Dimplex BF33ST-DX, BF39ST-DX User Manual

INSTALLATION GUIDE FOR THE
ELECTRIC FIREPLACE
MODEL NUMBERS:
BF33ST/DX BF39ST/DX BF45ST/DX
7206350200REV06
CONTENTS
PAGE 1 Listings and Code Approvals PAGE 1 Model Specifications PAGE 1 Step-by-Step Installation
Section A
PAGE 2 Framing
Section B
PAGE 2 Recommended Power Supply Wire
Specifications
PAGE 2 Recommended Wire and Fusing
Requirements PAGE 3 Voltage Selector Switch Location PAGE 3 Mounting Flanges
Section C
PAGE 4 Factory Setting Wiring 240 Volt
(Without Main Power Wall Switch) PAGE 5 Factory Setting Wiring 120 volt
(Without Main Power Wall Switch)
Section D
PAGE 6 - 7 Main Power Wall Switch Wiring for 240 Volt PAGE 8 - 9 Main Power Wall Switch Wiring for 120 Volt
Section E
PAGE 10 - 11 Heater Wall Switch Wiring for 120/240 Volt PAGE 12 - 13 Wall Mounted Thermostat Wiring for
120/240 Volt PAGE 14 - 15 Flame Override Switch Wiring for 120/240
Volt
Section F
PAGE 16 - 18 Wiring Diagrams
LISTINGS AND CODE APPROVALS
The BF series fireplaces have been tested in accordance with the UL 2021 and CSA C22.2 No. 46 standards for fixed and location-dedicated electric room heaters.
MODEL SPECIFICATIONS
Model
Number BF33ST
BF33DX 33” Deluxe BF39ST
BF39DX 39” Deluxe BF45ST
BF45DX 45” Deluxe
Description Voltage Volts Rated Power Watts
33”
Standard
39”
Standard
45”
Standard
120/120/208/
240
120/120/208/
240
120/120/208/
240
120/120/208
/240
120/120/208/
240
120/120/208/
240
245/1440/2100/
2700
245/1440/2100/
2700
245/1440/2100/
2700
245/1440/2100/
2700
245/1440/2100/
2700
245/1440/2100/
2700
Remote
Control
Option Option N/A 2.0 12.0 10.10 11.25 Option Option Included 2.0 12.0 10.10 11.25 Option Option N/A 2.0 12.0 10.10 11.25 Option Option Included 2.0 12.0 10.10 11.25 Option Option N/A 2.0 12.0 10.10 11.25
Option Option Included 2.0
Wall
Thermostat
Refractory Brick Look
AMPS No Heat 120 Volt
NOTE: Power ratings shown include the light bulbs and motors (275 watts)
WARNING
The installation of the fireplace unit must comply with the applicable Local and/or National Electrical Codes and utility requirements. This installation should be entrusted to duly qualified personnel where required by law.
AMPS
120 Volt
12.0
AMPS
208 Volt
10.10 11.25
AMPS
240 Volt
STEP-BY-STEP INSTALLATION (Note: Please read all instructions before installing)
1. Rough in framing opening following the recommended dimensions located in (Section A: Framing).
2. Allow 8” of service cable for connecting power supply wire to junction box on fireplace when installing before finishing wall. Allow up to 4 feet of service cable for connecting power supply wire to junction box on fireplace when installing after finishing wall. Remove the outer jacket and strip the individual conductors ½” from the end.
3. Loosen the screw securing the junction box cover and remove the cover.
4. Remove knockouts if necessary or use the provided cable clamp.
5. Place unit in position in the framed opening, level with shims if necessary and attach unit to frame using mounting flanges provided (see figure 3 on page 3).
6. Unit is factory wired for 208/240 volt power supply (see figure 1 on page 3). If 120 volt operation is required, slide the switch and reconfigure the wiring (see figure 2 on page 3). Wires L1, L2, N & G are attached to the rear of the junction box cable clamp for easy access.
Note
If wiring unit to operate with NO heat a dedicated circuit may not be required.
7. Wire a dedicated, properly fused circuit with a 15amp rating for the appropriate voltage (120, 208/240). (see Section C for factory setting wiring)
8. Make wall switch and or wall mounted thermostat connections as outlined in Section D: Wiring.
9. Place all connectors inside the unit and secure the junction box cover to unit. Ensure that the cable clamp grips only the jacket of service cable, thermostat and if applicable wall switch lines.
1
WARNING
A
Ensure method of installation does NOT obscure the air intake slots on bottom front of unit in any manner. (see diagram in Section A)
SECTION A: FRAMING
Dimensions
MODEL A B C D E F G H I J K L BF33ST/DX 15.0” 33.5” 29.5” 23.0” 14.3” 29.6” 32.8” 18.8” 28.5” 48.0” 34.0” 34.0” BF39ST/DX 16.0” 39.5” 33.5” 26.6” 15.3” 36.0” 38.7” 22.8” 32.7” 54.0” 38.0” 38.0” BF45ST/DX 16.0” 45.5” 33.5” 26.6” 15.3” 42.0” 44.7” 22.8” 32.7” 60.0” 42.0” 42.0”
Rough-in framing dimensions
Top Surface
ir Intake Slots
Firebox dimensions
Rough-in corner framing
This fireplace is a zero clearance design. No combustibles can be placed on the top surface of the fireplace. Combustibles may be installed to the edge of the unit. Four mounting flanges on the sides of the unit are provided to facilitate installation. Insulation and vapor barrier should be placed a minimum of 2 inches from the unit.
SECTION B: RECOMMENDED POWER SUPPLY WIRE SPECIFICATIONS
For 120 volt installations use two conductor, non-metallic sheath cable with ground wire (3
wires total) for the incoming power supply on fireplace inserts. Use the appropriate wire to meet local and national electrical codes for rated power consumption.
For 208 / 240 volt installations use three conductor, non-metallic sheath cable with ground wire (4 wires total) for the incoming power supply on fireplace inserts. Use the appropriate wire to meet local and national electrical codes for rated power consumption.
Two conductor, non-metallic sheath cable with ground wire (3 wires total) is recommended for installation of a wall mounted thermostat and/or wall switch for use on fireplace inserts. Use appropriate wire to meet local and national electrical codes for rated power consumption. All wire gauges should match the recommended wire sizes shown below.
RECOMMENDED WIRE AND FUSING REQUIREMENTS
VOLTS WIRE GAUGE FUSE RATING 120 VOLT 12 GAUGE 15 AMP 208 VOLT 12 GAUGE 15 AMP 240 VOLT 12 GAUGE 15 AMP
2
VOLTAGE SELECTOR SWITCH LOCATION
IMPORTANT:
Ensure that the incoming power supply voltage matches the setting of the voltage selector switch.
NOTE:
The voltage selector switch is located inside the exhaust panel on the top right hand corner.
CAUTION:
When changing the voltage selector switch from 240 volts to 120 volts ensure that the power supply is turned off.
NOTE: Carefully insert a flat headed screwdriver inside the exhaust panel to change the switch from 240 volts (230 position) to 120 volts (115 position).
When wiring the unit for 208 / 240 volts the voltage selector switch should be in the 230 volt position. (see figure 1)
When wiring the unit for 120 volts the voltage selector switch should be in the 115 volt position. (see figure 2)
MOUNTING FLANGES
There are two mounting flanges located on each side of the fireplace insert.
Bend tabs and mount to framing using suitable hardware.
FIGURE 1
FIGURE 2
FIGURE 3
Mounting
Flanges
3
X
SECTION C: FACTORY SETTING WIRING
(WITHOUT MAIN POWER WALL SWITCH)
IMPORTANT:
The unit is factory configured for 208/240 volt operation
NOTE:
Use 3 conductor wire with ground (4 wires total) from the power supply (breaker panel) to the junction box on the unit.
NOTE:
All wiring must be completed prior to installing the unit.
NOTE:
Ensure that the voltage selector switch is in the proper position for the required supply voltage prior to connecting the unit to the power supply.
240 VOLT INSTALLATION
1. Locate the voltage selector switch inside the exhaust panel on the top right hand corner of the unit. (see figure 1 on page 3)
2. Ensure that the switch is in the 240 volt position. (230 is printed on switch)
3. Loosen the screw securing the junction box cover and remove the cover.
4. Remove the knockouts (if necessary) or use the provided cable clamp.
5. Pull out the four wires marked L1, L2, N, and G.
6. Connect the black L1 wire from the unit to the black L1 from the power supply.
7. Connect the red L2 wire from the unit to the red L2 from the power supply.
8. Connect the white N wire from the unit to the to the white neutral from the power supply.
9. Connect the green ground wire from the unit to the ground from the power supply.
10. Ensure that all connections are tight.
11. Insert all the wiring back into the unit and secure with a cable clam p.
FIREPLACE JUNCTION BO
WHITE WIRE - N
RED WIRE – L2
BLACK WIRE – L1
GREEN WIRE - G
WHITE WIRE - N
RED WIRE –L2
BLACK WIRE –L1
GROUND WIRE - G
240 V
POWER
SUPPLY
(BREAKER
PANEL)
4
SECTION C: FACTORY SETTING WIRING
X
(WITHOUT MAIN POWER WALL SWITCH)
IMPORTANT:
The unit is factory configured for 208/240 volt operation
NOTE:
Use 2 conductor wire with ground (3 wires total) from the power supply (breaker panel) to the junction box on the unit.
NOTE:
All wiring must be completed prior to installing the unit.
NOTE:
Ensure that the voltage selector switch is in the proper position for the required supply voltage prior to connecting the unit to the power supply.
120 VOLT INSTALLATION
1. Locate the voltage selector switch inside the exhaust panel on the top right hand corner of the unit. (see figure 2 on page 3)
2. Flip the switch from 240 volt to 120 volt configuration. (230 and 115 is printed on switch)
3. Loosen the screw securing the junction box cover and remove the cover.
4. Remove the knockouts (if necessary) or use the provided cable clamp.
5. Pull out the four wires marked L1, L2, N, and G.
6. Connect the black L1 wire from the unit to the black L1 from the power supply.
7. Connect the red L2 and white N wire from the unit to the white neutral wire from the power supply.
8. Connect the green ground wire from the unit to the ground from the power supply.
9. When the unit has been configured for the appropriate power supply voltage, ensure that all connections are tight.
10. Insert all the wiring back into the unit and secure with a cable clamp.
WHITE WIRE - N
RED WIRE
L2
WHITE WIRE - N
120 V
POWER
SUPPLY
BLACK WIRE – L1
BLACK WIRE –L1
(BREAKER
PANEL)
GREEN WIRE - G
FIREPLACE JUNCTION BO
GROUND WIRE - G
5
SECTION C: FACTORY SETTING WIRING
X
(WITHOUT MAIN POWER WALL SWITCH) (NO HEAT INSTALLATION)
IMPORTANT:
The unit is factory configured for 208/240 volt operation
NOTE:
Use 2 conductor wire with ground (3 wires total) from the power supply (breaker panel) to the junction box on the unit.
NOTE:
All wiring must be completed prior to installing the unit.
NOTE:
Ensure that the voltage selector switch is in the proper position for the required supply voltage prior to connecting the unit to the power supply.
120 VOLT INSTALLATION (NO HEAT INSTALLATION)
1. Locate the voltage selector switch inside the exhaust panel on the top right hand corner
of the unit. (see figure 2 on page 3)
2. Flip the switch from 240 volt to 120 volt configuration. (230 and 115 is printed on switch)
3. Loosen the screw securing the junction box cover and remove the cover.
4. Remove the knockouts (if necessary) or use the provided cable clamp.
5. Pull out the four wires marked L1, L2, N, and G.
6. Connect the black L1 wire from the unit to the black L1 from the power supply.
7. Install a wire nut on the red L2. (wire nut not included).
8. Connect the white N wire from the unit to the white neutral wire from the power supply.
9. Connect the green ground wire from the unit to the ground from the power supply.
10. When the unit has been configured for the appropriate power supply voltage, ensure that all connections are tight.
11. Insert all the wiring back into the unit and secure with a cable clamp.
WHITE WIRE - N
RED WIRE
L2
WHITE WIRE - N
120 V
POWER
BLACK WIRE – L1
Wire Nut
BLACK WIRE –L1
SUPPLY
(BREAKER
PANEL)
GREEN WIRE - G
FIREPLACE JUNCTION BO
GROUND WIRE - G
6