Please read this manual completely before attempting to install or operate this equipment! Notify carrier of
damage! Inspect all components immediately. See page 2.
Refrigerators and Freezers
IMPORTANT INFORMATION
READ BEFORE USE
PLEASE SAVE THESE INSTRUCTIONS!
June 2011
6000XL Series Service and Installation Manual
Delfield
Contents
Serial Number Information ........................................................ 2
The serial number tag of all 6000XL Series refrigerators and
freezers is located inside the cabinet on the left side.
Always have the serial number of your unit available when
calling for parts or service. A complete list of authorized
Delfield parts depots is available at www.delfield.com.
This manual covers standard units only. If you have a custom
unit, consult the customer service department at the number
listed below.
Receiving And Inspecting The Equipment
Even though most equipment is shipped crated, care should
be taken during unloading so the equipment is not damaged
while being moved into the building.
1. Visually inspect the exterior of the package and skid or
container. Any damage should be noted and reported to
the delivering carrier immediately.
2. If damaged, open and inspect the contents with the
carrier.
3. In the event that the exterior is not damaged, yet upon
opening, there is concealed damage to the equipment
notify the carrier. Notification should be made verbally
NOTE: Upon powering unit, there could be up to a
10 minute delay before unit begins to cool.
as well as in written form.
4. Request an inspection by the shipping company of the
damaged equipment. This should be done within 10
days from receipt of the equipment.
5. Be certain to check the compressor compartment
housing and visually inspect the refrigeration package.
Be sure lines are secure and base is still intact.
6. Freight carriers can supply the necessary damage forms
upon request.
7. Retain all crating material until an inspection has been
made or waived.
Units represented in this manual are intended for indoor use
only. Be sure the location chosen has a floor strong enough to
support the total weight of the cabinet and contents. A fully loaded
6000XL series can weigh as much as 1500 pounds. Reinforce
the floor as necessary to provide for maximum loading. For the
most efficient refrigeration, be sure to provide good air circulation
inside and out.
Inside cabinet: Do not pack refrigerator so full that air cannot
circulate. The refrigerated air is discharged at the top rear of
the unit. It is important to allow for proper air flow from the
top rear to the bottom of the unit. Obstructions to this air flow
can cause evaporator coil freeze ups and loss of temperature
or overflow of water from the evaporator drain pan. The rear
of the unit has molded ribs and the shelves have a rear turn
up on them to prevent this. However,
bags and other items can still be
located to the far rear of the cabinet.
There is also a return air diffuser
along the top front of the cabinet
interior, this also requires proper air
circulation. Prevent obstruction by
locating large boxes and tall stacks of
product to the bottom of the cabinet.
Stabilizing
Some models are supplied on casters for your convenience,
ease of cleaning underneath and for mobility. It is very
important, however, that the cabinet be installed in a stable
condition with the front wheels locked while in use.
Should it become necessary to lay the unit on its side or back
for any reason, allow at least 24 hours before start-up so as to
allow compressor oil to flow back to the sump. Failure to meet
this requirement can cause compressor failure and unit damage.
Unit repairs will not be subject to standard unit
warranties due to improper installation procedures.
Electrical connection
Refer to the amperage data on page 3, the serial tag, your
local code or the National Electrical Code to be sure the unit is
connected to the proper power source. A protected circuit of the
correct voltage and amperage must be run for con nec tion of the
line cord, or permanent connection to the unit.
The thermostat must be turned to OFF and
the unit disconnected from the power source
whenever performing service, maintenance
functions or cleaning the refrigerated area.
Outside cabinet: Be sure that the
unit has access to ample air. Avoid
hot corners and locations near stoves
and ovens.
It is recommended that the unit be installed no closer than
2” from any wall with at least 12” of clear space above the
unit. Avoid exposing glass door units to direct sunlight. Direct
sunlight through the glass doors will make the ABS liner
fade and become brittle and will greatly reduce refrigeration
efficiency.
Leveling
A level cabinet looks better and will perform better because the
doors will line up with the frames properly, the cabinet will not
be subject to undue strain and the contents of the cabinet will
not move around on the shelves. Use a level to make sure the
unit is level from front to back and side to side. Units supplied
with legs will have adjustable bullet feet to make the necessary
adjustments. If the unit is supplied with casters, no adjustments
are available. Ensure the floor where the unit is to be located
is level.
1. Open door 90˚ and lift door straight up and off hinges.
2. Remove the metal screw covers on each door-side hinge
section by sliding it down and off.
3. Remove two outer screws that mount each hinge to door,
loosen the center screw, rotate hinge 180˚, reinstall outer
screws and retighten center screw.
4. Remove two screws that mount lock on top of door, turn
door up-side-down and remount lock to top of door.
5. Use a 3/16” drill to drill holes in cabinet face frame at the
marked hinge locations on the new hinge side.
6. Remove the cabinet hinge screw covers by gently prying
them out with a small screwdriver.
7. Remove all three screws from each hinge and mount them
to the opposite side of the door opening.
8. Remove the plastic cam from the hinges by pulling straight
up, then rotating the cam 180˚ and pushing back into the
hinge.
9. Remount the door and check for proper closure and gasket
seal. Adjust hinges as needed. Once adjustment is verified,
remove the door, reinstall all hinge screw covers and set the
door back in place.
10. If plugs are needed to plug old screw holes in cabinet face
frame, please contact Delfield Parts Department at (800)
733-8821, extension 12801.
1. Open door 90˚ and lift door straight up and off hinges.
2. Remove the metal screw covers on each door-side hinge
section by sliding it down and off.
3. Remove two outer screws that mount each hinge to door,
loosen the center screw, rotate hinge 180˚, reinstall outer
screws and retighten center screw.
4. Remove two screws that mount lock on top of door, turn
door up-side-down and remount lock to top of door.
5. Pry the plugs out of the hinge mounting holes on the side
opposite the current hinge locations and set them aside.
6. Remove the cabinet hinge screw covers by gently prying
them out with a small screwdriver.
7. Remove all three screws from each hinge and mount them
to the opposite side of the door opening. Press the plugs
removed in step 5 into the screw holes from the original
hinge locations.
8. Remove the plastic cam from the hinges by pulling straight
up, then rotating the cam 180˚ and pushing back into the
hinge.
9. Remount the door and check for proper closure and gasket
seal. Adjust hinges as needed. Once adjustment is verified,
remove the door, reinstall all hinge screw covers and set the
door back in place.
10. If additional plugs are needed due to loss or damage, please
contact Delfield Parts Department at (800) 733-8821, extension 12801.
Leg & Caster Installation
Some cabinets may weigh over 1000 lbs (450 kg).
Use a lifting device capable of supporting the unit
WARNING
To install the legs, or casters refer to Figure 1 and proceed as
follows:
1. Remove unit from skid.
2. Raise unit to access leg/caster mounting bolts on bottom
of unit.
3. Remove the bolts from the cabinet and use them to attach
the legs or casters.
when removing skid or installing legs or casters.
All single-section units require that the swivel
casters be mounted on the front and rigid casters
be mounted on the rear.
The electronic temperature control constantly monitors box
temperature as well as evaporator coil temperature to maintain
consistent product temperatures. The control also sends
temperature readings to the digital temperature display. The
control circuits continually self-check and if an error occurs,
the digital display will switch from temperature read-out to
error read-out, i.e. E 1. Even when an error is displayed, the
refrigeration and controls system should continue to function,
however not at optimal performance. Whenever the display has
an error read-out, Delfield Service should be contacted.
At initial start-up or anytime power is disconnected, then
reconnected to the unit, the control will delay all operations for
a short time (up to 10 minutes.) While in this delay period, the
control initializes the control parameters and confirms that the
temperature sensors and circuits are operational. The digital
temperature display will not display temperature OR errors until
the self-check is complete and the control has switched on the
evaporator fan motor, compressor and condenser fan motor.
IMPORTANT NOTE REGARDING FREEZERS: After initializing,
the control will immediately enter a DEFROST mode and the
display will read DEF. The compressor and condenser fan as
well as the evaporator fan will remain off until initialization
defrost is complete. This initial defrost cycle may take up to
15 minutes to complete, at which time the freezing cycle will
begin. The display will continue to read DEF for an additional
30 minutes before displaying temperature.
Refrigerator:
The control is located in the control box in the top of the
refrigerator behind the removable louvered panel on the left
side. It is factory set at mid-range to maintain about 38˚F
(3˚C) box temperature. To adjust for colder temperatures, turn
the knob clockwise. For warmer temperatures, turn the knob
counter-clockwise. Turn the knob fully counter-clockwise to
turn the refrigeration system off. Never turn the knob more
than 1 dial number and always allow 8 hours for temperature
stabilization before making any additional adjustments.
Freezer:
The control is located in the control box in the top of the
refrigerator behind the removable louvered panel on the left
side. It is factory set at mid-range to maintain about -3˚F
(-18˚C) box temperature. To adjust for colder temperatures,
turn the knob clockwise. For warmer temperatures, turn the
knob counter-clockwise. Turn the knob fully counter-clockwise
to turn the refrigeration system off. Never turn the knob more
than 1 dial number and always allow 8 hours for temperature
stabilization before making any additional adjustments.
The energy saver switch is a rocker switch located next to
the thermostat knob that controls the amount of heat applied
to the door perimeter. The normal operating position for this
switch is the ON position, providing the least heat. If excessive
condensation is observed on the door opening, press the
energy saver switch to the OFF position, to increase the amount
of heat (red portion of the rocker switch will be visible).
Refrigeration & Defrost Cycle
Refrigerator:
Whenever the refrigerator is plugged in, and the control
has completed initializing, the digital thermostat will display
box temperature. The temperature control will cycle the
compressor, evaporator fan motor and condenser fan motor to
maintain box temperature at the control setting. See evaporator
fan matrix for more information.
Refrigerator Defrost
The temperature control also monitors the evaporator
temperature and will turn off the compressor and condenser
fan motor when needed to allow accumulated frost on the
evaporator to clear. During this defrost cycle, the digital
temperature display will read dEF. After the defrost cycle is
complete, the temperature control will return to a normal
cooling cycle, but the display will continue to read dEF until the
evaporator returns to normal cooling temperatures (up to 30
minutes).
Freezer:
Whenever the freezer is plugged in, and the control has
completed initializing including the initial defrost cycle (also see
Electronic Temperature Control Operation, on this page). The
digital therostat will display box temperature. The temperature
control will cycle the compressor, evaporator fan motor and
condenser fan motor to maintain box temperature at the control
setting. See evaporator fan matrix for more information.
Freezer Automatic Defrost
The control also monitors compressor total running time
and will enter a defrost cycle after total compressor running
time is greater than 4-hours since the last defrost cycle OR
if evaporator coil temperature drops below -30˚F (-34°C)
(indicating excessive frost on the coil).
Freezer Manual Defrost
If a manual defrost is desired, simply unplug the unit for several
seconds, then plug unit back in. This will cause the control to
re-initialize and then enter a defrost cycle.
™
®
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.