Parts Central...................................................... 27
WARNING: Improper
installation, adjustment,
alteration, service or main-
tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency or
the gas supplier.
WARNING: This is an
unvented gas-red heater.
It uses air (oxygen) from the
room in which it is installed.
Provisions for adequate
combustion and ventilation air must be provided.
Refer to Air for Combustion
and Ventilation section on
page 5 of this manual.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
This appliance may be in-
stalled in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohibited by local codes.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
WARNING: This product con-
tains and/or generates chemicals
known to the State of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate
or service this heater. Improper
use of this heater can cause seri-
ous injury or death from burns, re,
explosion, electrical shock and
carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the heater may not be
working properly. Get fresh air at once! Have
heater serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or
lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
www.desatech.com
124011-01B2
SAFETY
Continued
Natural and Propane/LP Gas: Natural and
Propane/LP gases are odorless. An odor-making agent is added to these gases. The odor
helps you detect a gas leak. However, the odor
added to the gas can fade. Gas may be present
even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this heater.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Surface of heater becomes very
hot when running heater. Keep
children and adults away from
hot surface to avoid burns or
clothing ignition. Heater will
remain hot for a time after shut-
down. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the same
room with heater.
Make sure grill guard is in place
before running heater.
www.desatech.com
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convert ble for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors.
3. This heater shall not be installed in a
bedroom or bathroom.
4. If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do
not use any phone in your building
• Immediately call your gas supplier from
a neighbor ’s phone. Follow the gas
supplier’s instructions
• If you cannot reach your gas supplier,
call the re department
5. Manual Control Models Always run
heater with plaque control knob at the 1,
2, 3 or 4 locked positions. Never set control knob between locked positions. Poor
combustion and higher levels of carbon
monoxide may result.
6.
This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff
system. The ODS shuts down the heater if
not enough fresh air is available. See Air for Combustion and Ventilation, page 5.
7. Keep all air openings in front and bottom
of heater clear and free of debris. This will
insure enough air for proper combustion.
8. If heater shuts off, do not relight until you
provide fresh, outside air. If heater keeps
shutting off, have it serviced.
9. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
10. Do not use heater if any part has been
under water. Immediately call a qualied
service technician to inspect the room
heater and to replace any part of the
control system and any gas control which
has been under water.
3124011-01B
SAFETY
Continued
11. Turn off and unplug heater and let cool
before servicing. Only a qualied service
person should service and repair heater.
12. Operating heater above elevations of
4,500 feet (1,371 m) could cause pilot
outage.
13. To prevent performance problems, do not
use propane/LP fuel tank of less than 100 bs.
(45 kg) capacity.
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
14. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off.
If heated, the vapors from these products
may create a white powder residue within
burner box or on adjacent walls or furniture.
15. Provide adequate clearances around air
openings.
State of Massachusetts: The installation
must be made by a licensed plumber or
gas tter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are proh bited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
PRODUCT
IDENTIFICATION
Control Knob
Ignitor Button
Grill
Guard
Plaque
Front Panel
Heater Cabinet
Figure 1 - Vent-Free Gas Heater
(actual heater may vary from illustration)
www.desatech.com
UNPACkING
1. Remove heater from carton.
2. Remove all protective packaging applied
to heater for shipment.
3. Check heater for any shipping damage.
If heater is damaged, promptly return to
dealer where you bought heater or call
DESA Heating, LLC at 1-866-672-6040.
PRODUCT FEATURES
SAFETY DEvICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
IGNITION SYSTEM
Some models are equipped with a piezo
ignitor that requires no matches, batteries or
other sources to light heater.
Other heaters are equipped with an electronic
ignitor to light heater fuel supply.
THERMOSTATIC HEAT CONTROL
(Thermostat Models Only)
Thermostat models have a thermostat sensing bulb and a control valve. This results in the
greatest heater comfort. This can also result
in lower gas bills.
124011-01B4
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or
space unless the required volume of indoor combustion air
is provided by the method described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code, or
applicable local codes. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROvIDING ADEQUATE
vENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the outside
atmosphere have a continuous water
vapor retarder with a rating of one perm
-11
(6 x 10
openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to areas
such as joints around window and door
frames, between sole plates and oors,
between wall-ceiling joints, between wall
panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of these three criteria,
you must provide additional fresh air. See
Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location, page 6.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the aggregate input rating of all appliances installed
in that space. Rooms communicating directly
with the space in which the appliances are
installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
kg per pa-sec-m2) or less with
3
per kw) of the aggregate
www.desatech.com
5124011-01B
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (6.1 m) (length) x 16
ft. (4.88 m) (wid h) x 8 ft. (2.44 m) (ceiling height)
= 2560 cu. ft. (72.49 m
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (72.49 m3) (volume of
space) x 20 = 51,200 (maximum Btu/Hr the
space can support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free heater __________Btu/Hr
Gas water heater* __________Btu/Hr
Gas furnace __________Btu/Hr
Vented gas heater __________Btu/Hr
Gas replace logs __________Btu/Hr
Other gas appliances*+ __________ Btu/Hr
Total = _________Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr
Vent-free heater + _________ Btu/Hr
Total = _________ Btu/Hr
4.
Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_______ Btu/Hr (maximum can support) _______ Btu/Hr (actual amount used)Example: 51,200 Btu/Hr (maximum the
60,000 Btu/Hr (actual amount of
space can support)
Btu/Hr used)
3
) (volume of space)
40,000
20,000
60,000
The space in the above example is a conned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides
an unconned space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside
Building.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
vENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" (30.5
cm) of the ceiling and one within 12" (30.5 cm)
of the oor on the wall connecting the two
spaces (see options 1 and 2, Figure 2, page
7). You can also remove door into adjoining
room (see option 3, Figure 2, page 7). Follow
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
www.desatech.com
124011-01B6
AIR FOR COMBUSTION AND VENTILATION
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills into
Adjoining
Room,
Option 1
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
T o
Crawl
Space
T o A ttic
Continued
ing and one within 12" (30.5 cm) of the oor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the Na-
tional Fuel Gas Code, ANSI Z223.1/NFPA 54,
Air for Combustion and Ventilation for required
size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 2 - Ventilation Air from Inside
Building
ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills
or ducts. You must provide two permanent
openings: one within 12" (30.5 cm) of the ceil-
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualied ser-
vice person must install heater.
Follow all local codes.
CHECK GAS TYPE
Use only the correct type of gas (natural or
propane/LP). If your gas supply is not the
correct gas type, do not install heater. Call
dealer where you bought heater for proper
type heater.
www.desatech.com
Figure 3 - Ventilation Air from Outdoors
WARNING: This appliance is
equipped for either natural gas or
propane/LP gas but not both. Gas
type is indicated on the rating plate.
Field conversion is not permitted.
INSTALLATION ITEMS
Before installing heater, make sure you have
the items listed below.
• for propane/LP gas, external regulator
(supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection*
• hardware packet (included)
- wall anchor (4) 095112-02
- red key (1) 095116-01
- pan head screw, black (4) 097403-02
- nylon spacer (2) 099064-02
- clamp (1) 099123-01
- Phillips head screw, silver (4) 100159-02
* A CSA design-certied equipment shutoff
valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. The optional
CSA design-certied equipment shutoff valve
can be purchased from your dealer.
7124011-01B
INSTALLATION
Minimum
From
Sides Of
Heater
2" (5.1 cm)
FLOOR
CEILING
36"
(91.5 cm)
Minimum
Minimum To
Top Surface
Of Carpeting,
Tile Or Other
Combustible
Material
Left
Side
Right
Side
10" (25.4 cm)
36"
(91.5 cm)
Continued
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING: Maintain the
minimum clearances shown
in Figure 4. If you can, provide
greater clearances from oor,
ceiling and joining wall.
You can locate heater on oor, away from
a wall. An optional oor mounting stand is
needed. Purchase the oor mounting stand
from your dealer. See Accessories, page 26,
if stand is not included with your heater.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable
objects are less than 36"
(91.5 cm) from the front, top
or sides of the heater
• as a replace insert
• in high trafc areas
• in windy or drafty areas
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventila-tion, page 5. If high humidity is experienced,
a dehumidier may be used to help lower the
water vapor content in the air.
For convenience and efciency, install heater
• where there is easy access for operation,
inspection and service
• in coldest part of room
If not included with your heater, an optional fan
kit is available from your dealer. See Acces-sories, page 26. If planning to use fan, locate
heater near an electrical outlet (see page 16).
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must
be at least 18" (45.7 cm) above
oor
• locate heater where moving
vehicle will not hit it
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next
to vinyl or cloth wall coverings or
operating heater where impurities
(such as, but not limited to, tobacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
Figure 4 - Mounting Clearances As
Viewed From Front of Heater
THERMOSTAT SENSING BULB
(Thermostat Models Only)
The thermostat sensing bulb has been placed
below the heater.
1. Place clamp on thermostat sensing bulb
as shown in Figure 5. Clamp is provided
in hardware package.
2.
Snap clamp into upper mounting hole as
shown in Figure 5. Mounting hole is located
on lower left edge on back of heater. Make
sure thermostat sensing bulb is pointing up.
Figure 5 - Attaching Thermostat Sensing
www.desatech.com
Thermostat
Sensing
Bulb
Clamp
Bulb
124011-01B8
16"
Min.
14"
12"
Min.
Adjoining Wall
14"
Adjoining Wall
Only Insert Mounting
Screws Through Last
Hole On Each End
Only Insert Mounting
Screws Through Last
Hole On Each End
Floor
Floor
19 3/4"
Min.
19 3/4"
Min.
INSTALLATION
Continued
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater carton. Remove mounting bracket from heater carton.
Figure 6 - Mounting Bracket
Removing Front Panel Of Heater
1. Remove the four painted screws, two on
each side of front panel.
2.
Pull bottom of front panel forward, then out.
3.
Remove any remaining packaging materials.
Front Panel
Screw
Marking Screw Locations
1. Tape mounting bracket to wall where
heater will be located. Make sure mounting bracket is level.
WARNING: Maintain minimum
clearances shown in Figure 8. If
you can, provide greater clearances from oor and joining wall.
2.
Mark screw locations on wall (see Figure 8).
Note: Only mark last hole on each end of
mounting bracket. Insert mounting screws
through these holes only.
3. Remove tape and mounting bracket from
wall.
3 Plaque Heater
Figure 7 - Removing Front Panel Of Heater
(actual heater may vary from illustration)
Methods For Attaching Mounting Bracket
To Wall
Only use last hole on each end of mounting
bracket to attach bracket to wall. These two
holes are 14" (35.6 cm) apart from their centers. Attach mounting bracket to wall in one
of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method pro-
vides the strongest hold. Insert mounting
screws through mounting bracket and into
wall studs.
Attaching to Wall Anchor: This method allows you to attach mounting bracket to hollow
walls (wall areas between studs) or to solid
walls (concrete or masonry).
Decide which method better suits your needs.
Either method will provide a secure hold for
the mounting bracket.
Figure 8 - Mounting Bracket Clearances
Attaching Mounting Bracket To Wall
Note: Wall anchors, mounting screws and
spacers are in hardware package. The hardware package is provided with heater.
Attaching To Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64"
drill bit.
2. Place mounting bracket onto wall. Line
up last hole on each end of bracket with
holes drilled in wall.
3. Insert mounting screws through bracket
and into wall studs.
4. Tighten screws until mounting bracket is
rmly fastened to wall studs.
www.desatech.com
4 and 5 Plaque Heaters
9124011-01B
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.