100–240 V AC or 100–240 V DC Power Supply — Information Update
This document describes the requirements and wiring instructions for the power cable and safety ground wire for systems equipped with a 100–240 V AC or 100–240 V DC power supply.
WARNING: A qualified electrician must perform all connections to power and safety
grounds. The system must be safety grounded at the cabinet frame. All electrical wiring must comply with applicable local or national codes and practices.
WARNING: The system chassis must be positively grounded to the rack cabinet
frame. Do not attempt to connect power to the system until grounding cables are connected.
WARNING: An energy hazard will exist if the safety ground cable is omitted or
disconnected.
The following Dell PowerEdge systems support the 100–240 V AC or 100–240 V DC power supply:
R720
R720xd
R620
R520
Warning Statements
Protect the 100–240 V AC with a branch circuit overcurrent protection rated appropriately per local and national code for AC with a high interrupt current rating.
Protect the 100 appropriately per local and national code, rated for DC with a high interrupt current rating.
When connecting the 240 V DC, connect the equipment to a supply source that is electrically isolated from the AC source (reliably grounded 240 V DC source). Ensure that the 240 V DC source is efficiently grounded.
240 V DC with a branch circuit overcurrent protection rated
0YPKT0A01
WARNING: Use approved wiring termination, such as closed-loop or spade-type
with upturned lugs. These terminations should be the appropriate size for the wires and must be double crimped, one on the conductor and one on the insulation.
WARNING: When installing the unit, the ground connection must always be made
first and disconnected last to prevent an energy hazard.
WARNING: Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available.
Input Requirements
Supply voltage: 100–240 V AC or 100–240 V DC
Current consumption: 10
5 A or 4.5 A maximum
Connecting The Power Cable
1
Turn off the power source.
2
Connect the open terminal of the Dell provided power cable to the appropriate source.
3
Connect both the green/yellow safety ground wire and the black sense wire to the safety ground connection.
NOTE: The wiring terminals of the power source must be appropriate
to 1.5 mm
4
Connect the cable connector to the power supply unit.
5
Turn on the power source.
2
wire.
1
2
3
6
5
1 power supply socket 2 cable connector
3 safety ground (green/yellow wire) 4 power AC L1/DC source (brown wire)
5 power AC L2/DC return (blue wire) 6 sense wire (black wire)