System dimensions..............................................................................................................................................................4
System battery specifications.......................................................................................................................................... 7
Expansion bus specifications............................................................................................................................................ 7
Ports and connectors specifications..............................................................................................................................11
USB ports........................................................................................................................................................................11
NIC ports.........................................................................................................................................................................11
Serial connector............................................................................................................................................................ 11
Internal Dual SD Module or vFlash card..................................................................................................................12
Video specifications...........................................................................................................................................................12
Standard operating temperature.............................................................................................................................. 13
Particulate and gaseous contamination specifications....................................................................................... 15
Contents3
Page 4
Technical specifications
The technical and environmental specifications of your system are outlined in this section.
Topics:
•System dimensions
•Chassis weight
•Processor specifications
•Supported operating systems
•PSU specifications
•System battery specifications
•Expansion bus specifications
•Memory specifications
•Storage controller specifications
•Drive specifications
•Ports and connectors specifications
•Video specifications
•Environmental specifications
1
System dimensions
This section describes the physical dimensions of the system.
4Technical specifications
Page 5
Figure 1. System dimensions of PowerEdge R740 system
Table 1. Dimensions
SystemXaXbYZa (with
PowerEdge R740482.0 mm
(18.98
inches)
434.0 mm
(17.09
inches)
86.8 mm
(3.42
inches)
bezel)
35.84 mm
(1.41 inches)
Za
(without
bezel)
22.0 mm
(0.87
inches)
ZbZc
678.8 mm
(26.72
inches)
715.5 mm
(28.17
inches)
Chassis weight
Table 2. Chassis weight
SystemMaximum weight (with all drives/SSDs)
2.5 inch drive systems26.3 kg (57.98 lb)
3.5 inch drive systems28.6 kg (63.05 lb)
Processor specifications
The PowerEdge R740 system supports up to two Intel Xeon Processor Scalable Family processors, up to 28 cores per
processor.
NOTE: Processor sockets are not hot pluggable.
Technical specifications5
Page 6
Supported operating systems
The PowerEdge R740 supports the following operating systems:
Canonical Ubuntu LTS
Citrix XenServer
Microsoft Windows Server with Hyper-V
Red Hat Enterprise Linux
SUSE Linux Enterprise Server
VMware ESXi
NOTE: For more information, go to www.dell.com/ossupport.
PSU specifications
The PowerEdge R740 system supports up to two AC or DC power supply units (PSUs).
Table 3. PSU specifications
PSUClassHeat
495 W ACPlatinum1908 BTU/hr
750 W ACPlatinum2891 BTU/hr50/60 Hz100–240 V AC,
750 W ACTitanium2843 BTU/hr50/60 Hz200–240 V AC,
750 W
Mixed
Mode
HVDC (for
China
only)
750 W
Mixed
Mode
1100 W AC Platinum4100 BTU/hr50/60 Hz100–240 V AC,
1100 W DC N/A4416 BTU/hrN/A–(48 V to –60 V)
Platinum2891 BTU/hr50/60 Hz100–240 V AC,
Platinum2891 BTU/hrN/A240 V DC,
Platinum2891 BTU/hr50/60 Hz100–240 V AC,
Platinum(F
or China
only)
dissipation
(maximum)
2891 BTU/hrN/A240 V DC,
FrequencyVoltageHigh line
50/60 Hz
100–240 V AC,
autoranging
autoranging
autoranging
autoranging
autoranging
autoranging
autoranging
autoranging
DC, autoranging
200v240 V
495 W495 WNA6.5 A–3 A
750 W750 WNA10 A–5 A
750 WNA5 A
750 W750 WNA10 A–5 A
NANA750W4.5 A
750 W750 WNA10 A–5 A
NANA750 W5 A
1100 W1050 W12 A–6.5 A
NANA1100 W 32 A
Low line
100– 140 V
DCCurrent
1100 W
Mixed
Mode
HVDC (for
China and
Japan
only)
1600 W
AC
6Technical specifications
Platinum4100 BTU/hr50/60 Hz100–240 V AC,
N/A4100 BTU/hrN/A200–380 V DC,
Platinum6000 BTU/hr50/60 Hz100–240 V AC,
autoranging
autoranging
autoranging
1100 W1050 W12 A–6.5 A
NANA1100 W 6.4 A–3.2 A
1600 W800 WNA
10 A
Page 7
Table 3. PSU specifications (continued)
PSUClassHeat
dissipation
(maximum)
2000 WACPlatinum7500 BTU/hr50/60 Hz100–240 V AC,
2400 WACPlatinum9000 BTU/hr50/60 Hz100–240 V AC,
NOTE: Heat dissipation is calculated using the PSU wattage rating.
NOTE: This system is also designed to connect to the IT power systems with a phase to phase voltage not exceeding 240
V.
NOTE: PSUs rated for 1100 W Mixed Mode HVDC or 1100 W AC and higher require high-line voltage (200–240 V AC) to
supply their rated capacity.
FrequencyVoltageHigh line
200v240 V
2000 W1000 WNA
autoranging
2400 W1400 WNA
autoranging
Low line
100– 140 V
DCCurrent
11.5 A
16 A
System battery specifications
The PowerEdge R740 system supports CR 2032 3.0-V lithium coin cell system battery.
Expansion bus specifications
The PowerEdge R740 system supports up to eight PCI express (PCIe) generation 3 expansion cards that can be installed on the
system board using expansion card risers. The following table provides detailed information about the expansion card riser
specifications:
NOTE: 64 GB LRDIMMs, 128 GB LRDIMMs must not be mixed.
NOTE: Minimum of two CPUs are required for any configurations that support NVDIMM-N.
NOTE: DCPMM can be mixed with RDIMMs and LRDIMMs.
NOTE: Mixing of DDR4 DIMM Types (RDIMM, LRDIMM), within channel, integrated memory controller, socket, or across
sockets is not supported.
NOTE: x4 and X8 DDR4 DIMM can be mixed within channel.
NOTE: Mix of Intel Data center persistent memory module operating modes (App Direct, Memory Mode) is not supported
within socket or across sockets.
DIMM
type
DIMM rank
NA512 GBNANARDIMM: 384 GBRDIMM: 1536 GB
DIMM
capacity
Single processorDual processors
Minimum
RAM
NANADCPMM: 2048GBDCPMM: 3072 GB
NANADCPMM: 4096GBDCPMM: 6144 GB
Maximum
RAM
Minimum RAMMaximum RAM
NOTE: Memory DIMM slots are not hot pluggable.
Storage controller specifications
The PowerEdge R740 system supports:
● Internal storage controller cards: PowerEdge RAID Controller (PERC) H330, PERC H730P, PERC H740P, HBA330, S140, and
Boot Optimized Server Storage (BOSS-S1).
The BOSS card is a simple RAID solution card designed specifically for booting a server's operating system. The card
supports up to two 6 Gbps M.2 SATA drives. The BOSS adapter card has a x8 connector using PCIe gen 2.0 x2 lanes,
available only in the low-profile and half-height form factor.
● External storage controller cards: PERC H840 and 12Gbps SAS HBA.
NOTE: Mini-PERC socket is not hot pluggable.
Drive specifications
Drives
The PowerEdge R740 system supports SAS, SATA, Nearline SAS hard drives or SSDs.
Table 7. Supported drive options for the PowerEdge R740 system
DrivesSupported configuration
Eight drives systemUp to eight 3.5 inch or 2.5 inch (SAS, SATA or Nearline SAS) front
accessible drives in slots 0 through 7
10Technical specifications
Page 11
Table 7. Supported drive options for the PowerEdge R740 system (continued)
DrivesSupported configuration
Sixteen drives systemUp to sixteen 2.5 inch (SAS, SATA or SSD) front accessible drives in
slots 0 through 15
NOTE: Hard drives are hot swappable.
Optical drive
The PowerEdge R740 system supports one optional slim SATA DVD-ROM drive or DVD +/-RW drive.
Ports and connectors specifications
USB ports
The PowerEdge R740 system supports:
● Two USB 2.0-compliant ports on the front of the system
● One internal USB 3.0-compliant port
● One optional USB 3.0-compliant port on the front of the system
● One micro USB 2.0-compliant port in the front of the system for iDRAC Direct
● Two USB 3.0-compliant ports on the back of the system
NIC ports
The PowerEdge R740 system supports up to four Network Interface Controller (NIC) ports that are integrated on the network
daughter card (NDC), and are available in the following configurations:
● Four RJ-45 ports that support 10, 100 and 1000 Mbps
● Four RJ-45 ports that support 100 M, 1 G and 10 Gbps
● Four RJ-45 ports, where two ports support maximum of 10 G and the other two ports maximum of 1 G
● Two RJ-45 ports that support up to 1 Gbps and 2 SFP+ ports that support up to 10 Gbps
● Four SFP+ ports that support up to 10 Gbps
● Two SFP28 ports that support up to 25 Gbps
NOTE: You can install up to eight PCIe add-on NIC cards.
NOTE: NDC slot is not hot pluggable.
VGA ports
The Video Graphic Array (VGA) port enables you to connect the system to a VGA display. The PowerEdge R740 system
supports two 15-pin VGA ports on the front and back panels.
NOTE: The VGA ports are not hot pluggable.
Serial connector
The PowerEdge R740 system supports one serial connector on the back panel, which is a 9-pin connector, Data Terminal
Equipment (DTE), 16550-compliant.
NOTE: The Serial port is not hot pluggable.
Technical specifications11
Page 12
Internal Dual SD Module or vFlash card
The PowerEdge R740 system supports Internal Dual SD module (IDSDM) and vFlash card. In 14th generation of PowerEdge
servers, IDSDM and vFlash card are combined into a single card module, and are available in these configurations:
● vFlash or
● IDSDM or
● vFlash and IDSDM
The IDSDM/vFlash card sits in the back of the system, in a Dell-proprietary slot. IDSDM/vFlash card supports three micro SD
cards (two cards for IDSDM and one card for vFlash). Micro SD cards capacity for IDSDM are 16/32/64 GB while for vFlash the
microSD card capacity is 16 GB.
NOTE: IDSDM and vFlash slot is not hot pluggable.
Video specifications
The PowerEdge R740 system supports integrated Matrox G200eW3 graphics controller with 16 MB of video frame buffer.
Table 8. Supported video resolution options
ResolutionRefresh rate (Hz)Color depth (bits)
1024 x 768608, 16, 32
1280 x 800608, 16, 32
1280 x 1024608, 16, 32
1360 x 768608, 16, 32
1440 x 900608, 16, 32
1600 x 900608, 16, 32
1600 x 1200608, 16, 32
1680 x 1050608, 16, 32
1920 x 1080608, 16, 32
1920 x 1200608, 16, 32
NOTE: 1920 x 1080 and 1920 x 1200 resolutions are only supported in reduced blanking mode.
Environmental specifications
NOTE:
For additional information about environmental certifications, please refer to the Product Environmental Datasheet
located with the Manuals & Documents on www.dell.com/poweredgemanuals.
Table 9. Temperature specifications
TemperatureSpecifications
Storage–40°C to 65°C (–40°F to 149°F)
Continuous operation (for altitude less than 950 m or
3117 ft)
Maximum temperature gradient (operating and
storage)
12Technical specifications
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
20°C/h (68°F/h)
Page 13
Table 10. Relative humidity specifications
Relative humiditySpecifications
Storage5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere
must be non-condensing at all times.
Operating10% to 80% relative humidity with 29°C (84.2°F) maximum dew
point.
Table 11. Maximum vibration specifications
Maximum vibrationSpecifications
Operating0.26 G
Storage1.88 G
at 5 Hz to 350 Hz (all three axes).
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
rms
Table 12. Maximum shock specifications
Maximum shockSpecifications
OperatingSix consecutively executed shock pulses in the positive and negative x,
y, and z axes of 6 G for up to 11 ms.
StorageSix consecutively executed shock pulses in the positive and negative x,
y, and z axes (one pulse on each side of the system) of 71 G for up to
2 ms.
Table 13. Maximum altitude specifications
Maximum altitudeSpecifications
Operating
Storage12,000 m (39,370 ft)
3048 m (10,000 ft)
Table 14. Operating temperature de-rating specifications
Operating temperature de-ratingSpecifications
Up to 35°C (95°F)Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above
950 m (3,117 ft).
35°C to 40°C (95°F to 104°F)Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above
950 m (3,117 ft).
40°C to 45°C (104°F to 113°F)Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above
950 m (3,117 ft).
Standard operating temperature
Table 15. Standard operating temperature specifications
Standard operating temperatureSpecifications
Continuous operation (for altitude less than 950 m or
3117 ft)
Humidity percentage range10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
point.
Technical specifications13
Page 14
Expanded operating temperature
Table 16. Expanded operating temperature specifications
Expanded operating temperatureSpecifications
Continuous operation5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to
35°C), the system can operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C to 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported in the System
Event Log.
Expanded operating temperature restrictions
● 128 GB LRDIMM is not supported for FAC.
● Do not perform a cold startup below 5°C.
● The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
● 150 W/8 core, 165 W/12 core and higher wattage processor [Thermal Design Power (TDP)>165 W] are not supported.
● Redundant power supply unit is required.
● Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
● PCIe SSD is not supported.
● NVDIMM-Ns are not supported.
● DCPMMs are not supported.
● GPU is not supported.
● Tape backup unit is not supported.
Thermal restrictions
Following table lists the configuration required for efficient cooling.
The following table lists configurations that require ambient temperature less than 35°C.
NOTE: The ambient temperature limit must be adhered to ensure proper cooling and to avoid excess CPU throttling, which
may impact system performance.
Table 18. Configuration based ambient temperature restrictions
SystemFront backplane Processor
PowerEdge
R740
8 x 3.5 inch SAS/
SATA
Thermal
Design Power
(TDP)
150 W/8 core,
165 W/12 core,
200 W, 205 W
Processor heat
sink
1U high
performance
Fan typeGPUAmbient
High
performance fan
≥1 doublewidth/singlewidth
restriction
30°C
8 x 2.5 inch SAS/
SATA
16 x 2.5 inch
SAS/SATA
150 W/8 core,
165 W/12 core,
200 W, 205 W
150 W/8 core,
165 W/12 core,
200 W, 205 W
1U high
performance
1U high
performance
High
performance fan
High
performance fan
≥1 doublewidth/singlewidth
≥1 doublewidth/singlewidth
30°C
30°C
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous
contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
Air filtrationData center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE: The ISO Class 8 condition applies to data center
environments only. This air filtration requirement does not apply to
IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dustAir must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE: This condition applies to data center and non-data center