Delfield DCH-FS-48L Service Manual

F18 SERIES
Service and Installation Manual
Please read this manual completely before attempting to install or operate this equipment! Notify carrier of damage! Inspect all components immediately.
Refrigerated Work Tables, Salad Tables & Freezer Bases
IMPORTANT INFORMATION
READ BEFORE USE
July 2011
F18 Series Service and Installation Manual
Important Warning And Safety Information
WARNING Read This Manual Thoroughly Before Operating, Installing, Or Performing Maintenance On The Equipment.
WARNING Failure To Follow Instructions In This Manual Can Cause Property Damage, Injury Or Death.
WARNING Do Not Store Or Use Gasoline Or Other Flammable Vapors Or Liquids In The Vicinity Of This Or Any Other
Appliance.
WARNING Unless All Cover And Access Panels Are In Place And Properly Secured, Do Not Operate This Equipment.
WARNING This Appliance Is Not Intended For Use By Persons Who Lack Experience Or Knowledge, Unless They Have
Been Given Supervision Or Instruction Concerning Use Of The Appliance By A Person Responsible For Their Safety.
WARNING This Appliance Is Not To Be Played With.
WARNING Do Not Clean With Water Jet.
WARNING Do Not Use Electrical Appliances Inside The Food Storage Compartment Of This Appliance.
CAUTION Observe the following:
• Minimum clearances must be maintained from all walls and combustible materials.
• Keep the equipment area free and clear of combustible material.
• Allow adequate clearance for air openings.
• Operate equipment only on the type of electricity indicated on the specification plate.
• Unplug the unit before making any repairs.
• Retain this manual for future reference.
2
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
F18 Series Service and Installation Manual
Contents Serial Number Location
Serial Number Location ........................................................3
Receiving & Inspecting .........................................................3
Specifications .................................................................... 4-6
Installation ............................................................................7
Operation ..............................................................................8
Temperature Settings ............................................................9
Maintenance .................................................................. 10-11
Wiring Diagrams ........................................................... 12-15
Replacement Part Lists ................................................. 16-19
Replacement Part Assemblies ...................................... 20-23
The serial number on all self-contained F18 Series refrigerated work tables and freezer bases is located on the electrical specifications tag affixed inside the compressor section next to the pressure control.
On remote refrigerated bases with doors, the tag is inside the unit on the coil side. On remote refrigerated bases with drawers, the tag is affixed to the drawer divider. On remote freezer bases, the tag is located on the inside back of the unit.
Always have the serial number of your unit available when calling for parts or service. A complete list of authorized Delfield parts depots is available at www.delfield.com.
©2012 The Deleld Company. All rights reserved. Reproduction without written permission is prohibited. “Deleld” is a registered trademark of The Deleld Company.
Warranties..................................................................... 24-26
Notes ..................................................................................27
The models are certified by:
National Sanitation Foundation (NSF)
Underwriters Laboratories (UL)
Receiving and Inspecting the Equipment
Even though most equipment is shipped crated, care should be taken during unloading so the equipment is not damaged while being moved into the building.
1. Visually inspect the exterior of the package an skid or container. Any damage should be noted and reported to the delivering carrier immediately.
2. If damaged, open and inspect the contents with the carrier.
3. In the event that the exterior is not damaged, yet upon opening, there is concealed damage to the equipment notify the carrier. Notification should be made verbally as well as in written form.
4. Request an inspection of the concealed equipment. This should be done within 10 days from receipt of the equipment.
5. Check the lower portion of the unit to be sure legs or casters are not bent.
6. Also open the compressor compartment housing and
7. Freight carriers can supply the necessary forms upon
8. Retain all crating material until an inspection has been
Uncrating the Equipment
First cut and remove the banding from around the crate. Remove the front of the crate material, use of some tools will be required. If the unit is on legs remove the top of the crate as well and lift the unit off the skid. If the unit is on casters it can be "rolled" off the skid.
Regulatory Certifications
visually inspect the refrigeration package. Be sure lines are secure and base is still intact.
request.
made or waived.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
3
F18 Series Service and Installation Manual
Specifications
Remote Refrigerated Work Tables
Model # Of Doors
F18WR31 (1) 19” 70 7.56 2.56 115/60/1 3.0 383 120/3°
F18WR39 (1) 27” 124 10.23 3.95 115/60/1 3.0 465 120/4°
F18WR44 (2) 19” 70 12.14 5.12 115/60/1 3.0 605 120/5°
F18WR52 (1) 19” & (1) 27” 70/124 15.12 6.51 115/60/1 3.0 686 120/6°
F18WR60 (2) 27” 124 18.10 7.90 115/60/1 3.0 768 120/6°
F18WR70 (2) 32” 140 21.23 9.64 115/60/1 3.0 869 120/7°
F18WR79 (2) 27” & (1) 19” 124/70 24.48 10.29 115/60/1 6.0 1050 240/4°
F18WR87 (3) 27” 124 27.46 11.85 115/60/1 6.0 1131 240/5°
Shelf Max Load (lbs)
Self-Contained Refrigerated Work Tables
Model # Of Doors
F18WC39 (1) 19” 70 7.56 2.56 115/60/1 8.0 383 1462 16 1/5 5-15P
F18WC47 (1) 27” 124 10.23 3.95 115/60/1 8.0 465 1462 16 1/5 5-15P
F18WC52 (2) 19” 70 12.14 5.12 115/60/1 8.0 605 1462 16 1/5 5-15P
F18WC60 (1) 19” & (1) 27” 70/124 15.12 6.51 115/60/1 8.0 686 1462 16 1/5 5-15P
F18WC68 (2) 27” 124 18.10 7.90 115/60/1 10.0 768 1462 16 1/4 5-15P
F18WC78 (2) 32” 140 21.23 9.64 115/60/1 10.0 869 1994 16 1/4 5-15P
F18WC87 (2) 27” & (1) 19” 124/70 24.48 10.29 115/60/1 10.0 1050 2261 16 1/4 5-15P
F18WC95 (3) 27” 124 27.46 11.85 115/60/1 10.0 1131 2261 16 1/4 5-15P
Shelf Max Load (lbs)
Base Storage
Base Storage
Cap. FT
Cap. FT
3
3
Shelf
Area FT
Shelf
Area FT
Volts/Hertz/
2
Phase Amps BTU Load EVAP. BTU/°TD
Volts/Hertz/
2
Phase Amps BTU Load BTU System Cap.
R-404A
oz. H.P.
NEMA
Plug
Remote Refrigerated Mega Top Salad Tables
Model # Of Doors
F18MR31A (1) 19” 70 4.14 6 115/60/1 3.0 280/265 120/2°/12/22°
F18MR44A (2) 19” 70 7.15 6 115/60/1 3.0 444/265 120/4°/12/22°
F18MR44D (2) 19” 70 7.15 12 115/60/1 3.0 444/529 120/4°/22/25°
F18MR52A (1) 19” & (1) 27” 70/124 8.97 6 115/60/1 3.0 515/265 120/4°/12/22°
F18MR52D (1) 19” & (1) 27” 70/124 8.97 12 115/60/1 3.0 515/529 120/4°/22/25°
F18MR52E (1) 19” & (1) 27” 70/124 8.97 18 115/60/1 3.0 515/794 120/4°/31/26°
Shelf Max Load (lbs)
Base Storage
Cap. FT3# of Pans
Volts/Hertz/
Phase Amps
BTU Load Base/Rail
EVAP. BTU/°TD
Base/Rail
Self-Contained Refrigerated Mega Top Salad Tables
Model # Of Doors
F18MC39A (1) 19” 70 4.14 6 115/60/1 10.0 280/265 1903/925 16 1/4 5-15P
F18MC39D (1) 19” 70 4.14 12 115/60/1 10.0 280/529 1903/1156 16 1/4 5-15P
F18MC52A (2) 19” 70 7.15 6 115/60/1 10.0 444/265 1903/925 16 1/4 5-15P
F18MC52D (2) 19” 70 7.15 12 115/60/1 10.0 444/529 1903/1156 16 1/4 5-15P
F18MC52E (2) 19” 70 7.15 18 115/60/1 10.0 444/794 1903/1321 16 1/4 5-15P
F18MC60A (1) 19” & (1) 27” 70/124 8.97 6 115/60/1 10.0 515/265 2314/864 16 1/4 5-15P
F18MC60D (1) 19” & (1) 27” 70/124 8.97 12 115/60/1 10.0 515/529 2314/1141 16 1/4 5-15P
F18MC60E (1) 19” & (1) 27” 70/124 8.97 18 115/60/1 10.0 515/794 2314/1361 16 1/4 5-15P
F18MC60F (1) 19” & (1) 27” 70/124 8.97 24 115/60/1
Shelf Max Load (lbs)
Base Storage
Cap. FT3# of Pans
Volts/Hertz/
Phase Amps
BTU Load Base/Rail
10.0 515/1058 2314/1540 16 1/4 5-15P
BTU System Cap.
Base/Rail
R-404A
oz. H.P.
NEMA
Plug
4
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
F18 Series Service and Installation Manual
Specifications
Remote Refrigerated Salad Top Tables
Model # Of Doors
F18SR31A (1) 19” 70 4.14 6 115/60/1 3.0 280/265 120/2°/13/21°
F18SR44A (2) 19” 70 7.15 6 115/60/1 3.0 491/441 120/4°/13/21°
F18SR44B (2) 19” 70 7.15 8 115/60/1 3.0 491/441 120/4°/16/22°
F18SR44C (2) 19” 70 7.15 10 115/60/1 3.0 491/441 120/4°/19/23°
F18SR52A (1) 19” & (1) 27” 70/124 8.97 6 115/60/1 3.0 532/529 120/4°/13/21°
F18SR52B (1) 19” & (1) 27” 70/124 8.97 8 115/60/1 3.0 532/529 120/4°/16/22°
F18SR52C (1) 19” & (1) 27” 70/124 8.97 10 115/60/1 3.0 532/529 120/4°/19/23°
F18SR52D (1) 19” & (1) 27” 70/124 8.97 12 115/60/1 3.0 532/529 120/4°/23/23°
Shelf Max Load (lbs)
Self-Contained Refrigerated Salad Top Tables
Model # Of Doors
F18SC39A (1) 19” 70 4.14 6 115/60/1 10.0 280/265 1903/745 16 1/4 5-15P
F18SC39B (1) 19” 70 4.14 8 115/60/1 10.0 280/353 1903/867 16 1/4 5-15P
F18SC52A (2) 19” 70 7.15 6 115/60/1 10.0 444/265 1903/745 16 1/4 5-15P
F18SC52B (2) 19” 70 7.15 8 115/60/1 10.0 444/353 1903/867 16 1/4 5-15P
F18SC52C (2) 19” 70 7.15 10 115/60/1 10.0 444/441 1903/971 16 1/4 5-15P
F18SC52D (2) 19” 70 7.15 12 115/60/1 10.0 444/529 1903/1061 16 1/4 5-15P
F18SC60A (1) 19” & (1) 27” 70/124 8.97 6 115/60/1 10.0 515/265 2314/667 16 1/4 5-15P
F18SC60B (1) 19” & (1) 27” 70/124 8.97 8 115/60/1 10.0 515/353 2314/798 16 1/4 5-15P
F18SC60C (1) 19” & (1) 27” 70/124 8.97 10 115/60/1 10.0 515/441 2314/916 16 1/4 5-15P
F18SC60D (1) 19” & (1) 27” 70/124 8.97 12 115/60/1 10.0 515/529 2314/1023 16 1/4 5-15P
Shelf Max Load (lbs)
Base Storage
Base Storage
Cap. FT
Cap. FT
3
3
# of
Pans
# of
Pans
Volts/Hertz/
Phase Amps
Volts/Hertz/
Phase Amps
BTU Load Base/Rail
BTU Load Base/Rail
Evap. BTU/°TD
Base/Rail
BTU System
Cap. Base/Rail
R-404A
oz. H.P.
NEMA
Plug
Remote Refrigerated Reduced Height Rail
Model # Of Doors
F18DR44 (2) 19” 70 9.54 5.12 10 115/60/1 3.0 547/441 120/5°/19/23°
F18DR52 (1) 19” & (1) 27” 70/124 13.89 6.51 12 115/60/1 3.0 625/529 120/5°/23/23°
F18DR60 (2) 27” 124 16.64 7.9 16 115/60/1 5.0 703/617 120/6°/26/24°
F18DR70 (2) 32” 140 22.96 9.64 18 115/60/1 5.0 800/794 120/7°/32/24°
F18DR79 (1) 19” & (2) 27” 70/124 22.47 10.29 18 115/60/1 5.0 962/882 240/4°/36/25°
F18DR87 (3) 27” 124 25.22 11.85 22 115/60/1 5.0 1032/970 240/4°/39/25°
Shelf Max Load (lbs)
Base Storage
Cap. FT
3
Shelf
Area FT
# of
Pans
Volts/Hertz/
Phase Amps
2
BTU Load Base/Rail
Evap. BTU/°TD
Base/Rail
Self-Contained Refrigerated Reduced Height Rail
Model # Of Doors
F18DC52 (2) 19” 70 9.54 5.12 12 115/60/1 10.0 547/529 1903/1061 16 1/4 5-15P
F18DC60 (1) 19” & (1) 27” 70/124 13.89 6.51 14 115/60/1 12.0 625/617 2314/1121 24 1/3 5-15P
F18DC68 (2) 27” 124 16.64 7.9 18 115/60/1 12.0 703/794 2314/1544 24 1/3 5-15P
F18DC82 (2) 32” 140 22.96 9.64 20 115/60/1 14.0 800/882 3097/1648 32 1/2 5-20P
F18DC91 (1) 19” & (2) 27” 70/124 22.47 10.29 22 115/60/1 14.0
F18DC99 (3) 27” 124 25.22 11.85 24 115/60/1 14.0 1032/1147 3807/1839 32 1/2 5-20P
Shelf Max Load (lbs)
Base Storage
Cap. FT
3
Shelf
Area FT
# of
Pans
Volts/Hertz/
Phase Amps
2
BTU Load Base/Rail
962/1058 3807/1839 32 1/2 5-20P
BTU System
Cap. Base/Rail
R-404A
oz. H.P.
NEMA
Plug
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
5
F18 Series Service and Installation Manual
Specifications
Remote Refrigerated Reduced Height Rail
Model # Of Doors
F18RR44 (2) 19” 70 9.49 5.12 115/60/1 3.0 547/441 120/5°/19/23° 10
F18RR52 (1) 19” & (1) 27” 70/124 11.81 6.51 115/60/1 3.0 625/529 120/5°/23/23° 12
F18RR60 (2) 27” 124 14.14 7.9 115/60/1 5.0 703/617 120/6°/26/24° 16
F18RR70 (2) 32” 140 17.05 9.64 115/60/1 5.0 800/794 120/7°/32/24° 18
F18RR79 (1) 19” & (2) 27” 70/124 18.68 10.29 115/60/1 5.0 962/882 240/4°/36/25° 18
F18RR87 (3) 27” 124 21.30 11.85 115/60/1 5.0 1032/970 240/4°/39/25° 22
Shelf Max Load (lbs)
Self-Contained Refrigerated Reduced Height Rail
Model # Of Doors
F18RC52 (2) 19” 70 9.49 5.12 115/60/1 10.0 547/529 1903/1061 12 16 1/4 5-15P
F18RC60 (1) 19” & (1) 27” 70/124 11.81 6.51 115/60/1 12.0 625/617 2314/1121 14 24 1/3 5-15P
F18RC68 (2) 27” 124 14.14 7.9 115/60/1 12.0 703/794 2314/1544 16 24 1/3 5-15P
F18RC82 (2) 32” 140 17.05 9.64 115/60/1 14.0 800/882 3097/1648 20 32 1/2 5-20P
F18RC91 (1) 19” & (2) 27” 70/124 18.68 10.29 115/60/1 14.0 962/1058 3807/1839 22 32 1/2 5-20P
F18RC99 (3) 27” 124 21.30 11.85 115/60/1 14.0 1032/1147 3807/1839 24 32 1/2 5-20P
Shelf Max Load (lbs)
Base Storage
Base Storage
Cap. FT
Cap. FT
3
3
Shelf
Area FT
Shelf
Area FT
Volts/Hertz/
2
Phase Amps
Volts/Hertz/
2
Phase Amps
BTU Load Base/Rail
BTU Load Base/Rail
Evap. BTU/°TD
Base/Rail
BTU System
Cap. Base/Rail
# of
Pans
# of
Pans
R-404A
oz. H.P.
NEMA
Plug
Remote Freezer Base
Model # Of Doors
F18FR35 (1) 19” 70 5.58 2.56 115/60/1 10.0 943 160/6°
F18FR50 (2) 19” 70 12.21 5.12 115/60/1 10.0 1471 160/9°
F18FR58 (1) 19” & (1) 27” 70/124 15.00 6.51 115/60/1 10.0 1844 160/10°
F18FR66 (2) 27” 124 17.79 7.9 115/60/1 10.0 2020 160/11°
F18FR76 (2) 32” 140 21.28 9.64 115/60/1 10.0 2437 160/13°
Shelf Max Load (lbs)
Base Storage
Cap. FT
3
Shelf
Area FT
Volts/Hertz/
2
Phase Amps
BTU Load Base/Rail Evap. BTU/°TD
Self-Contained Freezer Base
Model # Of Doors
F18FC43 (1) 19” 70 5.58 2.56 115/60/1 10.0 943 1558 1/3 24 5-15P
F18FC62 (2) 19” 70 12.21 5.12 115/60/1 12.0 1471 1776 1/2 40 5-15P
F18FC70 (1) 19” & (1) 27” 70/124 15.00 6.51 115/60/1 16.0 1647 2713 3/4 56 5-20P
F18FC78 (2) 27” 124 17.79 7.9 115/60/1 16.0 1824 2713 3/4 56 5-20P
F18FC88 (2) 32” 140 21.28 9.64 115/60/1 16.0 2045 2713 3/4 56 5-20P
Shelf Max Load (lbs)
Base Storage
Cap. FT
3
Shelf
Area FT
Volts/Hertz/
2
Phase Amps
BTU Load Base/Rail
BTU System
Cap. Base/Rail H.P.
R-404A
oz.
NEMA
Plug
Self-Contained Dual Rails
Model # Of Doors
F18PD48 (1) 27” 124
F18PD72 (2) 27” 124
Shelf Max Load (lbs)
Base Storage
3
Cap. FT
9.38 3.95
16.64 7.90
Shelf
Area FT
Volts/Hertz/
2
Phase Amps
115/60/1 10.0 424/1058 2001/1865 1/5, 1/3 40 5-20P
115/60/1 12.7 703/1588 2001/3174 1/5. 1/2 48 5-20P
BTU Load Base/Rail
BTU System
Cap. Base/Rail H.P.
R-404A
oz.
NEMA
Plug
6
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
CAUTIO N
Installation
F18 Series Service and Installation Manual
Location
These units are intended for indoor use only. Be sure the location chosen has a floor strong enough to support the total weight of the cabinet and contents. A fully loaded 72” (183cm) long model may weigh as much as 1500 pounds (680kg)! Reinforce the floor as necessary to provide for maximum loading.
It is very important to allow for proper air flow, both inside and outside.
Avoid hot corners and locations near stoves, ovens and other pieces of cooking equipment.
It is recommended that the unit be installed no closer than 1” (2.54cm) from any wall. Do not install the unit near any combustible material or object affected by heat or moisture.
PDL models also require 14" (36cm) clearance at the top and 6" (15cm) clearance at the bottom (casters).
Leveling
A level cabinet looks better and will perform better because the drain pan will drain properly, the doors will line up with the frames properly, and the cabinet will not be subject to undue strain.
A unit on legs will have an adjustable bullet foot on each leg, adjust each for a level unit. A unit on casters will not be adjustable. Be sure the unit is on a level floor, make necessary changes to the floor for proper level.
Lock all front casters to ensure the stability of the unit.
Plumbing
Self-contained models are standard with a condensate evaporator. If, for some reason a unit does not have a condensate evaporator, or if the evaporator fails, the unit’s drain must have an outlet to an appropriate drainage area or container. A refrigerated rail will have a 1" (2.54cm) drain which will need to be run to an appropriate floor drain or container. The drain will be stubbed to the bottom of the machine compartment. Either run drain to a floor drain or add a valve to the base of the machine compartment and drain the rail to a container when convenient. The LiquiTec option will NOT have a drain available.
Moisture collecting from improper drainage can create a slippery surface on the floor and a hazard to employees. It is the owner’s responsibility to provide a container or outlet for drainage.
Electrical connection
Refer to the specification pages amperage data, the serial tag, your local code or the National Electrical Code to be sure the unit is connected to the proper power source. A protected circuit of the correct voltage and amperage must be run for connection of the line cord, or permanent connection of the unit.
Self-contained units with a cord and plug have an ON/OFF switch located directly behind the louvered panel covering the compressor section. Simply turn the switch to ON to begin operation.
The power switch must be turned to OFF and the unit disconnected from the power source whenever performing service or maintenance functions.
Never operate the unit without the louvered panel in place!
If electrical receptacles are to be mounted in the unit’s backsplash, they must be wired independently from the existing unit wiring.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
7
F18 Series Service and Installation Manual
Refrigerator Operation
Power up the unit by turning ON the unit’s ON/OFF switch. Delfield refrigerated bases are designed to maintain an operational temperature of 36°F to 40°F (2°C to 4°C). Temperature in the salad top and refrigerated rail opening is 33°F to 41°F (0°C to 5°C) with pans recessed 2” (5.1cm) on a standard wrapped refrigerated rail or flush with the LiquiTec option at 86°F (30°C) ambient room temperature.
Do not place hot pans on/against the blue ABS liner. Do not throw items into the storage area. Failure to heed these recommendations could result in damage to the interior of the cabinet or to the blower coil.
Overloading the storage area, restricting the air flow, and continuous opening and closing of the doors and drawers will hamper the units ability to maintain operational temperature.
Refrigerated rail units
Product in the rail should be removed to the refrigerated base at the end of the day. This allows you to turn the rail off at night to save energy and the rail will have time to defrost as needed. It also helps maintain product quality. The standard wrapped refrigerated units are controlled by the pressure control which is set to maintain the proper rail temperature. An on/off switch is also provided for the rail and is required to be shut off at night. The rail switch shuts off the rail only. With a LiquiTec rail a thermostat is provided to maintain rail temperature as well as the rail on/off switch. The LiquiTec rail is required to be shut off at night as well to allow for defrosting. To ensure product
quality in the rail it is recommended that product be rotated every four hours.
If adding any item to the unit, be sure to keep in mind the location of the refrigeration lines on wrapped rail units. A refrigeration leak in a rail is extremely difficult and costly to repair. In some cases it cannot be repaired at all.
Refrigerator Evaporator Fan Operation
When the refrigerator is initially powered up or immediately following a power outage the unit will begin cooling after a 3-6 minute delay. During normal operation the evaporator fan pulses independently of the compressor as dictated by the controller as follows:
1. During the cooling mode, compressor and evaporator fan run simultaneously.
2. During the compressor off mode, evaporator fan pulses three minutes on and three minutes off.
3. During an actual defrost event other than the off-cycle defrost, compressor stays off but the evaporator fan runs continuously.
Cooling Cycle Defrost Cycle
Compressor On Compressor Off Compressor Off
Evap Fan OnEvap Fan
Off
X
Evap Fan OnEvap Fan
Off
Cycles On 3-Min, Off
3-Min
Evap Fan OnEvap Fan
Off
X
Freezer Operation
Power up the unit by turning ON the unit’s ON/OFF switch. Delfield freezer bases are designed to maintain an operational temperature of 0°F (-18°C).
Do not place hot pans on/against the blue ABS liner. Do not throw items into the storage area. Failure to heed these recommendations could result in damage to the interior of the cabinet or to the blower coil.
Overloading the storage area, restricting the air flow, and continuous opening and closing of the doors and drawers will hamper the units ability to maintain operational temperature.
Freezer Evaporator Fan Operation
The evaporator fan(s) and condenser fan will cycle off and on with the compressor to conserve energy. The temperature control will cycle the compressor and condenser fan motor and evaporator fan motor to maintain box temperature at the control setting.
8
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Cooling Cycle Defrost Cycle
Compressor On Compressor Off Compressor Off
Evap Fan OnEvap Fan
Off
X X X
Evap Fan OnEvap Fan
Off
Evap Fan OnEvap Fan
Off
Freezer Defrost
Self-contained models use hot gas to defrost the evaporator coils. Remote freezers use electric defrost.
Temperature Control Settings
F18 Series Service and Installation Manual
A thermostat controls temperature in the self-contained F18WC, F18FC, F18MC base, F18SC base, F18RC base, F18DC base, F18PD base and F18PD rails.
Thermostats are located in the machine compartment. They are field adjustable and do not require a service agent. The factory setting is 2.5. Set toward 1 for higher temperatures and toward 7 for lower temperatures.
A thermostat controls temperature in the remote F18FR. The temperature control is located in the machine compartment. It is field adjustable and does not require a service agent. The factory setting for a remote freezer is 0°F cut-in with a 5°F differential.
Pressure Control Settings
A pressure control controls temperature in the F18MC mega top, F18SC salad top, F18RC rail and F18DC rail.
The factory recommended low-pressure control settings are: 55psi cut-in and 30psi cut-out to maintain proper
temperature for product. The interior temperature is controlled by the thermostat mounted in the mechanical compartment.
A pressure control is located in the machine compartment. An adjustable control has the word COLDER on the knob, with an arrow to indicate the adjustment direction. These controls are field adjustable and do not require a service agent.
In attempting to adjust the pressure control, you can do damage to your unit by accidentally adjusting the differential. Please make small incremental adjustments if a temperature adjustment is necessary, please contact the service department at Delfield (800) 733-8829 or your local service agent. Delfield is not responsible for charges incurred while having the pressure control adjusted.
Please make small incremental adjustments if a temperature adjustment is necessary. Contact the service department at Delfield +1 (989) 773­7981 or your local service agent for additional assistance. Delfield is not responsible for charges incurred while adjusting the thermostat.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
9
F18 Series Service and Installation Manual
Maintenance
Door Gasket Maintenance
Door gaskets require regular cleaning to prevent mold and mildew build up and also to retain the elasticity of the gasket. Gasket cleaning can be done with the use of warm soapy water. Avoid full strength cleaning products on gaskets as this can cause them to become brittle and crack. Never use sharp tools or knives to scrape or clean the gasket. Gaskets can be easily replaced and do not require the use of tools or an authorized service person. The gaskets are “Dart” style and can be pulled out of the groove in the door and new gaskets can
be “pressed” back into place.
Drain Maintenance - Base
Each unit has a drain located inside the unit that removes the condensation from the evaporator coil and routes it to an external condensate evaporator pan. Each drain can become loose or disconnected during normal use. If you notice water accumulation on the inside of the unit be sure the drain tube is connected to the evaporator drain pan. If water is collecting underneath the unit make sure the end of the drain tube is in the condensate evaporator in the machine compartment. The leveling of the unit is important as the units are designed to drain properly when level. Be sure all drain lines are free of obstructions.
Drawer Maintenance Drawer Assembly Cleaning
The drawer assembly is designed to be cleaned easily. Both drawer and tracks are removable without tools. The drawer tracks are dishwasher safe or can be cleaned in a sink with detergents and a soft bristle brush. Drawers and tracks should be cleaned on a weekly basis.
Remove Drawers
Pull the drawer box out until it stops. Lift up on the drawer front and pull the drawer box completely out. Using a soft bristle brush, clean the track on the bottom of the drawer box. When finished, it should be wiped clean of all food and debris.
Tracks
The drawer box assembly must be removed. Pull the drawer tracks out until they hit a stop. Locate blue safety clips towards the back of each drawer track. Blue safety clips have a tab on the top. Push the tab back until it clicks. Lift up and pull the drawer tracks all
the way out of the drawer cage. The drawer tracks are dishwasher safe or can be cleaned in a sink with detergents and a soft
tab on top of
blue safety clip
a soft bristle brush, wash the track making sure each roller is thoroughly cleaned. The drawer cage should be cleaned with a soft bristle brush, removing any food and debris gathered on the bottom ledge. Once it’s cleaned thoroughly with a soft bristle brush, wipe remaining debris clean with a soft towel.
bristle brush. Drawers and tracks should be cleaned on a weekly basis. Using
Reassembly
Push the drawer tracks into the drawer cage. The blue safety clip must remain pushed towards the back. Lift up and slide the drawer track all the way into the drawer cage. The blue safety clip will lock in place automatically. Once all tracks are replaced, insert the drawer box. Rest the drawer box bottom track on the front track roller. Then push the drawer back in place SLOWLY. When the drawer box is about half way in you will hit a STOP. You must lift the front of the drawer up approximately ½” (1.3cm) to continue inward. Clean tracks as often as possible. The cleaner the tracks are the better they will operate.
Caster Maintenance
Wipe casters with a damp cloth monthly to prevent corrosion.
The power switch must be turned to OFF and the unit disconnected from the power source whenever performing service, maintenance functions or cleaning
the refrigerated area.
Refrigerators and Freezers
The interior and exterior can be cleaned using soap and warm water. If this isn’t sufficient, try ammonia and water or a nonabrasive liquid cleaner. When cleaning the exterior, always rub with the “grain” of the stainless steel to avoid marring the finish. Do not use an abrasive cleaner because it will scratch the stainless steel and can damage the
breaker strips and gaskets.
Stainless Steel Care and Cleaning
To prevent discoloration of rust on stainless steel several important steps need to be taken. First, we need to understand the properties of stainless steel. Stainless steel contains 70- 80% iron, which will rust. It also contains 12-30% chromium, which forms an invisible passive film over the steels surface, which acts as a shield against corrosion. As long as the protective layer is intact, the metal is still stainless. If the film is broken or contaminated, outside elements can begin to breakdown the steel and begin to form discoloration of rust. Proper cleaning of stainless steel requires soft cloths or plastic
scouring pads.
NEVER USE STEEL PADS, WIRE BRUSHES OR SCRAPERS!
Cleaning solutions need to be alkaline based or non-chloride cleaners. Any cleaner containing chlorides will damage the protective film of the stainless steel. Chlorides are also commonly found in hard water, salts, and household and industrial cleaners. If cleaners containing chlorides are used be sure to rinse repeatedly and dry thoroughly. Routine cleaning of stainless steel can be done with soap and water. Extreme stains or grease should be cleaned with a non-abrasive cleaner and plastic scrub pad. Always rub with the grain of the steel. There are stainless steel cleaners available which can restore and preserve the finish of the steels protective layer. Early signs of stainless steel breakdown are small pits and cracks. If this has begun, clean thoroughly and start to apply stainless steel cleaners in attempt
to restore the passivity of the steel.
Never use an acid based cleaning solution! Many food products have an acidic content, which can deteriorate the finish. Be sure to clean the stainless steel surfaces of ALL food products. Common items include, tomatoes,
peppers and other vegetables.
10
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Maintenance, continued
F18 Series Service and Installation Manual
Cleaning the Condenser Coil
In order to maintain proper refrigeration performance, the condenser fins must be cleaned of dust, dirt and grease regularly. It is recommended that this be done at least every three months. If conditions are such that the condenser is totally blocked in three months, the frequency of cleaning should be increased. Clean the condenser with a vacuum cleaner or stiff brush. If extremely dirty, a commercially available condenser cleaner may be required.
Failure to maintain a clean condenser coil can initially cause high temperatures and excessive run times. Continuous operation with a dirty or clogged condenser coil can result in compressor failure. Neglecting the condenser coil cleaning procedures will void any warranties associated with the compressor and cost to replace the compressor.
Never use a high-pressure water wash for this cleaning procedure as water can damage the electrical components
located near or at the condenser coil.
Doors/Hinges
Over time and with heavy use doors the hinges may become loose. If this happens tighten the screws that mount the hinge brackets to the frame of the unit. Loose or sagging doors can cause the hinges to pull out of the frame, which may damage both the doors and the hinges. In some cases this may require qualified service agents or maintenance
personnel to perform repairs.
Do not place hot pans on/against the blue ABS liner. Do not throw items into the storage area. Failure to follow these recommendations could result in damage to the interior of the cabinet or to the blower coil. Overloading the storage area, restricting the airflow, and continuous opening and closing of the doors and drawers will hamper the units ability to maintain
operational temperature.
Preventing blower coil corrosion
To help prevent corrosion of the blower coil, store all acidic items, such as pickles and tomatoes, in sealable containers. Immediately
wipe up all spills.
Units with pans should be operated with pans in place. Operating the unit without all pans in place will lower
efficiency and may damage the unit.
Continuous opening and closing of the doors will hamper the unit’s ability to maintain optimum refrigeration temperature. Top section is not intended for overnight storage. Product should be removed from pans. Pans can remain in unit while empty.
Refrigerated rail units
Product in the rail should be removed to the refrigerated base at the end of the day. This allows you to turn the rail off at night to save energy and to defrost the rail. It also helps maintain product quality. The standard wrapped refrigerated rail units are controlled by a low­pressure control that is set to maintain the proper rail temperature. An on/off switch is also provided for the rail and is required to be shut off at night. With a LiquiTec rail a thermostat is provided to maintain rail temperature as well as the rail on/off switch. The LiquiTec rail is required to be shut off at night as well to allow for defrosting. To ensure product quality in the rail it is recommended that product be
rotated every four hours.
If adding any item to the unit, be sure to keep in mind the location of the refrigeration lines on wrapped rail units. A refrigeration leak in a rail is extremely difficult and costly to repair. In some cases it cannot be repaired
at all.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
11
F18 Series Service and Installation Manual
Wiring Diagram, F18WC
Wiring Diagram, F18WR
12
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
F18 Series Service and Installation Manual
Wiring Diagram, F18MC, F18SC, F18DC & F18RC
Wiring Diagram, F18MR, F18SR, F18DR & F18RR
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
13
F18 Series Service and Installation Manual
Wiring Diagram, F18FC
Wiring Diagram, F18FR
14
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Wiring Diagram, F18PD
F18 Series Service and Installation Manual
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
15
F18 Series Service and Installation Manual
Replacement Parts
F18DC
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-BN5-0035 Condensing unit, 1/2hp, R404a
*000-BN5-0037 Condensing unit, 1/3hp, R404a
*000-BN5-0030 Condensing unit, 1/4hp, R404a
2194810 Control, Danfoss, GDM, 115V
2193927 Control, pressure, low
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0160179 Hinge Kit
3234645 Leg, 6", s/s
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
2190154 Switch, rocker
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
3234290 Shelf support, 1" blue
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
2190154 Switch, rocker
2194201 Thermostat, rail
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
F18FC
*000-BN5-0053 Condensing unit, 1/3HP, w/rec, hg
*000-BN5-0054 Condensing unit, 1/2HP, low temp, hg
*000-BN5-0055 Condensing unit, 3/4HP, low temp, hg
*000-249-0004 Coil, assembly, freezer, R404a
2194758-4 Control, Danfoss, Freezer, 115V
0160179 Hinge Kit
3234645 Leg, 6", s/s
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
3234290 Shelf support, 1" blue
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
2190154 Switch, rocker
F18DR
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
2194810 Control, Danfoss, GDM, 115V
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0160179 Hinge Kit (left or right hinged)
3234645 Leg, 6", s/s
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
3234290 Shelf support, 1" blue
16
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
F18FR
*000-249-0006 Coil assembly, frz evap, remote
3516053 Coil, solenoid, 120V/50/60HZ
3516056 Control, Temperature
0160179 Hinge Kit
3234645 Leg, 6", s/s
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
3234290 Shelf support, 1" blue
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
2194151 Timer, Paragon, #8145-00
3516102 Valve, solenoid
*Replacement part assemblies on pages 19-22.
Replacement Parts, continued
F18 Series Service and Installation Manual
F18MC
030-209-0030 Angle, Coil, Top Bae
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
*000-BN5-0030 Condensing unit, 1/4hp, R404a
2194810 Control, Danfoss, GDM, 115V
2193927 Control, pressure, low
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0420068 Hinge kit, lo prole (left or right)
2190154 Switch, rocker
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
3234645 Leg, 6", s/s
F18MR
030-209-0030 Angle, Coil, Top Bae
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
2194810 Control, Danfoss, GDM, 115V
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0420068 Hinge kit, lo prole (left or right)
3234645 Leg, 6", s/s
9321041 Nut, acorn (for pan cover)
2190154 Switch, rocker
2194201 Thermostat, rail
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
F18PD48
*000-248-0037 Coil assembly, R404A, Fan Lt
*000-BN5-0040 Condensing Assembly, 1/3-1/5 Stacked
2194810 Control, Danfoss, GDM, 115V
2194938 Control, Tstat, Danfoss, Etc1h-1
*000-402-0056 Cover Assembly, hinged, 6 pan, l/t
*000-187-006B Door Assembly, ref, 27x26, lt
3234645 Leg, 6, s/s, removable Foot
*356-478-0038 Panel, louver, 14.0, sw Cut, lh
3978014 Shelf, wire, coated
3234290 Support, shelf, plastic
2190154 Switch, rocker, 20a/125v
3516135 Thermometer, hanging, 4
F18PD72
*000-248-0030 Coil assembly, R404A
*000-BN5-003Y Condensing Assembly, 1/2-1/5 Stacked
2194810 Control, Danfoss, GDM, 115V
2194938 Control, Tstat, Danfoss, Etc1h-1
*000-402-0056 Cover Assembly, hinged, 6pan, l/t
*000-187-006B Door Assembly, ref, 27x26, lt
*000-187-006A Door Assembly, ref, 27x26, rt
3234645 Leg, 6, s/s, removable Foot
*356-478-0039 Panel, louver, 18.0, sw Cut, lh
3978014 Shelf, wire, coated
3234290 Support, shelf, plastic
2190154 Switch, rocker, 20a/125v
3516135 Thermometer, hanging, 4
*Replacement part assemblies on pages 19-22.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
17
F18 Series Service and Installation Manual
Replacement Parts, continued
F18RC
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-BN5-0035 Condensing unit, 1/2hp, R404a
*000-BN5-0037 Condensing unit, 1/3hp, R404a
*000-BN5-0030 Condensing unit, 1/4hp, R404a
2194810 Control, Danfoss, GDM, 115V
2193927 Control, pressure, low
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0160179 Hinge Kit
3234645 Leg, 6", s/s
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
3234290 Shelf support, 1" blue
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
2190154 Switch, rocker
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
2190154 Switch, rocker
2194201 Thermostat, rail
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
F18SC
030-209-0030 Angle, Coil, Top Bae
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
*000-BN5-0030 Condensing unit, 1/4hp, R404a
2194810 Control, Danfoss, GDM, 115V
2193927 Control, pressure, low
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0420068 Hinge kit, lo prole (left or right)
3234645 Leg, 6", s/s
2190154 Switch, rocker
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
F18RR
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
2194810 Control, Danfoss, GDM, 115V
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0160179 Hinge Kit
3234645 Leg, 6", s/s
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
3234290 Shelf support, 1" blue
18
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
*Replacement part assemblies on pages 19-22.
Replacement Parts, continued
F18 Series Service and Installation Manual
F18SR
030-209-0030 Angle, Coil, Top Bae
3516053 Coil, solenoid, 120V/50/60HZ (rail)
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
2194810 Control, Danfoss, GDM, 115V
3234392 Hinge, pan cover, center
3234282 Hinge, pan cover, left
3234266 Hinge, pan cover, right
9321374 Hinge, pin (for pan cover)
0420068 Hinge kit, lo prole (left or right)
3234645 Leg, 6", s/s
2190154 Switch, rocker
2194201 Thermostat, rail
3516225 Valve, expansion (rail)
3516102 Valve, solenoid (rail)
F18WC
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
*000-BN5-0030 Condensing unit, 1/4hp, R404a
*000-BN5-0031 Condensing unit, 1/5hp, R404a
2194810 Control, Danfoss, GDM, 115V
0160179 Hinge Kit
3234645 Leg, 6", s/s
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
2190154 Switch, rocker
3234290 Shelf support, 1" blue
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
F18WR
*000-248-0030 Coil assembly, R404A
*000-248-0037 Coil assembly, R404A, Fan Lt
2194810 Control, Danfoss, GDM, 115V
0160179 Hinge Kit (left or right hinged)
3234645 Leg, 6", s/s
3977984 Shelf, 19" door
3977998 Shelf, 24" door
3978014 Shelf, 27" door
3977983 Shelf, 32" door
3234290 Shelf support, 1" blue
9321040 Shelf support screw (coil side)
9321132 Shelf support screw (wall side)
*Replacement part assemblies on pages 19-22.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
19
F18 Series Service and Installation Manual
Replacement Part Assemblies
3
2
1
4
5
3
1
2
4
5
6
8
9
7
Key Part Number Description
- 000-249-0004 Coil Assembly, Evap, Freezer
1 030-262-0001 Side, evaporator 2 2160023 Fan, axiel 3 2160024 Guard, fan, 4.7", SC120-W2 4 030-260-0001 Top, frz, evaporator 5 030-259-0000 Front, enclosure 6 3516271 Valve, expansion, R404a 7 265-261-0001 Pan, freezer evaporator 8 3516073 Coil, Evaporator 9 030-263-0001 Back, evaporator
- 2184318 Harness, coil, frz, male
- 2194808 Probe, Defrost, Danfoss, Control
- 2194809 Probe, Temp, Sensor, Danfoss
1
2
4
3
7
6
8
10
9
Key Part Number Description
- 000-249-0006 Coil Assembly, Freezer Evap, Remote
1 030-262-0001 Side, evaporator 2 2160023 Fan, axiel 3 2160024 Guard, fan, 4.7", SC120-W2 4 030-260-0001 Top, frz, evaporator 5 030-259-0000 Front, enclosure 6 3516271 Valve, expansion, R404a 7 3516073 Coil, Evaporator 8 2194034 Heater, Defrost 9 265-261-0001 Pan, freezer evaporator 10 030-263-0001 Back, evaporator
- 2194046 Control, Limit, Fan Delay/Defrost
- 2194631 Fuse, Defrost Heater, 7 Amp
- 2184323 Harness, coil, frz, male, remote
1
2
3
4
5
6
5
8
7
Key Part Number Description
- 000-248-0030 Coil Assembly, R404A, Ref
1 2160024 Guard, fan, 4.7" 2 2160023 Fan, axiel, 120V 3 3516095 Coil, evaporator 4 030-232-0003 Back, evaporator, enclosure 5 3516273 Expansion valve, 1/4, R-404a 6 030-233-0001 Side, coil, angled 7 075-231-0033 Drip pan, evaporator 8 030-234-0003 Front, coil
- 2184317 Harness, coil
- 2194808 Probe, Defrost, Danfoss, Control
- 2194809 Probe, Temp, Sensor, Danfoss
20
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
6
7
9
8
Key Part Number Description
- 000-248-0037 Coil Assembly, R404A, Ref, Fan Lt
1 2160024 Guard, fan, 4.7" 2 2160023 Fan, axiel, 120V 3 3516095 Coil, evaporator 4 030-232-0003 Back, evaporator, enclosure 5 000-BNH-0030 Drip pan, evaporator 6 030-233-0038 Side, coil, angled, Rt, Blank
7 3516273 Expansion valve, 1/4, R-404a 8 030-234-0003 Front, coil 9 030-233-0039 Side, Coil, Angled, Lt, 2Fan
- 2184317 Harness, coil
- 2194808 Probe, Defrost, Danfoss, Control
- 2194809 Probe, Temp, Sensor, Danfoss
Replacement Part Assemblies, continued
3
2
1
4
F18 Series Service and Installation Manual
4
3
2
1
5
6
7
8
Key Part Number Description
- 000-BN5-0030 Assembly, 1/4 HP Condensing Unit
1 3516457 Fan Blade 2 2160020 Fan Guard 3 2162717 Fan Motor 4 3526999 Compressor, Danfoss, NF5.5CLX 5 2194787 Start Capacitor 6 3516322 Filter Dryer 7 075-231-0030 Condensate Pan 8 3516454 Condenser Coil
- 3516444 Comp, Relay, Overload, NF5.5CLX
5
4
3
2
1
6
6
7
8
Key Part Number Description
- 000-BN5-0031 Assembly, 1/5 Condensing Unit
1 3516457 Fan Blade 2 2160020 Fan Guard 3 2162717 Fan Motor 4 3526997 Compressor, Danfoss, TF4CLS 5 2194787 Start Capacitor 6 3516322 Filter Dryer 7 075-231-0030 Condensate Pan 8 3516454 Condenser Coil
- 3516446 Comp, Relay, Danfoss
1
2
5
7
8
9
Key Part Number Description
- 000-BN5-0054 Assembly, 1/2HP Cond, Low, Hot gas
1 3516554 Blade, Fan, 9.00” 2 2160019 Guard, Fan, Wire 3 2162716 Motor, Fan, 16W, 115V, CW 4 3516324 Cutout, High Pressure 5 3527001 Compressor, SC12CLX.2,115/60HZ 6 3516322 Drier, Filter, (2)Inlet 7 2194789 Capacitor, Start, 240MFD 8 3516441 Relay, Comp, SC12CLX.2 9 3516455 Coil, Condenser, 1/2 HP
- 024-034-0031 Pan, Comp, 18.00
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
3
4
Key Part Number Description
- 000-BN5-0055 Assembly, 3/4 HP Cond, Low, Hot gas
1 2160019 Guard, fan condenser
2162716 Motor, condenser fan 16W, 155V 3516433 Blade, fan 10” CW
2 3527002 Compressor, SC18CLS.2, 115V60hz
3516442 Capacitor, start, run assembly
3 3516322 Filter drier 4 3516456 Coil, condenser, 3/4hp
21
F18 Series Service and Installation Manual
Replacement Part Assemblies, continued
5
4
3
2
1
6
2
1
3
4
9
8
Key Part Number Description
- 000-BN5-0035 Assembly, 1/2HP Condenser, Med
1 3516554 Condenser fan blade 2 2160019 Condenser fan guard 3 2162716 Condenser fan motor, 115V 4 3516462 Capacitor, start-run assy 5 3527026 Compressor, Danfoss, SC12MLX 6 3516331 Hi pressure switch 7 3516322 Filter Drier 8 075-231-0031 Pan, Condensate 9 3516455 Condenser coil
5
3
4
2
1
7
8
6
7
5
Key Part Number Description
- 000-BN5-0037 Assembly, 1/3 Condensing Unit 1 3516457 Fan Blade 2 2160020 Fan Guard 3 3527000 Compress, Danfoss, NF7CLS 4 2194788 Start Capacitor 5 3516322 Filter Drier 6 075-231-0030 Pan, Condensate 7 2162717 Fan Motor 8 3516454 Condenser Coil
- 3516438 Relay, overload, compressor
6
7
8
9
10
11
Key Part Number Description
- 000-BN5-0053 Assembly, 1/3HP Cond, w/rec, hg
1 3516457 Blade, Fan, 7.25”
2160020 Guard, Fan, 7.25"
2162717 Motor, Fan, 9W, 115V
2 3527000 Compressor, NF7.0,115/60HZ, Danfoss 3 3516053 Coil, Solenoid, 120V 4 3516102 Valve, Solenoid, 1/4ODF 5 3516438 Relay, Comp, ovld 6 3516397 Accumulator 7 000-998-0030 High Pressure Assembly, 8Amp 8 2194788 Capacitor, Start, 320MFD 9 3516322 Filter Drier, (2)Inlet 10 3516458 Receiver 11 3516454 Coil, Condenser
22
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Replacement Part Assemblies, continued
000-BN5-003Y Assembly, 1/2-1/5 Stacked,
3516457 Blade, Fan, 7.25 Dia., 3516433 Blade, fan, 25deg, 10", cw 2194789 Capacitor, start, 240mfd 2194787 Capacitor, start, 280mfd 3516454 Coil, Condenser, 1/5, 1/4, 3516455 Coil, Condenser, 1/2 Hp 3526997 Compressor, 1/5hp, 115/60, r404a 3527001 Compressor, sc12clx.2, 115/60hz, 3516322 Drier, lter, (2)inlet 2160020 Guard, Fan, 7.25 2160019 Guard, fan, wire 2162717 Motor, fan, 9w, 115v, cw 2162513 Motor, fan, 35w, blast 3516193 Regulator, pressure, 1/2 3516446 Relay, Compressor, Danfoss 3516441 Relay, compressor, sc12clx.2 3516225 Valve, expansion, frz, 1/4ton
359-478-003E Panel, louver, 15.0, ptb
359-478-003D Panel, louver, 18.0, ptb
356-478-0038 Panel, louver, 14.0, sw Cut,lh
356-478-0039 Panel, louver, 18.0, sw Cut, lh
F18 Series Service and Installation Manual
000-BN5-0040 Assy, 1/3-1/5 Stacked,
3516457 Blade, Fan, 7.25 Dia. 2194787 Capacitor, start, 280mfd 2194788 Capacitor, start, 320mfd 3516454 Coil, Cond., 1/5, 1/4 3526997 Comp, 1/5hp, 115/60, r404a 3527000 Comp, nf7cls, 115v/60hz 3516322 Drier, lter, (2)inlet 2160020 Guard, Fan, 7.25 2162717 Motor, fan, 9w,115v,cw 3516193 Regulator, pressure, 1/2 3516446 Relay, Comp, Danfoss 3516438 Relay, comp, ovld, nf7clx 3516225 Valve, exp, frz, 1/4ton
000-187-0081 Door Assembly, ref, 27x26, rt, 430
000-187-0082 Door Assembly, ref, 27x26, lt, 430
000-187-006B Door Assembly, ref, 27x26, lt
000-187-006A Door Assembly, ref, 27x26, rt
1701185 Gasket, door, 27, mark7
0420067 Hinge Kit
000-402-0054 Cover Assembly, hinged, 6 Pan, ptl
000-402-0056 Cover Assembly, hinged, 6pan, l/t
9321374 Pin, hinge, salad Pan
3234266 Hinge, pan Cover, end, rh,
3234282 Hinge, pan Cover, end, lh,
3234392 Hinge, pan Cover,
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
23
F18 Series Service and Installation Manual
Standard One Year Limited Warranty
The Delfield Company (“Delfield”) warrants to the Original Purchaser of the Delfield product (herein called the “Unit”) that such Unit, and all parts thereof, will be free from defects in material and workmanship under normal use and service for a period of one (1) year from the date of shipment of the Unit to the Original Purchaser or one (1) year from the date of installation if registration is completed one (1) year from installation. During this one year warranty period, Delfield will repair or replace any defective part or portion there of returned to Delfield by the Original Purchaser which Delfield determines was defective due to faulty material or workmanship. Only during the first 90 days of the this one year warranty period, Delfield will, subject to the limits set forth below, pay labor, crating, and freight incurred in the removal of the Unit of defective component and shipment to Delfield. A maximum of 1-hour is allowed to diagnose a defective component. A maximum of 1-hour is allowed for retrieval of parts not in stock. A maximum travel distance of 100 miles round trip and 2-hours will be reimbursed. Overtime, installation/start-up, normal control adjustments, general maintenance, glass breakage, freight damage, delayed site entry because of security or hours of operation and/or correcting an end­user installation error will not be reimbursed under warranty unless pre-approved with a Service Work Authorization from Delfield. Delfield will pay the return costs if the Unit or part thereof was defective.
The term “Original Purchaser” as used herein means that person, firm, association, or corporation for whom the Unit was originally installed.
This warranty does not apply to any Unit or part thereof that has been subjected to misuse, neglect, alteration, or accident, such as accidental damage to the exterior finish, operated contrary to the recommendations specified by Delfield; or repaired or altered by anyone other than Delfield in any way so as to, in Delfield’s sole judgment, affect its quality or efficiency. This warranty does not apply to any Unit that has been moved from the location where it was originally installed. This warranty also does not cover the refrigerator drier, door gaskets or the light bulbs used in the Unit. The warranty is subject to the user’s normal maintenance and care responsibility as set forth in the Service and Installation Manual, such as cleaning the condenser coil, and is in lieu of all other obligations of Delfield. Delfield neither assumes, nor authorizes any other person to assume for Delfield, any other liability in connection with Delfield’s products.
Removal or defacement of the original Serial Number or Model Number from any Unit shall be deemed to release Delfield from all obligations hereunder or any other obligations, express or implied.
Parts furnished by suppliers to Delfield are guaranteed by Delfield only to the extent of the original manufacturer’s express warranty to Delfield. Failure of the Original Purchaser to receive such manufacturers warranty shall in no way create any warranty, expressed or implied, or any other obligation or liability on Delfield’s part in respect thereof.
Under no condition does this warranty give the Original Purchaser the right to replace the defective Unit with a complete Unit of the same manufacturer or of another make. Unless authorized by Delfield in writing, this warranty does not permit the replacement of any part, including the motor-compressor, to be made with the part of another make or manufacturer.
No claims can be made under this warranty for spoilage of any products for any reason, including system failure.
— One Year Parts, 90 Day Labor
The installation contractor shall be responsible for building access, entrance and field conditions to insure sufficient clearance to allow any hood(s), vent(s), or Unit(s) if necessary, to be brought into the building. Delfield will not be responsible for structural changes or damages incurred during installation of the Unit or any exhaust system.
Delfield shall not be liable in any manner for any default or delay in performance hereunder caused by or resulting from any contingency beyond Delfield’s control, including, but not limited to, war, governmental restrictions or restraints, strike, lockouts, injunctions, fire, food, acts of nature, short or reduced supply of raw materials, or discontinuance of the parts by the original part manufacturer.
Except as provided in any Additional Four Year Protection Plan, if applicable, and the Service Labor Contract, if applicable, the preceding paragraphs set forth the exclusive remedy for all claims based on failure of, or defect for Delfield products sold hereunder, whether the failure or defect arises before or during the warranty period, and whether a claim, however instituted, is based on contract, indemnity, warranty, tort (including negligence), strict liability, implied by statute, common-law or otherwise , and Delfield and its agents shall not be liable for any claims for personal injuries or consequential damages or loss, howsoever caused. Upon the expiration of the warranty period, all such liability shall terminate. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, IMPLIED OR STATUTORY. NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE SHALL APPLY, DELFIELD DOES NOT WARRANT ANY PRODUCTS OR SERVICES OF OTHERS
This warranty supersedes and excludes any prior oral or written representations or warranties. The sole and exclusive remedies of any person relating to the Unit, and the full liability of Delfield for any breach of this warranty, will be as provided in this warranty.
Other than this Delfield Standard One Year Limited Warranty, any applicable Delfield Additional Four Year Protection Plan or applicable Delfield Service Labor Contract, the Original Purchaser agrees and acknowledges that no other warranties are offered or provided in connection with or for the Unit or any other part thereof. The liability of Delfield for breach of any warranty obligation hereunder is limited to: (i) the repair or replacement of the Delfield Product on which the liability is based, or with respect to services, re-performance of the services; or (ii) at Delfield’s option, the refund of the amount paid for said equipment or services. Any breach by Delfield with respect to any item or unit of equipment or services shall be deemed a breach with respect to that item or unit or service only
IN NO EVENT WILL DELFIELD BE LIABLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES, OR FOR DAMAGES IN THE NATURE OF PENALTIES.
If shipment of a replacement part is requested prior to the arrival in the Delfield factory of the part claimed to be defective, the Original Purchaser must accept delivery of the replacement part on a C.O.D. basis, with credit being issued after the part has been received and inspected at Delfield’s plant and determined by Delfield to be within this warranty.
24
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
F18 Series Service and Installation Manual
F18PD One Year Limited Warranty
The Delfield Company (“Delfield”) warrants to the Original Purchaser of the Delfield product (herein called the “Unit”) that such Unit, and all parts thereof, will be free from defects in material and workmanship under normal use and service for a period of one (1) year from the date of shipment of the Unit to the Original Purchaser or one (1) year from the date of installation if registration is completed one (1) year from installation. During this one year warranty period, Delfield will repair or replace any defective part or portion there of returned to Delfield by the Original Purchaser which Delfield determines was defective due to faulty material or workmanship. During this one year warranty period, Delfield will, subject to the limits set forth below, pay labor, crating, and freight incurred in the removal of the Unit of defective component and shipment to Delfield. A maximum of 1-hour is allowed to diagnose a defective component. A maximum of 1-hour is allowed for retrieval of parts not in stock. A maximum travel distance of 100 miles round trip and 2-hours will be reimbursed. Overtime, installation/start-up, normal control adjustments, general maintenance, glass breakage, freight damage, delayed site entry because of security or hours of operation and/or correcting an end-user installation error will not be reimbursed under warranty unless pre-approved with a Service Work Authorization from Delfield. Delfield will pay the return costs if the Unit or part thereof was defective.
The term “Original Purchaser” as used herein means that person, firm, association, or corporation for whom the Unit was originally installed.
This warranty does not apply to any Unit or part thereof that has been subjected to misuse, neglect, alteration, or accident, such as accidental damage to the exterior finish, operated contrary to the recommendations specified by Delfield; or repaired or altered by anyone other than Delfield in any way so as to, in Delfield’s sole judgment, affect its quality or efficiency. This warranty does not apply to any Unit that has been moved from the location where it was originally installed. This warranty also does not cover the refrigerator drier, door gaskets or the light bulbs used in the Unit. The warranty is subject to the user’s normal maintenance and care responsibility as set forth in the Service and Installation Manual, such as cleaning the condenser coil, and is in lieu of all other obligations of Delfield. Delfield neither assumes, nor authorizes any other person to assume for Delfield, any other liability in connection with Delfield’s products.
Removal or defacement of the original Serial Number or Model Number from any Unit shall be deemed to release Delfield from all obligations hereunder or any other obligations, express or implied.
Parts furnished by suppliers to Delfield are guaranteed by Delfield only to the extent of the original manufacturer’s express warranty to Delfield. Failure of the Original Purchaser to receive such manufacturers warranty shall in no way create any warranty, expressed or implied, or any other obligation or liability on Delfield’s part in respect thereof.
Under no condition does this warranty give the Original Purchaser the right to replace the defective Unit with a complete Unit of the same manufacturer or of another make. Unless authorized by Delfield in writing, this warranty does not permit the replacement of any part, including the motor-compressor, to be made with the part of another make or manufacturer.
No claims can be made under this warranty for spoilage of any products for any reason, including system failure.
— Parts And Labor
The installation contractor shall be responsible for building access, entrance and field conditions to insure sufficient clearance to allow any hood(s), vent(s), or Unit(s) if necessary, to be brought into the building. Delfield will not be responsible for structural changes or damages incurred during installation of the Unit or any exhaust system.
Delfield shall not be liable in any manner for any default or delay in performance hereunder caused by or resulting from any contingency beyond Delfield’s control, including, but not limited to, war, governmental restrictions or restraints, strike, lockouts, injunctions, fire, food, acts of nature, short or reduced supply of raw materials, or discontinuance of the parts by the original part manufacturer.
Except as provided in any Additional Four Year Protection Plan, if applicable, and the Service Labor Contract, if applicable, the preceding paragraphs set forth the exclusive remedy for all claims based on failure of, or defect for Delfield products sold hereunder, whether the failure or defect arises before or during the warranty period, and whether a claim, however instituted, is based on contract, indemnity, warranty, tort (including negligence), strict liability, implied by statute, common-law or otherwise , and Delfield and its agents shall not be liable for any claims for personal injuries or consequential damages or loss, howsoever caused. Upon the expiration of the warranty period, all such liability shall terminate. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, IMPLIED OR STATUTORY. NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE SHALL APPLY, DELFIELD DOES NOT WARRANT ANY PRODUCTS OR SERVICES OF OTHERS
This warranty supersedes and excludes any prior oral or written representations or warranties. The sole and exclusive remedies of any person relating to the Unit, and the full liability of Delfield for any breach of this warranty, will be as provided in this warranty.
Other than this Delfield Standard One Year Limited Warranty, any applicable Delfield Additional Four Year Protection Plan or applicable Delfield Service Labor Contract, the Original Purchaser agrees and acknowledges that no other warranties are offered or provided in connection with or for the Unit or any other part thereof. The liability of Delfield for breach of any warranty obligation hereunder is limited to: (i) the repair or replacement of the Delfield Product on which the liability is based, or with respect to services, re-performance of the services; or (ii) at Delfield’s option, the refund of the amount paid for said equipment or services. Any breach by Delfield with respect to any item or unit of equipment or services shall be deemed a breach with respect to that item or unit or service only
IN NO EVENT WILL DELFIELD BE LIABLE FOR SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES, OR FOR DAMAGES IN THE NATURE OF PENALTIES.
If shipment of a replacement part is requested prior to the arrival in the Delfield factory of the part claimed to be defective, the Original Purchaser must accept delivery of the replacement part on a C.O.D. basis, with credit being issued after the part has been received and inspected at Delfield’s plant and determined by Delfield to be within this warranty.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
25
F18 Series Service and Installation Manual
Additional Four Year Protection Plan
Delfield Model# Serial# Installation Date
In addition to the Standard One Year Warranty on the Motor­Compressor contained in the above listed Delfield product (the “Unit”), The Delfield Company (“Delfield”) also agrees to repair, or exchange with similar or interchangeable parts in design and capacity at Delfield’s option, the defective Motor-Compressor contained in the Unit (the “Motor-Compressor”), or any part thereof, for the Original Purchaser only, at any time during the four (4) years following the initial one (1) year period commencing on the date of installation for the Original Purchaser. This additional Warranty is only available if the Motor-Compressor is inoperative due to defects in material or factory workmanship, as determined by Delfield in its sole judgment and discretion. The Original Purchaser shall be responsible for returning the defective Motor-Compressor to Delfield prepaid, F.O.B. at the address shown on the back cover of this manual.
The term “Original Purchaser” as used herein shall be deemed to mean that person, firm, association, or corporation for whom the equipment was originally installed.
The term “Motor-Compressor” as used herein does not include unit base, air or water-cooled condenser, receiver, electrical accessories such as relay, capacitors, refrigerant controls, or condenser fan/motor assembly. This warranty does not cover labor charges incidental to the replacement of parts. This warranty further does not include any equipment to which said condensing unit is connected, such as cooling coils, temperature controls or refrigerant metering devices. This warranty shall be void if the Motor-Compressor, in Delfield’s sole judgment, has been subjected to misuse, neglect, alteration or accident, operated contrary to the recommendations specified by the Unit manufacturer, repaired or altered by anyone other than Delfield in any way so as, in Delfield’s sole judgment, to affect its quality or efficiency or if the serial number has been altered, defaced or removed. This Warranty does not apply to a Motor-Compressor in any Unit that has been moved from the location where it was originally installed. The addition of methyl chloride to the condensing unit or refrigeration system shall void this warranty.
— For Motor-Compressor Only
General Conditions
Delfield shall not be liable in any manner for any default or delay in performance thereunder caused by or resulting from any contingency beyond Delfield’s control including, but not limited to, war, governmental restrictions or restraints, strikes, lockouts, injunctions, fire, floods, acts of nature, short or reduced supply of raw material or discontinuance of any part or the Motor-Compressor by the unit manufacturer.
Replacement of a defective Motor-Compressor is limited to one (1) Motor-Compressor by us during the four (4) year period. Delfield shall replace the Motor-Compressor part only at no charge.
This Warranty does not give the Original Purchaser of the Motor­Compressor the right to purchase a complete re placement Motor­Compressor of the same make or of another make. It further does not permit the replacement to be made with a Motor-Compressor of another kind unless authorized by Delfield. In the event Delfield authorizes the Original Purchaser to purchase a replacement Motor­Compressor locally, only the wholesale cost of the Motor-Compressor is refundable.
Expressly excluded from this warranty are damages resulting from spoilage of goods.
Except as provided in any applicable Standard One Year Limited Warranty or applicable Service Labor Contract, the foregoing is exclusive and in lieu of all other war ran ties, whether written or oral, express or implied. This Warranty supersedes and excludes any prior oral or written representations or warranties. Delfield expressly disclaims any implied warranties of merchantability, fitness for a particular purpose or compliance with any law, treaty, rule or regulation relating to the discharge of substances into the environment. The sole and exclusive remedies of any person relating to the Motor-Compressor, and the full liability of Delfield for any breach of this Warranty, will be as provided in this Warranty.
Other than any applicable Delfield Standard One Year Limited Warranty, this Delfield Additional Four Year Protection Plan and any applicable Delfield Service Labor Contract, the Original Purchaser agrees and acknowledges that no other warranties are offered or provided in connection with or for the Motor-Compressor or any part thereof. In no event will Delfield be liable for special, incidental or consequential damages, or for damages in the nature of penalties.
26
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Notes
F18 Series Service and Installation Manual
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
27
Mt. Pleasant, MI
Covington, TN
Thank you for choosing Delfield!
Help is a phone call away. Help our team of professional, courteous
customer service reps by having your model number and serial number
available at the time of your call (800) 733-8829.
Model: ____________________ S/N: ___________________
Installation Date: ____________
For a list of Delfield’s authorized parts depots,
visit our website at www.delfield.com.
980 S. Isabella Rd., Mt. Pleasant, MI 48858, U.S.A. • (989) 773-7981 or (800) 733-8829 • Fax (989) 773-3210 • www.deleld.com
Deleld reserves the right to make changes in design or specications without prior notice. ©2011 The Deleld Company. All rights reserved. Printed in the U.S.A.
DM18 07/11
Loading...