws installed through the front
base, which includes the lower front strip installa-
tion. The refrigerator is provided with a lower front strip (shipped as a loose part). The front strip is to be attached after the refrigerator is set into the cutout opening.
A.Install the lower front strip by maneuvering it under
the bottom hinge plates, as shown in FIG. 7.
FIG. 7
B. Carefully tilt the top decoration panel and lift up to
remove from top frame. See FIG. 9.
FIG. 9
USE SCREWDRIVER TO PUSH TABS OUT OF HOLE
C. Install the second two screws in the top frame as
shown in FIG. 10.
FIG. 10
B.Secure the refrigerator and the lower front strip with
two screws: One screw through each hinge. See FIG. 8.
FIG. 8
STEP 2: Install the two screws in the top frame.
A. The top decoration panel must be removed from
the refrigerator before the screws can be in­stalled. Open refrigerator door and gently push the tabs out of the hole in the hinge with flat blade screwdriver. See FIG. 9.
STEP 3: Two screws installed in the rear base.
See FIG. 11
FIG. 11
Screws
Failure to follow the sequence in securing refrigera­tor in the enclosure can cause leakage between the frame and cabinet.
26
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
9.4 DOOR POSITION
The door position can be checked by observing any misalignment of the door in relation to the frame.
SMOOTH FIT, PROPER SEAL
NOTE: Improper position of the refrigerator door can
cause the interior light to stay on when the door is closed.
To adjust either door, loosen the hinge bracket screws, reposition the door then tighten the hinge bracket screws.
To adjust up or down, remove the door and add or remove washers from the lower hinge pin. Reinstall door and check for correct clearances.
9.5 AMBIENT TEMPERATURE
This is the temperature surrounding the recreational vehicle, as well as the temperature of air at the back of the refrigerator. As the ambient temperature increases, the air temperature in the area of the cooling unit increases. The RM7030 and RM7732 will maintain approximately 43 degrees food storage temperature at 110 degree ambient temperature. As the ambient temperature increases, it is possible for the interior temperature of the refrigerator to increase. This means proper installation, ventilation and leveling are important for proper operating temperature of the refrigerator.
9.6 COOLING UNIT
The cooling unit is a self-contained, hermetically sealed set of coils where the refrigeration process takes place. The chemicals involved in the cooling process include hydrogen, ammonia, water and a rust inhibiting agent. There are no repairs recommended on the cooling unit. If it is defective, replace with a new cooling unit.
To check the cooling unit, first verify the AC heating elements are good (see Sec. 3). Then place approxi­mately one gallon of water inside the refrigerator and
place a thermometer in one of the containers of water. Next, supply 115 volts directly to the AC heating ele­ments and operate for at least 12 hours. Then check the temperature on the thermometer. It should be at 45 degrees or lower depending on test conditions (see Sec. 9.2 and 9.5). If so, the cooling unit is good. If the temperature of the water is above 45 degrees, replace the cooling unit.
9.7 FOOD STORAGE
Proper refrigeration requires free air circulation within the food storage compartment. Restricted air circulation within the compartment will cause higher cabinet temperatures. To remedy this situation, simply rear­range your food items. It is also essential that the shelves are not covered with paper or large storage containers. Always remember to allow for proper air circulation.
Odors or highly flavored foods should always be stored in covered dishes, plastic bags or wrapped in foil or waxed paper to prevent food odors. Vegetables, lettuce, etc., should be covered to retain their crispness. NEVER PUT HOT FOOD INTO THE REFRIGERATOR.
To reduce frost formation in and on the freezing com­partment, cover stored liquids and moist foods and do not leave the door open longer than necessary.
When the refrigerator is heavily loaded, it takes longer to lower the refrigerator temperature, and longer to make ice. A very heavy load may also cause defrosting.
9.8 HIGH HUMIDITY
High humidity may cause a small amount of condensa­tion to form on the frame of the refrigerator. In extreme cases, the condensation may actually run off the frame. As the humidity is reduced, the sweating will decrease. High humidity can also be a factor in rapid formation of frost.
The RM7030 and RM7732 refrigerators have climate controls installed (see Sec. 5.12). Use of the climate control will reduce the formation of condensation on the frame.
27
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
9.9 INTERIOR LINER SEAL TO FRAME
There is a seal that is applied to the liner in the area where the metal frame makes contact with the interior liner. If this seal is incomplete, cold air can migrate out to the metal frame. If this happens, condensation could form on the frame and could promote rapid formation of frost. If you suspect an improper seal, apply a small bead of silicone all the way around the perimeter where the frame meets the interior liner.
Remove all screws securing the refrigerator into the cabinet and slide the refrigerator out approximately 24 inches. Clean the metal frame and foil-backed insulation around the refrigerator. Apply a foil-backed adhesive tape to the joint between outer frame and foil-backed refrigerator insulation. Refer to illustration top of page
22.
Make sure the refrigerator is dry and that the surface temperatures are above 50°F. Use a clear silicon caulking compound and seal the seam between the refrigerator's plastic liner and the metal frame. Apply the silicon in a continuous bead around both the refrigerator freezer and food compartments.
NOTE: TO FORM A PROPER SEAL, IT IS IMPOR­TANT NOT TO LEAVE ANY GAPS.
28
(Section 10. Icemaker Operation, continue to Page 29)
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
SECTION 10
ICE MAKER OPERATION
The refrigerator must be allowed to precool properly before starting the ice maker. The refrigerator has to be connected to 120 volts AC before the ice maker can operate. The water line manual shutoff valve must be open. To start making ice, move the ice level bail arm to DOWN position.
ICE LEVEL BAIL ARM
DOWN POSITION
When the ice maker thermostat senses the preset temperature for ejection of the ice cubes, the fingers will start to rotate  dumping any ice cubes and filling the mold with water.
When the storage container is full of ice, the ice level bail arm can not return to the DOWN position. This will stop further production of ice until the container is emptied and the bail arm is returned to the down position.
The absorption system will keep the compartment at the proper temperature for storage of ice. Ice making is accelerated if the thermostat is set to the coldest position. It is a good idea to do this a few hours before you anticipate a need for ice.
NOTE: IF THE ICE MAKER WAS CLEANED AND DRAINED, NO ICE CUBES WILL BE DUMPED INTO THE STORAGE CONTAINER DURING THE FIRST CYCLE.
The first few cycles may have small cubes due to air trapped in the water lines. The first container of ice cubes should be dumped if the water system has been winterized or not used for several weeks.
SECTION 11
ICE MAKER COMPONENTS
11.1 MOLD HEATER
The mold heater uses 165 watts to thaw the ice free from the mold. It is wired in series with the thermostat which also acts as a safety device. With power to the appli­ance off, check for resistance be­tween the two leads to the heater element. You should obtain a reading of approximately 80 ohms. If the heater is found to be defective, the manufacturer recommends replacement of the entire ice making unit for proper operation.
11.2 ICE EJECTOR
The ice ejector blades sweep the ice from the mold cavities during the ejection cycle.
The drive end of the ejector is "D" shaped for positive coupling. The bearings at both ends are lubricated with silicone grease. If the ejector blades are frozen into the ice, defrost the ice maker and manually cycle the ice making unit, making sure the ejector stops at the right location.
11.3 MOLD THERMOSTAT
This is a single-pole, single-throw, bimetal switch. It starts an ejection cycle by closing at 18ºF ± 5º. The reset temperature is 50ºF ± 5º. The thermostat is in series with the mold heater and acts as a safety against overheating in case of a mechanical failure. If the thermostat is defective, replace it.
THERMOSTAT
MOLD HEATER (Staked in Place)
"D" SHAPED DRIVE END
CLAMP
29
DOMETIC® RM7030/RM7732 Refrigerators
11.4 SHUTOFF ARM
The shutoff arm is cam driven. It operates a switch to control the quantity of ice produced. During the ejection cycle the arm is raised and lowered during each of the two revolutions of the timing cam. If the shutoff arm comes to rest on top of the ice in the storage bin during either revolution, the switch will remain open and stop the ice maker at the end of that revolution. The arm has a manual shutoff built into the linkage; by raising the arm as high as possible, it will lock in that position until forced down.
If the arm and switch do not operate properly, check for damage and repair or replace parts as necessary.
ARM UP
ARM DOWN ICE MAKER WILL OPERATE
STOPS OPERATION
DIAGNOSTIC SERVICE MANUAL
11.6 TIMING MOTOR
This is a low-wattage, stall-type motor which is geared to the timing cam and ice ejector. It is a one RPM motor.
To check the motor, disconnect power to the appliance and test for continuity between the two leads. If you DO NOT have continuity, replace the motor. If you have continuity and the motor runs, DO NOT replace.
11.7 WATER VALVE
This valve is solenoid operated. When it is open, it releases water from the source to the mold. The amount of water is proportional to the length of time the water valve switch is held closed by its timing cam.
11.5 MOLD SWITCHES
These three switches are single-pole, double-throw style. They are identical and interchangeable. The holding switch assures completion of a revolution once a cycle has started. The water valve switch opens the water valve during the fill stage of the cycle. NOTE: This is the only adjust­able component of the ice maker. If you use a double­throw switch, DO NOT use the N.O. terminal. The shutoff switch stops the ice maker's operation when the storage bin is full.
Shutoff SWITCH
LEVER ARM
MOTOR
MOUNTING PLATE
TIMING CAM
WATER VALVE SWITCH
HOLDING SWITCH
FRONT VIEW
Disconnect power to the appliance, remove the wires to the water valve solenoid coil, and check for continuity between the two terminals. If you have continuity, the solenoid is good. It takes 10-15 watts to energize the solenoid coil. The mold heater and coil are in series. When the mold heater is activated, this causes the voltage to drop to about 105 VAC at the coil.
The valve has a flow washer inside which acts as a pressure regulator. A strainer is installed to prevent dirt, rust, etc. from entering the valve. Check for any debris which might obstruct the flow of water, or prevent the valve from closing completely when the circuit is not energized. Remove any obstructions. If the valve still fails to operate properly, replace it.
WATER VALVE
VALVE BODY
SOLENOID COIL
STRAINER
FLOW WASHER
30
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
11.8 ICE MAKER ASSEMBLY
It may be necessary to replace the entire ice maker assembly.
Disconnect power to the appliance. Disconnect the leads inside the ice maker unit. Check each wire for continuity to make sure the wiring is good before replacing the ice maker unit. If there is no continuity on any of these wires, replace or repair them as necessary and recheck the ice maker unit to determine whether the problem was in the wiring or the unit itself.
(SCHEMATICS CONTINUED ON PAGES 32 THROUGH 34)
OPERATION
While the operation of the ice maker is fairly simple, an understanding of its cycle is necessary for the service technician to diagnose specific problems.
The following series of electrical schematics (on the following pages) will show a typical cycle, and the positions of various components during the cycle: the mold and its contents, the ejector, the shutoff arm and the storage bin.
NOTE: If you have difficulty in reading schematics and circuit diagrams, please enroll in a basic electrical course at your local school or college.
31
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
32
DIAGNOSTIC SERVICE MANUAL
DOMETIC® RM7030/RM7732
Refrigerators
33
DOMETIC® RM7030/RM7732 Refrigerators
DIAGNOSTIC SERVICE MANUAL
SECTION 12
ICE MAKER  OTHER
12.1 WATER FILL ADJUSTMENT
The correct water level in the mold is important for the proper production of ice. The size of the ice cubes depends on the amount of water which enters the mold. The cubes should be approximately 1/2" wide, 3/4" high and 2-1/2" long. If the water overflows in the mold, first check to see if the ice maker unit is level in the appliance. Next ensure that the appliance is installed level in the RV.
If there is still water overflow, adjustment of the water fill screw is necessary. Locate the screw on the ice maker assembly. Turn the screw as necessary toward the "+" or "" side. One full turn of the screw will make an 18cc change in the amount of water. DO NOT turn the screw more than one full turn at a time.
If the water level is too high, it can also cause the ejector blades to become frozen in the ice. Follow the procedures above to correct the problem.
WATER FILL ADJUSTING SCREW
1 FULL TURN = 18 cc's CHANGE
34
DIAGNOSTIC SERVICE MANUAL
12.2 WIRING
Refer to the wiring diagram supplied with the unit you are working on, and make sure all wiring connections are correct and tight.
THIS IS AN ENERGIZED CIRCUIT. ELECTRICAL SHOCK CAN OCCUR.
BEFORE CHECKING THESE COMPONENTS BE SURE THERE IS NO POWER TO THE APPLIANCE.
DOMETIC® RM7030/RM7732
Refrigerators
ICE MAKER TYPICAL WIRING DIAGRAM
12.3 WATER SUPPLY
To operate properly, the water pressure in the water supply line must be between 15 lbs. PSI and 125 lbs. PSI.
Lower water pressure, water turned off, or obstructions or air in the water line can cause low or no ice produc­tion.
First check to see that the water supply is fully turned on. Visually check the line for kinks, etc. which might obstruct the flow of water.
To remove trapped air, loosen the connection at the water solenoid valve of the appliance. Ensure that pressurized water is reaching this point, and bleed off any air in the line. Retighten the connection, making sure there are no leaks.
35
Loading...