Dometic Americana, Americana Plus, Classic, New Dimensions, New Generations User Manual

Americana /Americana Plus
Classic
New Dimensions
New Generations
Home Refrigerators
vs
Compressor vs Absorption
Controlled Environment vs
Changing Environment
Recovery time is vastly
different 30-45 minutes vs 1-2 hours recovery
CONDENSER
EVAPORATOR
ABSORBER
BOILER
SOLUTION IS
MADE UP OF:
AMMONIA
WATER
HYDROGEN
RUST INHIBITOR
The
Absorption
System
PG.
26
PG.
25
To properly test a Cooling Unit
Three criteria have to be met:
Level ?
Ventilation ?
Heat Source?
Ventilation
Make sure you check Ventilation and Air Flow
-0” clearance on the sides and top
-No more than 1” from back of CU to sidewall. (A baffle may need to be installed to help direct air across coils)
-If there is an auxiliary fan, check that it is
working properly.
PG.
21
Typical Double Door Install
0” clearance on the side and top and less than 1” from CU
to sidewall
Application Guide 3308666.XXX
PG.
21
Typical Side by Side Installation
in Slide Out/2 Sidewall Vents
Application Guide 3308666.XXX
PG.
21
Symptom: Not Cooling
Air is not being forced through the
condenser – to much space!
Warm air is being trapped around
the refrigerator from a poor
installation.
AUXILIARY FANS
Helps with air flow. 3108705.751 for Single Door refers
Fan limit switch will close at 105°F and open at
90°F +/- 10%.
3108705.744 for Double Door refers
Fan limit switch will close at 150°F and open at 120° +/-
10%.
Will draw only .5 amps each. In-line fuse to protect circuit
Small Fan # 3851183016
Note: Please write these Part #’s down as they are not in the service manual.
Limit Switch only: 3104723.006
Limit Switch only: 3104133.016
Heating Elements
The function of the heating element
is to provide the boiler with a
specific amount of BTU’s of Heat
AC Heating Element 6,8,10 cu ft.
Ohms – Approx. 44 +/- 10%
Amps – Approx. 2.7
Watts – 325
Series AC Heating Element for side wise/side by side
Ohms – Approx. 34.3 +/- 10% Amps – Approx. 3.5 Watts – 420
DC Heating element (Not shown) 6 cu ft.
Continuity – yes or no
Amps – Approx 18
Watts – Approx. 215
Note: Only use DC heating element when driving to or from a location.
PG.
10/11
To Perform a By-Pass Test of
the Cooling Unit
Disconnect the Thermister from Control Board
(with the thermister unplugged no temperature is
sensed, therefore, it will run continuously).
Place a glass of water in the refrigerator along with
a thermometer.
Plug unit into 115 VAC and allow to run “wide
open” for approximately 12 hours.
DO NOT DIRECT WIRE HEATING ELEMENT!
PG.
26
Loading...
+ 28 hidden pages