DeLonghi CPC206AU, CPC306AU, CPC505AU Operating And Installation Manual

Page 1
OPERATING AND INSTALLATION MANUAL
SINGLE SPLIT AIR-CONDITIONER AND HEAT PUMP
Please carefully read this manual before operating the appliance.
eco
Page 2
INDEX
SINGLE SPLIT
1English 11/2002
Safety standards 2
Identification of the parts 4
Remote control 6
Operating modes 8
AUTO mode 9
TIMER mode 9
DRY mode 10
SLEEP mode 10
Maintenance 11
Troubleshooting 12
Installation instructions 13
Installation of the indoor unit 15
Installation of the outdoor unit 19
Venting the air 19
Note 20
Useful information 20
U AI
U AI
U A
I
U AI
U A
I
U AI
U A
I
U AI
U AI
U A
I
AI
A
I
AI
A
I
U AI
U A
I
U User I Installer A Service
Page 3
SINGLE SPLIT
2 English 11/2002
Use the power supply voltage shown on the rating plate. Keep the power switch or plug clean. Connect the power cable correctly and securely to the out­let, avoiding the risk of electric shock or fire due to insufficient contact.
Check that the outlet is suitable for the plug, oth­erwise have the outlet replaced. Do not use the power switch or pull out the plug to switch the appliance off when operating. This may cause fires due to sparks,etc.
The user must contact qualified personnel to earth the appliance, in compliance with the legis­lation in force, and to install a thermal-magnetic circuit breaker.
Do not bend, pull or press the power cable, as it may break.Electric shock or fire are usually caused by damaged power cables. The power cable must only be replaced by special­ist technicians.
Do not use power supply cables that are too long,or multiple adapters.
Do not operate the air-conditioner with wet hands;this may cause electric shock.
Do not modify or alter the characteristics of the appliance in any wa y. Contact the Service Centres authorised by the Manufacturer for all repairs.Incorrect repair may cause electric shock,etc.
Make sure the appliance is disconnected from the power supply when not used for extend­ed periods, and before performing any clean­ing or maintenance operations.
Do not install the appliance in environments where the air may contain gases,oil or sulphur, or near sources of heat.
Check that the base of the outdoor unit is installed securely.
This appliance must only be used by adults; do not allow children to play with the appliance. Do not climb onto or rest objects on the out­door unit.
Never insert sticks or tools into the appliance. This may cause injuries.
Do not block the air inlet or outlet of either the indoor or outdoor unit. Extended exposure to cold air is a health risk.
If smoke or a smell of burning is detected,imme­diately disconnect power and contact the Service Centre.
SAFETY STANDARDS AND WARNINGS
U I A
Page 4
SINGLE SPLIT
3English 11/2002
Keep the appliance at least 50cm from flamma­ble substances (alcohol, etc.) or from pres­surised containers (e.g.spray cans).
Selecting the most suitable temperature will avoid damaging the appliance.
The direction of air flow must be adjusted correct­ly.The louvers must be adjusted downwards in heating mode,and upwards in cooling mode.
Do not leave doors and windows open when the air-conditioner is operating f or long periods.
Do not aim the air stream directly at plants or animals. Do not spray water onto the air-conditioner .
This appliance has been designed to air-condition the home and must not be used for other pur­poses,such as drying clothes, cooling food,etc.
If the appliance is used in areas without the renewal of fresh air, precautions must be taken to prevent any leaks of refrigerant gas from stagnating in the environment and creating the risk of fire. Do not rest heavy or hot objects on the appliance.
The packing materials are recyclable.It is therefore recommended to place them in suitable containers for separate waste disposal. At the end of its working life, take the air-condi­tioner to a special waste disposal centre.
Only use the air-conditioner as shown in this booklet. These instructions are not intended to cover every possible situation that may arise. Common sense and prudence must be applied in the installation,operation and conservation of all household appliances.
Lowers
the inside temperature by 5°C from
the outside
temperature
Working temperature range
Maximum cooling
Maximum heating
Minimum cooling
Minimum heating
36
Indoor side DB()
30
16
16
45
Outdoor side DB()
27
18
-10
Page 5
SINGLE SPLIT
4 English 11/2002
IDENTIFICATION OF THE PARTS
AUTO TEST RUN STOP
AUTO STOP
1
4
5
11
10
7
9
6
8
12
4
4
14
13
2
3
Air inlet
INDOOR UNIT
OUTDOOR UNIT
The above figure represents a simplified layout of the appliance and may not correspond to the appearance of the unit actually purchased.
U I A
Air outlet
Air inlet
Air outlet
1Front panel 2 Air filter 3 Electrostatic filter (optional) 4 Manual switch 5 Cable panel 6 Activated carbon filter 7 Louvers 8 Signal receiver 9 LED display 10 Power plug 11 Drain hose 12 Remote control 13 Handle 14 Air outlet grill
4
AUTO
STOP
RUN
TEST
Page 6
SINGLE SPLIT
5English 11/2002
1
2
3
4
5
AUTO TEST RUN STOP
1. Manual switch
This is used to start the appliance if the remote con­trol is not working.*
2. Heating indicator
This comes on when the appliance is in heating mode.
3. Cooling indicator
This comes on when the appliance is in cooling mode.
4. Operation indicator
This comes on when the appliance is operating.
5. Signal receiver
Receives the signals from the remote control.
OPERA TION AND DISPLA Y
The shape and the position of the switches and indicators may change according to the model, howe v er their functions r emain the same.
Power on when grill open.
*This operation must be carried out by spe­cialist technicians.
Page 7
REMOTE CONTROL
SINGLE SPLIT
6 English 11/2002
3 4
1
5 6
7
10
2
8
9
1. Liquid crystal display
Displays all the operating modes.
2. MODE button
Used to select the operating mode.
3. FAN button
Used to set the fan speed, in sequence , to automatic, low,medium,high.
4. SLEEP button
Used to set or cancel SLEEP mode.
5. SWING button
Used to start or stop the movement of the vertical louvers.
6. TIMER ON button
When the appliance is off, this button is used to switch the air-conditioner on automatically.
7-8. ROOM TEMPERATURE SETTING buttons
Used to set the room temperature.
9. TIMER OFF button
When the appliance is on, this button is used to switch the air-conditioner off automatically.
10. button
Used to switch appliance on or off.
Meaning of the symbols shown on the liquid crystal display:
Automatic fan speed Low fan speed Medium fan speed High fan speed Cooling indicator Dehumidification indicator Fan only operation indicator Heating indicator Automatic mode indicator SLEEP indicator Louver swing indicator
The display on the remote control remains on even when the unit is off.
The remote control sends signals to the appliance.
U I A
Page 8
SINGLE SPLIT
7English 11/2002
HOW T O FIT THE BA TTERIES
• Remove the cover of the battery compartment in the direction of the arrow.
• Fit the new batteries, making sure the (+) and (-) signs on the battery match correctly.
• Put the cover back on by sliding it into position.
Use 2 x R03 AAA (1.5 V) batteries. Do not use rechargeable batteries. Replace the used batteries with new batter­ies of the same type when the display is no longer visible. The batteries last around one year. The batteries in the remote control must be disposed of appropriately according to the legislation in force in the country concerned.
TIPS ON STORING AND USING THE REMOTE CONTROL
The remote control can be stored in a special support mounted on the wall.
The remote control holder is standard
HOW T O USE THE REMO TE CONTROL
To switch the air-conditioner on, aim the remote control towards the signal receiver. The remote control will work at a distance of up to 8 metres from the indoor unit.
Store the remote control at least 1m from television sets or other electrical appliances.
Signal receiver
Remote control holder
Page 9
SINGLE SPLIT
8 English 11/2002
OPERATING MODES
OPERATING MODES
1. Selecting the operating mode
Each time that the MODE button is pressed the oper­ating mode is changed,in the following sequence:
FULL AUTO COOLING DRY FAN ONLY
HEATING
2. FAN mode
Each time that the FAN button is pressed,the speed is changed,in the following sequence: AUTO LOW MEDIUM HIGH
3. Setting the temperature
Press once to increase the set temperature by 1°C. Press once to decrease the set temperature by 1°C.
Range of temperature settings available: HEATING 16°C ~ 30°C COOLING 16°C ~ 30°C DEHUMIDIFICATION 16°C ~ 30°C FAN ONLY no setting allowed
4. Starting the appliance
Press the button .
When the unit is switched on it will start operating in the mode selected prior to being switched off.
5. Adjusting the air flow
Pressing the “SWING” button star ts moving the air flow louvers start automatically; pressing the “SWING” button again stops the louvers.
Do not move the vertical air flow louvers manually,as this may cause poor operation.If this happens, first turn the appliance off, then disconnect and reconnect it to the power supply.
Adjusting the horizontal air flow (manual)
Turn the louver sliders for the horizontal adjustment of the air outlet to change the angle of the air flow,as shown (the unit illustrated may be different from the air-condi­tioner you have purchased).
This operation must be carried out by specialist technicians.
1
2
5
4
3
3
U I A
Sliders for adjusting the horizontal air flow louvers.
Page 10
AUTOMATIC START
After having switched the appliance off, press the T-ON button to set the time you want the air-conditioner to switch back on; pressing the T-ON button again increases the time by 30 minutes,until a maximum of 24 hours from when the TIMER is set.
E.g.: If the setting is performed at 4 p.m. and the TIMER is set
to 2.5h, the appliance will start at 6.30 p.m.
When the unit is switched on it will start operating in the mode selected prior to being switched off.
AUTOMATIC STOP
When the appliance is on,press the T-OFF button to set the time you want the air-conditioner to switch off; pressing the T-ON button again increases the time by 30 minutes, until a maximum of 24 hours from when the TIMER is set.
E.g.: If the setting is performed at 8.30 p.m. and the TIMER
is set to 3.5h, the appliance will switch off at midnight.
AUTO MODE
SINGLE SPLIT
9English 11/2002
AUTO OPERATING MODES
Press the MODE button until displaying AUTO ();in this mode,the temperature and the fan speed are set auto­matically based on the actual room temperature.
The operating mode and the temperature setting depend on the room temperature.
In AUTO mode, the pre-set temperature is 25°C in cooling mode,while the fan speed may change.
2.5
U I A
TIMER MODE
U I A
23°C ~ 26°C FAN ONLY
higher than 26°C COOLING
Lower than 23°C HEATING
Room temperature Mode
Page 11
DRY MODE
SINGLE SPLIT
10 English 11/2002
SLEEP MODE
Press the MODE button until displaying the COOL () or DRY ( ) mode.
To set the requested temperature.
Press the SLEEP ():button:the set temperature will be increased by 1°C in one hour and 2°C in two hours. The appliance will then hold the temperature until switching off (after 6 hours).
DEHUMIDIFICATION MODE
Press the MODE button until displaying the DRY () mode. The appliance will start according to the room tempera­ture and the set temperature:
• If the room temperature is lower than the set tempera­ture, the compressor, the outdoor unit and the indoor unit will stop.
• If the room temperature is within ± 2°C of the set tem­perature, the appliance will start in dehumidification mode.
• If the room temperature is more than 2°C above the set temperature, the appliance automatically starts in cooling mode.
U I A
SLEEP MODE
U I A
Page 12
MAINTENANCE
SINGLE SPLIT
11English 11/2002
Unplug the appliance from the power outlet
To remove the front panel,pull it outwards,as
shown by the arrows in the figure
Replace the filters with the side marked as “FRONT”
facing the outside
Clean with a soft damp cloth,using water or
detergent,then dry in the shade.
Never use water at temperatures above 45°C,as the panel may be deformed or fade in colour.
Installation of the activated carbon filters*
- Remove the air filters
- Remove the new filters from the packaging
- Insert them in the special slots
- Reposition the air filters
Insert the front panel as shown by the arrows in
the figure
Cleaning the air filters
Open the front panel,grip the filter and lift it slightly,
then remove it.
Never use water at temperatures above 45°C,as the panel may be deformed or fade in colour.
To remove dust from the filter, use a vacuum cleaner or wash the filter in water and then leave it to dry in the shade.
The air filters should be cleaned every 3 weeks
These operations must be performed by spe­cialist technicians. * The carbon filters can’t be washed.
U I A
Air filter
Slot
Page 13
TROUBLESHOOTING
SINGLE SPLIT
12 English 11/2002
The appliance doesn't work
• Are the protection devices or fuses faulty?
Have the connections come loose or the cable unplugged?
• At times operation is stopped to protect the appliance.
• Is the voltage above 244V or below 206V?
• Is the TIMER-ON functions active?
Insufficient cold or hot air produced
• Is the temperature suitably set?
Are the outlets and inlets of the air-conditioner blocked?
• Is the air filter dirty?
• Is the fan speed set to the minimum?
• Are there other sources of heat in the room?
The appliance does not respond to
• Is the remote control near the indoor unit?
• Are the batteries in the remote control flat?
• Are there obstacles between the remote control and the signal receiver on the indoor unit?
Immediately switch off the air-conditioner and disconnect the power supply in the event of:
Strange noises during operation.
• Faulty fuses or switches.
• Sprays of water or objects inside the appliance.
• Hot cables or plugs.
• Very strong smell coming from the appliance.
Strange noises can be heard
• This noise is produced by the expansion or contrac­tion of the front panel due to the thermal variations, and does not indicate a problem.
Sprays of atomised water from
• This occurs when the air in the room cools down very quickly,for example in “COOLING” or “DEHUMIDIFI­CATION” mode.
The appliance doesn't work
• Once switched off the air-conditioner cannot be started for around 3 minutes
FAULT POSSIBLE CAUSE
Strange smell
• This smell may come from other sources,such as fur­niture or the like.
Sound of running water
• This derives from the flow of refrigerant in the air-con­ditioner,and is not a fault.
U I A
Wait
OFF
the air outlet
the remote control
Page 14
INSTALLATION INSTRUCTIONS
SINGLE SPLIT
13English 11/2002
A
I
INSTALLATION DIAGRAM
The distance from the ceiling must be greater than 150mm
The distance from the wall must be greater than 150mm
The distance between the air inlet and the wall must be greater than 300mm
The distance from the wall must be greater than 500mm
286
The distance from the wall must be greater than 150mm
The distance from the floor must be greater than 2500mm
The distance from the wall must be greater than 300mm
The distance of the air outlet from the wall must be greater than 2000mm
The above figure represents a simplified lay­out of the appliance and may not correspond to the appearance of the unit actually pur­chased.
The clearance of the air outlet must be at least 300mm
The distance from the wall must be greater than 500mm
540
Insulation tape
Flexible sleeve
Page 15
SINGLE SPLIT
14 English 11/2002
Minimum installation height of the indoor unit (Min. 2.5m).
Places suitable for the installation of the outdoor unit
• Install the unit in a suitable and well-ventilated site; avoid installing it in places where there are possible leaks of combustible gases.
• Observe the distance indicated from the wall.
•Do not install the outdoor unit in areas that are dirty or greasy, near gas emissions from vulcanisation or very salty sea areas.
•Avoid installing the unit on the side of a road where it may come into contact with muddy water.
• On a fixed base that does not increase the operating noise.
• In a place where the air outlet is not blocked.
The unit must not be started before having been completely assembled in its place of operation. The installation and maintenance of the equipment must be carried out exclusively by qualified technicians. The appliance must be installed according to the legislation in force in the country con­cerned. Before starting the appliance, check that it is correctly earthed, according to the legisla­tion in force in the country concerned.
SELECTING THE BEST SITE Suitable places for installation of the indoor unit
• Absence of obstacles near the air outlet so that the air can flow freely around the room.
• Places where it is easy to make holes in the wall and lay the pipes.
• Observe the distances from the ceiling and from the wall indicated in the wiring diagram.
• Places where the air filter can be removed easily.
• Place the unit and the remote control 1 metre or more from television sets,radios, etc.
•Keep the appliance as far away as possible from fluores­cent lamps,to prevent harmful effects.
• Do not place objects near the air inlet, so as not to block it.
In a site that can support the weight and not increase the operating noise and vibrations.
Indoor unit
Outdoor unit
Maximum length of the pipe 15m
Height less than 5m
Indoor unit
Outdoor unit
Maximum length of the pipe 15m
Height less than 5m
The appliance shall not be installed in the laundry.
Page 16
INSTALLATION OF THE INDOOR UNIT
SINGLE SPLIT
15English 11/2002
AI
1
2
3
4
1.
INSTALLATION OF THE FASTENING PLATE
Select the position for installing the fastening plate, according to of the location of the indoor unit and the layout of the pipes. Adjust the level of the fastening plate, using a straight­edge or a plumb line. Make 32mm deep holes in the wall to mount the plate. Insert the plastic plugs in the holes,then secure the fas­tening plate using the self-threading screws supplied with the unit. Check that the fastening plate is securely fitted so as to support a 60kg adult.
Your fastening plate may differ from the one described above, yet the installation proce­dure is the same.
2.MAKE A HOLE FOR THE PIPES
Choose the location of the hole for the pipes, accord­ing to the position of the fastening plate. Make a hole in the wall. The hole must slope down­wards towards the outside. Place a sleeve through the hole in the wall to protect the wall and keep it clean.
3. INSTALLATION OF THE PIPES ON THE INDOOR UNIT
Place the pipes (for liquid and gas) through the hole in the wall from the outside, or alternatively from the inside after having completed the installation of the pipes and the connection of the cables on the indoor unit,for connection to the outdoor unit. Decide whether to remove the plastic segment, according to the direction of the pipes.
When the pipe is fastened along the direc­tion 1,2 or 4,remove the corresponding plas­tic segment from the base of the indoor unit.
After having connected the pipes according to the instructions,install the drain hose.Then install the pow­er supply cables. After having completed the connec­tions,wrap the pipes,cables and drain hose in a layer of thermal insulation.
Line the joints of the pipe with thermal insu­lation and cover them with vinyl tape.
Sleeve with hole in the wall (rigid polythene pipe sup­plied by the user)
5mm (downwards slope)
INSIDE
OUTSIDE
Direction of pipe insertion
Thermal insulation
Vinyl tape covering
Remove the plastic segment along the raceway
Raceway
Plastic segment
Page 17
SINGLE SPLIT
16 English 11/2002
Thermal insulation lining
•Position the drain hose under the pipes.
•Insulation material: polythene foam, thickness greater than 6mm.
The drain hose must be supplied by the user.
•The drain hose must run downwards,to assist drainage.
• Do not bend the drain hose, allow it to protrude, twist it or immerse the end in water. If the drain hose is con­nected to an extension, check that this is thermally insu­lated when running in the indoor unit.
• If the pipes run to the right, the pipes, the power cable and the drain hose must be thermally insulated and fas­tened to the rear of the unit by a pipe coupling.
1.Insert the pipe coupling in the opening.
2.Press the pipe coupling to secure it to the base.
Connecting the pipes
• Connect the pipes to the indoor unit using two span­ners. Pay careful attention to the torque specified below to avoid deforming and damaging the pipes, connectors and countersunk nuts.
• First tighten by hand,and then use the spanners.
(1) Quantity of refrigerant for each metre of pipe over the
5 m.
Drain hose
Connection cables
Insulation tape
Control cable
Power cable
Base
Pipe coupling
Insert here
Pipe coupling
Base
Fasten here
Base
Large
pipe
Large
pipe
Small
pipe
Small
pipe
Drain
hose
Drain hose
7-9-12-17,3 K Liquid side (ø 6 o 1/4") 1,8 Kg.m 17 mm 23,5 K Liquid side (ø 10 o 3/8") 3,5 Kg.m 22 mm 7-9 K Gas side (ø 10 o 3/8") 3,5 Kg.m 22 mm 12-17,3 K Gas side (ø 12 o 1/2") 5,5 Kg.m 24 mm 23,5 K Gas side (ø 16 o 5/8") 7,5 Kg.m 27 mm
Model Pipe dimensions Torque Nut
7 - 9 - 12 - 17,3 K 10 g/m 23,5 K 20 g/m
Model Q/m (1)
Page 18
SINGLE SPLIT
17English 11/2002
3. CONNECTING THE CABLE Indoor unit
Connect the power cable to the indoor unit by connect­ing the wires to the terminals on the control panel indi­vidually,according to the connection to the outdoor unit.
To make the connection to the indoor unit ter­minal,remove the console.
Outdoor unit
Remove the access door from the unit by loosening the screw. Connect the wires to the terminal on the control panel with a terminal screw. Place the access door back in position and tighten the screw.
Use an approved switch between the power supply source and the unit. An isolating device must be fitted to correctly disconnect all the power supply lines. Use a separate power supply circuit specifi­cally for the air-conditioner. For details on the wiring method, refer to the circuit dia­gram inside the access door. Check that the thickness of the cable com­plies with the specifications of the power supply. Check the wires and make sure that they are all securely fastened following the connec­tion of the cable. Make sure an earth leakage switch is installed in wet or damp areas. The connection cable between the outdoor and indoor unit must be suitable for outdoor use. The plug must remain accessible following the installation of the appliance, so that the appliance can be unplugged if required.If this is not possible, connect the appliance to a two-pole switch,with a distance between the contacts of at least 3mm, which must be installed in an accessible position.
Terminal (inside)Front panel
Console
Frame
Indoor unit
Outdoor unit
Access door fastener (inside)
Page 19
SINGLE SPLIT
18 English 11/2002
Indoor unit
Outdoor unit
Power cable
Blue
Blue
Yellow/Green
Yellow/Green
Brown
Brown
1N
2
3
1N
2
3
Terminal Terminal Terminal Terminal
Indoor unit
Outdoor unit
Power cable
Blue
Blue
Yellow/Green
Brown
Brown
Red
Red
1N
2
3
1N
2
3
CONNECTION DIAGRAM
Check that the colours of the connections on the outdoor unit and the terminal block are not the same as those on the indoor unit.
PFor connections between the indoor and outdoor unit exceeding 5 metres (standard cable supplied), two quick connectors are supplied (see the figure).
All the electrical connections must be performed
by specialist technicians, in accordance with the legislation in force in the country concerned. Respect the sequence and the colour of the cables when using the two connectors supplied.
OUTDOOR UNIT CONTROL CABLE
Yellow/Green
Models 12K-17,3K-23,5K
(inside) (outside)
MODELS 7K - 9K -12K MODELS 17.3K-23.5K
Models 7K-9K-12K-17,3K-23,5K
Models 7K-9K
Quick connectors
Page 20
VENTING THE AIR
INSTALLATION OF THE OUTDOOR UNIT
SINGLE SPLIT
19English 11/2002
AI
Refrigerant flow direction
2-way valve
(6) Open 1/4 turn
valve cap
(1) Turn
(8) Tighten
(2) Turn
3-way valve
(8) Tighten
(1) Turn
(7) Turn to fully open the valve
(7) Turn to fully open the valve
(8) Tighten
Service port
Connect to outdoor unit
indoor unit
Valve cap
1. Install the drain fitting and the drain hose (heat pump model only)
The condensate is drained from the outdoor unit when the appliance operates in heating mode. To avoid dis­turbing neighbours and to respect the environment, install a drain fitting and a drain hose to convey the condensate. Simply install the drain fitting and the rub­ber washer on the chassis of the outdoor unit, then connect a drain hose as shown in the figure.
2. Installation and fastening of the outdoor unit
Bolt the unit securely to a level and sturdy floor. If the unit is to be installed on a wall or on the roof, make sure the support is fastened securely to prevent it from moving following intense vibrations or strong winds.
3. Connecting the pipe to the outdoor unit
Remove the cap from the 2- and 3-way valves.Connect the pipes to the 2- and 3-way valves separately, tighten­ing to the torque specified.
4. Connecting the cable to the outdoor unit (see the previous page)
The air that contains moisture remaining inside the refrig­erant circuit may cause problems to the compressor.After having connected the indoor and outdoor unit,vent the air and the moisture from the refrigerant circuit using a vacu­um pump.
(1) Unscrew and remove the caps from the 2- and 3-way
valves.
(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the valve being
used.
(4) Run the vacuum pump for 10-15 minutes,until reaching
an absolute depression of 10mm Hg.
(5) With the vacuum pump still on, close the low pressure
knob on the vacuum pump hose.Then stop the vacuum pump.
(6) Open the 2-way valve a 1/4 of a turn, then close it
again after 10 seconds. Check the seal of all the joints using liquid soap or an electronic leak detector.
(7) Turn the body of the 2- and 3-way valves. Disconnect
the vacuum pump hose.
(8) Reposition and tighten all the caps on the valves.
Washer
Drain hose (supplied by the user)
Drain fitting
Vacuum pump
A
I
Page 21
NOTES
USEFUL INFORMATION
SINGLE SPLIT
20 English 11/2002
• Read this manual before installing and use the appliance.
• Check that air does not enter the refrigerant system and that there are no leaks of refrigerant when the air-condi­tioner is moved.
•Run a test cycle after the installation of the air-condition­er and record the operating data.
•The type of fuse installed on the indoor control unit is rated to 3.15A,T, 250V.
•The user must fit the entire unit with a fuse suitable for the maximum input current or use another safety cut­out device.
• The plug must remain accessible following the installation of the appliance, so that the appliance can be unplugged if required.
U
A
I
For information on service and the supply of spare parts,please contact:
FIXED AIR-CONDITIONING TECHNICAL SERVICE DEP ARTMENT DE’ LONGHI GROUP
via L.Seitz,47 - 31100 Treviso (ITALY)
U I A
Numero Verde
800 019 190
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
Loading...