Desa VTGF33PRB User Manual

UNVENTED (VENT-FREE) GAS FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Shown with optional cabinet mantel with hearth base and trim accessory.
VTGF33NRB AND VTGF33PRB
GAS FIREPLACE WITH TOTAL CONTROL SYSTEM (TCS)
WARNING: If the information in this manual is not fol­lowed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provi­sions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 5 of this manual.
This appliance may be installed in an aftermarket,* per­manently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indi cated on the rating plate. This appliance is not convert­ible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Common wealth of Massachusetts.
TABLE OF CONTENTS
Safety Information ............................................... 3
Product Identification ...........................................
Local Codes ........................................................ 5
Unpacking ........................................................... 5
Product Features ................................................. 5
Air for Combustion and Ventilation ...................... 5
Installation ........................................................... 8
Operating Fireplace ........................................... 21
Inspecting Burners ............................................ 24
Cleaning and Maintenance ................................ 25
Specifications .................................................... 26
4
Troubleshooting ................................................. 27
Replacement Parts ............................................ 31
Service Hints ..................................................... 31
Technical Service ..............................................
Illustrated Parts Breakdown .............................. 32
Accessories ....................................................... 36
Wiring Diagram .................................................. 39
Warranty Information ...........................
Back Cover
-
-
31
2
www.desatech.com
113134-01E

SAFETY INFORMATION

WARNING: This product con­tains and/or generates chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely be fore tr ying to assemb le, operate or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the flu, with head aches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn ings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Fireplace front and screen be­come very hot when running fire place. Keep children and adults
-
away from hot surfaces to avoid burns or clothing ignition. Fire place will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil­dren when they are in the room with fireplace. When using the optional hand-held remote ac­cessory, keep selector switch in the OFF position to prevent
-
children from turning on burners with remote.
-
-
WARNING: Any change to this heater or its controls can be dangerous.
You must operate this fireplace with the fireplace screen and hood in place. Make sure fire­place screen and hood are in
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved for use with this heater.
place before running heater.
Keep the appliance area clear and free from combustible ma­terials, gasoline and other flam­mable vapors and liquids.
113134-01E 3
www.desatech.com
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in side any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighborʼs phone. Follow the gas supplierʼs instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bed room or bathroom.
5. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, page 25.
8. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9. This fireplace needs fresh air ventilation to run properly. This fireplace has an Oxygen Deple tion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combustion and Ventilation, page 5. If fireplace keeps shutting off, see Troubleshooting, pags 27.
10. Do not run fireplace
• where flammable liquids or vapors are used
or stored
• under dusty conditions
11. Do not use this fireplace to cook food or burn paper or other objects.
12. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
-
13. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
14. Turn fireplace off and let cool before servicing. Only a qualified service person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16. To prevent performance problems with pro pane/LP units, do not use propane/LP fuel tanks of less than 100 lb. capacity.
17. Prov ide adeq ua te clearan ce s around air openings.
-
PRODUCT
IDENTIFICATION
Log Set
Piezo Ignitor
Fan Switch
Figure 1 - Log Set and Base
Top Louver Assembly
-
Screen Assembly
Bottom Louver Assembly
Base Assembly
Top Outer Casing
Blower Assembly
Figure 2 - Fireplace
-
4
www.desatech.com
113134-01E

LOCAL CODES

Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the lat­est edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269

UNPACKING

CAUTION: Do not remove the data plates attached to the heater base assembly. The data plates contain important warranty and safety information.
1. With utility knife, cut the carton all the way around above the staples on the bottom tray. Lift the carton off the heater. Remove packing. Note: The hood is located in the packing on the right hand side of the heater front. Lift the heater off the bottom tray.
2. Locate two screws above top corners of the fireplace screen. Remove and discard these screws. Lift fireplace screen up and pull out to remove.
3. Remove protective packaging applied to logs, log base assembly and fireplace.
4. Remove fireplace hood from carton insert.
5. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought fireplace.

PRODUCT FEATURES

OPERATION
This vent-free fireplace is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing embers. When used without the optional blower, the fireplace requires no electricity making it ideal for emergency backup heat.
SAFETY DEVICE
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/ pilot is a required feature for vent-free room heat­ers. The ODS/pilot system shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches, batteries or other sources to light fireplace.
WIRELESS REMOTE CONTROL
This fireplace features an infrared wireless remote control. This control system can be used to auto matically light the pilot and adjust the burner flame height at the push of a button.
WIRED WALL-MOUNTED REMOTE CONTROL
This fireplace features a two-button wall switch assembly with glowing LEDʼs. The wall switch performs the same functions as the wireless hand­held remote control with the added feature of LEDʼs for visual feedback of operation and status.
BLOWER ASSEMBLY
This fireplace includes a blower assembly. The blower operates thermostatically. The blower circu lates heated air from the fireplace into the room.
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construc tion unless provisions are provid­ed for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Todayʼs homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
-
-
-
-
113134-01E 5
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
Continued
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the out
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors page 7.
If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow for Fireplace Location.
6
-11
kg per pa-sec-m2) or
www.desatech.com
Confined Space and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m
3
per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour
3
(4.8 m
per kw) of the aggregate input rating of
all appliances installed in that space. Rooms com
-
municating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless pas­sageways or ventilation grills between the rooms.
-
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 18 ft.
(width) x 8 ft. (ceiling height) = 2880 cu. ft. (volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2880 cu. ft. (volume of space) x 20 =
57,600 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
,
Vent-free fireplace
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances* + ________
Total = ________
* Do not include direct-vent gas appliances. Di
rect-vent draws combustion air from the outdoors and vents to the outdoors.
__________ Btu/Hr
__________ Btu/Hr
__________ Btu/Hr
__________ Btu/Hr
__________ Btu/Hr
113134-01E
-
Btu/Hr
Btu/Hr
-
AIR FOR COMBUSTION
Outlet Air
Ve
ntilated
Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ve
ntilation Grills
Into Adjoining
Room,
Option 1
12"
12"
AND VENTILATION
Continued
Example:
Gas water heater _____________
Vent-free fireplace + ____________
Total = ____________
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________
_________
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
Example: 57,600 Btu/Hr (maximum the space
can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad ditional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin
ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila
tion Air From Outdoors.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, confined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be oper ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
40,000 33,000 73,000
Btu/Hr
Btu/Hr
Btu/Hr
the space is an un-
-
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un confined space. When ventilating to an adjoining unconfined space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
-
-
-
Figure 3 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostat­controlled power vent. Heated air entering the attic will activate the power vent.
-
113134-01E 7
www.desatech.com
Figure 4 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser­vice person must install fire place. Follow all local codes.
WARNING: Never install the fireplace
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing or other flammable objects are less than 42 inches from the front, top or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
CAUTION: This fireplace cre­ates warm air currents. These currents move heat to wall sur faces next to fireplace. Installing fireplace next to vinyl or cloth wall coverings or operating fireplace where impurities (such as, but not limited to, tobacco smoke, aromatic candles, clean­ing fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
Note: Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the rear, sides or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall
-
or framing materials.
Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fire place Installation, page 17).
IMPORTANT:
the air. Although this is beneficial, installing fire place in rooms without enough ventilation air may cause mildew to form from too much moisture. See
Air for Combustion and Ventilation,
IMPORTANT: Make sure the fireplace is level. If fireplace is not level, log set will not work properly.
CHECK GAS TYPE
-
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
Vent-free heaters add moisture to
WARNING: This appliance is equipped for (natural or pro­pane/LP) gas. Field conversion is not permitted.
ELECTRICAL HOOKUP
Thi s fir ep lace normally operates under 120 VAC/60 Hz line voltage. The electrical cord sup plied with your fireplace is five feet in length. You must locate fireplace within reach of a 120 volt grounded electrical outlet. If not, you must install an electrical outlet within reach of the fireplace power cord. The GA3555 outlet accessory may be used for built-in applications.
-
INSTALLATION CLEARANCES
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling and adjoining wall.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Top Left and Bottom Right Sides and Rear
0" 16" 0"
-
-
page 5.
-
8
www.desatech.com
113134-01E
INSTALLATION
Continued
Carefully follow the instructions below. This will ensure safe installation.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall should follow diagram in Figure 5.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 tible material must be 4" from the side of the fireplace cabinet (see Figure 5).
B. Clear ances from the top of the firep lace
opening to the ceiling should not be less than 42 inches.
*Minimum 16 inches from Side Wall
Figure 5 - Minimum Clearance for
1
/2" from the wall. This combus-
Example
Combustible to Wall
*
REMOVING FIREPLACE SCREEN AND FLOOR ASSEMBLY
NOTICE: Shutoff gas supply and disconnect heater from gas supply if installing blower into previously installed fireplace. Contact a qualified service per
-
son to do this.
1. To remove fireplace screen, remove two screws that hold fireplace screen in place for shipping. These screws are located near top of screen. Discard screws. Lift fireplace screen up and pull out to remove.
2. If logs are installed, carefully remove the logs and set aside, noting the properly mounted location of each.
3. Remove screws that attach fireplace floor as sembly to fireplace. Open lower louver door. Carefully lift up fireplace floor assembly and remove from fireplace, taking care to pull flexible gas line through the access holes (see Figure 6). Note: Be careful of all wires on underside of log base.
CAUTION: Do not pick up fireplace floor assembly by burn­ers. This could damage burners. Only handle base by grates.
-
INSTALLATION SEQUENCE
After unpacking fireplace (see Unpacking, page 5), we suggest that you install your fireplace system in the following sequence:
1. Removal of fireplace floor assembly (re quired)
2. Electrical connections for power cord (required)
3. Relocating wall switch (optional)
4. Installing blower accessory (optional)
5. Connecting fireplace to gas supply (required)
6. Checking gas connections (required)
7. Firebox installation, conventional or built-in (required)
8. Installing perimeter trim (optional)
9. Installing fireplace hood (required)
10. Installing logs (required)
11. Installing fireplace screen (required)
Use the following instructions to complete each step.
113134-01E 9
www.desatech.com
Screw
-
Fireplace Floor Assembly
Figure 6 - Removing Fireplace Floor
Screw
Flexible Gas Line
Assembly
INSTALLATION
Continued
ELECTRICAL CONNECTIONS FOR POWER CORD
This fire place operate s on 120 VAC, 60 Hz power. An electrical power cord is supplied with this unit.
For Mantel Installation
1. Determine from which side of the fireplace the power cord will exit. Locate the 1.5" diameter hole near the center of floor support bracket on appropriate side of lower cavity (see Figure 7).
2. Locate power cord. Remove wire tie or tape holding plug end of power cord.
3. Power cord has 2 plastic hole bushings threaded onto it. Route cordʼs 3-prong plug through the 1.5" diameter hole in appropriate floor support bracket.
4. Push first plastic bushing completely through hole. Squeeze bushing as needed to do this.
5. Install the second plastic bushing into the hole in the floor support bracket by snapping into place.
6. Route the 3-prong plug through the 1.5" hole in fireplace outer casing.
7. Install the first plastic bushing into this hole by snapping into place.
8. After you have connected to gas supply and checked your gas connections (see pages 14 and
15), plug power cord into any convenient 3­prong grounded wall receptacle near fireplace.
Hole in Floor Support Bracket
Bushings
Figure 7 - Routing Power Cord
Hole in Outer Casing
Power Cord
RELOCATING WALL SWITCH ASSEMBLY
Note: The decorative wall switch plate supplied is white. The wall switch plate may be painted to match your decor.
The push-button switch and decorative wall plate assembly supplied with your fireplace is pre-mounted at the factory in the lower cavity of the fireplace. You may relocate this wall switch assembly to a more convenient location such as the side of your mantel or directly onto the wall near the fireplace. To mount the wall switch assembly, you must first cut openings in the mantel or wall where the switch will be located.
Note: If you choose to relocate the wall switch as sembly, do so before final installation into a mantel or recessing into a wall. If you are installing an optional blower accessory, install it at the same time you relocate the wall switch assembly.
CAUTION: The wall switch assembly must never be mount­ed directly above the fireplace where heat may damage it. If you relocate wall switch assembly from lower fireplace cavity, it must be mounted either on side wall of mantel or on wall to side of fireplace.
For Recessed Installation
If fireplace is to be recessed into a wall (see Built-In Fireplace Installation, page 17), we recommend mounting wall switch assembly to left side of fireplace. The wall switch assembly should be mounted approximately 12" from left edge of fireplace and less than 60" from the floor. IMPORTANT: Do not locate wall switch assembly directly in front of wall stud - there must be room behind wall board for wires from switch. If you choose to locate wall switch assembly to right side of fireplace, the length of the cord restricts you to less than 6" from right edge of fireplace and less than 48" from floor.
-
For Recessed Installation
If an outlet is not installed in fireplace, install model GA3555 - Outlet Kit with Cover. This kit will supply a convenient 3-prong grounded electrical outlet for power. Refer to installation manual provided with this optional accessory for instructions on wiring. Note: A qualified installer must make all electrical connections.
10
www.desatech.com
113134-01E
4 3/4"
3 3/4"
3/8"
3/16"
3/4"
3/8" Diameter 2 Holes
INSTALLATION
Continued
For Mantel Installation
If fireplace is to be installed into a mantel, (see Conventional Fireplace Installation, page 16) the wall switch assembly may be mounted on either side of the mantel, facing to the side. Do not locate wall switch assembly anywhere on the front face of the mantel.
CAUTION: Be careful of gas lines and wiring when moving floor.
1. Determine the new location for the wall switch assembly. The wires attached to switch are six feet long.
2. Remove 2 screws securing plastic wall switch assembly to bracket in fireplace lower cavity. Save screws.
3. Remove wire tie holding coiled wire attached to wall switch assembly (see Figure 8).
4. Remove wall switch assembly from bracket.
5. Carefully pass wall switch assembly and cord through large elongated hole in rear of either left or right floor support bracket, depending on desired location of switch. Pass wall switch as sembly and cord through 1.5" diameter hole in side of fireplace outer casing (see Figure 9).
Burner Outlet Tube
Firebox Bottom
Wire Tie
6. Pull wall switch assembly and cord from fireplace making sure wall switch assembly will reach desired mounting location without straining cord assembly.
If you are mounting wall switch assembly to a wall, continue reading. If you are mounting your wall switch assembly to the side of the mantel, see page 12.
CAUTION: Do not apply ex-
cessive pull on cord.
Mounting Wall Switch Assembly to Wall for Recessed Fireplace
7. Create three openings on wall according to Template 1, page 37. This is best done by making a pattern to work with on your wall. Carefully cut page 37 from manual and tape paper template vertically onto wall at pre­ferred location. Pierce the paper at the centers of the 2 holes with a nail or sharp pencil, leaving a mark on the wall. Do the same at centers of the four circles near the corners of the rectangle.
8. Remove paper template from wall.
9. Drill 3/8" holes at each mark.
10. Using a straight edge and pencil, connect the
­outer edges of the 4 holes for the rectangle (see
Figure 10). This will give you cutting lines for the rectangle you will cut in the wall.
Template from Page 37 of This Manual
Tape
Cutting Lines
Gas Control Valve
Figure 8 - Relocating Wall Switch
Hole in Outer Casing
Wall Switch Assembly
Assembly
Make Marks at Centers of Holes
Hole in Floor Support Bracket
Wall Switch Assembly
Figure 9 - Routing Wall Switch Assembly
Through Fireplace for Relocation
113134-01E 11
www.desatech.com
Figure 10 - Using Template (Page 37) for
Wall Switch Assembly Installation
INSTALLATION
Continued
11. Using a keyhole saw, hack saw blade, drill, file or other suitable tool, carefully cut out the rectangular opening. Note: The corners of the rectangle may be round. IMPORTANT: Do not exceed the size of the rectangle on template.
12. From inside the recessed opening for the fireplace, carefully pass wall switch assembly through the rectangular opening to the outside of the wall.
13. Using wall anchors supplied in hardware pack age, fold wall anchor as shown in Figure 11.
14. Insert wall anchor, wings first, into hole. Tap anchor flush to wall.
15. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to “pop” open anchor wings. See Figure 12. IMPORTANT: Do not hammer key! For thick walls (over 1/2" thick), do not pop open wings.
16. Position wall switch assembly vertically over wall openings with decal lettering upright (see Figure 13).
Figure 11 - Folding Anchor
Figure 12 - Popping Open Anchor Wings
for Thin Walls
Opening in Wall or Mantel Wall
Wall Switch Assembly
Screws
17. Insert mounting screws, removed in step 2 of Relocating Wall Switch Assembly on pages 10 and 11, through holes in wall plate and into wall anchors.
18. Tighten screws until wall plate is firmly at tached to wall. Do not overtighten.
Mounting Wall Switch Assembly to Side of Mantel
7. Create three openings in the mantel wall ac cording to Template 2, page 37. This is best done by making a pattern to work with on the mantel. Carefully cut page 37 from manual
-
and tape paper template vertically onto mantel wall at preferred location. Pierce the paper at the centers of the 2 holes with a nail or sharp pencil, leaving a mark on the wall. Do the same at centers of the four circles near the corners of the rectangle.
8. Remove paper template from mantel wall.
9. Drill 1/8" pilot holes at each mark for top and bottom screw holes. Drill 3/8" holes at each mark for centers of four circles near corners of rectangle.
10. Using a straight edge and pencil, connect the outer edges of the 4 holes for the rectangle (see Figure 10, page 11). This will give you cutting lines for the rectangle you will cut in the mantel wall.
11. Using a keyhole saw, hack saw blade, drill, file or other suitable tool, carefully cut out the rectangular opening. Note: The corners of the rectangle may be round. IMPORTANT: Do not exceed the size of the rectangle on template.
12. Carefully pass wall switch assembly through rectangular opening from inside mantel (see Figure 13).
13. Position wall switch assembly vertically over opening with decal lettering upright. Make sure wires freely pass through wall without binding. Align holes in wall plate with 1/8” pilot holes in mantel wall.
14. Drive mounting screws, removed in step 2 of Relocating Wall Switch Assembly on pages 10 and 11, through wall plate holes and into pilot holes in mantel wall.
15. Tighten screws until wall switch assembly is firmly attached to mantel. Do not over tighten.
-
-
-
Figure 13 - Securing Wall Switch
Assembly
12
www.desatech.com
113134-01E
Loading...
+ 28 hidden pages