Desa DVFH34P, DVFH34 User Manual

DIRECT-VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
NATURAL GAS MODEL DVFH34
PROPANE/LP GAS MODEL DVFH34P
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assis­tance or additional information con­sult a qualified installer, service agency, or the gas supplier.
— Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
— This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
Save this manual for future reference.
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this fireplace. Im­proper use of this fireplace can cause serious injury or death from burns, fire, explosions, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This fireplace is a vented product. This fireplace will not produce any gas leakage into your home if properly installed. This fireplace must be properly installed by a qualified service person. The glass door must be properly seated and sealed. If this unit is not properly installed by a qualified service person with glass door properly seated and sealed, gas leakage can occur.
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have fireplace inspected and ser­viced by a qualified service person. Some people are more affected by carbon monox­ide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odor-making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
2. For propane/LP fireplace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent perfor­mance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier's instructions
• if you cannot reach you gas supplier ,
call the fire department.
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or
other flammable objects are less than 42" from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
5. This fireplace reaches high tempera­tures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
6. Carefully supervise young children when they are in the room with fireplace.
7. Do not modify this fireplace under any circumstances. Any parts removed for servicing must be replaced prior to op­erating fireplace.
8. Turn fireplace off and let cool before servicing, installing, or repairing. Only a qualified service person should in­stall, service, or repair this fireplace. Have fireplace inspected annually by a qualified service person.
9. You must keep control compartments, burners, and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning fireplace.
10. Have venting system inspected annu­ally by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Mainte- nance, page 28.
11. Keep the area around your fireplace clear of combustible materials, gaso­line, and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace.
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fire­place nameplate.
14. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electri-
cal Code, ANS/NFPA 70, or the Cana­dian Electrical Code, CSA C22.1.
15. Do not obstruct the flow of combus­tion and ventilation air in any way . Pro­vide adequate clearances around air openings into the combustion chamber along with adequate accessibility clear­ance for servicing and proper operation.
16. Do not install fireplace directly on car ­peting, vinyl tile, or any combustible material other than wood. The fireplace must set on a metal or wood panel ex­tending the full width and depth of the fireplace.
17. Do not use fireplace if any part has been exposed to or under water. Immediately call a qualified service person to ar­range for replacement of the unit.
18. Do not operate fireplace if any log is broken.
19. Do not use a blower insert, heat ex­changer insert, or other accessory not approved for use with this fireplace.
20. Do not operate fireplace with glass door removed, cracked, or broken.
2
106394
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Top Louver Panel
Nailing Flange
Glass Door Assembly
Piezo Ignitor
Valve
Lower Louver Panel
Glowing Embers
Blower Adjustment (Optional Installation)
Figure 1 - FMI Direct-Vent Fireplace DVFH Series
Vent Opening
Standoff
Log Set
Lava Rock
Grate Assembly
ON/OFF/REMOTE Switch (Optional Installation)
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code, ANS Z223.1, also known as NFPA 54* (USA) or the current CAN/CGA-B149[.1 or .2] Installation Codes (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
OPERATION
This direct-vent fireplace is clean burning and vents easily through outside walls or vertically using outside air for combustion. Heat is generated by both realistic flames and glowing embers. When used without the blower accessory, the fireplace requires no electricity making it ideal for emergency backup heat.
PIEZO IGNITOR
This fireplace has a piezo ignitor. This sys­tem requires no matches, batteries, or other sources to light fireplace.
106394
GLOSSARY OF TERMS
Chase - A boxlike enclosure to protect
venting from the elements when the venting run is on the outside of a structure.
Mastic - A pliable sealant for use around the
vent terminal.
Snorkel Termination - A box that raises the
horizontal termination above ground level clearances.
Vent Terminal - Mounted on an outside
wall or roof to separate the inlet and outlet of the vent system and protect it from weather.
Vinyl Siding Standoff - A metal box that
separates the vent cap from vinyl siding.
Wall Thimble/Firestop - A metal plate used
to secure the vent pipe when it passes through a wall or ceiling.
3
DVFH34, DVFH34P
34 3/4"
34
1
/4"
20" Vertical Termination 19" Horizontal Termination
D
RW
FW
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efficient loca­tion for your FMI direct-vent fireplace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a loca­tion where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common loca­tions. Read all venting information in this manual. Be aware of all restrictions and precautions before deciding the exact loca­tion for your fireplace.
When deciding the location of your fire­place, follow these rules:
1. Do not connect this fireplace to a chim­ney flue serving a separate solid-fuel burning fireplace or appliance.
2. Due to high temperatures, do not lo­cate this fireplace in high traffic areas or near furniture or draperies.
3. Proper clearances must be maintained.
4. If your fireplace is to be installed di­rectly on carpeting, vinyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace. See Figure 3.
CLEARANCES
Minimum clearances to combustibles for the fireplace are as follows:
Back, and sides 0"/mm Perpendicular walls 6" (152mm) Floor 0"/mm Ceiling to louver opening 42" (1067mm) Front 36" (914mm) Top of Standoffs 0"/mm
See General Venting on pages 5 and 6 for specific venting clearances.
FRAMING AND FINISHING
Figures 4 and 5 show typical framing of this fireplace. Figure 6 on page 5 shows framing for corner installation. All minimum clear­ances must be met. Do not install fireplace directly on carpeting, vinyl tile, or any com­bustible material other than wood. The fire­place must set on a metal or wood panel extending the full width and depth of the fireplace.
See Accessories on pages 36 and 37 for mantel kits available for this fireplace. If you are using a separate combustible mantel piece, refer to Figure 7 on page 5 for proper installation height. You can install noncom­bustible mantels at any height above the fireplace. may discolor!
Note:
Noncombustible mantels
Must maintain a minimum 1" clearance to combustibles
34
"
20"
5/8" for drywall facing
Figure 5 - Framing Clearances for Typical Fireplace Installation
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
Fireplace size D x FW x RW
34" 18 1/2" 34 3/8" 14"
Figure 3 - Fireplace Bottom Dimensions
Figure 4 - Framing Clearances for Installation Against an Exterior Wall
4
106394
OWNER’S MANUAL
PRE-INSTALLATION PREPARATION
Continued
13"
29"
5
/8"
12
34
58"
Figure 6 - Framing Clearances for Corner Installation
Note:
There must be a minimum clear­ance of 18" above top of louver opening when installing a television or entertainment center above the fireplace.
Ref. Mantel Depth Ref. Mantel from Top
1 14" (356mm) A 16" (406mm) 2 12" (305mm) B 14" (356mm) 3 10" (254mm) C 12" (305mm) 4 8" (203mm) D 10" (254mm) 5 6" (152mm) E 8" (203mm) 6 4" (101mm) F 6" (152mm) 7 2" (51mm) G 4" (101mm)
A
B
C
of Louver Opening
1
9
/4"
3
/8"
1
35
/16"
D
E
F
G
Top of Louver Opening
GENERAL VENTING
These models are approved for use with FMI 7" direct-vent pipe components and terminations.
Your fireplace is approved to be vented either through the side wall, or vertically using the following guidelines:
• Only use FMI venting components or kits
41"
Nailing Tabs
1 2
3
4
5 6 7
Wall
specifically approved for this fireplace.
• Minimum clearance between vent pipes and combustible materials is 1" (25 mm), except where stated otherwise.
• Combustible material may be flush with the top front of fireplace with a maxi­mum thickness of 3/4".
• Do not recess venting terminals into a wall or siding.
• If exterior wall is vinyl, you must use a vinyl siding standoff.
• Install horizontal venting with a 1/4" rise for every 12" of run toward the termination.
• You may paint the vent terminal with 450ºF (232ºC) heat-resistant paint to co­ordinate with the exterior finish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks, or utility buildings within 24" from the front of the termination cap.
• Do not locate termination cap where ex­cessive snow or ice build up may occur. Be sure to clear vent termination area af­ter snow falls to prevent accidental block­age of venting system. When using snow blowers, do not direct snow towards vent termination area.
Location of Vent Termination
When locating vent termination, it is impor­tant to observe the minimum clearances shown in Figure 8, page 6. You will avoid extra framing by positioning your fireplace against an already existing framing mem­ber. The sides of the fireplace may be posi­tioned directly against combustible walls.
*Check with local codes or with the current
CAN/CGA B149 [.1 or .2] Installation Codes
for Canada or the USA Installations follow the current National Fuel Gas Code, ANS Z223.1, also known as NFPA 54.
Figure 7 - Clearances for Combustible Mantels
106394
Continued
5
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
C
Fixed
Closed
Openable
B
Continued
V
Openable
B
AIR SUPPLY INLET
X
B
Fixed
Closed
B
J
V
A
X
I = clearance to service regulator vent outlet [*72 inches (1829mm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (305mm) minimum]
K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84 inches (2133mm) minimum] M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡] N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm)
GENERAL VENTING
D
E
V
B
L
F
V
TERMINATION CAP
V
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (305mm) minimum]
B = clearance to window or door that may be opened
[12 inches (305mm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(305mm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum] E = clearance to unventilated soffit [12 inches (305mm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within
36 inches (914mm) horizontally from the center-line of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow
the current Note: Local codes or regulations may require different clearances
National Fuel Gas Code, ANS Z223.1
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
Outside Corner Recessed Location
N
H
V
G
G
GAS METER RESTRICTED AREA
I
M
V
(TERMINATION PROHIBITED)
N
G
V
G
X
K
V
A
A
Balcony with No Side Wall
G = Combustible 24" (610mm)
Noncombustible 18" (457mm)
V
G V
A = 6" (152mm)
V
Balcony with Perpendicular Side Wall
H
Combustible & Noncombustible H = 24" (610mm) J = 20" (508mm)
Figure 8 - Minimum Clearances for Vent Terminations
B
V
J
B = 6" (152mm)
6
D
C
V
C = Maximum depth of 48" (1219mm) for
recessed location
D = Minimum width for back wall of
recessed location ­Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in
recessed location­Combustible - 6" (152mm) Noncombustible - 2" (51mm)
C
E
106394
OWNER’S MANUAL
VENTING INSTALLATION
WARNING: Read all instruc­tions completely and thoroughly before attempting installation. Fail­ure to do so could result in serious injury, property damage or loss of life. Operation of improperly in­stalled and maintained venting sys­tem could result in serious injury, property damage or loss of life.
WARNING: Seal all vent con-
nections. Seal only the outer pipe connections with high tempera­ture silicone (600°F/316° C). Be­fore joining elbows and pipes, ap­ply a bead of high temperature silicone sealant (GE RTV 106/ Loctite RTV 81585) to the male end of the elbow or pipe. High tem­perature silicone must also be used to re-seal any connections after maintenance to venting system.
NOTICE: Failure to follow these instructions will void the warranty.
INSTALLATION PRECAUTIONS
Consult local building codes before begin­ning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified service person should in­stall venting system. The installer must fol­low these safety rules:
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the war­ranty on your venting system:
• Installation of any damaged venting component
• Unauthorized modification of the vent­ing system
• Installation of any component part not manufactured or approved by DESA International
• Installation other than as instructed by these instructions
WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning ap­pliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING: Horizontal sec­tions of this vent system require a minimum clearance of 2" from the top of the pipe and 1" minimum to the sides and bottom. 1 1/2" clear­ance is required where termina­tion penetrates a combustible wall. Vertical sections of this sys­tem require a minimum of 1" clear­ance to combustible materials on all sides of the pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal T ermination
• Vertical Termination It is important to select the proper length of vent
pipe for the type of termination you choose. It is also important to note the wall thickness.
For Horizontal Termination: Select the
amount of vertical rise desired. The horizon­tal run of venting must have 1/4" rise for every 12" of run towards the termination.
WARNING: Never run the vent downward as this may cause ex­cessive temperatures which could cause a fire.
You may use one or two 90° elbows in this vent configuration. See Horizontal Termina- tion Configurations on pages 10 and 11.
For Vertical Termination: Measure the dis-
tance from the fireplace flue outlet to the ceiling. Add the ceiling thickness, the verti­cal rise in an attic or second story, and allow for sufficient vent height above the roofline.
You may use one or two 90° elbows in this vent configuration. See Vertical Termination Configurations on pages 13 and 14.
Note:
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows.
For two-story applications, firestops are re­quired at each floor level. If an offset is needed in the attic, additional pipe and el­bows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase, below.
Your FMI direct-vent fireplace has been tested for a minimum 3' rise with a maxi­mum 10" wall thickness. The maximum horizontal run is 20' with 8' vertical rise (see Installation for Horizontal Termination, page 8). The maximum vertical run is 30' (see Installation for Vertical Termination, page 12).
It is very important that the venting system maintain its balance between the combus­tion air intake and the flue gas exhaust. Certain limitations apply to vent configura­tions and must be strictly followed.
Installing Vent System in a Chase
A chase is a vertical boxlike structure built to enclose venting that runs along the out­side of a building. A chase is not required for such venting.
NOTICE: Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the re­quirements of local building codes. You must follow all local building codes .
Note:
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im­portant in cold climates. Minimum clear­ance between vent pipes and combustible materials such as insulation is 1".
After framing the chase (see Framing and Finishing on page 4) install the vent system by following the installation instructions.
Continued
106394
7
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
VENTING INSTALLATION
Continued
INSTALLATION FOR HORIZONTAL TERMINATION
1. Determine the route your horizontal venting will take. of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed.
WARNING: Do not recess vent
terminal into a wall or siding.
Snorkel terminations are available for terminations requiring a vertical rise on the exterior of the building (see Figures 9 and 10). Follow the same installation procedures as used for standard horizon­tal terminations. If installing the snor­kel termination below grade (basement applications), you must provide proper drainage to prevent water from entering the snorkel termination (see Figure 10). Do not back fill around the snorkel ter­mination.
2. Rigid vent pipes and fittings have spe­cial twist-lock connections. Assemble the desired combination of pipe and el­bows to the appliance adaptor with pipe seams oriented towards the wall or floor.
Twist-lock Procedure: The female ends of the pipes and fittings have four locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes and fit­tings. (All connections must be sealed with high temperature silicone sealant as specified in the second warning state­ment on page 7.) Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. See Figure 11, page 9. must be supported every three feet. Use wall straps for this purpose.
Note:
Note:
The location
Horizontal runs of vent
Snorkel
12" Minimum
Figure 9 - Snorkel Termination
Snorkel
12" Minimum
Adequate Drainage
Figure 10 - Snorkel Termination with Drainage Pipe
8
106394
OWNER’S MANUAL
VENTING INSTALLATION
Continued
3. Attach vent pipe assembly to the fire­place. Set fireplace in front of it’s per ­manent location to insure minimum clearances. Mark the wall for a 10" square hole (for noncombustible ma­terial such as masonry block or con­crete, a 7 1/2" diameter hole is accept­able). See Figure 12. The center of the hole should line up with the center­line of the horizontal rigid vent pipe. Cut a 10"x10" (254mm x 254mm) square hole through combustible ex­terior wall (7 1/2" [190mm] diameter hole if noncombustible). Frame as nec­essary (see Figure 12).
Female Locking Lugs
Male Slots
4. Apply a bead of non-hardening mastic around the outside edge of the vent cap. Position the vent cap in the center of the 7 1/2" or 10" hole on the exterior wall with the arrow on the vent cap pointing up. Insure proper clearance of 1" to combustibles is maintained. At­tach the vent cap with four wood screws supplied (see Figure 13).
Note
: Re­place the wood screws with appropri­ate fasteners for stucco, brick, concrete, or other types of siding.
WARNING: Do not recess vent termination in to any wall. This will cause a fire hazard.
For vinyl siding, stucco, or wood ex­terior use vinyl siding standoffs be­tween vent cap and exterior wall. The vinyl siding standoff prevents exces­sive heat from melting the vinyl sid­ing material. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of the standoff in­stead of the vent cap assembly. Use wood screws provided to attach the standoff. See Figure 14.
5. Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap (see Figure 15).
6. Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 1 1/4". Apply silicone to the outer pipe connection. Fasten all vent connections with screws provided. Refer to Fir eplace Installation on page 16 for instructions on securing unit to framing or floor.
7. Slide the wall thimble against the inte­rior wall surface and attach with screws provided (see Figure 15).
Cut Vinyl Siding Away to Fit Standoff
Wood Screw
Standoff
UP
Nut
Apply Mastic to All Four Sides
Figure 14 - Installing Vinyl Siding Standoff
Vent Cap
Bolt
Figure 11 - Rigid Vent Pipe Connections
Vent Opening
Combustible Wall
10"
(254mm)
10"
(254mm)
(Framing
Vent Opening
Noncombustible Wall
7 1/2"
(190mm)
Figure 12 - Vent Opening Requirements
106394
Detail)
Apply Mastic to All Four Sides
UP
Wood Screw
Vent Cap
Figure 13 - Installing Horizontal Vent Cap
9
Interior Wall Surface
Wall Thimble
Vent Cap (Horizontal Termination)
Figure 15 - Connecting Vent Cap with Horizontal Vent Pipe
Screw
Horizontal Vent Pipe
Continued
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
VENTING INSTALLATION
Continued
Horizontal Termination Configurations
Figures 16 through 19 show different con­figurations for venting with horizontal ter­mination. Each figure includes a chart with vertical minimum/maximum and horizon­tal maximum dimensions which must be met. Seal all connections with high tem­perature silicone sealant (outer pipe only) as specified in the second warning statement on page 7. All horizontal terminations re­quire 1/4" rise per 12" of horizontal run.
FD60 60˚ Starter/ Adapter Required
UP
Horizontal Venting
Vertical (V) Horizontal (H)
37" min. 10" max.
Figure 16 - Horizontal Termination Configuration for Rigid Venting
UP
FD30 30˚ Starter/ Adapter Required
Horizontal Venting
Vertical (V) Horizontal (H)
44" min. 29" max.
(30° and 90° only, no vertical pipe)
55" min. 41" max.
(30° elbow, 1' vertical pipe, 90° elbow)
67" min. 60" max. 79" min. 84" max. 96" min. 20' max.
Note:
This configuration for use with
corner installation.
Figure 17 - Horizontal Termination Configuration for Rigid Venting Using One
°
Elbow
90
10
106394
VENTING INSTALLATION
Continued
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) Horizontal (H1) +
Horizontal (H2)
5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' min. 20' max.
20' max. 8' max. 20' max.
OWNER’S MANUAL
FD60 60˚ Starter/ Adapter Required
UP
Figure 18 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) +
Horizontal (H2)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
20' max. 20' max.
FD30 30˚ Starter/ Adapter Required
Figure 19 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows with Termination at 90° with Fireplace
Continued
106394
11
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
VENTING INSTALLATION
Continued
INSTALLATION FOR VERTICAL TERMINATION
Note:
Vertical restrictors must be installed
in all vertical installations.
1. Determine the route your vertical vent­ing will take. If ceiling joists, roof rafters, or other framing will obstruct the venting system, consider an offset (see Figure 20) to avoid cutting load bearing members. attention to these installation instruc­tions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum verti­cal rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shown in Figure 8 on page 6.
2. Set the fireplace in desired location. Drop a plumb line down from the ceil­ing to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locating hole in the ceil­ing. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.
Note:
Pay special
Roof Flashing
Flat Ceiling Installation
1. Cut a 10" square hole in the ceiling us­ing the locating hole as a center point. The opening should be framed to 10"x10" (254mm x 254mm) inside di­mensions, as shown in Figure 12 on page 9 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceil­ing or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 21).
2. Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. All connections must be sealed with high temperature silicone sealant as specified in the second warning state­ment on page 7. Be sure all pipe and elbow connections are fully twist­locked (see Figure 11, page 9).
3. Cut a hole in the roof using the locating hole as a center point. (Cover any ex­posed open vent pipes before cutting hole in roof.) The 10"x10" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combus­tible materials. Frame the opening as shown in Figure 12, page 9.
If area above is a room, install firestop above framed hole.
4. Connect a section of pipe and extend up through the hole.
Note:
If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 20). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less re­striction to the flow of the flue gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure
20. There must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the mini­mum building code requirements de­scribed in Figure 8 on page 6. must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar fac­tors may cause poor draft or down-draft­ing in high winds. Increasing the vent height may solve this problem.
7. Twist-lock the vent cap onto the last section of vent pipe and seal outer pipe connection with high temperature sili­cone sealant as specified in the second warning statement on page 7.
Note:
If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclo­sure with standard construction material. Make sure and meet the minimum allowable clear­ances to combustibles. Do not fill any of the required air spaces with insulation.
Note
: Y ou
Wall Strap
45° Elbow
Ceiling Firestop
Figure 20 - Offset with Wall Strap and
°
Elbows Figure 21 - Installing Firestop
45
If area above is not a room, install firestop below framed hole.
12
Cathedral Ceiling Installation
1. Remove shingles or other roof cover-
ing as necessary to cut the rectangular hole for the support box. Mark the out­line of the cathedral ceiling support box on the roof sheathing using the locat­ing hole as a center point.
2. Cut the hole 1/8" larger than the sup-
port box outline (see Figure 22, page 13).
106394
OWNER’S MANUAL
VENTING INSTALLATION
Continued
3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling (see Figure 22). Align the support box vertically and horizontally using a level. T emporarily tack the support box in place through the inside walls and into the roof sheathing.
4. Using tin snips, cut the support box from the top corners down to the roofline and fold the resulting flaps over the roof sheathing (see Figure 23). Apply a bead of non-hardening mastic around the top edges of the support box to make a seal between the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be in­side of the support box.
5. Complete the cathedral ceiling instal­lation by following the same proce­dures outlined in steps 2 through 7 for Flat Ceiling Installation, page 12
.
Vertical Termination Configurations
Figures 24 through 27 show four different configurations for vertical termination. All connections must be sealed with high temperature silicone sealant as specified in the second warning statement on page 7.
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) +
Horizontal (H2)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max.
FD60 60˚ Starter/ Adapter Required
8' min. 8' max.
20' max. 8' max.
Note:
Install restrictor into 4" collar of stove as shown.
Level
Cathedral ceiling support box
2" minimum below
finished ceiling
Cut hole 1/8" larger than support box when projected onto roofline
Figure 22 - Cathedral Ceiling Support Box Installation
Non-hardening Mastic under all edges of support box before nailing
Figure 23 - Installed Cathedral Ceiling Support Box
Figure 24 - Vertical Rigid Venting Configuration Using Two 90° Elbows with Two Horizontal Runs
Note:
Install restrictor into 4"
collar of stove as shown.
Venting with One 90° Elbow
FD60 60˚ Starter/ Adapter Required
Vertical (V) Horizontal (H)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max.
20' max. 8' max.
Figure 25 - Vertical Rigid Venting Configuration Using One 90° Elbow
Continued
106394
13
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
VENTING INSTALLATION
Continued
FD30 30˚ Starter/ Adapter Required
Vertical (V1) Horizontal (H)
Note:
Vertical (V1) + Vertical (V2) = 20' max.
Install restrictor
Note:
into 4" collar of stove as shown.
Venting with Two 90° Elbows
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
Note:
Install restrictor into 4" collar of stove as shown.
FD30 30˚ Starter/ Adapter Required
Vertical V enting
V = 40' max.
Figure 27 - Vertical Rigid Venting Configuration With No Horizontal Run
Figure 26 - Vertical Rigid Venting Configuration Using Two 90° Elbows
14
106394
OWNER’S MANUAL
VENTING INSTALLATION
Continued
HIGH ALTITUDE INSTALLATION
Your FMI direct-vent fireplace has been AGA tested and approved for elevations from 0-2000 feet and CGA certified for elevations from 0-4500 feet.
When installing this fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Re­duce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.
When installing this fireplace at an eleva­tion above 4500 feet (in Canada), check with local authorities.
Consult your local gas company to help de­termine the proper orifice for your location.
For assistance with any high altitude instal­lation contact DESA International’s Tech­nical Services Department at 1-800-DESA­LOG (1-800-337-2564).
PARTS LISTS FOR VENTING KITS AND COMPONENTS
FMI Rigid Venting
Number Description
FD30 30˚ Starter/Adapter (6 5/8" to 7")
6 per box
FD60 60˚ Starter/Adaptor (6 5/8" to 7")
6 per box
F7030 7" to 12" Adjustable pipe length
6 per box
D1031 7" to 12" Adjustable pipe length
1 per box
D3050 Vertical restrictor
6 per box
01806 Basic vertical kit
Adjustable flashing - storm collar, vertical cap
01807 48" Pipe length
6 per box
01808 36" Pipe length
6 per box
01809 24" Pipe length
6 per box
01810 12" Pipe length
6 per box
01811 6" Pipe length
6 per box
01812 17" to 24" adjustable pipe length
6 per box
01813 45˚ Elbow
6 per box
01814 90˚ Elbow
6 per box
01817 Wall firestop
6 per box
01818 Adjustable flashing (0/12-8/12)
6 per box
01819 Steep pitch flashing (12/12
6 per box
01820 Vinyl/Stucco siding standoff 01821 Firestop plate
6 per box
01822 Vertical termination cap
01823 Horizontal round termination
cap
Number Description
01825 36" Snorkel termination 01826 14" Snorkel termination 01827 Termination/high
rise/horizontal
01828 Wall strap
6 per box
01829 Storm collar
6 per box
01797 Vertical round high wind
termination
01799 Horizontal square high wind
termination
106394
15
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE INSTALLATION
NOTICE: This fireplace is in­tended for use as supplemental heat. Use this fireplace along with your primary heating system. Do not install this fireplace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using fireplace. This will help circulate the heat through­out the house. In the event of a power outage, you can use this fireplace as a heat source.
WARNING: A qualified ser­vice person must install fireplace. Follow all local codes.
CAUTION: This fireplace cre­ates warm air currents. These cur­rents move heat to wall surfaces next to fireplace. Installing fire­place next to vinyl or cloth wall coverings or operating fireplace where impurities (such as to­bacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls.
Note:
Your fireplace is designed to be used in zero clearance installations. Wall or fram­ing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing material. See framing details on page 4.
Place the fireplace into position and shim with noncombustible material if needed. Nail the side flanges to the framing to secure the unit in place. There are two floor brack­ets included with each unit. Use these as an alternative method of securing the fireplace.
IMPORTANT:
before securing. If fireplace is not level it will not work properly.
Make sure fireplace is level
CHECK GAS TYPE
Use proper gas type for the fireplace unit you are installing. If you have conflicting gas types, do not install fireplace. See re­tailer where you purchased the fireplace for proper fireplace according to your gas type.
INSTALLING OPTIONAL BLOWER ACCESSORY
NOTICE: If installing blower in an existing fireplace with gas con­nections, shut off gas supply and disconnect heater from gas sup­ply. Contact a qualified service person to do this.
Attaching Thermal Switch to DA3610TA Thermostatically­Controlled Blower
When installing the DA3610T thermostati­cally-controlled blower accessory, you must first secure the thermal switch to the blower.
1. Remove the two hex head screws on the blower assembly as shown in Figure 28.
2. Place the green wire between the bot­tom hole on the thermal switch bracket and the bottom hole on the blower as­sembly. Insert one of the hex screws into all three pieces and tighten.
3. Insert the top screw through the ther­mal switch bracket and into the blower assembly. Tighten screw.
4. Connect the blue wire on the blower assembly to the right side of the ther­mal switch.
5. Connect the black wire to the left side of the thermal switch.
Thermal Switch with Bracket
Black Wire
Hex Head Screws
Figure 28 - Attaching Thermal Switch to DA3610TA Thermostatically-Controlled Blower Accessory
White Wire
Blue Wire
Installing GA3700/DA3610TA Blowers
IMPORTANT
bly and grate/burner assembly are not shown in Figures 29 through 32, page 17. They will, however, be in your fireplace when you are installing the blower. Also for clarity the firebox is shown with dotted lines.
1. Open lower louver panel or remove for easier access.
2. Place the blower against the lower rear wall of firebox outer wrapper with the exhaust port directed upward. Align the holes in the top mounting tabs of blower with holes in wall of wrapper (see Figure 29, page 17). Using the two screws provided, mount blower and tighten screws securely.
Note:
thermal switch is comfortably between the back of the firebox and the blower as shown in Figure 30, page 17.
3. Be sure to securely attach all wire ter­minals to terminals on blower motor (and thermal switch where applicable) and that the screw retaining the green ground wire is tight.
4. Remove screws securing the switch plate to the bottom of the firebox and set aside.
5. Place speed control against back of this plate and push the plastic control shaft through opening (see Figure 31, page 17).
6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clock­wise until tight against the plate. Place control knob provided onto shaft (see Figure 31, page 17).
7. Replace plate containing the switch and tighten screws securely.
Green Wire
: For clarity, gas valve assem-
For DA3610TA, make sure the
Blower Assembly
16
106394
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
8. Plug in blower power cord.
a. If your fir eplace system is installed
as a freestanding unit with an ac­cessory mantel, determine whether
the power cord will exit the left side or the right side of the firebox. In­stall one plastic bushing provided into the 1 1/2" hole in the outer cas­ing through which the power cord will exit. Install the second plastic bushing provided into the floor sup­port bracket if exiting through the right side (see Figure 32). Route power cord through (both) plastic bushing(s) and plug the power cord into a properly grounded 3-prong wall receptacle near the firebox.
b.If your fireplace system installation
is recessed and/or pre-wired, a qualified installer must make all elec­trical connections for the outlet kit included with the fireplace.
9. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign ob­jects in blower wheel. Turn blower on and check for operation. Turn blower off by rotating knob fully counterclock­wise before continuing.
WARNING: Never touch the
blower wheel while in operation.
10. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 3" to the right of the blower speed control bracket (Figure 32).
WARNING: Failure to position the parts in accordance with sup­plied diagrams or failure to use only parts specifically approved with this heater may result in dam­age or personal injury.
11. Connect or reconnect gas supply to fire­place per Connecting Fir eplace to Gas Supply on page 19 of this manual.
WARNING: A qualified ser­vice person must connect fire­place to gas supply. Follow all local codes.
Firebox Bottom
Thermal Switch
Thermal Switch Bracket
Firebox Back
Firebox Flange
Blower
Lower Rear Wall of Firebox Wrapper
Blower
Screws
Figure 29 - Mounting Blower to Firebox
Lower Louver Panel
Exhaust Port
Top Mounting Tab
Thermal Switch
Figure 30 - Locating Thermal Switch Against Back of Firebox
Speed Control
Control Knob
Locknut
Figure 31 - Attaching Speed Control to Firebox
Wiring Diagram
Blower Speed Control Bracket
Figure 32 - Installing Plastic Bushing and Wiring Diagram Sticker
Control Shaft
Plastic Bushing
Side View
Continued
106394
17
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE INSTALLATION
Continued
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: A qualified ser­vice person must connect fire­place to gas supply. Follow all local codes.
CAUTION: For propane/LP units, never connect heater di­rectly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved flexible gas line with gas con­nector (if allowed by local codes) (not provided)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur­chase the CSA design-certified equipment shutoff valve from your retailer.
For propane/LP connection only, the in­staller must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 33. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of pressure will occur.
Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 34).
Propane/LP Supply Tank
External Regulator
Vent Pointing Down
Figure 33 - External Regulator with Vent Pointing Down (Propane/LP Only)
CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*
Approved Flexible Gas Line
3" Minimum
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Figure 34 - Gas Connection
* The CSA design-certified equipment shutoff valve may be supplied with the appliance or you can purchase it from your retailer.
(equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.
CAUTION: Use pipe joint seal­ant that is resistant to liquid pe­troleum (LP) gas.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 35. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contami­nants. This keeps them from going into fireplace gas controls. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.
IMPORTANT:
Install main gas valve
Natural - From Gas Meter (5" W.C. to 10.5" W.C. Pressure )
Propane/LP - From External Regulator (11" W.C. to 14" W.C. Pressure)
18
106394
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1. Open lower louver door panel by gen-
tly pulling forward.
2. Route flexible gas line (provided by
installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.
3. Attach flexible gas line from gas sup-
ply to control valve (see Figure 35).
4. Check all gas connections for leaks. See
Checking Gas Connections, pages 19 and 20.
To Gas Supply (Natural)
Equipment Shutoff Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip­ing and connections for leaks after installing or servicing. Cor­rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.
Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by ei­ther opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, using compressed air.
4. Check all joints of gas supply piping system. Apply commercial leak test solution to all gas joints. Bubbles form­ing show a leak. Correct all leaks at once.
5. Reconnect fireplace and equipment shutoff valve to gas supply. Check re­connected fittings for leaks.
or
To External Regulator (Propane/LP)
Flexible Gas Line from Equipment Shutoff Valve Provided by Installer
Figure 35 - Attaching Flexible Gas Line to Control Valve
Control Valve
Continued
106394
19
DVFH34, DVFH34P
ON
POSITION
OFF
POSITION
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE INSTALLATION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig­ure 36).
2. Pressurize supply piping system by ei­ther opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, using compressed air.
3. Check all joints from propane/LP sup­ply tank or gas meter to equipment shutoff valve (see Figure 37 for pro­pane/LP or Figure 38 for natural). Ap­ply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Fireplace Gas Connections
1. Open equipment shutoff valve (see Fig­ure 36).
2. Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natu­ral gas fireplace.
3. Make sure control knob of fireplace is in the OFF position.
4. Check all joints from equipment shutoff valve to thermostat gas valve (see Fig­ure 37 for propane/LP or Figure 38 for natural). Apply commercial leak test so­lution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
5. Light fireplace (see Operating Fire- place, pages 25 through 27). Check all other internal joints for leaks.
6. Turn off fireplace (see To Turn Off Gas to Appliance, page 25).
or
Open
Equipment Shutoff Valve
Closed
Figure 36 - Equipment Shutoff Valve
Propane/LP Supply Tank
Equipment Shutoff Valve
Gas Valve
Figure 37 - Checking Gas Joints for Propane/LP Gas Fireplace
Equipment Shutoff Valve
Gas Meter
Gas Valve
Figure 38 - Checking Gas Joints for Natural Gas Fireplace
20
106394
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
INSTALLING OPTIONAL WIRELESS HAND-HELD REMOTE CONTROL - GHRC SERIES/GHRCT SERIES
NOTICE: Use only alkaline bat­teries (not included).
Installing Remote Receiver
1. Open bottom louver and locate the switch bracket on the left.
2. Unscrew the switch bracket. Lean bracket forward so you are able to ac­cess the back of the remote receiver.
3. Locate the battery clip mounted on the back of the receiver. Slide a 9-volt al­kaline battery (not included) through the clip (see Figure 39).
4. Attach the terminal wires to the battery.
5. Remove wire from TH to TPTH on control valve (see Figure 40).
6. Connect wires from receiver to TH and TPTH to control valve (see Figure 41).
7. Replace the switch bracket.
Receiver
Terminal Wires
Battery Clip
9-Volt Alkaline Battery
Figure 39 - Attaching Alkaline Battery to Receiver
To Optional Remote Accessory
Figure 41 - Control Valve Terminals
Installing 9-Volt Alkaline Battery in Hand-Held Remote Control Unit
1. Remove battery cover on back of re­mote control unit.
2. Attach terminal wires to a 9-volt alka­line battery (not included). Place bat­tery into the battery housing.
3. Replace battery cover onto remote con­trol unit.
Battery
Terminal Wires
9-Volt Alkaline Battery
Figure 42 - Installing Alkaline Battery in Hand-Held Remote Control Unit
Cover
Remote Control Unit
Battery Housing
Remote Control Unit
INSTALLING OPTIONAL WALL MOUNTED THERMOSTAT - GWMT1
WARNING: Installation must be done by a qualified installer familiar with low voltage wiring procedures.
WARNING: Do not connect this thermostat to any electrical source! Electrical shock and/or fire hazard will occur.
NOTICE: The GWMT1 includes 25' of wire for installation. Your fire­place includes 15' of wire for ac­cessory installation. Choose the length that best fits your needs when installing this accessory.
1. Open lower louver panel. The valve is attached to the underside of the fire­box assembly.
2. Disconnect the wire that runs from TH to TPTH from the valve as shown in Figure 40.
3. Connect one terminal of the provided wire for the wall thermostat to the TPTH terminal on the valve. Connect remain­ing wire terminal to the TH terminal on the valve. Make sure that the wire termi­nals are in the positions on the unit as pictured in Figure 44. If wires are not connected as shown the thermostat will not work.
To Wall Optional Remote Accessory
Figure 40 - Disconnecting TH to TPTH Wire
106394
Figure 43 - Installing Battery in Hand-Held Remote Control Unit (GHRCTA Series Only)
Figure 44 - Control Valve Terminals
Continued
21
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE INSTALLATION
Continued
4. Route the wire through openings pro­vided on the sides of the fireplace to a convenient location to mount your ther­mostat (no outside wall).
IMPORTANT:
ened but must not be lengthened. The thermostat should be mounted 54"
above the floor in a location where there is good air circulation. Avoid heat sources such as lamps, direct sunlight, fireplace, or heat and air conditioning ducts.
5. Gently remove the cover of the ther­mostat from the base. Grasp the sides of the cover firmly and pull to separate from the base.
6. Feed the electrical wires through the rectangular slots (from the back) on each side of the base (see Figure 45).
WARNING: Do not connect this thermostat to a power source. Electrical shock and/or fire haz­ard will occur.
7. Connect one bare wire end to each ter­minal (“W” and “R”) of the thermostat base (see Figure 46).
8. Install the base to the wall with screws provided with thermostat.
9. Move the temperature adjustment back and forth to insure the bimetal is free from restrictions.
10. Replace the cover onto the base. (Upon installation, the thermostat must be al­lowed to stabilize at room temperature for a minimum of 30 minutes for proper operation.)
11. Set the temperature adjustment to the desired setting.
This thermostat has been electronically calibrated at the factory . No adjustment or leveling is necessary.
The wire may be short-
Feed wires through rectangular slots
Figure 45 - Back View of Thermostat Base
W
R
Figure 46 - Thermostat Base Terminals “W” and “R”
Terminal “W”
Terminal “R”
INSTALLING OPTIONAL WALL MOUNT SWITCH GWMS2
NOTICE: The GWMS2 includes 25' of wire for installation. Your fireplace includes 15' of wire for accessory installation. Choose the length that best fits your needs when installing this accessory.
1. Connect one terminal of the provided wire for the wall switch to the TPTH terminal on the valve. Connect remain­ing wire terminal to the TH terminal on the valve. Make sure that the wire terminals are in the positions on the unit as pictured in Figure 41, page 21. If wires are not connected as shown the switch will not work.
2. Route the wire through openings pro­vided on the sides of the fireplace to a convenient location to mount your switch.
3. Connect one bare wire end to each of the terminals of the GWMS2 wall switch.
4. Install the wall switch and cover in the wall.
REMOVING/REPLACING GLASS DOOR
You must remove glass door to install op­tional brick liners, logs, lava rock, and em­ber material.
CAUTION: Do not operate this fireplace with a broken glass door panel or without the glass door panel securely in place. For re­placement part information see
Replacement Parts
1. Remove the upper louver panel by lift­ing upward and out (see Figure 47).
2. Remove the screws from the three tabs at the top of the glass door while hold­ing door securely keeping it from fall­ing forward.
3. Grasp door by both sides and ease it upward off of the lower bracket (see Figure 48).
4. T o replace glass door, follow the above instructions in reverse.
Figure 47 - Removing Top Louver Panel
Screw
Glass Door Assembly
Lower Bracket for Glass Door Assembly
Figure 48 - Removing/Replacing Glass Door
, page 33.
Top Louver Panel
22
106394
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
Attaching Magnetic Decorative Brass Strips (Optional Installation)
Before attaching strips to fireplace, remove plastic film from brass pieces. After install­ing door, attach these strips to the top and bottom of glass door frame.
INSTALLING OPTIONAL BRICK LINER D8037A
WARNING: If fireplace has been running, turn off and un­plug fireplace. Let cool before installing brick liner.
This brick liner kit is optional. You may purchase brick liner from your local retailer or see Accessories, pages 36 and 37.
7. Install the right brick panel using the same method described in step 5.
8. Slide the right retainer bracket against the right side brick panel. Tighten the bracket screw. This secures both the right side and rear brick panels.
9. Follow instructions on page 24 to install logs, lava rock, and ember material.
10. Replace glass door (see page 22).
Rear Brick Panel
CAUTION: Always handle brick panels with two hands. Do not force brick panels into place. Excessive force will break brick panels.
1. Remove glass door. See Removing/Re­placing Glass Door, page 22.
2. If installing brick liner in new fireplace, go to step 3. If installing brick liner in an existing fireplace, carefully remove logs, lava rock, and ember material.
3. Install rear brick panel first. Rest bot­tom edge of panel on back edge of grate (see Figure 49).
4. Loosely secure retainer brackets to grate. Brackets are adjustable left to right to allow proper placement of panel. These will hold rear panel in place while installing side panels.
5. Install left side brick panel by sliding it between the grate and the side of the firebox (see Figure 50).
6. Slide the left retainer bracket against the left side brick panel. Tighten the bracket screw. This secures both the left side and rear brick panels.
Retaining Brackets
Figure 49 - Installing Rear Brick Panel and Retainer Brackets
Left Side Brick Panel
Retainer Brackets
106394
Figure 50 - Installing Left Side Brick Panel
23
Continued
DVFH34, DVFH34P
3
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
FIREPLACE INSTALLATION
Continued
INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERS
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury.
Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with fireplace.
Remove glass door. See Removing/Replacing Glass Door, page 22. Install logs according to the following instructions.
1. Place log #1 (back log) on top of grate. Make sure the notches in the bottom of the log fit over the grate (see Figure 51).
2. Rest log #2 (large front log) on the pins on the front part of the grate (see Figure 52).
3. Place log #3 (left log) onto the rear and front logs. Make sure it is seated prop­erly into the notch on the front log and over the raised triangular portion of the rear log as shown in Figure 53.
4. Place log #4 (right log) onto the front left part of the grate making sure the notches fits over the prong of the grate (see Figure 54).
5. Place lava rock along sides and front of firebox bottom in areas that are vis­ible only. It is not necessary to use all of the lava rock provided.
6. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto the exposed section of the front burner and along the space between the burner and grate prongs (see Figure 55). This will create the glowing ember ap­pearance as the flame touches the em­ber material. Do not block air slots by using too much ember material in one area. It is not necessary to use all of the ember material provided.
7. Replace the glass door. See Removing/ Replacing Glass Door, page 22.
WARNING: The glass door must be securely in place before running this fireplace. Do not run this fireplace if glass is missing or broken.
1
Figure 51 - Installing Log No. 1
2
Figure 53 - Installing Log No. 3
4
Figure 54 - Installing Log No. 4
Ember Material
NOTICE: Do not put lava rock on burner or under burner. Placing lava rock on burner could cause performance problems.
Figure 52 - Installing Log No. 2
24
Figure 55 - Placing Ember Material on Burner
106394
OWNER’S MANUAL
OPERATING FIREPLACE
FOR YOUR SAFETY
READ BEFORE
LIGHTING
WARNING: If you do not fol­low these instructions exactly, a fire or explosion may result caus­ing property damage, personal injury or loss of life.
A. This appliance has a pilot which must
be lighted by hand. When lighting the pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all
around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHA T TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call y our gas supplier from a neighbor’s phone. Follow the gas supplier's instructions.
C. Use only your hand to push in or turn
the gas control knob. Ne ver use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. For ce or attempted repair may result in a f ire or explosion.
D. Do not use this appliance if any part
has been under water . Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas con­trol which has been under water.
LIGHTING
INSTRUCTIONS
1. STOP! Read the safety information in column one.
2. Open lower louver panel.
3. Disconnect the wire that runs from TH to TPTH from the contr ol valve.
4. Turn off all electric power to the fireplace.
5. Push in gas control knob slightly and turn clockwise to “OFF”.
6. Wait f ive (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety in­formation in column one. If you don't smell gas, go to the next step.
7. The pilot is located by the main burner and should not require ac­cessing for lighting.
8. T urn gas control knob counter clock­wise to “PILOT”.
9. Push in gas control knob all the way and hold. Immediately light the pi­lot by repeatedly depressing the piezo spark ignitor until a flame appears. Continue to hold for about one (1) minute after the pilot is lit. Release gas control knob and it will pop back. Pilot should remain lit. If it goes out, repeat steps 5 through 8.
• If gas control knob does not pop
up when released, stop and immediately call your service technician or gas supplier.
• If the pilot will not stay lit after sev-
eral tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
Gas Control Knob Piezo
Ignitor
Figure 56 - Control Valve
Variable Control Knob
I
H
T
O
L
I
O
P
N
F
F
O
L
O
10. Reconnect the wire that runs from TH to TPTH to the control valve.
11. Turn on all electric power to the fireplace.
12. Turn gas control knob counterclock­wise to “ON”.
13. This valve is equipped with a HI/LO feature. Set fir eplace input as desired.
14. Close lower louver panel.
TO TURN OFF GAS
TO APPLIANCE
1. Open lower louver panel.
2a. Disconnect wire that runs from TH
to TPTH.
2b. Set selector switch in the OFF position
to prevent draining battery.
3. Turn off all electrical power to the appliance if service is to be performed.
4. Push in gas control knob slightly and turn clockwise to “OFF”.
5. Close lower louver panel.
Shutting Off Burners Only (pilot stays lit)
You may shut off the burners and keep the pilot lit by doing one of the following:
1. Turn gas control knob clockwise
to the PILOT position.
2. Set selector switch in the OFF position.
MANUAL LIGHTING
PROCEDURE
1. Remove glass door (see Removing/ Replacing Glass Door, page 22).
2. Follow steps 1 through 8 under Light­ing Instructions.
3. Depress gas control knob and light pilot with match.
4. Keep gas control knob pressed in f or 30 seconds after lighting pilot. After 30 seconds, release gas control knob . Follow steps 10 through 14 under
Lighting Instructions.
5. Replace glass door (see Removing/ Replacing Glass Door, page 22).
106394
Continued
25
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
OPERATING FIREPLACE
Continued
OPTIONAL REMOTE
OPERATION
Note:
All remote control accessories must be purchased separately (see Accessories, pages 36 and 37). Follow instructions in­cluded with the remote control.
Thermostat Control Operation
(Optional GHRCTA Series Only) The thermostat control setting on the remote control unit can be set to any comfort level between WARMER and COOLER. The burners will turn on and off auto­matically to maintain the comfort level you select. The ideal comfort setting will vary by household depending upon the amount of space to be heated, the output of the central heating system, etc.
NOTICE: You must light the pilot before using the hand-held re­mote control unit. See
Instructions
on page 25.
1. After lighting, let pilot flame burn for about one minute. Turn gas control knob to ON position. Adjust varia ble control knob anywhere between HI and LO. Slide the selector switch to the REMOTE position (see Figure
57).
Note:
The burners may light if hand-held remote ON button was on when selector switch was last turned off. Y ou can no w turn the bur ners on and off with the hand-held remote control unit.
IMPORTANT
: Do not leave the selec­tor switch in the REMOTE position when the pilot is not lit. This will drain the battery.
IMPORTANT:
Be sure to press the ON/OFF buttons on the hand-held remote control unit for up to 3 sec­onds to assure proper operation.
Lighting
GHRC Series Operation:
2a. Press the ON/OFF b utton to turn the
burners on and off. When turning burners off, the pilot will remain lit.
GHRCTA Series Operation:
2b. Press the AUTO/ON/OFF button on
the hand-held remote control (see Fig­ure 58). The lights to the left of the button will show A UTO, ON, or OFF.
• In the ON mode, the burners will ignite. The heater is in manual mode when ON is lit.
• In the A UTO mode, the thermostat in the hand-held remote unit con­trols the room temperature. To in­crease the room temperature, pr ess the top arrow of the TEMP b utton. To lower the room temperature, press the bottom arrow of the TEMP button. At higher settings the heater will run longer.
Blower Control Knob (Optional Accessory)
OFF
ON
ON
OFF
REMOTE
Selector Switch in Remote Position
Figure 57 - Setting the Selector Switch, Gas Control Knob, and Variable Control Knob for Remote Operation
Shows Temperature Setting
The Log Heater will Automatically Cycle between Pilot and the Heat Setting that has been Selected
Variable Control Knob
N
O
O
F
T
F
O
L
I
P
Gas Control Knob in ON Position
L
O
I
H
IMPORTANT:
This remote contr ol has been specially engineered to take an air temperature sample ev­ery minute in the auto mode. It will not respond immediately to the temperature setting being turned up or down.
IMPORTANT:
The hand-held re­mote control unit must be near the heater. Do not keep the hand-held remote control unit too close to the heater. The thermostat on the hand-held remote control unit will heat up too quickly and turn the heater off.
3. To turn the burner off, press the AUTO/ON/OFF button until OFF lights. The pilot will remain lit.
IMPORTANT :
To turn the pilot off, manually turn the control knob on the heater to the OFF position.
OPERATING
OPTIONAL GWMS2
WALL MOUNTED
SWITCH
Make sure the heater switch is on AUTO. This wall switch works just like the con­ventional light switch. Flip the switch up for on and down for off.
Note:
Make sure that this switch is not in a position to be mistaken for a light switch. This may result in the heater being inad­vertently turned on without the proper precautions being taken. See installation instructions on page 22 of this manual.
Increases Room Temperature in AUTO Mode
Decreases Room Temperature in AUTO Mode
Turns Burners On or Off and Allows You to Choose the Auto Setting
Figure 58 - Thermostat Hand-Held Remote Control Unit Selections (GHRCTA Series Only)
26
106394
OWNER’S MANUAL
OPERATING FIREPLACE
Continued
OPERATING
OPTIONAL GWMT1
WALL MOUNTED
THERMOSTAT
WARNING: Do not connect the thermostat to a power source. Electrical shock and/or a fire haz­ard will occur.
Light the fireplace as instructed in Light­ing Instructions on page 25. Set wall ther-
mostat to desired temperature. This thermostat has been electronically
calibrated at the factory and requires no adjustment or leveling.
Upon installation, the thermostat must be allowed to stabilize at room tempera­ture for a minimum of 30 minutes for proper operation.
To turn the fireplace off, adjust thermo­stat to the lowest setting and turn the gas control knob back to PILOT. The pilot will remain lit.
IMPORTANT:
the gas control knob on the heater to the OFF position.
OPTIONAL BLOWER
Locate the blower controls by opening the lower louver panel on the fireplace. Blower controls are located on the left side of the switch bracket to the left just inside the louver panel.
Both the GA3700 manual blower and the DA3610TA thermostatically-controlled blower have an ON setting and an OFF setting. The blower will only run when the switch is in the ON position. In the OFF position, the blower will not operate.
To turn the pilot off, turn
OPERATING
ACCESSORY
Note for DA3610TA Only:
using DA3610TA blower with optional thermostat (wall mounted or remote con­trol) for the fireplace, your fireplace and blower will not turn on and off at the same time. The fireplace may run for several minutes before the blower turns on. After the heater modulates to the pilot position, the blower will continue to run. The blower will shut off after the firebox temperature decreases.
The blower helps distribute heated air from the fireplace. Periodically check the louvers of the firebox and remove any dust, dirt, or other obstructions that will hinder the flow of air.
If you are
INSPECTING BURNERS
Check pilot flame pattern and burner flame patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the proper flame height. Alterations may have occurred during shipping and handling. Call a qualified service person to readjust the pilot if necessary.
The height of the thermopile must be 3/8" to 1/2" above the pilot flame as shown in Figure
60. The thermocouple must be at a height of about 1/8" above the pilot flame. The flame from the pilot burner must extend beyond both the thermocouple and thermopile.
If you pilot assembly does not meet these requirements:
• turn fireplace off (see To Turn Off Gas to Appliance, page 25)
• see Troubleshooting, pages 29 through 31
Thermopile
3/8" to 1/2"
Pilot Burner
1/8"
Thermocouple
Piezo Ignitor
Figure 59 - Pilot Assembly
BURNER FLAME PATTERN
Burner flames will be steady; not lifting or floating. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent configuration is installed incor­rectly, the flames will lift or "ghost". This can be dangerous. Inspect the flames after installation to ensure proper installation and performance.
Figure 60 shows a typical flame pattern for DVFH34(P) models.
If burner flame pattern differs from that described:
• turn fireplace off (see T o T urn Off Gas to Appliance, page 25)
• see Troubleshooting, pages 29 through 31
Figure 60 - Typical Flame Pattern
106394
27
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
CLEANING AND MAINTENANCE
WARNING: Turn off fireplace
and let cool before cleaning.
CAUTION: You must keep con­trol areas, burners, and circulat­ing air passageways of fireplace clean. Inspect these areas of fire­place before each use. Have fire­place inspected yearly by a quali­fied service person. Fireplace may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
GLASS DOOR
WARNING: Handle glass door panel with care. Do not strike, slam, or otherwise abuse glass. Do not operate fireplace with the glass door removed, cracked, or broken.
WARNING: Do not use abra­sive cleaners as this may damage glass. Use a nonabrasive house­hold glass cleaner to clean glass. Do not clean glass when hot.
WARNING: Only parts sup­plied by the manufacturer should be used when replacing broken or damaged glass door panel (see
Replacement Parts
glass door panel is a complete unit. No substitute materials may be used.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep chil­dren and pets away from glass.
If glass has been broken, carefully remove glass door (see Removing/Replacing Glass Door, page 22). Vacuum all glass pieces with a shop vac.
CAUTION: Do not vacuum if pieces are hot.
Use only the ceramic glass door replace­ment intended for this fireplace (see Re- placement Parts, page 32 for detail on or­dering). No substitutions may be made. See Removing/Replacing Glass Door, page 22 for instructions for replacing glass door.
WARNING: Do not operate fireplace with the glass door re­moved, cracked, or broken.
, page 32). This
LOGS
• If you remove logs for cleaning, refer to
Installing Logs, Lava Rock, and Glowing Embers, page 23, to properly replace logs.
• Use a vacuum cleaner to remove any car­bon buildup on logs.
• Replace log(s) if broken. See Replace- ment Parts on page 32.
• Replace ember material periodically as needed. See Replacement P arts on page 32.
VENTING SYSTEM
Conduct annual inspection of the venting system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced imme­diately by a qualified service person.
2. Remove the vent cap and shine a flash-
light into the vent. Remove any foreign material.
3. Check for evidence of excessive con-
densation. Continuous condensation can cause corrosion of caps, pipes, and fittings and can be caused by having excessive lateral runs, too many el­bows, or exterior portions of the sys­tem being exposed to cold weather.
4. Inspect joints to verify that no pipe sec-
tion or fitting has been disturbed and loosened. Check mechanical supports such as wall straps for rigidity.
Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust, and other airborne particles to cling to the glass surface. During initial start-up a slight film may form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, non­abrasive household cleaner and warm water after the first two weeks of operation. There­after, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door on page 22 of this manual when removing glass door for cleaning.
PILOT AND BURNERS
• Remove ember material before cleaning burners and replace when cleaning is complete.
• Burner and controls should be cleaned with compressed air to remove dust, dirt, or lint.
• Use a vacuum cleaner or small, soft bristled brush to remove excess dust, dirt, or lint.
28
106394
OWNER’S MANUAL
TROUBLESHOOTING
Note:
For additional help, visit DESA
International’s technical service web site at www.desatech.com.
Note:
All troubleshooting items are listed in
order of operation.
OBSERVED PROBLEM
When ignitor button is pressed, there is no spark at pilot
When ignitor button is pressed, there is spark at pilot but no ignition
WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
POSSIBLE CAUSE
1. Ignitor electrode not connected to igni­tor cable
2. Ignitor cable pinched or wet
3. Piezo ignitor nut is loose
4. Broken ignitor cable
5. Bad piezo ignitor
6. Ignitor electrode broken
7. Ignitor electrode positioned wrong
1. Gas supply turned off or equipment shutoff valve closed
2. Gas control knob not in PILOT position
3. Gas control knob not pressed in while in PILOT position
4. Air in gas lines when installed
5. Depleted gas supply (propane/LP models only)
6. Pilot is clogged
7. Gas regulator setting is not correct
CAUTION: Never use a wire, needle, or similar object to clean pilot. This can damage pilot unit.
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
3. Tighten nut holding piezo ignitor. Nut is located behind the mounting bracket
4. Replace ignitor cable
5. Replace piezo ignitor
6. Replace pilot assembly
7. Replace pilot assembly
1. Turn on gas supply or open equipment shutoff valve
2. Turn gas control knob to PILOT position
3. Press in gas control knob while in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is re­moved
5. Contact local propane/LP gas company
6. Clean pilot (see Cleaning and Mainte- nance, page 28) or replace pilot assembly
7. Replace gas control
Pilot lights but flame goes out when control knob is released
106394
1. Gas control knob not fully pressed in
2. Gas control knob not pressed in long enough
3. Equipment shutoff valve not fully open
4. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob­lem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged pilot
5. Thermocouple connection loose at con­trol valve
6. Thermocouple damaged
7. Control valve damaged
www.desatech.com
29
1. Press in gas control knob fully
2. After pilot lights, keep gas control knob pressed in 30 seconds
3. Fully open equipment shutoff valve
4. A) Contact local gas company
B) Clean pilot (see Cleaning and Maintenance, page 28) or replace pi­lot assembly
5. Hand tighten until snug, then tighten 1/4 turn more
6. Replace thermocouple
7. Replace control valve
Continued
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Burner does not light after pilot is lit
Delayed ignition burner
Burner backfiring during combustion
Slight smoke or odor during initial operation
Heater produces a whistling noise when burner is lit
POSSIBLE CAUSE
1. Burner orifice clogged
2. Inlet gas pressure is too low
3. Thermopile leads disconnected or im­properly connected
4. Thermopile is defective
1. Manifold pressure is too low
2. Burner porting or orifice clogged
1. Burner orifice is clogged or damaged
2. Damaged burner
3. Gas regulator defective
1. Residues from manufacturing processes and logs curing
1. Turning gas control knob to HI position when burner is cold
2. Air in gas line
3. Dirty or partially clogged burner orifice
REMEDY
1. Clean burner (see Cleaning and Mainte­nance, page 28) or replace burner orifice
2. Contact local propane/LP or natural gas company
3. Reconnect leads (see Wiring Diagram, page 32)
4. Replace thermopile
1. Contact local propane/LP or natural gas company
2. Clean burner (see Cleaning and Main- tenance, page 28) or replace burner orifice
1. Clean burner (see Cleaning and Mainte- nance, page 28) or replace burner orifice
2. Replace damaged burner
3. Replace gas control
1. Problem will stop after a few hours of operation
1. Turn gas control knob to LO position and let warm up for a minute
2. Operate burner until air is removed from line. Have gas line checked by local pro­pane/LP or natural gas company
3. Clean burner (see Cleaning and Mainte- nance, page 28) or replace burner orifice
Glass soots
Fireplace produces a clicking/ticking noise just after burners are lit or shut off
Remote does not function
1. Flame impingement on logs
2. Debris around burner air mixer
1. Metal expanding while heating or con­tracting while cooling
1. Battery is not installed or battery power is low
www.desatech.com
30
1. Adjust the log set so that the flame does not excessively impinge on it
2. Inspect the opening at the base of the burner to see that it is NOT packed with any type of material
1. This is common. If noise is excessive, contact qualified service person
1. Replace 9-volt batteries in receiver and remote control
106394
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
OWNER’S MANUAL
IMPORTANT:
paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Fireplace produces unwanted odors
Fireplace shuts off in use
Operating fireplace where impurities in air exist may create odors. Cleaning supplies,
POSSIBLE CAUSE
1. Gas leak. See Warning statement above
1. High or gusting winds
2. Low line pressure
3. Pilot is partially clogged
4. Inner vent pipe leaking exhaust gasses into system
5. Horizontal vent improperly pitched
6. Glass too loose and air tight gasket leaks in corners after usage
7. Bad thermopile or thermocouple
8. Improper vent cap installation
REMEDY
1. Locate and correct all leaks (see Check­ing Gas Connections, pages 19 and 20)
1. Fireplace has been tested for up to 40mph winds. However, extreme con­ditions may occur. See Lighting Instruc- tions on page 25
2. Contact local propane/LP or natural gas company
3. Clean pilot (see Cleaning and Mainte- nance, page 28)
4. Locate and correct all leaks (see Check- ing Gas Connections, pages 19 and 20)
5. Horizontal vent termination should slope down only enough to prevent any water from entering the unit. The maximum downward slope of the vent termination is 1/4" for any horizontal run
6. Tighten glass
7. Replace faulty component
8. Check for proper installation and free­dom from debris or blockage
Gas odor even when control knob is in OFF position
Gas odor during combustion
Dark residue on logs or inside of fireplace
106394
1. Gas leak. See Warning statement above
2. Control valve defective
1. Gas leak. See Warning statement
above
1. Improper log placement
2. Air holes at burner inlet blocked
3. Burner flame holes blocked
www.desatech.com
31
1. Locate and correct all leaks (see Check­ing Gas Connections, pages 19 and 20)
2. Replace control valve
1. Locate and correct all leaks (see Check- ing Gas Connections, pages 19 and 20)
1. Properly locate logs (see Installing Logs, Lava Rock, and Glowing Embers, page 23)
2. Clean out air holes at burner inlets. Pe­riodically repeat as needed
3. Remove blockage or replace burner
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
REPLACEMENT PARTS
Note:
Use only original replacement parts.
This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized retailers of this product. If they can not supply original replacement part(s), call DESA International’s Technical Service Department at 1-800-DESA LOG (1-800-337-2564).
When calling DESA International, have ready
• your name
• your address
• model and serial numbers of your fireplace
• how fireplace was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date Usually, we will ask you to return the defec-
tive part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized retailers of this product. If they can not supply original replacement part(s), call DESA International’s Parts Department at 1-800-972-7879 for referral information.
When calling DESA International, have ready
• model number of your fireplace
• the replacement part number
WIRING DIAGRAM
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Variable
Fan Switch
1
Off
110/115
V.A.C.
Figure 61 - Blower Wiring Diagram for Thermostat-Controlled Models
Black White
Green
2
Black
On
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• fireplace will not produce specified heat
• propane/LP gas supply might be low (propane/LP units only)
When Gas Quality Is Bad
• pilot will not stay lit
• burners will produce flames and soot
• fireplace will backfire when lit
If you feel your gas pressure is too low or gas quality is bad, contact your local natural or propane/LP gas supplier.
Fan Switch
(N.O.)
Blue
Blower
Motor
TECHNICAL SERVICE
You may have further questions about in­stallation, operation, or troubleshooting. If so, contact DESA International’s Technical Service Department at 1-800-DESA LOG (1-800-337-2564).
You can also visit DESA International’s technical service web site at www.desatech.com.
32
106394
OWNER’S MANUAL
SPECIFICATIONS
DVFH34 DVFH34P
Btu 17,000/24,000 Btu/hr 17,000/22,000 Btu/hr Gas Type Natural Propane/LP Ignition Piezo Piezo Manifold Pressure 3.5" w.c. 10.0" w.c. Minimum Inlet Supply Pressure 4.5" w.c. 11.0" w.c. Thermal Efficiency 70% 70% Dimension, Inches/mm (HxWxD)
Fireplace (Actual size of firebox. Measurements do not 32 3/16" x 34 3/8" x 18 1/2" 32 3/16" x 34 3/8" x 18 1/2" include nailing flanges or 817 x 873 x 470mm 817 x 873 x 470mm stand-offs).
Carton 34" x 40" x 21" 34" x 40" x 21"
940 x 1016 x 533mm 940 x 1016 x 533mm
Weight, lbs/kg
Fireplace 123 lbs/56 kg 123 lbs/56 kg Shipping 126 lbs/57 kg 126 lbs/57 kg
106394
33
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
ILLUSTRATED PARTS BREAKDOWN
DVFH34 DVFH34P
34-3
34-2
36
7
34-4
20
35
18
34-1
6
30
41
25
29
19
2
11 (Included in
33
6
24
47
40
32
26 27
31
16
Hardware Pack)
1
44
37
6
4
45
35
7
46
35
43
34
28
22
21
6
23
42
48
3
39
28
17
9
5
10
14
38
15
5
8
13
12
5
106394
OWNER’S MANUAL
PARTS LIST
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 32 of this manual.
DIRECT-VENT FIREPLACE DVFH34 DVFH34P
KEY NO. PART NUMBER DESCRIPTION QTY.
1 104445-01 Top Outer Casing 1 2 105278-01 Outer Casing 1 3 105297-01 Bottom Outer Casing 1 4 104479-10BR Firebox Assembly 1 5 M11084-26 Screw, Hex 50 6 M11084-46 Screw, Hex 8 7 105394-01 Louver, Extruded 2 8 104443-01 Firebox Support, Right 1 9 104486-01 Firebox Support, Left 1 10 104482-01 Switch Bracket 1 11 104483-01 Floor Mounting Bracket 2 12 104491-01 Relief Cover 1 13 104518-01 Relief Cover Gasket 1 14 104527-01 Relief Spring 2 15 104528-01 Relief Washer 2 16 104537-01 Valve Bracket 1 17 104496-01 SIT Valve, Natural 1
104496-02 SIT Valve, Propane/LP 1
18 104497-01 SIT Pilot, Natural 1
104497-02 SIT Pilot, Propane/LP 1 19 104498-01 Thermocouple 1 20 104499-01 Thermopile 1 21 104500-01 Ignitor 1 22 104501-01 Ignitor Bracket 1 23 104502-01 Ignitor Screw 1 24 104503-01 Ignitor Wire 1 25 104504-01 Burner, Natural 1
104504-02 Burner, Propane/LP 1 26 104506-01 Orifice, Natural 1
104506-02 Orifice, Propane/LP 1
KEY NO. PART NUMBER DESCRIPTION QTY.
27 104507-01 Brass Elbow 1 28 104508-01 Brass Fitting 2 29 104509-01 Aluminum Tubing Assy 1 30 104510-01 Pilot Tubing Assy 1 31 104954-01 Screw 3 32 104963-01 Washer 3 33 104955-01 Nut 3 34 107166-01 Log Set 34-1 107453-01 Rear Log 1 34-2 105772-02 Front Log 1 34-3 105772-03 Left Log 1 34-4 105772-04 Right Log 1 35 M10908-2 Screw 6 36 M12461-65 Screw 3 37 H5C4-20B Bolt 2 38 NTC-4C Locknut 2 39 M12461-26 Screw 4 40 104555-02CJ Grate Assembly 1 41 105775-16 Glass Door Assy 1 42 104490-02CJ Baffle 1 43 105450-01CK Front Assembly 1 44 104615-02 Insulation 1 45 104313-01 Hinge, Pin - Left 1 46 104313-02 Hinge, Pin - Right 1 47 105325-01 Burner Baffle 1 48 105575-01 Wire Harness 1
PARTS AVAILABLE - NOT SHOWN
GA6060 Lava Rock 1 104529-01 Ember Material 1
106394
35
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
ACCESSORIES
Purchase these fireplace accessories from your local dealer. If they can not supply these accessories, call DESA International’s Sales Department at 1-800-432-2382 for information. You can also write to the ad­dress listed on the back page of this manual.
CABINET MANTEL
GM101UC Series - Unfinished GM106FC Series - Oak Finished
with Medium Stain
Shown with optional base and laminate hearth and mantel trim accessories.
Dimensions (WxHxD): 56 3/4" x 48 3/4" x 22 3/4"
IMPORTANT: The above mantel model numbers must end with the letter "C" to fit this fireplace.
DUPLEX OUTLET KIT GA3555 (Not Shown)
For recessed installation when accessory blowers are used.
BRASS PERIMETER TRIM KIT - GA6090 (Not Shown)
Optional three sided brass trim kit covers unfinished edges around fireplace. Provides a finished appearance with the class of brass.
BRASS LOUVER KIT D6034 (Not Shown)
These louvers will give your fireplace an elegant look and allows you to customize your fireplace. They easily replace the stan­dard black louvers by screwing into place.
DECORATIVE 2-PIECE BRASS ACCENT TRIM D5037 (Not Shown)
These strips have a magnetic backing which makes installation and removal quick and easy. They are designed to go at the top and bottom of the glass door on DVFH units.
Note:
Remove the plastic film covering on
strips before installing on fireplace.
BRICK LINER D8037A (Not Shown)
This brick liner adds a touch of style to your direct-vent fireplace and comes with easy to follow instructions for installation.
WALL MOUNTED THERMOSTAT CONTROL KIT GWMT1 (Not Shown)
MANUAL BLOWER KIT GA3700
Manual-variable control blower accessory for the DVFH Series fireplaces.
THERMOSTATICALLY­CONTROLLED BLOWER KIT DA3610TA
Provides better heat distribution. Blower turns off and on automatically, as needed. Complete installation and operation instruc­tions included in this manual.
HARDWOOD HEARTH BASE
G3001U Series - Unfinished G3006F Series - Oak Finished
with Medium Stain
The hearth base creates a handsome riser for the fireplace (cannot be used with corner mantel).
Dimensions (WxHxD): 58" x 6 1/2" x 28 9/16"
Allows easy wall access to the operation of your fireplace. This will allow you thermo­static control with the convenience of a wall switch.
ON/OFF WALL MOUNT SWITCH - GWMS2 (Not Shown)
For all models. Allows the heater to be manually turned on and off.
36
106394
ACCESSORIES
Continued
RECEIVER AND HAND-HELD REMOTE CONTROL KIT GHRC SERIES
For all models. Allows the heater to be turned on and off conveniently.
WARMER
COOLER
TEMP
AUTO
ON
OFF
OWNER’S MANUAL
RECEIVER AND HAND-HELD THERMOSTAT REMOTE CONTROL KIT GHRCT SERIES
Allows the fireplace to be operated in a manually or thermostatically-controlled mode. You can adjust your heat settings and turn the heater on or off without leaving the comfort of your easy chair.
106394
37
DVFH34, DVFH34P
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
NOTES
_______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________
38
106394
OWNER’S MANUAL
NOTES
_______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________
106394
39
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model Serial No. Date Purchased
Always specify model and serial numbers when communicating with the factory. We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written
warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
DIRECT-VENT FIREPLACE
DESA International warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized retailers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURA­TION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state. For information about this warranty write:
INTERNATIONAL
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004
www.desatech.com
106394 01
NOT A UPC
106394-01 Rev. A 04/00