Warning to proceed strictly in accordance with the information contained in the
documentation in order to ensure the safety and full functionality of the device.
i
Information particularly useful during installation and operation of the device.
Information particularly useful during installation and operation of a type Ex device.
Information on disposal of used equipment
Symbols used
BASIC REQUIREMENTS AND SAFE USE
- The manufacturer will not be liable for damage resulting from incorrect installation,
failure to maintain the device in a suitable technical condition, or use of the device
other than for its intended purpose.
- Installation should be carried out by qualified staff having the required authorizations to install
electrical and pressure-measuring devices. The installer is responsible for performing the
installation in accordance with these instructions and with the electromagnetic compatibility
and safety regulations and standards applicable to the type of installation.
- The device should be configured appropriately for the purpose for which it is to be used.
Incorrect configuration may cause erroneous functioning, leading to damage to the device or
an accident.
- In systems with pressure transmitters there exists, in case of leakage, a danger to staff on
the side where the medium is under pressure. All safety and protection requirements must be
observed during installation, operation and inspections.
- If a device is not functioning correctly, disconnect it and send it for repair to the manufacturer
or to a firm authorized by the manufacturer.
In order to minimize the risk of malfunction and associated risks to staff, the device is not to be
installed or used in particularly unfavourable conditions, where the following dangers occur:
- possibility of mechanical impacts, excessive shocks and vibration;
- excessive temperature fluctuation, exposure to direct sunlight;
- condensation of water vapour, dust, icing.
Installation of intrinsic safety versions should be performed with particular care, in accordance
with the regulations and standards applicable to that type of installation.
The manufacturer reserves the right to make changes (not having a negative impact on the
operational and metrological parameters of the products) without updating the contents of the
technical manual.
A 1 IOM-DPCDPR-A: FEB 2014
CONTENTS
I. APPENDIX Exd ..................................................................................................................................... 2
II. APPENDIX Exi ...................................................................................................................................... 5
5.2.DPC...-MEASUREMENT RANGES AND METROLOGICAL PARAMETERS. ........................................................................... 12
5.3.DPR-2000ALW,DPR-2200ALWMEASUREMENT RANGES AND METROLOGICAL PARAMETERS. ................................... 13
5.4.DPR–2000GALW,MEASUREMENT RANGES AND METROLOGICAL PARAMETERS. ............................................................. 14
5.5.DPR–2000YALW.MEASUREMENT RANGES AND METROLOGICAL PARAMETERS. ............................................................. 14
6. CONSTRUCTION .......................................................................................................................................15
7.3.HIGH MEDIUM TEMPERATURE. .................................................................................................................................. 16
8. INSTALLATION AND MECHANICAL CONNECTIONS .........................................................................17
8.1.DPC...INSTALLATION AND CONNECTIONS .................................................................................................................. 17
8.2.DPR...INSTALLATION AND CONNECTIONS .................................................................................................................. 17
8.3.DPR-2000GALW.INSTALLATION AND CONNECTIONS ................................................................................................ 17
8.4.DPR-2000YALW.INSTALLATION AND CONNECTIONS ................................................................................................. 18
9.2.ELECTRICAL CONNECTIONS FOR DPC...,DPR... ........................................................................................................ 18
9.3.PROTECTION FROM EXCESS VOLTAGE ........................................................................................................................ 18
10.2.CONFIGURATION AND CALIBRATION ......................................................................................................................... 19
11. INSPECTIONS AND SPARE PARTS. ...................................................................................................32
11.1.PERIODIC SERVICE ................................................................................................................................................. 32
FIG.5.M-TYPE CONNECTOR WITH M20X1.5 THREAD ......................................................................................................... 39
FIG.6.P-TYPE CONNECTOR WITH M20X1.5 THREAD ......................................................................................................... 39
FIG.7.CM30X2-TYPE CONNECTOR WITH FLUSH DIAPHRAGM WITH M30X2 THREAD............................................................. 39
FIG.8.PROCESS CONNECTIONS G1/2” AND G1”. .............................................................................................................. 40
FIG.9.DPR-2000ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH C TYPE VENTED COVERS. ......................................... 41
FIG.10.DPR-2000ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH A SINGLE DIRECT DIAPHRAGM SEAL (EXAMPLE). ........ 41
FIG.11.EXAMPLE: HOW TO INSTALL THE DPR-2200ALW TRANSMITTERS WITH REMOTE DIAPHRAGM. ................................. 42
FIG.12.EXAMPLE: HOW TO INSTALL THE DPR-2000ALW TRANSMITTER ON A VERTICAL OR HORIZONTAL PIPE. .................... 43
FIG.13.EXAMPLE: HOW TO INSTALL THE DPR-2000ALW TRANSMITTER WITH A VALVE MANIFOLD TO A 2” PIPE. ................... 43
FIG.14.DPR-2200ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH TWO REMOTE DIAPHRAGM SEALS (EXAMPLES) .......... 45
FIG.15.DPR-2200ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH DIRECT AND REMOTE DIAPHRAGM SEAL (EXAMPLES) . 45
FIG.16.EXAMPLE: HOW TO INSTALL THE DPC...,DPR... TRANSMITTER ............................................................................. 46
FIG.17.DPR-2000GALW SMART DIFFERENTIAL PRESSURE TRANSMITTER FOR LOW RANGES. ............................................ 46
FIG.18.DPR–2000YALW SMART LEVEL PROBE FOR PRESSURE TANKS. ........................................................................... 47
FIG.19.THE EXPLOSION - PROOF JOINTS OF DPC...,DPR... TRANSMITTERS. ..................................................................... 48
FIG.20.HOW TO LEAD THE CASING OF DPC...,DPR... TRANSMITTERS ............................................................................... 48
FIG.21.ADDITIONAL EQUIPMENT FOR FITTING OF PRESSURE TRANSMITTERS. ..................................................................... 49
A 2 IOM-DPCDPR-A: FEB 2014
1180
pressure transmitter
Zone 0Safe areaZone 1 or 2
Pressure transmitter
or differential
Appendix Exd0.2
I. APPENDIX Exd
DPC–2000ALW/XX PRESSURE TRANSMITTER,
1. Introduction
1.1. This “Appendix Exd.02” applies to transmitters of types DPC-2000ALW/XX, DPR-2000ALW/XX,
DPR-2200ALW/XXand DPR-2000YALW/XX in Exd versions only, marked on the rating plate as shown in
p.3 and denoted Exd in the Product Certificate.
1.2. The appendix contains supplementary information relating to the Exd (flame-proof) versions of mentioned
transmitters.
During installation and use of Exd transmitters, reference should be made to DTR.DPC.DPR.ALW.02(ENG) in
conjunction with “Appendix Exd”.
2. Use of DPC… DPR… transmitters in dangers zones.
2.1. The transmitters are produced in accordance with the requirements of the following standards:
EN 60079-0:2009, EN 60079-1:2007, EN 60079-11:2012, EN 60079-26:2007, EN 60079-31:2009.
2.2. The transmitters may operate in areas where there is a risk of explosion, in accordance with the rating of
the explosion protection design:
I M2 Ex ia/d I Mb (version with enclosure ss316)
II 1/2G Ex ia/d IIC T5/T6 Ga/Gb
II 1/2D Ex ia /t IIIC T85°C/T100°C Da/Db
KDB 08 ATEX 224X
marking T6 and T85°C applies to range -40°C <Ta ≤ 45°C
marking T5 and T100°C applies to range -40°C <Ta ≤ 75°C
2.3. Transmitter category and hazard areas.
The category 1/2G, contained within the rating, means that the transmitter may be installed within a type 1 or
2 hazard zone. The DPC…, DPR… process connections may connect to a 0 zone type (see the diagram
below for an example).
DPR-2000ALW/XX, DPR-2200ALW/XX,
DIFFERENTIAL PRESSURE TRANSMITTERS,
DPR-2000YALW/XX LEVEL PROBE,
Exd VERSION
3. Identifying marks.
Flame-proof transmitters must have a rating plate containing the information specified in paragraph 4 of
DTR.DPC.DPR.ALW.02(ENG) and also at least the following:
- CE mark and number of notified unit:, , mark,
- designation of explosion protection design, certificate number,
- temperature use range,
- year of manufacture.
In place of XX letters in product rating plate will be write a pressure connection type symbols.
A 3 IOM-DPCDPR-A: FEB 2014
i
i
i i i
Appendix Exd0.2
4. User information.
Together with the ordered transmitters, the user will receive:
a. Product Certificate,
b. Declaration of conformity,
c. Copy of certificate – on request
d. User’s Manual numbered: DTR.DPC.DPR.ALW.03 with Appendix Exd0.2.
User can find them b), c), d) at www.delta-controls.com
5. Power supply and exploitation of transmitters.
5.1 The transmitter connecting should be made after introduction with present instruction content.
Electrically transmitter should be connected according to scheme at p.6 Appendix Exd. Transmitter
electrical installation should be realised with engineering standard requirements. Electrical connections
of transmitters in danger zone should be made by people who have indispensable knowledge and
experience in this branch. Earth clamps must be used to earth transmitters. In the event that
transmitters come in contact with structural metal parts or pipes which are connected to the
equipotential bonding system, transmitters do not require to be earthed.
5.2. Transmitters should be supplied from DC electrical source with voltage max.45V from transformer
feeders or other devices which have at least a strengthened isolation among primary and secondary
windings in which don’t appear voltage higher than 250V. The duty of power supply installation with
above mentioned requirements rests on user.
5.3. Transmitters can be use in ambient temperatures (Ta) between -40°C < Ta ≤ 45°C for T6 class or
between -40°C < Ta 75°C forT5 class.
5.4. Transmitter sensor diaphragm not should be subject on damage during installation and exploitation.
The diaphragm is made from 316ss or Hastelloy thin foil and cannot be subject on medium which can
entail its damage.
5.5. With regard on kind of casing material (light alloy with large aluminium content), the user is obliged to
assure, that possibility of hitting casing does not step out in place of transmitter installation.
5.6. In transmitter casing are two holes to assembly of packing glands from thread M20x1,5 or 1/2 NPT.
5.7. Normally transmitters are delivered without installed glands but with blank plugs (corks) in the second
hole. They are at table 1 and table 2 at list of packing glands and plugs agreeable with production
documentation and accepted by certificate station. Customer should install packing glands according to
tables 1 and plugs according to tables 2 (if plugs aren’t installed) or other accordance with flame-proof
standards.
5.8. It is necessary apply a shield cable or without shield cable with round cross-section in protection from
elastomer, not moisture absorbing, for example: YKSLY 2 * 1, YnTKSYekw 1 * 2 * 1, LIYCY 2 *In case
of need of use cable about different building customer should co-ordinate this with transmitters
manufacturer to choose intakes with cable diameter.
5.9. The general principles of connecting and the exploitation of transmitter in Exd realization should be
compatible with principles and relating standards for Exd casing devices how in p.2.1, in this including
also : EN600079-14, EN60079-17.
5.10. During service must be made a check of the tight fastening of covers and the packing glands and the
fastening of the cable in the glands. The casing and supply line must be inspected for mechanical
damage, and the transmitter rating plate for legibility. Periodic checks should also be made of the
diaphragm, which should not carry signs of damage. During maintenance it is recommended that the
threads of the covers be lubricated with non-acid vaseline.
Blocking cover method before unscrewing and plumbing possibility is shown at fig 20.
Because of the transmitter damage possibility, the ambient temperature should not be allowed
to become higher than 80C, even when there is no explosion risk.
It is not permitted to repair or otherwise interfere with the transmitter’s electrical circuits in any
way. Damage estimation and repair possibility may be assessed by the manufacturer or another
authorized party only.
In danger zone don’t unscrew transmitter covers and don’t change the display position or its
back lighting.
A 4 IOM-DPCDPR-A: FEB 2014
Ex power supply
see p.5..
_
+
TEST
short-circuit( jumper)
Fuse: In = 0,05A, Un = 250V
according to EN 60127
RD
Communicator
Safe area
_
TEST
SIGNAL
_
+
.
32
VWX
MNO
DEF
YZ#
5 6
PQR*+/
9
GHI
8 0
@%&
1
4
JKL
7
STU
ABC
REF2PV F4
F3 F4PFF1
+
Ro
Hazardous area
Type
Producer
Screw
Feature
Other marking
No of certificate
501/423
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
501/421
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
ICG 623
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0058X
501/453
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
*
501/453/RAC
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0056X
*
501/453/Universal
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0057X
*
ICG 653
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A
Baseefa 06 ATEX 0058X
*
8163/2-A2F
STAHL
M20x1.5
EXd IIC
SIRA06ATEX1188X
A2F, A2FRC, SS2K
CMPProducts
M20x1,5
Exd IIC
SIRA06ATEX1097X
E1FW, E1FX/Z,
E2FW, E2FX/Z
CMPProducts
M20x1,5
Exd IIC
SIRA06ATEX1097X
*
T3CDS, T3CDSPB
CMPProducts
M20x1,5
Exd IIC
SIRA06ATEX1283X
*
PX2K, PXSS2K,
PX2KX, PXB2KX
CMPProducts
M20x1,5
Exd IIC
SIRA06ATEX1097X
*
Table 2. permitted plugs
Type
Producer
Screw
Feature
Other marking
No certificate
AGRO AG
M20x1,5
Exd IIC
475
HAWKE
M20x1,5
Exd IIC
477
HAWKE
M20x1,5
Exd IIC
i
Appendix Exd0.2
6.How to connect Exd transmitters DPC…, DPR…
In case of transmitter calibration outside danger zone is possible communicator connecting to
<SIGNAL+> and <TEST+> terminals. Transmitter is furnished in communication resistor (RD = 240Ω),
closed with jumper at <SIGNAL-> and <TEST-> terminals installed by manufacturer. RD resistor can be
use then, when it is necessary to communicate with transmitter from its terminals and the load resistance
(Ro) in current loop is lover then 250Ω. Than <SIGNAL-> and <TEST-> terminals have to be open.
Table 1. permitted packing glands
*) for special cable only.
Fig. 2.
A 5 IOM-DPCDPR-A: FEB 2014
1453
Zone 1 or 2 Safe area
pressure transmitter
or differential
Pressure transmitter
Zone 0
1180
Appendix Exi
II. APPENDIX Exi
DPR-2000ALW, DPR-2200ALW, DPR-2000GALW
1. Introduction
1.1. This “Appendix Exi” applies to transmitters of types DPC-2000ALW, DPR-2000ALW,
DPR-2200ALW, DPR-2000GALW and DPR-2000YALW in Ex versions only, marked on the rating plate as
shown in 2.2 and denoted Ex in the Product Certificate.
1.2. The appendix contains supplementary information relating to the Ex versions of these transmitters. During installation and use of Ex transmitters, reference should be made to DTR.DPC.DPR.ALW.02(ENG)in conjunction with “Appendix Exi”.
2. Use of DPC… DPR… transmitters in danger zones.
2.1. The transmitters are produced in accordance with the requirements of the following standards
EN 60079-0:2009, EN 60079-26:2007, EN 60079-11:2012, EN 50303:2000
2.2. The transmitters may operate in areas where there is a risk of explosion, in accordance with the rating of
the explosion protection design:
II 1/2G Ex ia IIC T4/T5 Ga/Gb
II 1/2G Ex ia IIB T4/T5 Ga/Gb (version with Teflon-shielelded cable)
II 1D Ex ia IIIC T105C Da
I M1 Ex ia I Ma (version with enclosure ss316)
FTZÚ
2.3. Transmitter category and hazard areas
The category 1/2G, contained within the rating, means that the transmitter may be installed within a type 1
or 2 hazard zone. The DPC…, DPR… process connections may connect to a 0 zone type (see the diagram
below for an example).
DPC–2000ALW PRESSURE TRANSMITTER,
DIFFERENTIAL PRESSURE TRANSMITTERS,
DPR-2000YALW LEVEL PROBE,
Ex VERSION
3. Identifying marks.
Intrinsically safe transmitters must have a rating plate containing the information specified in paragraph 4 of
DTR.DPC.DPR.ALW.03 and also at least the following:
CE mark and number of notified body:, , mark
designation of explosion protection design, certificate number
values of parameters such as. Ui, Ii, Pi, Ci, Li
year of manufacture
"SC Version" - transmitters version with lowered values of Ci=2,5nF and Li=18µH.
"SC, SA Version" - separate power supply for transmitters with surge arresters. Power supply must be separate to
earth.
A 6 IOM-DPCDPR-A: FEB 2014
Io
Ui
Uo
D
I
RwUqIi
Rw
Uo
I DIi
Io
transmitter
4Po
Io
Uq
Io
Uo(Uq – Uo)
Rw
transmitter
Uq
2
Appendix Exi
4. User information.
Together with the ordered transmitters, the user will receive:
Product Certificate,
Declaration of conformity,
Copy of certificate – on request
User’s Manual numbered: DTR.DPC.DPR.ALW.03 with Appendix Exi.
User can find them at www.delta-controls.com
5. Permitted input parameters (based on data from the FTZÚ certificate, and
certification documentation).
The transmitters should be powered via the associated power feeding and measurement devices
provided with the relevant intrinsic-safe certificates. The parameters of their outputs to the danger zone
should not exceed the limit power supply parameters for the below specified transmitters.
5.1 - for power supply with a “linear“ characteristic
Ui = 28V Ii = 0,1A Pi = 0,7W for Ta ≤ 70°C i T5
Power supply with a “linear” characteristic may be e.g. a typical barrier with parameters
Uo = 28V Io = 0.093A Rw = 300Ω.
Fig.1. Power supply from a source with “linear” characteristic
5.2. - for power supply with a “trapezial” characteristic
Ui = 24V Ii = 50mA Pi = 0,7W for Ta ≤ 80°C and T5
Example of power supply from a source with “trapezial” characteristic (see Fig. 2).
If Uo < then parameters Uq, Io, Po are interrelated as follows:
Fig. 2. Power supply from a source with “trapezial” characteristic
Uq = , Rw = , Po = for Uo ≤ 1/2Uq
5.3. - for power supply with “rectangular” characteristic
Ui = 24V Ii = 25mA Pi = 0,6W for Ta ≤ 80°C and T5
Ui = 24V Ii = 50mA Pi = 1,2W for Ta ≤ 80°C and T4
The supply of power from a source with a “rectangular” characteristic means that the voltage of the Ex power
supply remains constant until current limitation activates.
The protection level of power supplies with a “rectangular” characteristic is normally “ib”.
The transmitter powered from such a supply is also a Ex device with protection level “ib”.
Example of practical provision of power supply.
– use a stabilized power supply with Uo=24V with protection level „ib” and current limited to Io=25mA.
5.4. Input inductance and capacity Ci = 20nF, Li = 1,1mH
b) Ci=2,5nF, Li=18µH – for „Version SC”
A 7 IOM-DPCDPR-A: FEB 2014
i
+
_
TEST
+
SIGNAL
Ex-Milliammeter
mA
_
Aplisens KAP-03Ex Communicator
RD
TEST
F1PFF4F3
F4PVF2RE
ABC
STU
7
JKL
4
1
@%&08GHI
9
+/*PQR
65
YZ#
DEF
MNO
VWX
2 3
.
Jumper
Ro
+
_
a Ex power supply
see p.5.
Safe area
In hazardous areas, connections
to the control terminals must be
made using only instruments which
are permitted to be used in such areas.
Hazardous area
To measure the current in the transmitter without
disconnecting the signalling circuit, connect
a milliammeter to control sockets TEST+, TEST-.
28V – 13.5V** – (300Ω* * 0,02A)
0,0225A
Usup. – 13.5V
0,0225A
Delta Controls KAP-03Ex Communicator
Appendix Exi
5.5. Temperature of measured medium can not cause increase temperature housing of transmitter above
the ambient temperature Ta specified for a given category
5.6. Supply voltage min. 13,5VDC **
5.7. Load resistance:
from 28V linear supply
Ro max [Ω] = for transmitter without display back lighting
from a source with “trapezial” or “rectangular” characteristic supply
Ro max [Ω] =
*) barrier resistance
**) 16,5V for transmitter with display back lighting
6.How to connect Ex transmitters DPC…, DPR…
The transmitter and other devices in the measuring loop should be connected in accordance
with the intrinsic-safety and explosion-safety regulations and the conditions for use in
dangerous areas.
Failure to observe the intrinsic-safety regulations can cause explosion and the resulting hazard
to people.
The transmitter is equipped in additional communication resistor RD = 240Ω
During normal operation terminals <Signal –> and <Test –> are shorted.
RD resistor is used when you wish to communicate with the transmitter locally (from its terminals)
and Ro < 250. Terminals <Signal –> and <Test –> must be opened.
Transmitter electrical installation should be realised with engineering standard requirements.
It is not allowed to repair or otherwise interfere with the transmitter’s electrical circuits in any
way. Damage and possible repair may be assessed only by the manufacturer or another
authorized party.
Special conditions for safe use:
- Version of transmitter with surge arrester, marked on the plate "SC, SA", does not meet the
requirements of Section 10.3 of the EN 60079-11:2012 (500Vrms). This must be taken into account
when installing the equipment.
A 8 IOM-DPCDPR-A: FEB 2014
i
1. INTRODUCTION
1.1.This Manual is intended for users of DPC-2000ALW smart pressure transmitters, DPR-2000ALW, DPR-
2200ALW, DPR-2200GALW smart differential pressure transmitters, and DPR-2000YALW smartlevel probe
and their intrinsic-safety versions, containing the data and guidelines necessary to understand the functioning of
the transmitters and how to operate them. It includes essential recommendations concerning installation and
use, as well as emergency procedures. The parameters and information specified for transmitters identified
herein with the sign DPC..., DPR... also apply to transmitters: DPC-2000ALW, DPR-2000ALW, DPR-2200ALW,
DPR-2200GALW, DPR-2000YALW and their explosion-proof versions, as well as all the variations differing by
the type of the process terminals. Information on the transmitter sizes and the method of installation apply to
both, all versions of transmitters.
1.2. Technical data for the diaphragm seals and for the DPC... and DPR... transmitters are contained in the
catalogue cards “DIAPHRAGM SEALS”.
1.3. The transmitters comply with the requirements of EU directives as shown on the plate and with the relevant
Declaration of Conformity.
1.4. Additional data on DPC-2000ALW, DPR-2000ALW, DPR-2200ALW, DPR-2000GALW and
DPR-2000YALW transmitters in Ex versions is contained in the appendix designed to
DTR.DPC.DPR.ALW.02(ENG). Exi Appendix and in Exd versions in the appendix designed to
DTR.DPC.DPR.ALW.02(ENG). Exd Appendix.
During installation and use of the transmitters in Ex or Exd version, reference should be made to
DTR.DPC.DPR.ALW.02(ENG) in conjunction with Exi or Exd Appendix.
2. USER MATERIALS
Transmitters are delivered in single and/or multiple packs.
Together with the transmitter are delivered:
a) Product certificate, which is also as the warranty card
b) Declaration of conformity - on request
c) Copy of ATEX certificate – on request,
d) User’s Manual numbered: DTR.DPC.DPR.ALW.02(ENG).
Items b), c), d) are available at:www.delta-controls.com
3. APPLICATIONS AND MAIN FEATURES
3.1. The DPC... smart pressure transmitters are designed to measure gauge pressure, vacuum pressure and
absolute pressure of gases, vapours and liquids (including corrosive substances).
Differential pressure transmitters type DPR… are used to measure liquid levels in closed tanks, with static
pressure up to 25MPa, or 32MPa for special versions and to measure differential pressure across constrictions
such as filters and orifices.
3.2. The transmitters may be fitted with a range of types of process connectors, which enables them to
be used in a variety of conditions such as thick or highly reactive media, high and low temperatures,
etc.
3.3. DPC..., DPR... transmitters generate a 4...20mA output signal and a digital communication signal in a twowire system (current loop). The use of smart electronics enables regulation of the zero point, the measurement
range, damping, radical conversion characteristic and other functions using an Delta Controls KAPcommunicator or from a PC using a Hart/RS232 converter and Delta Controls “D-Soft” configuration software.
A 9 IOM-DPCDPR-A: FEB 2014
02505007501000
10
15
20
25
30
35
40
45
Ro[ ]
Vmin [V]
Umin = f(Ro) z podświetleniem
02505007501000
10
15
20
25
30
35
40
45
Ro[ ]
Vmin [V]
Umin = f(Ro) bez podświetlenia
50
55
50
55
1250
15001750
1250
15001750
Usup[V]-12V*
0,0225A
i
4. IDENTIFYING MARKS. ORDERING PROCEDURE
4.1. Every transmitter carries a rating plate containing at least the following information: CE mark, manufacturer
name, transmitter type, serial number, pressure range, static pressure limit, output signal, power supply voltage.
Version types and the method of specifying the desired product are described in the current “Information Cards”
and the Catalogue.
4.2. DPC...DPR...transmitters in Ex version or Exd version have additional markings as described in
DTR.DPC.DPR.ALW.02(ENG) Appendix Exi or Exd.
4.4. DPC...DPR... transmitters in realization for sea uses have additional information about signs
Location Classe and DNV Certificate No. A-11308.
5. TECHNICAL DATA.
5.1. DPC..., DPR...- Common parameters
5.1.1. DPC..., DPR... Electrical parameters
Power supply 12* ÷ 55V DC
Power supply for intrinsic-safe versions in accordance with Appendix Exi.
Output signal 4÷20mA + Hart rev.5.1
Communication realised via a 4÷20mA signal using KAP-03 communicator
or RS/Hart modem and PC computer with “D-Soft” software
Resistance for communication 250÷1100Ω, min 240Ω
Load resistance R
U
min. = 12*+ 0,0225xRL [V]
suply
*) 15V for transmitters with display backlight.
[Ω] =
Lmax
Safe working area (grid) upper colour area.
Output updating time 500ms
Additional electronic damping 0...30s
Voltage for insulation testing 500 VAC or 750 VDC, see p.9.3.
Excess voltage protection see p.9.3.
A 10 IOM-DPCDPR-A: FEB 2014
t = 200ms
t = 10 - 250ms
4mA
20mA
9.89mA
wyłączenieciśnienia
d
t dt c
c
t = 460ms
r max.
t
I
t = t + t
rdc
t = 210ms
r min.
pressure
switch off
DPC...DPR...transmitter, response time on pressure stroke tr
measuring cycle 0,5s , damping = 0.
Operating temperature range for intrinsic-safe versions in accordance with Appendix Exi
Operating temperature range for flame-proof versions in accordance with Appendix Exd
Medium temperature range -40°C ÷ 120°C – for direct measurement,
over 120°C measurement with a transmission tube or diaphragm seal using
for intrinsic-safe versions in accordance with Appendix Exi.
Thermal compensation range -25º ÷ 80ºC,
(-40º ÷ 80ºC for special version DPC...)
Relative humidity max. 98%
5.1.2.3. Climatic immunity: dry heat, cold, humidity, salt mist:
Dry heat:
EN 60068-2-2, test B; T = 700C, RH = max 55%
Cold :
EN 60068-2-1, test A; T = -250C,
Damp heat cycle:
EN 60068-2-30, test D ; (T = 550C, RH = min95%, 24h)x2
Salt mist:
EN 60068-2-52; (spraying: 2h duration, T = 250C, storage in damp chamber: 7 days, T = 400C, RH = 93%)x4,
28days total
5.1.2.4. Mechanical immunity
Shocks:
EN 60068-2-27, 50g/11ms
Vibrations:
EN 60068-2-6, test Fc; up to 1,6mm for 2 … 25Hz, up to 4g for 25 … 100Hz
5.1.3.1. Insulation Resistance
>100 MΩ @110V transmitters with gas arresters
>100 MΩ @750V DC transmitters without gas arresters
5.1.3.2. High Voltage Test
500V AC, or 750V DC, 1min, transmitters without gas arresters
75V AC, or 110V DC, 1min, transmitters with gas arresters
5.1.4. Enclosure ingress protection
EN 60529, IP 66,67
5.1.5. DPC..., DPR... Construction materials
Diaphragm seal for DPC... Stainless steel 316L (00H17N14M2) or Hastelloy C276
Diaphragm seal for DPR... Stainless steel 316L (00H17N14M2) or Hastelloy C276
Sensing module Stainless steel 316L (00H17N14M2)
Liquid filling the interior the sensing module Silicone oil, chemically inactive liquid for measurement of
oxygen uses.
Connectors for DPC... Stainless steel 316L (00H17N14M2) or
Hastelloy C276 only for P, GP, CM30x2
C-type vented covers and connectors for DPR.. Stainless steel 316L (00H17N14M2)
Electronics casing High pressure cast of aluminium alloy, lacquered with
chemical-resistant oxide enamel, colour yellow (RAL 1003).
A 12 IOM-DPCDPR-A: FEB 2014
N
Nominal measuring range
(FSO)
Minimum set range
Rangeability
Overpressure limit
(without hysteresis)
1.
0...1000bar (0...100MPa)
10bar (1MPa)
100:1
1200bar (120MPa)
2.
0...300bar (0...30MPa)
3bar (300kPa)
100:1
450bar (45MPa)
3.
0...160bar (0...16MPa)
1,6bar (160kPa)
100:1
450bar (45MPa)
4.
0...70bar (0...7MPa)
0,7bar (70kPa)
100:1
140bar (14MPa)
5.
0...25bar (0...2,5MPa)
0,25bar (25kPa)
100:1
50bar (5MPa)
6.
0...7bar (0...0,7MPa)
0,07bar (7kPa)
100:1
14bar (1,4MPa)
7.
-1...6bar (-100...600kPa)
300mbar (30kPa)
23:1
14bar (1,4MPa)
8.
0...2bar (0...200kPa)
100mbar (10kPa)
20:1
4bar (400kPa)
9.
0...1bar (0...100kPa)
50mbar (5kPa)
20:1
2bar (200kPa)
10.
-0,5...0,5bar (-50...50kPa)
50mbar (5kPa)
20:1
2bar (200kPa)
11.
0...0,25bar (0...25kPa)
25mbar (2,5kPa)
10:1
1bar (100kPa)
12.
-100...100mbar (-10...10kPa)
20mbar (2kPa)
10:1
1bar (100kPa)
13.
-15...70mbar* (-15...7kPa)
5mbar (0,5kPa)
17:1
0,5bar (50kPa)
14.
-7...7 mbar* (-700...700Pa)
1mbar (0,1kPa)
14:1
0,5bar (50kPa)
15.
0...1,3bar abs (0...110kPa abs)
50mbar abs (5kPa abs)
26:1
2bar (200kPa)
16.
0...7bar abs (0...7MPa abs)
0,07bar abs (7kPa abs)
100:1
14bar (1,4MPa)
17.
0...25bar abs (0...2,5MPa abs)
0,25bar abs (25kPa abs)
100:1
50bar (5MPa)
18.
0...70bar abs (0...7MPa abs)
0,7bar abs (70kPa abs)
100:1
140bar (14MPa)
* - only for transmitters without diaphragm seal,
5.2. DPC...- Measurement ranges and metrological parameters.
5.2.1. DPC..., Measurement ranges
5.2.2. DPC..., Metrologicalparameters
Accuracy max ± 0,075% for the basic range (0,16% for range 14)
Long term stability accuracy for 3 years (for the nominal measuring range)
Error due to supply voltage changes max ± 0,002%(FSO)/1V
Thermal error max ± 0,08%(FSO)/10ºC
max ± 0,1% FSO/10C for n°12, 13, 14 ranges.
Thermal error for the whole thermal max ± 0,25%(FSO)
compensation range (max ± 0,4% FSO/10C for n°12, 13, 14 ranges.
5.2.3. DPC..., Pressure Connectors
M-type connector with M20x1.5 thread – see figure 5a,
P-type connector with M20x1.5 thread – see figure 6a,
CM30x2-type connector with flush diaphragm – see figure 7a,
G1/2 -type connector with G1/2” thread – see figure 8a,
GP -type connector with G1/2” thread,
CG1-type connector with G1” thread and flush diaphragm – see figure 8e,
RM-type connector with M20x1.5 thread and radiator
RP-type connector with M20x1.5 thread and radiator
A 13 IOM-DPCDPR-A: FEB 2014
N
Nominal measuring range
(FSO)
Minimum set range
Rangeability
Overpressure
limit
Static pressure
limit
1
0...16bar (0...1,6MPa)
1,6bar (160kPa)
10:1
250, 320bar
(40bar for P-type connector)
2
0...2,5bar (0...250kPa)
0,25bar (25kPa)
10:1
3
0...1bar (0...100kPa)
70mbar (7kPa)
14:1
4
0...0,25bar (0...25kPa)
10mbar (1kPa)
25:1
5
-100...100mbar (-10...10kPa)
4mbar (0,4kPa)
50:1
6
-5...70mbar (-0,5...7kPa)
4mbar (0,4kPa)
18:1
7
-0,5...0,5bar (-50...50kPa)
0,1bar (10kPa)
10:1
8
-25...25mbar (-2,5...2,5kPa)
2,5mbar (0,25kPa)
20:1
20 bar
Nominal range
(FSO)
Minimum set
range
Vertical spacing
of diaphragm
seals.
Maximum configurable range dependent
on the actual vertical spacing of
diaphragm seals. (m)
Static
pressure
limit
-160...160 mbar
0,1 mH2O
1,7m
[1,6+( vertical spacing of sealsx94)]mH2O
40bar
-0,5...0,5 bar
0.5 mH2O
6m
[5+(vertical spacing of sealsx1,04)]mH2O
40bar
-1,6...2 bar
1,5 mH2O
15m
[20+(vertical spacing of sealsx1,04)]mH2O
40bar
-1,6...16 bar
1bar
15m
16bar
40bar
i
G1/4-type connector with G1/4 thread,
1/2"NPT -type connector with 1/2"NPT tread,
R1/2-type connector with R1/2 tread,
CG1/2-type connector with G1/2 tread and flush diaphragm,
other connection types by arrangement.
5.3. DPR-2000ALW, DPR-2200ALW Measurement ranges and metrological
parameters.
5.3.1. DPR-2000ALW, Measurement ranges
5.3.2. DPR-2200ALW, Measurement ranges
The maximum vertical diaphragm seal spacing shown in the table applies to level measurement,
ensuring that it is possible to set the zero point of the transmitter when the tank is empty.
For measurements of density or phase boundaries (in the sugar and chemical industries and in
refineries) the vertical spacing of the diaphragm seals can be larger.
Accuracy ± 0,075% (FSO) for the DPR-2000ALW nominal range
Long term stability accuracy / 3 years
Error due to supply voltage changes ± 0,002%(FSO)/1V
Thermal error ± 0,08%(FSO)/10ºC
Thermal error for the whole thermal
compensation range ± 0,3%(FSO)
Zero shift error for static pressure* ± 0,08 % (FSO)/10bar
± 0,01 % (FSO)/10bar (for range n°4)
± 0,03 % (FSO)/10bar (for range n°5, 6)
Cut-off on radical characteristic curve up to10% of flow.
* zeroing in static pressure conditions with zero differential pressure eliminate this error.
5.3.4. DPR-2000ALW, Pressure Connectors
DPR-2000/ALW– C-type connector to mount together with a valve manifold see fig.9,
DPR-2000/ALW with single direct diaphragm seal – as in the example (fig.10) or with other diaphragm seals in
accordance with “DIAPHRAGM SEALS” catalogue cards.
0,1 % (FSO)/ 10C, max 0,4 % (FSO) for the whole thermal compensation
range
Thermal compensation range
-10 … 700C
Additional electronic damping
0...60 s
N
1
2
Nominal range
0... – 6000 mmH2O
0... – 1600 mmH2O
Minimum set range
600 mmH2O
160 mmH2O
Static pressure limit
40 bar
Nominal range N
1
2
Accuracy for basic range
± 0,16 %
± 0,2 %
Accuracy for minimum range
± 0,5 %
± 0,6 %
temperature error
0,4 % for temperatures –25...+80°C
Zero shift error from static pressure *
0,08 % / 10bar
0,1 % / 10bar
5.4. DPR–2000GALW, Measurement ranges and metrological parameters.
5.4.1 DPR–2000GALW. Measurement ranges
5.4.2. DPR–2000GALW. Metrologicalparameters.
5.4.3. DPR–2000GALW. Construction materials
M20x1,5/6x1 adapter brass
Valve manifold ss316L
Valve manifold adapter ss316L
¼ NPT connector brass, ss316L or galvanized St3S carbon steel
(Other materials as given in 5.1.3 for DPR...).
5.4.4. DPR–2000GALW. Pressure Connectors
- The terminals fit adapted to ø 6x1 plastic tubes,
- Valve manifold adapter or ¼ NPT connector- (see p. 8.3. and fig.17).
5.5. DPR–2000YALW. Measurement ranges and metrological parameters.
5.5.1. DPR–2000YALW. Measurement ranges.
5.5.2. DPR–2000YALW. Metrological parameters.
* zeroing in static pressure conditions with zero differential pressure eliminate this error.
Medium density range – up to 1,1 g/cm
– over 1,1 g/cm
3
– (standard version)
3
– (special version by arrangement with DELTA CONTROLS)
A 15 IOM-DPCDPR-A: FEB 2014
i
6. CONSTRUCTION
6.1. Measurement Principles, Electronic System.
DPC... electronic pressure transmitters and DPR... electronic differential pressure transmitters work by
converting changes in the resistance of a piezoresistance bridge, which are proportional to the measured
pressure, into a standard current signal. The active sensing element is a silicon diaphragm with piezoresistors,
separated from the medium by a sealing diaphragm and manometric fluid. The electronic system digitally
processes the measurement signal and generates output signals: an analogue 4÷20 mA signal with a digital
communication signal.
A block diagram of the transmitter is presented in Figure 1. At the circuit input two analogue signals are provide:
the measured pressure reflecting and the sensing module temperature. These signals are digitalized and
provide to a microprocessor input which controls the transmitter’s operation. Using input data during the
production process adjusts for thermal errors and carries out linearization. After digital processing, the signal is
converted into an analogue 4÷20mA current signal again, with a superimposed digital communication signal.
For communication with the transmitter via the signal line a special Delta Controls KAP communicator, or a
computer meeting the requirements given in 10.2.4, are used.
The transmitter’s output is fitted with a radio-noise filter and other elements protecting against ESD.
6.2. Construction.
The basic units of transmitter are: measuring sensor, in which pressure signal is converted into electric signal,
and electronic units, transforming signal from measuring sensor into unified output signal.
DPC..., DPR... transmitters are equipped in LCD display with LED back lighting, enabling reading two the
process variables simultaneously as well as the unit process variable reading. The electronic board is closed in
poly-carbonate casing. The casing construction enables turning of display by
On the electronic casing the set of buttons is placed, used to local adjustment.
The transmitters construction enables connecting of the separately compensated measuring sensor to
separately compensated electronic board enables fast servicing at the plant.
The electronic circuit of sensor has a galvanic separation from measuring line. Thanks of that construction the
measurement susceptibility at interferences is reduced as well as the enlarged safety of work in the Ex and
flameproof applications.
In dependence from needs we can choose a needed bank of coefficients memory for transmitter work. DPC..., DPR...transmitters monitor work of their equipment as well as the calculation correctness and in case of rises
of incorrigibility inform about mistakes displaying the announcement on LCD screen as well as putting out the
alarm current in current loop.
6.2.1. The pressure connectors may be fitted to the DPC... sensing module as in figures 5a, 6a, 7a, 8 and other.
The DPR… transmitters have the sensing modules with two P-type connectors, or C-type connecting covers for
installation on a valve manifold (figure 9). The sensing modules, for both types, are equipped with a diaphragm
separating the internal part of the head from the measuring medium.
6.2.2. For measuring the pressure of dense, chemically reactive or hot media, the transmitter may be
additionally fitted with various types of diaphragm seal depending on the type of medium and the
conditions in which measurement is carried out (see catalogue cards “Diaphragm Seals).
The diaphragm seal transmits the pressure obtained from the medium. The pressure is transmitted via a
manometric fluid which fills the space between the diaphragm of the seal and the diaphragm of the
sensing module. In the case of remote diaphragm seals, pressure is transmitted via a capillary linking
the transmitter’s sensing module to the diaphragm seal. The seals construction depends on the
medium properties and operating conditions for which they are intended.
Technical data relating to the diaphragm seals’ dimensions and operating conditions can be found in catalogue cards “DIAPHRAGM SEALS”.
6.2.3. The DPR… transmitters may be fitted with an single direct diaphragm seal, mounted on the “+” pressure
input of the sensing module, while the “–” input is a ¼NPT F connector (fig.10).
The DPR-2200ALW transmitter is fitted with two diaphragm seals and can be produced in two versions:
- with one direct diaphragm seal and one remote diaphragm seal (fig.15);
- with two remote diaphragm seals (fig.14).
A 16 IOM-DPCDPR-A: FEB 2014
i
6.2.4. In the case of the DPR-2000GALW transmitters, the sensing module is located inside the transmitter
casing. It is designed for the measurement of low pressures of non-aggressive gases, with a permitted
overpressure of 1bar (or 350mbar). The basic (economy) version of this transmitter has ø6x1 elastic tubes
terminals fitting, while the industrial version has adapters as shown in fig. 17.
6.2.5. DPR-2000YALW smart level probe is equipped in diaphragm seal and flange to fixing on tank.
7. PLACE OF INSTALLATION
7.1. General recommendations
7.1.1. The smart pressure transmitter and differential pressure transmitter can be installed both indoors and
outdoors. It is recommended that transmitters intended for outdoor use be placed in a box or under cover.
7.1.2. The place of installation should be chosen in such a way as to allow access to the device and to protect it
from mechanical damage. In planning the installation of the transmitter and configuration of the impulse lines,
attention should be paid to the following requirements:
- The impulse lines should be as short as possible, with a sufficiently large cross-section, and free of
sharp bends, in order to prevent blockages;
- Where the medium is a gas, the transmitters should be installed above the measuring point, so that
condensation flows down towards the site of the pressure measurement; where the medium is a liquid
or where a protective liquid is used, the transmitters should be installed below the place where the
pressure measurement is taken;
- The impulse lines should be inclined at a gradient of at least 10cm/m;
- The levels of filling liquid in the impulse lines should be equal or kept constant difference,
- The configuration of the impulse lines and the valve connection system should be chosen with regard
to the measurement conditions and to requirements such as the need to reset the transmitters in
position and the need for access to the impulse lines during water or gas removal and flushing.
7.1.3. Where there is a risk of heavy objects hitting the instrument (resulting, in extreme cases, in
a part of the system with transmitters being torn off and medium leakage), appropriate means of
protection should be applied for safety reasons and to avoid the possibility of sparkling or other,
more appropriate location should be selected for the transmitter.
7.1.4. Attention should also be paid to possible installation faults which may lead to measurement errors, such
as connections which are not tight, sediment blockage in lines which are too narrow, gas bubbles in a liquid line
or liquid column in a gas line etc.
7.2. Low Ambient Temperature.
When the solidification point of the liquid whose pressure is being measured is higher than the
ambient temperature, steps should be taken to protect the measurement apparatus from freezing
effects.
This is particularly important in the case open-air installations.
Protection is obtained by filling the impulse lines with a mixture of ethylene glycol and water, or another liquid
whose solidification point does not exceed the ambient temperature. Thermal insulation can protect the
transmitter casing and lines only from brief exposure to low temperatures. Where the temperature is very low,
the transmitter and impulse lines should be heated.
7.3. High Medium Temperature.
The DPC..., DPR... transmitters may be used to measure media with temperatures of up to 120°C. To protect the
sensing module from temperatures higher then 120ºC, long impulse lines are used to disperse the heat and to
lower the temperature of the sensing module.
Where it is not possible to use impulse lines of the required length, DPC..., DPR... transmitters with remote
diaphragm seals should be used (see “DIAPHRAGM SEALS ”catalogue cards).
Data as per Appendix Exi or Appendix Exd.02 apply for the Ex or Exd version.
A 17 IOM-DPCDPR-A: FEB 2014
i
7.4. Mechanical Vibration, Corrosive Media.
7.4.1. Transmitters should correctly work with vibrations with amplitudes to 1,6 mm and accelerations to 4g.
If strong vibrations are carried via the pressure line and disturb of measuring, use should be made of elastic
pulse lines or transmitters with a remote diaphragm seal.
7.4.2. Transmitters should not be installed in places where the diaphragm, made of 316L steel
00H17N14M2), would be subject to corrosion by the medium being measured. If possible, transmitters
with diaphragms made of Hastelloy C276 should be used, or other means of protection applied (e.g. in
the form of a separating liquid) or transmitters with diaphragm seals adapted for measuring aggressive
mediums according to “DIAPHRAGM SEALS” catalogue cards should be used).
8. INSTALLATION AND MECHANICAL CONNECTIONS
The DPC..., DPR... transmitters can operate in any position.
When installed on an object with a high-temperature medium, it is advantageous to mount the transmitter
in a horizontal position or downwards, in such a way that the transmitter is kept away from the rising hot
air.
For the small measurement ranges, the reading can be affected by the transmitter position, and by the
impulse lines configuration, or the way in which they are filled with liquid. This error can be corrected
using the zero-setting function.
8.1. DPC... Installation and connections
8.1.1. The DPC... transmitters can be mounted directly on the rigid impulse lines.
For used connectors as in figures 5a, 6a and 7a, it is recommended that connection sockets be used as shown
in figure 5b, 6b, 7b or 7c. It is recommended that sockets labeled “Socket CG1” and „Socket CG1/2” Fig. 8 are
used for CG1 and CG1/2 connections, respectively.
Besides, there are adapters for standard DIN50, (DIN40, DIN25, Clamp2”, Clamp1,5”, Clamp1”) type connections
provided for readouts carried out in aseptic conditions using transmitters with CM30x2 connection.
There are gaskets provided for every transmitter with P, CM30x2, CG1, CG1/2 and GP type connections.
The gasket material is selected based on the pressure value, temperature and the type of the medium.
8.1.2. If the pressure is applied via a flexible plastic tube, the transmitter should be mounted on a support with
Red Ø6-M reduction.
The types of the impulse tubes (Fig.21) are to be selected depending on the pressure measured value and the
medium temperature.
8.1.3. Tighten the transmitter in the socket with a torque suitable for the type of the gasket used and the
pressure measured.
8.1.4. The DPC… transmitter can be installed using a universal “AL” holder allowing to mount the transmitter in
any position on the support or a horizontal or vertical pipe Ø35... Ø65 (Fig. 16).
8.2. DPR... Installation and connections
8.2.1. The DPR … transmitters can be mounted directly on rigid impulse lines.
To connect the transmitter basic versions, with two M20 x 1.5 connectors (P-type connector), can use (for
example) straight connecting elements with C type nuts. If elastic impulse lines are used, the transmitter should
be additionally fastened to a pipe, panel or supporting construction.
8.2.2. The DPR-2000ALW and DPR-2200ALW can be installed using the ø25 Fastener (fig.11) on a ø25 pipe
or on a flat surface using an angle bracket.
8.2.3. The DPR-2000ALW with connecting cover (C-type connector) (fig.9) are designed for installation on
3-valve or 5-valve manifolds to a 2” pipe or to a flat surface using “C-2” holder (fig.12), (fig.13).
8.3. DPR-2000GALW. Installation and connections
8.3.1. The “economy” version of the DPR-2000G transmitter can be mounted on a wall, panel or other stable
construction, using a clamp with Ø9 holes (Fig.17). The transmitter is fitted with connectors which fit to a Ø6x1
elastic impulse tube. When the measuring impulse is transmitted via a metal terminal with M20 x 1.5 connector,
an adapter is used between the M20 x 1.5 thread and the Ø6x1 terminal.
Transmitters should be installed in a vertical position. The way of impulse line leading should enable the
vapour flowing towards the pipeline. Where there is a significant difference between the height at which the
transmitter is mounted and the height of the impulse source, particularly if the measurement range is small, the
reading may fluctuate depending on the temperature difference between the impulse lines. This effect can be
reduced by ensuring that the impulse lines run side by side.
A 18 IOM-DPCDPR-A: FEB 2014
i
i
i
8.3.2. The DPR-2000GALW transmitter can also be fitted with an adapter (Fig.17) creating a C-type connector,
designed for installation on a 3-valve or 5-valve manifold. Delta Controls can also supply ready transmitters
mounted on valves.
8.4. DPR-2000YALW. Installation and connections
The DPR-2000YALW level probes installed in places where liquid levels are measured in closed tanks, with
access to medium from top of tank as fig.15 and 10.2.6. Level probes should be installed in a vertical position.
Pressure may be transmitted to the installed device only after checking that it has a measurement
range which properly corresponds to the value of the measured pressure, that gaskets have been
properly selected and fitted, and the connectors have been properly screwed tight.
Attempts to undo the screws or fixing connector pipes on a transmitter under pressure may
cause the medium to leak and create hazards for the personnel.
When disassembling the transmitter, it is necessary to disconnect it from the process pressure or
bring the pressure to atmospheric level, and to take particular care and precautions in case of
media which are highly reactive, caustic, explosive or otherwise hazardous to personnel.
If necessary, rinse out this part of the system.
Transmitters with flange diaphragm seals are to be installed on the corresponding counter flanges on the
facility.
It is recommended that the user matches the screw joints material to the pressure, temperature, flange
material and seal to ensure tightness of the flange joint in the expected operating conditions..
Screws complying with ISO 261 are to be used for flanges used in the DPC..., DPR... transmitters.
Additional data concerning the diaphragm seals are specified in the “DIAPHRAGM SEALS” catalogue cards.
9. ELECTRICAL CONNECTION
9.1. General recommendations
9.1.1. It is recommended that twisted pair cabling be used for the signal lines. If the transmitter and signal line
are subject to a large amount of electromagnetic interference, then shield pair cable should be used. The signal
wires should not run alongside network power supply cables or near to large electrically-powered devices.
The devices used together with the transmitters should be resistant to electromagnetic interference from the
transmission line in accordance with compatibility requirements. It is also beneficial to use anti-interference
filters on the primary side of the transformers, the power supplies used for the transmitters and apparatus used
in conjunction with them.
9.1.2. Wet or rising damp inside transmitter can cause its damage.
When the isolation of the wires in the packing gland is ineffective (for example, when single
wires are used) the opening of the gland should be carefully sealed with an elastic sealing
compound to obtain IP66 protection. It is useful to form the segment of the signal wire leading
to the packing gland into a protective loop to prevent condensation from running down in the
direction of the gland.
9.2. Electrical connections for DPC..., DPR...
The DPC..., DPR... transmitters are to be connected as shown in fig. 2a – 2d.
In DPC..., DPR... transmitters, a 240Ω resistor is permanently fitted in series in the transmitter’s current
circuit and blocked up with jumper between <SIGNAL –> and <TEST –> as shown in fig.2a and 2b.
When the resistance in the current loop is lower than 240Ω it is necessary to jumper disassemble to
Hart communication.
9.3. Protection from excess voltage
9.3.1. The transmitters may be in danger from excess voltage caused by connection faults or atmospheric
electrical discharge.
Protection from excess voltage between the wires of the transmission line is provided by TVS diodes installed in
all types of transmitter (see the table, column 2).
A 19 IOM-DPCDPR-A: FEB 2014
1
2
3
Type of
transmitter
Protection between wires (TVS
diodes) – permitted voltage
Protection between wires and earth and/or casing –
type of protection, permitted voltage
DPC...,
DPR...
68V DC
(39V DC for Exi version)
Plasma surge arresters - 230V DC
(Not applicable to Exd version).
i
9.3.2. In order to protect against excess voltage between the transmission line and the casing or earth (not
prevented by the diodes connected between the transmission wires), additional protection is provided in the
form of plasma surge arresters (see the table, column 3).
Also external protective devices may be used, e.g. the UZ-2 Delta Controls system, or others. When the
transmission lines are long, it is advantageous to use one protective device near the transmitter (or inside it), and
another near entry points to other devices used in conjunction with it.
Internal protection of transmitters:
9.3.3. The voltage in the protective elements must not exceed the maximum permitted values given in columns
2 and 3 of the table.
The insulation test voltages (500V AC or 750V DC) given in 5.1.1 refer to transmitters plasma surge
arresters - such protection is not used in Exi versions of transmitters.
9.4. Earthing
The transmitters are fitted with internal and external earth terminals.
10. SETTING AND REGULATION
DPC..., DPR... transmitters are factory calibrated to the range stated in the order or to the basic range.
After installation, the transmitter’s zero-point may move and require adjustment.
This applies particularly in cases where the measurement range is small, where the impulse lines are filled with
a separating liquid or where DPC..., DPR... transmitters are used with remote diaphragm seals.
10.1. Transmitter Range,Basic Range. Definitions
10.1.1. The maximum range of pressure, or differential pressure, which the transmitter can measure is called
the “basic range” (for specifications of basic ranges see section 5.2.1, 5.3.1, 5.3.2, 5.4.1, 5.5.1).
The width of the basic range is the difference between the upper and lower limits of the basic range.
The internal characteristic conversion curve for the basic range is coded in the transmitter’s memory.
This is the reference curve used when making any adjustments which affect the transmitter’s output signal.
10.1.2. When the transmitter is in use the term “set range” is used. The set range is the range whose lower
end-point corresponds to an output current of 4mA and whose upper end-point corresponds to a current of
20mA (or 20mA and 4mA respectively when the conversion curve is inverted).
The set range may cover the whole of the basic range or only a part of it.
The width of the set range is the difference between its upper and lower end-points.
The transmitter may be set to any range within the basic range of pressure values, subject to the restrictions set
out in the table in section 5.2.1, 5.3.1, 5.3.2, 5.4.1, and 5.5.1.
10.2. Configuration and Calibration
10.2.1. The transmitter has features which enable metrological and identification parameters to be set and
altered. The configurable metrological parameters affecting the transmitter’s output current include the
following:
a) unit in which the measured pressure is expressed on the display
b) upper end-point of the set range
c) lower end-point of the set range
d) time constant
e) type of characteristic curve: linear or radical
Parameters of an informational nature which cannot be altered include the following:
f) upper limit of the basic range
g) lower limit of the basic range
h) minimum range
A 20 IOM-DPCDPR-A: FEB 2014
10.2.2. Other identification parameters, not affecting the output signal, include: device address, device type
code, factory identification code, factory device code, number of preambles (3÷20), UCS, TSD, program
version, electronics version, flags, serial number, label tag, description tag, date tag, message, record number,
sensing module number.
The process of setting the parameters listed in 10.2.1 and 10.2.2 is called “Configuration”.
10.2.3. It is possible to carry out a “pressure zeroing” procedure, for example to compensate for
measurement deviation caused by a change in position during the transmitter installation.
The transmitter may also be calibrated, by taking readings with the input pressure controlled using a standard
device. This process and zero-point adjustment are called “Calibration”.
10.2.4. Configuration and Calibration of the transmitter are carried out using a Delta Controls KAP
communicator, certain Hart communicators or a PC with Hart/RS232 converter and Delta Controls “D-Soft”
software.
Together with the “D-SOFT” configuration software there is a „INTERVAL LINEARIZATION” software supplied
to enable the input of 21-point nonlinear functional characteristics to the transmitter.
A description of the functions of the KAP communicator is contained in the KAP Communicator Operating
Manual, and information on the Hart/RS232 converter can be found on the Hart/RS232/01 Converter
information sheet.
MID_WP→ [↓][roll down][↑][roll up]→ ◙ [set]BACK BACK
ON OFF
OFF ON
60 [S] 0 [S]
30 [S] 2 [S]
10 [S] 5 [S]
2 [S] 30 [S]
0 [S] 60 [S]
1.0 % 0.0 %
0.8 % 0.2 %
0.6 % 0.4 %
0.2 % 0.8 %
0.0 % 1.0 %
A 22 IOM-DPCDPR-A: FEB 2014
If the option of local configuration is active, operator can change transmitter set using buttons being below
display. The access to buttons will get after unscrewing the side cover. Then we can also change the display
position turning it with 900 angle position. (see fig. 4).
If the option of local configuration is active, operator can change transmitter set using buttons being below
display. To enter at the local set change of the work mode, you should press one button and hold its about 4s.
If using buttons can't change the transmitter configuration , the local transmitter configuration is switched of and
to its switching on is necessary to use the KAP 3 Calibrator.
The buttons are signed with symbols: [↑] [↓] [◙]
After pressing by 4 seconds any of buttons there will appear on display “EXIT”.
If we will confirm this announcement across pressing and holding button [[◙] by 1 sec, we will go out from the
local change of the MENU set. If we will not confirm, we can move in MENU and change interesting us
parameters. The time of pressing [↑]] [↓] [◙] has to be longer than 1s.
Pressing button [↑] moves up in tree's structure MENU
Pressing button [↓] moves down in tree's structure MENU
Pressing [◙]confirms choice and leads change.
|
EXIT (First announcement which will see after inclusion of Menu Local.
| If you will confirm this option, you will go out from Local Menu
| and you will come back to continue of measuring)
PV ZERO_________
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| |
| PV ZERO (Pressure zeroing. If you will confirm this option,
| transmitter will confirm the party of command
| by the "DONE" announcement or the proper number of error will
| notify.)
|
SET LRV_________ (The Setting of the range of the set LRV beginning) -(no change of span)
\
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| BY PRESsure (Setting LRV across setting pressure. If you will confirm this
| | option, transmitter will confirm the party of command by the
| | "DONE" announcement or the proper number of error will notify)
| |
| BY VALUE (Setting the LRV across inscribing of value.)
(After confirmation will display current LRV value before the passage
in mode of edition)
| 00000 (Introduce in sequence , digit after digit, 5 digital number with point
| or without point. After confirmation the last 5 digit of the parameter
| transmitter will confirm the party of command by the "DONE"
| announcement or the proper number of error will notify.
| The parameter will be written down in units "UNIT")
|
A 23 IOM-DPCDPR-A: FEB 2014
SET URV___ (The setting of the end of the set URV range) – (change of span)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| BY PRESsure (Setting URV across setting pressure. If you will confirm this
| | option, transmitter will confirm the party of command by the
| | "DONE" announcement or the proper number of error will notify
| |
| BY VALUe (Setting the URV across inscribing of value)
| \
| (After confirmation will display current URV value before the passage
in mode of edition)
| ↓
| ↓
| +/- (Choose and confirm sign introduced parameter)
| ↓
| 00000 (Introduce in sequence, digit after digit, 5 digital number with point
| or without point. After confirmation the last 5 digit of the parameter
| transmitter will confirm the party of command by the "DONE"
| announcement or the proper number of error will notify.
| The parameter will be written down in units "UNIT")
|
UNIT______
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following characteristics across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| IN_H2O
| IN_HG
| FT_H2O
| MM_H2O
| MM_HG
| PSI
| BAR
| MBAR
| G/SQCM
| KG/SQCM
| PA
| KPA
| TORR
| ATM
| M_H2O
| MPA
| INH20@4
| MMH2O@4
||
A 24 IOM-DPCDPR-A: FEB 2014
|DAMPING________ (Setting of the solid temporary suppression of the process variable)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following values time constant across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
|
| 0 [S]
| 2 [S]
| 5 [S]
| 10 [S]
| 30 [S]
| 60 [S]
||
TRANSFEr_______ (Setting of the current output form)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following characteristics across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| LINEAR (Linear)
| SQRT (square root)
| SPECIAL (user’s )
| SQUARE (square)
|
% SQRT______ (Square root characteristic cut-of point setting)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following percent value across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| 0.0 %
| 0.2 %
| 0.4 %
| 0.6 %
| 0.8 %
| 1.0 %
LCD1 VARiable__ (Type of the process variable displayed on LCD1)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following option across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| CURRENT (On LCD1 will displayed current value in current loop)
| |
| |
| PERCENT (The percent value output signal will displayed on LCD1)
A 25 IOM-DPCDPR-A: FEB 2014
|LCD2 VARiable(Type of the process variable displayed on LCD2)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following option across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| |
|PRESSURe (The pressure value will displayed on LCD2)
| |
| USER (The user’s units will displayed on LCD2)
| |
| |
| UNIT (The current unit or user’s unit alternately
| | with process variable will displayed on LCD2)
| |
| SENS_T* (The pressure sensor temperature in Celsius degrees
will displayed on LCD2)
| NO UNIT (The current unit or user’s unit alternately
| with process variable will not displayed on LCD2)
CPU_T* (The main electronics board temperature in Celsius degrees
will displayed on LCD2)
*) UNIT and NO UNIT sequence is enabled to the older solutions of transmitters , in solutions since
2011: SENS T and CPU T sequence is applicable.
LCD2 DP_________ (The process variable point position on LCD2)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following option across
| | longer press button ◙. After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| | |XXXXX
| |
| XXXXX
| |
| XXXXX
| |
| XXXXX
| |
| XXXXX
|
FACTORY________ (Come back to factory setting)
| \
| BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm the command as bellow across longer press
| | button ◙. After parameter confirmation transmitter will
| | confirm the party of command by the "DONE")
| |
| RECALL
|
A 26 IOM-DPCDPR-A: FEB 2014
|RESET____ (The program enforcement of the transmitter restart)
\
BACK (Return to Local Menu. If you will confirm this option,
| you will come back to main tree of Local Menu)
| |(Confirm the command as bellow across longer press
|button ◙. After parameter confirmation transmitter will |confirm the party of command by the "DONE")
|RESET
for transmitters with the display in accordance with EN 12405-1(MID)
MID_WP_________ (Lock modify the parameters associated with MID)
| \
| BACK (Back to the Local Menu. If you approve this option,
| | return back to the main menu Tree Local)
| |
| | (Submit one of the following through constant
| | ◙ pressing. Once approved, the parameter transmitter
| | will confirm receipt of the command message "DONE")
| |
| |
| ON (Lock Activation parameters affecting the metrology)
| |
| OFF (Turns lock parameters affecting the metrology)
A 27 IOM-DPCDPR-A: FEB 2014
10.2.5.2. Setting up a local LCD display
There 3 main displays are visible:
LCD1 – the current or guidance percent preset range display. In accordance with display configuration the
current value in 4 -20 mA current loop, or percent guidance preset range is possible to display.
LCD2 – the measured pressure digital value display; the calibrated pressure value according to user’s
units display; the process variable units or user’s units display; the MENUannouncement and other
information or warning announcement display. In the case the digital pressure value or the calibrated
pressure value display, the sign „–„ can be visible before displayed value. The decimal point position is
possible to set in local MENU or remotely. The pressure unit or user’s unit can be displayed.The
transmitter makes possible rescale on the user's individual the pressure value. To make this is necessary
with using communicator or PC software write the corresponding to beginning and to end values of setting
range as well as write the own unit name. After activating user's mode the rescale value will be visible on
display.
LCD3 – information display. During normal operation is designed for continuous display of the base unit or
the user units. In case of errors in the transmitter's work , it displays an error number. In manual mode, the
local change settings menu displays options of selecting the setting. It also displays errors related to the
implementation of commands in the local menu of the settings change.
Display backlighting - Local display is equipped in backlight, switching on and switching off with jumper
on electronic board. How to handle display backlight is shown in Figure 4a. Figure 4 shows how to change
the display position by rotation.
Warning!
Exceeding the basic transmitter measuring range over 50% range in the up or down is indicated
by " o V E r " or " u n d E r " in the display LCD2. Such situation is encountered most often when
overloaded a difference pressure transmitter, created when the large static pressure compared
to the pressure range will blockage or a leak in one of the capillaries.
After configuration it is important to protect the transducers using command HART [247].
During work transmitter should be safe prior to entries. This prevents accidental or intentional
changes configurational data. The protection function is accessible in KAP03 communicator, “DSoft's” software, as well as, in applying DD or DMT programs libraries.
A 28 IOM-DPCDPR-A: FEB 2014
Descriptions
EXIT return from the local Menu to the normal operation of the transmitter
UNIT menu process variable units. Options:
DAMPIN menu damping of process variable [s]. You can choose 0,2,5,10,30,60 [s]
TRANSF type of current output characteristic Menu. Options:
%SQRT menu of, point insensitivity of square root characteristics. To select 0%, 0.2%, 0.4%, 0.6%,
PVZERO pressure zeroing.
SETURV setting the upper range value by the done pressure
SETLRV setting the lower range of values set by the done pressure
RESET reboot your transmitter
LCD1VR assigning a process variable to LCD1. Options:
LCD2VR assigning a process variable to LCD2. Options:
Scaling of the user range and record of the user units can be made using a computer or
SENS_T sensor temperature value in the pressure header in °
CPU_T CPU electronics board temperature value - in º C
LCD2DP setting the decimal point position on LCD2. Options:
FACTOR back to factory settings (removing of current and pressure calibrations).
MID_WP blocking records / change the parameters associated with transmitter metrology
IN_H2O inches of water at a temperature of 68 ° Fahrenheit
IN_HG inches of mercury at a temperature of 68 ° Fahrenheit
FT_H2O foot of water a temperature of 68 ° Fahrenheit
MM_H2O mm of water at a temperature of 68 ° Fahrenheit
MM_HG mm of mercury at 0 ° C
PSI
BAR bar
MBAR millibar
G/SQCM grams per square centimetres
KG/SQCM kilogram per square centimetres, technical atmosphere
PA pascal
KPA kilopascal
TORR tor (mm Hg)
ATM physical atmosphere
M_H2O meter of water at 4 ° C
MPA megapascal
INH2O@4 inch of water at a temperature of 4 ° C
MMH2O@4 mm of water at 4 ° C
LINEAR linear
SQRT square root
SPECIA user’s special
SQUARE square
0.8%, 1.0% range
CURREN current in the line in [mA]
PERCEN percent of the set range - controling in%
PRESS pressure value in units UNIT
USER pressure value in user’s units
communicator, see → HART command No. 244.245
XXXXX·
XXXX·X
XXX·XX
XX·XXX
X·XXXX
In a situation where the value provided to display on the display LCD2 can not be
displayed properly due to the position of the decimal point, this is indicated by displaying
the four flashing dots • • • •. In this case, you must enter to the local menu setting and
move the decimal point respectively to the right.
ON switch on blocking
OFF switch of blocking
A 29 IOM-DPCDPR-A: FEB 2014
10.2.6. Local Menu, error reports.
During executing in Local Menu some functions, LCD2 announcement can be displayed on the screen.
The error displaying evidences about no realization of command of Local Menu.
The shortened description of errors announcements is showed below.
ERR_L07 [in_write_protected_mode]. Error will ensue out when we try to change setting in Local
Menu, but transmitter is protected before recording. To to make the change of setting with
Local Menu using, transmitter has to have the included service of Local Menu as well as
switched off protection before record. These parameters modification is possible by using
KAP -03 communicator, “D-SOFT” program or software using library EDDL.
default setting:
Local Menu service switched on
ERR_L09[applied_process_too_high]. Error will ensue out when given parameter (pressure) exceed admissible value. Zeroing or the range setting verifying is necessary.
ERR_L10[applied_process_too_low]. Error will ensue out when given parameter (pressure) will too low. Zeroing or the range setting verifying is necessary.
ERR_L14[span_too_small]. Error will ensue out when in result of setting range executing change the width of the range will be smaller than admissible.
ERR_L16[acces_restricted]. Error will ensue out when the service of Local Menu is switched off,
and the user tries to call out the Menu Local service. You should switch on the service of
Local Menu with the KAP-03 communicator, “D-SOFT” program, or software using library
EDDL.
Warning!, ERR_L16 announcement can be displayed as well by zeroing attempt of the
absolute transmitter .
WNG_L14[WARNING!, new Lower Range Value Pushed !] Error will ensue out when the end of range set ( the URV) change will cause the change of the range set beginning (LRV).
10.2.7. Remote configuration
Remote configuration is possible with KAP-XX communicator or PC software. Measuring circuit should be in accordance with the fig. 2.
protection before record switched off
A 30 IOM-DPCDPR-A: FEB 2014
Configuration of the DPR-2200ALW transmitters to measure the level of liquid in a tank.
Configuration of the DPR-2200ALW transmitters to measure density of liquids.
10.2.8. Configuration of the DPR-2200ALW transmitters to measure the level, density of liquid and phase
boundary
A 31 IOM-DPCDPR-A: FEB 2014
Example:
Determine the maximum vertical spacing of the seals for
the DPR-2200/-10…10kPa transmitter when measuring
the density of liquid between 0.6 and 1.2g/cm³. The
sealing system uses AK-20 silicone oil with a density of
0.945g/cm³.
A 32 IOM-DPCDPR-A: FEB 2014
i
Mechanical installation
On the flange of the tank
Upper equalization hole
Lower
equalization hole
Diaphragm
seal unit
Principle of operation
Measurement is carried out using a DPR-2000 differential
pressure transmitter, enabling compensation for static pressure
in the tank. The value processes is just the hydrostatic
pressure of the medium measured at the level of the
diaphragm of the lower seal. This pressure is the sum of the
hydrostatic pressure of the liquid and vapour phases of the
medium. In most practical measurement situations the density
of the vapour phase is negligibly small, and therefore the
measured hydrostatic pressure relates only to the height of the
liquid phase is significant (e.g. propane) the level found by the
method described can be treated as the theoretical level of the
liquid level obtained by adding the actual liquid phase to the
condensed vapour phase.
10.2.9. Configuration of the DPR-2200YALW smart level probes
11. INSPECTIONS AND SPARE PARTS.
11.1. Periodic service
Periodic inspections should be made in accordance with the regulations to which the user is subject. During
inspection, the pressure connectors should be checked for loose connections and leaks, the electrical
connectors should be checked with regard to tightness and the state of the gaskets, packing glands, and the
diaphragm seals should be checked for tarnishing and corrosion.
Check the characteristic conversion curve by following the procedures for “Calibration” and, where appropriate,
“Configuration”.
11.2. Periodic services
If the transmitters are installed in a location where they may be exposed to mechanical damage, excess
pressure, hydraulic impulses or excess voltage, or the diaphragm may be in danger from sedimentation,
crystallization or erosion, inspections should be carried out as required.
Where it is found that the signal in the transmission line is absent or its value is incorrect, a check should
be made on the line and its terminal connections.
Check whether the values of the supply voltage and load resistance are correct.
If a communicator is connected to the power supply line of the transmitter, a fault in the line may be
indicated by the message “No response” or “Check connection”.
If the line is in order, check the operation of the transmitter.
A 33 IOM-DPCDPR-A: FEB 2014
i
11.3. Cleaning the Diaphragm Seal, Overloading Damage
11.3.1. Sediment and dirt which have formed on the diaphragm in the course of operation must not be removed
by mechanical means, as this may damage both the diaphragm and the transmitter itself.
The only permitted method is the dissolving of sediment.
11.3.2. Sometimes transmitters malfunction due to damage caused by overloading, e.g. in case of:
- application of excessive pressure;
- freezing or solidification of the medium;
- action of a hard object, such as a screwdriver, on the diaphragm.
Usually in such cases the symptoms are such that the output current falls below 4mA or rises above 20mA, and
the transmitter fails to respond to input pressure.
11.4. Spare parts.
Parts of the transmitter which may be subject to wear or damage and require replacement: cover gasket
Other listed parts, due to the specific features and requirements of explosion-protected devices,
may be replaced only by the manufacturer or by a firm authorized by the manufacturer.
12. PACKING, STORAGE AND TRANSPORT.
The transmitters should be packed singly or in sets, in such a way as to protect them from damage during
transportation.
The transmitters should be stored in multiple packs under cover, in a place free of vapours and reactive
substances, with an air temperature between +5°C and +40°C, and relative humidity of not more than 85%.
Transmitters with uncovered diaphragm or seal connectors, stored without packaging, should have covers to
prevent damage to the diaphragm.
During transportation, the transmitters should be packed and secured so as to prevent them from shifting.
Any means of transport may be used, provided direct atmospheric effects are eliminated.
13. GUARANTEE
The manufacturer guarantees the proper operation of the transmitters for a period of 24 months from the date of
purchase and servicing provided under the guarantee and following the guarantee period. In the case of special
versions, the guarantee period shall be agreed by the manufacturer and the user, but shall not be less than 12
months.
14. ADDITIONAL INFORMATION
The manufacturer reserves the right to make constructional and technological changes which do not lower the
quality of the transmitters.
14.1. Related documents.
- “KAP–Communicator User’s Manual” supplied with the Delta Controls communicator.
Communicator or modem electrical connections to transmitter measuring lines.
For successful communication with transmitter the resistance in measuring loop, behind connected
device to communication, should be higher than 250Ω. If necessary install the additional resistor in the
line. The communicator or modem connecting ways to the measuring loop are presented at diagrams.
During increasing of resistance in the measure loop at making the good transmission, is necessary to
make sure that the tension falls at sum resistances in the loop don't lower minimum tension at transmitter
terminals. (see p.5.1.1)
Fig.2. Electrical connections for DPC...,DPR... transmitters
Fig.2a. The link of transmitter and communicator or modem to current line by the switch box ( in case of the
resistance in current loop is higher than 250Ω).
A 35 IOM-DPCDPR-A: FEB 2014
A 36 IOM-DPCDPR-A: FEB 2014
+TEST
-TEST
-
+
SIGNAL
240
Ro
mA
4÷20 mA
+
_
F1
.
32
VWX
MNO
DEF
YZ#
5 6
PQR*+/
9
GHI
80
@%&
1
STU
4
JKL
ABC
7
RE PV F4PF
F2 F3 F4
RAPORT
BELL
202
RS 232
Communicator
Current loop
JUMPER
Power
supply
BELL
202
RS 232
Communicator
Current loop
+TEST
-TEST
-
+
SIGNAL
240
4÷20 mA
+
_
F1
.
32
VWX
MNO
DEF
YZ#
5 6
PQR*+/
9
GHI
80
@%&
1
STU
4
JKL
ABC
7
RE PV F4PF
F2 F3 F4
RAPORT
Ro
mA
JUMPER
Power
supply
To measure the transmitter current without
disconnecting the measuring loop, connect
a milliammeter to control terminals <Test ->
and <Test +>.
D-Soft
D-Soft
Fig.2b. The link of transmitter and communicator or modem to <SIGNAL+> <SIGNAL-> transmitter terminals in
case of the resistance in current loop is higher than 250Ω.
Fig.2c. The link of transmitter and communicator or modem to <SIGNAL+> <TEST+> transmitter terminals in
case of the resistance in current loop is smaller than 250Ω.
A 37 IOM-DPCDPR-A: FEB 2014
1
STU
4
JKL
ABC
7
RE PV F4PF
F2 F3 F4
RAPORT
BELL
202
RS 232
+TEST
-TEST
-
+
SIGNAL
240
4÷20 mA
+
_
F1
.
32
VWX
MNO
DEF
YZ#
5 6
PQR*+/
9
GHI
80
@%&
Communicator
Current loop
JUMPER
Ro
mA
Power
supply
133
38,5
91,5
M20x1,5
Cable
packing gland
The electronic
circuits
and display side
terminals side
The electrical
Lock preventing
of the casing
rotation
Earthing terminal
FIELD TERMINALS
18132
2 x M6
18
D-Soft
Fig.2d. The link of transmitter and communicator or modem to <SIGNAL+> <SIGNAL-> transmitter terminals in
case of the resistance in current loop is smaller than 250Ω.
If Ro in current loop is lower than 250Ω is necessary to connect 240Ω resistor to current loop by
remove jumper from <SIGNAL-> and <TEST-> terminals.
After communication jumper should cam back at its place.
Fig. 3. DPC-2000ALW smart pressure transmitter
A 38 IOM-DPCDPR-A: FEB 2014
Jumper in radial position
(as at photo) –back lighting
off; jumper in circular
position –back lighting on.
±180o with 900 pitch
unscrew the
display cover
and casing
display screws
Configuration
buttons
Move the electronic unit from transmitter casing, take
up the upper part of the casing with display from the
catch and revolve its to left or to right to the display
setting at needed position.
Rotation possibility ±1800 with 90° pitch.
Screw on the display unit screws and display cover.