Warranty .............................................. Back Cover
WARNING: Improper
installation, adjustment,
alte ration , serv ice or
maintenance can cause
injury or property damage. Refer to this manual
for correct installation
and operational procedures. For assistance or
additional information
consult a qualified installer, service agency or
the gas supplier.
WARNING: This ap-
pliance is for installation
only in a solid-fuel burning
masonry or UL127 fac-
tory-built replace or in a
listed ventless rebox enclosure. It is design-certied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do
not install this appliance
in a factory-built replace
that includes instructions
stating it has not been tested or should not be used
with unvented gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
per man ent ly l oca ted ,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.desatech.com
122001-01C2
SAFETy
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u,
with headaches, dizziness or nausea. If you
have these signs, the replace may not be
working properly. Get fresh air at once! Have
replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or
lung disease or anemia, those under the inu-
ence of alcohol and those at high altitudes.
Natural and Propane/LP gases are odorless.
An odor-making agent is added to these gases.
The odor helps you detect a gas leak. However,
the odor added to the gas can fade. Gas may
be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Heater base assembly becomes
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater. When using the hand-
held remote accessory (Remote-
Ready Models Only), keep selector switch in the OFF position to
prevent children from turning on
burners with remote.
You must operate this heater
with the replace screen and
hood in place. Make sure replace screen and hood are in
place before running heater.
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
122001-01C3
www.desatech.com
SAFETy
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP
units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas
supplier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This heater shall not be installed in a bed-
room or bathroom, unless installed as a
vented appliance. See Installing Damper
Clamp Accessory for Vented Operation,
page 12 (Remote-Ready Models Only).
This gas log set may not be installed as a
vented appliance in a bedroom or bathroom
in the Commonwealth of Massachusetts.
5. Before installing in a solid fuel burning replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue for damage. If damaged, repair ue
and rebox before operating heater.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat
buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 27.
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if enough fresh air is not available.
See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see
Troubleshooting, page 29.
11. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn
paper or other objects.
13. Do not use heater if any part has been exposed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
14. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
15. Turn heater off and let cool before ser-
vicing, installing or repairing. Make sure
the selector switch is in the OFF position
(Remote-Ready Models Only). Only a
qualied service person should install,
service or repair heater.
16. Make sure the selector switch is in the
OFF position when you are away from
home for long periods of time (RemoteReady Models Only).
17. Remote-ready heaters must not be connected to any external electrical source.
18. Operating heater above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do not
use propane/LP fuel tank of less than 100
lb. capacity (propane/LP units only).
20. Provide adequate clearances around air
openings.
www.desatech.com
122001-01C4
UNPACkING
CAUTION: Do not remove the
data plates from the grate assembly. The data plates contain
important warranty and safety
information.
1. Remove logs and heater base assembly
from carton.
PRODUCT IDENTIFICATION
Note: Do not pick up heater base assem-
bly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied
to logs and heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged call DESA Heating, LLC
at 1-866-672-6040 for replacement parts
before returning to dealer.
Log Set
Ignitor
Remote Control
(Optional)
Control
Knob
Flame Adjustment Knob
Figure 1 - Product Identication
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Rear Burner
Base Assembly
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
OPTIONAL REMOTE CONTROL ACCESSORIES
There are four optional remote controls that
can be purchased separately for RemoteReady Models Only:
• wall switch
•
hand-held ON/OFF remote
•
wall thermostat
• hand-held thermostat remote
122001-01C5
www.desatech.com
See Accessories, page 40.
The wall thermostat or hand-held thermostat
may not be used where vented decorative
listing is required.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
both realistic ames and glowing coals. This
heater is designed for vent-free operation with
ue damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented
heaters. State and local codes in some areas
prohibit the use of vent-free heaters. This heater
may also be operated as a vented decorative
(ANSI Z21.60) product by opening the ue
damper (Non-Thermostat Models Only).
AIR FOR COMbUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or
space unless the required volume of indoor combustion air
is provided by the method described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code, or
applicable local codes. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
www.desatech.com
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light
heater fuel supply.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
-11
kg per pa-sec-m2) or
122001-01C6
AIR FOR COMbUSTION AND VENTILATION
Continued
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 8.
If your home does not meet all of the
three criteria above, proceed to Determin-
ing Fresh-Air Flow For Heater Location,
below.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed
in that space. Rooms communicating directly
with the space in which the appliances are
installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free replace __________ Btu/Hr
Gas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + _________Btu/Hr
Total = _________Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:Gas water heater __________ Btu/Hr
Vent-free replace + _________Btu/Hr
Total = _________Btu/Hr
4.
Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_______ Btu/Hr (maximum can support)
_______ Btu/Hr (actual amount used)
Example: 51,200 Btu/Hr (maximum the
73,000 Btu/Hr (actual amount of
The space in the above example is a conned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides
an unconned space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
space can support)
Btu/Hr used)
40,000
33,000
73,000
122001-01C7
www.desatech.com
AIR FOR COMbUSTION AND VENTILATION
Outlet
Air
Ve ntilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ve ntilated
Crawl Space
T o
Crawl
Space
T o Attic
Or
Remove
Door into
Adjoining
Room,
Option
3
Ve ntilation Grills
Into Adjoining Room,
Option 2
Ve ntilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Continued
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combus-
tion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside Building
www.desatech.com
122001-01C8
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri-
mary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualied ser-
vice person must install heater.
Follow all local codes.
NOTICE: State or local codes may
only allow operation of this appli-
ance in a vented conguration.
Check your state or local codes.
WARNING: Make sure the
selector switch is in the OFF
position before installing heater
(Remote-Ready Models Only).
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
the house. Inspect chimney and
rebox ue for damage. If damaged, repair ue and rebox
before operating heater.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
unless installed as a vented
appliance, see page 12 (Remote-Ready Models Only)
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable
objects are less than 36" from
the front and 42" from top
heater, For side clearances
see Figure 4 page 10
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventila-
tion, page 6.
122001-01C9
www.desatech.com
INSTALLATION
Continued
CHECK GAS TYPE
Use the correct type of gas (natural or propane/
LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from oor, ceiling and adjoining
wall.
Minimum Fireplace Clearance to
Combustible Materials
Side Wall 16", Ceiling 42", Floor 5",
Front 36"
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This combustible material must be 4" from the side
of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
ens ur e safe inst al lation into a masonry,
UL127-listed manufactured replace or listed
vent-free rebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Front
Width
Rear
Width*
www.desatech.com
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
122001-01C10
INSTALLATION
Heat Resistant
Material
(A)
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Top of
Fireplace
Opening
Underside of
Mantel Shelf
12"
8"
(A)
18"
14"
20"
17"
22"
19"
24"
20"
All minimum
distances are
in inches
Log Set
24"/30"/36"
Models
18" Model
2 1/2"
6"
8"
10"
Mantel Shelf
Continued
MINIMUM NONCOMbUSTIbLE
MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow the information on this page.
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile,
etc.) must be at least 1/2" thick. With sheet
metal, you must have noncombustible material behind it. Noncombustible material
must extend at least 8" up (for all models).
If noncombustible material is less than 12",
you must install the replace hood accessory
(24" and 30" Models Only). See Figure 5 for
minimum clearances.
Noncombustible
Material
Distance (A)
1
2" or moreNoncombustible mate-
Between 8" and 12"
Less than 8"
Requirements for Safe
Installation
rial OK.
24", 30" or 36" Models:
Install replace hood
accessory (GA6050,
GA6052 or GA6053 see
Accessories, page 40).
18" Model: Noncombustible material OK.
Noncombustible material must be extended
to at least 8". See
Between 8" and 12",
above. If you cannot ex-
tend material, you must
operate heater with ue
damper open.
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 8" up (for all models). If noncombus-
tible material is less than 12", you must install
the replace hood accessory (24" and 30"
Models Only). Even if noncombustible mate-
rial is more than 12", you may need the hood
accessory to deect heat away from your
mantel shelf. See Figures 5 and 6 and Figure
7, page 9, for minimum clearances.
IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater
with chimney ue damper open. Go to Install-
ing Damper Clamp Accessory for Vented
Operation, page 12.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 5 - Heat Resistant Material (Slate,
122001-01C11
www.desatech.com
Marble, Tile, etc.) Above Fireplace
Figure 6 - Minimum Mantel Clearances
Without Using Hood
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18"
All minimum
distances are
in inches
Log Sets
18", 24",
30" & 36"
Models
20"
2
1
/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050,
GA6052,
or GA6053)
Top of
Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf
INSTALLATION
Continued
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 11, are
not met, you must have a hood. When using
a hood there are still certain minimum mantel
clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
Figure 7 - Minimum Mantel Clearances
When Using Hood
www.desatech.com
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the replace, you must install appliance
at least 5" above the combustible ooring
(see Figure 9).
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, appliance must be installed only in a solid-fuel
burning fireplace with a working flue and
constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this gas log set as a vented appliance
in the Commonwealth of Massachusetts requires the damper be permanently removed
or welded in the fully open position.
If your heater is a manually-controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The replace does not meet the clearance
to combustibles requirements for ventfree operation.
122001-01C12
INSTALLATION
Continued
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
If reasons number 1 or 2 apply to you, you
must permanently open chimney ue damper.
You must install the damper clamp accessory
(to order, see Accessories, page 40). This
will insure vented operation (see Figure 10).
The damper clamp will keep damper open.
Installation instructions are included with
clamp accessory.
See chart below for minimum permanent ue
opening you must provide. Attach damper
clamp so the minimum permanent ue opening will be maintained at all times.
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access
to heater control panel. This
will insure adequate air ow
and guard against sooting and
controls being damaged. Raise
replace oor with noncombustible material. Make sure material
is secure.
CAUTION: Do not pick up
heater base assembly by burners. This could damage heater.
Only handle base assembly by
grates.
IMPORTANT: Make sure the heater burners
are level. If heater is not level, heater will not
work properly. For thermostat models, avoid
damage to thermostat bulb. Avoid nicks or
sharp bends in thermostat bulb wire. Keep
thermostat bulb in mounting bracket until
ready to mount base to oor. See Optional
Positioning Of Thermostat Sensing Bulb,
page 33.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings (not
provided) (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
Note: Install optional Receiver and Hand-Held
Remote Control Kit (see Accessories, page
40) before installing gas log heater (RemoteReady Models Only). See installation instructions included with the kit.
INSTALLATION
Continued
1. Apply pipe joint sealant lightly to male
threads of gas fitting (provided). For
Thermostatically-Controlled Models con-
nect approved exible gas hose to gas
regulator of heater (see Figure 11). For
Remote-Ready models connect approved
exible gas hose to inlet side of gas control (see Figure 12).
IMPORTANT: Hold gas regulator with
wrench when connecting flexible gas
hose (Thermostatically-Controlled Models
Only).
2. Po s i t i o n he a t e r base as s e m b l y in
fireplace.
3. Mark screw locations through holes in
front panel of base (see Figure 13). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16"
drill bit.
6. Attach base, through holes in front panel
of base, to replace oor using masonry
screws provided in hardware package
(see Figure 13).
7. Connect to gas supply. See Connecting To Gas Supply.
Heater Gas
Regulator
Flexible Gas Hose (if
allowed by local codes)
Figure 11 - Attaching Flexible Gas Hose to
Heater Gas Regulator (Thermostatically-
Controlled Models Only)
Gas Control
Masonry
Screw
Figure 13 - Attaching Base to Fireplace
Floor (Remote-Ready Models Only)
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 1/2" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualied service person must connect heater
to gas supply. Follow all local
codes.
CAUTION: Never connect
propane/LP replace directly
to the propane/LP supply. This
heater requires an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
Flexible Gas Hose
(if allowed by local
codes)
Figure 12 - Attaching Flexible Gas Hose
to Heater Gas Regulator
(Remote-Ready Models Only)
www.desatech.com
WARNING: Never connect
natural gas replace to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
122001-01C14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.