Please read this manual completely before attempting to install or operate this equipment! Notify carrier of damage! Inspect all
components immediately. See page 2.
18600PTL
Pizza Tables with Rail
18600PDL
Dual LiquiTec® Rail Prep Table
IMPORTANT INFORMATION
18600PTBM
Pizza Tables with Raised Rail
18600BSTM
Work Table with Backsplash
READ BEFORE USE
18600BUCM
Work Tables
CTP-NB
Countertop Condiment Rail
PLEASE SAVE THESE INSTRUCTIONS!
July 2010
Page 2
18600 and CTP-NB Series Service and Installation Manual
The serial number on 18600 Series units is located on the electrical
specifications tag affixed inside the compressor section next to the
pressure control.
The serial number on CTP-NB Series units is located on the front of
the unit.
Always have the serial number of your unit available when calling for
written permission is prohibited. “Delfield” is a registered trademark of The
Delfield Company.
Warranty may be deemed invalid if other than
authorized OEM (original equipment manufacture)
replacement parts are used in Delfield equipment.
Receiving And Inspecting The Equipment
Even though most equipment is shipped crated, care should be
taken during unloading so the equipment is not damaged while
being moved into the building.
1. Visually inspect the exterior of the package and skid or
container. Any damage should be noted and reported to
the delivering carrier immediately.
2. If damaged, open and inspect the contents with the
carrier.
3. In the event that the exterior is not damaged, yet upon
opening, there is concealed damage to the equipment
notify the carrier. Notification should be made verbally as
well as in written form.
4. Request an inspection by the shipping company of the
damaged equipment. This should be done within 10 days
from receipt of the equipment.
5. Check the lower portion of the unit to be sure legs or
6. Also open the compressor compartment housing and
7. Freight carriers can supply the necessary damage forms
8. Retain all crating material until an inspection has been
Uncrating the Equipment
First cut and remove the banding from around the crate.
Remove the front of the crate material, use of some tools will
be required. If the unit is on legs remove the top of the crate
and lift the unit off the skid. If the unit is on casters it can be
"rolled" off the skid.
casters are not bent.
visually inspect the refrigeration package. Be sure lines
are secure and base is still intact.
18600 and CTP-NB Series Service and Installation Manual
CAUTION
Installation
Location
These units are intended for indoor use only. Be sure the location
chosen has a floor strong enough to support the total weight of the
cabinet and contents. A fully loaded 72” long model may weigh as
much as 1200 pounds. Reinforce the floor as necessary to provide
for maximum loading.
For the most efficient refrigeration, be sure to provide good air
circulation inside and out.
Inside cabinet: Do not pack refrigerator so full that air cannot
circulate.
Outside cabinet: Be sure that the unit has access to ample air. Avoid
hot corners and locations near stoves and ovens.
It is recommended that the unit be installed no closer than 1” from
any wall. PDL models also require 14” (36cm) clearance at the top
and 6” (15cm) clearance at the bottom (casters).
Plumbing
Self-contained models are standard with a condensate evaporator. If,
for some reason, a unit does not have a condensate evaporator, or the
evaporator fails, the unit’s drain must have an outlet to an appropriate
drainage area or container.
Moisture collecting from improper drainage can create
a slippery surface on the floor and a hazard to
employees. It is the owner’s responsibility to provide
a container or outlet for drainage.
Electrical connection
Refer to the amperage data on page 3, the serial tag, your local code
or the National Electrical Code to be sure the unit is connected to the
proper power source. A protected circuit of the correct voltage and
amperage must be run for connection of the line cord, or permanent
connection to the unit.
Leveling
A level cabinet looks better and will perform better because the drain
pan will drain properly, the doors will line up with the frames properly,
and the cabinet will not be subject to undue strain.
Some models have casters for your convenience, for ease of cleaning
underneath and for mobility. It is important that the unit be installed in
a stable condition with the front casters locked before operating.
Care & Cleaning
Door Gasket Maintenance
Door gaskets require regular cleaning to prevent mold and mildew
build up and also to retain the elasticity of the gasket. Gasket cleaning
can be done with the use of warm soapy water. Avoid full strength
cleaning products on gaskets as this can cause them to become
brittle and crack. Never use sharp tools or knives to scrape or clean
the gasket. Gaskets can be easily replaced and do not require the use
of tools or an authorized service person. The gaskets are “Dart” style
and can be pulled out of the groove in the door and new gaskets can
be “pressed” back into place.
Drain Maintenance - Base
Each unit has a drain located inside the unit that removes the
condensation from the evaporator coil and routes it to an external
condensate evaporator pan. Each drain can become loose or
disconnected during normal use. If you notice water accumulation
on the inside of the unit be sure the drain tube is connected to the
evaporator drain pan. If water is collecting underneath the unit make
sure the end of the drain tube is in the condensate evaporator in the
machine compartment. The leveling of the unit is important as the
units are designed to drain properly when level. Be sure all drain lines
are free of obstructions.
Drawer Maintenance
Drawer Assembly Cleaning
The drawer assembly is designed to be cleaned easily. Both drawer
and tracks are removable without tools. The drawer tracks are
dishwasher safe or can be cleaned in a sink with detergents and a
soft bristle brush. Drawers and tracks should be cleaned on a weekly
basis.
The power switch must be turned to OFF and the
unit disconnected from the power source whenever
performing service or maintenance functions.
Never operate the unit without the louvered panel in
place!
Remove Drawers
Pull the drawer box out until it stops. Lift up on the drawer front and
pull the drawer box completely out. Using a soft bristle brush, clean
the track on the bottom of the drawer box. When finished, it should
be wiped clean of all food and debris.
Tracks
The drawer box assembly must be removed. Pull the drawer tracks
out until they hit a stop. Locate blue safety clips towards the back
of each drawer track. Blue safety clips have a tab on the top. Push
the tab back until it clicks. Lift up and pull the drawer tracks all
the way out of the drawer
cage. The drawer tracks
are dishwasher safe or
can be cleaned in a sink
with detergents and a soft
tab on top of
blue safety clip
a soft bristle brush, wash the track making sure each roller is
thoroughly cleaned. The drawer cage should be cleaned with a soft
bristle brush, removing any food and debris gathered on the bottom
ledge. Once it’s cleaned thoroughly with a soft bristle brush, wipe
remaining debris clean with a soft towel.
Reassembly
Push the drawer tracks into the drawer cage. The blue safety clip
must remain pushed towards the back. Lift up and slide the drawer
track all the way into the drawer cage. The blue safety clip will lock
in place automatically. Once all tracks are replaced, insert the drawer
box. Rest the drawer box bottom track on the front track roller. Then
bristle brush. Drawers and
tracks should be cleaned
on a weekly basis. Using
push the drawer back in place SLOWLY. When the drawer box is about
half way in you will hit a STOP. You must lift the front of the drawer up
approximately ½” (1.3cm) to continue inward. Clean tracks as often
as possible. The cleaner the tracks are the better they will operate.
Caster Maintenance
Wipe casters with a damp cloth monthly to prevent corrosion.
The power switch must be turned to OFF and the
unit disconnected from the power source whenever
performing service, maintenance functions or cleaning
the refrigerated area.
Refrigerators and Freezers
The interior and exterior can be cleaned using soap and warm water.
If this isn’t sufficient, try ammonia and water or a nonabrasive liquid
cleaner. When cleaning the exterior, always rub with the “grain” of
the stainless steel to avoid marring the finish. Do not use an abrasive
cleaner because it will scratch the stainless steel and can damage the
breaker strips and gaskets.
Stainless Steel Care and Cleaning
To prevent discoloration of rust on stainless steel several important
steps need to be taken. First, we need to understand the properties
of stainless steel. Stainless steel contains 70- 80% iron, which will
rust. It also contains 12-30% chromium, which forms an invisible
passive film over the steels surface, which acts as a shield against
corrosion. As long as the protective layer is intact, the metal is still
stainless. If the film is broken or contaminated, outside elements
can begin to breakdown the steel and begin to form discoloration of
rust. Proper cleaning of stainless steel requires soft cloths or plastic
scouring pads.
NEVER USE STEEL PADS, WIRE BRUSHES OR SCRAPERS!
Cleaning solutions need to be alkaline based or non-chloride cleaners.
Any cleaner containing chlorides will damage the protective film of
the stainless steel. Chlorides are also commonly found in hard water,
salts, and household and industrial cleaners. If cleaners containing
chlorides are used be sure to rinse repeatedly and dry thoroughly.
Routine cleaning of stainless steel can be done with soap and water.
Extreme stains or grease should be cleaned with a non-abrasive
cleaner and plastic scrub pad. Always rub with the grain of the
steel. There are stainless steel cleaners available which can restore
and preserve the finish of the steels protective layer. Early signs of
stainless steel breakdown are small pits and cracks. If this has begun,
clean thoroughly and start to apply stainless steel cleaners in attempt
to restore the passivity of the steel.
Never use an acid based cleaning solution! Many food
products have an acidic content, which can deteriorate
the finish. Be sure to clean the stainless steel surfaces
of ALL food products. Common items include, tomatoes,
peppers and other vegetables.
Cleaning the Condenser Coil
In order to maintain proper refrigeration performance, the
condenser fins must be cleaned of dust, dirt and grease regularly.
It is recommended that this be done at least every three months.
If conditions are such that the condenser is totally blocked in three
months, the frequency of cleaning should be increased. Clean the
condenser with a vacuum cleaner or stiff brush. If extremely dirty, a
18600 and CTP-NB Series Service and Installation Manual
commercially available condenser cleaner may be required.
Failure to maintain a clean condenser coil can initially cause high
temperatures and excessive run times. Continuous operation with
a dirty or clogged condenser coil can result in compressor failure.
Neglecting the condenser coil cleaning procedures will void any
warranties associated with the compressor and cost to replace the
compressor.
Never use a high-pressure water wash for this
cleaning procedure as water can damage the electrical
components located near or at the condenser coil.
Doors/Hinges
Over time and with heavy use doors the hinges may become loose. If
this happens tighten the screws that mount the hinge brackets to the
frame of the unit. Loose or sagging doors can cause the hinges to pull
out of the frame, which may damage both the doors and the hinges. In
some cases this may require qualified service agents or maintenance
personnel to perform repairs.
Do not place hot pans on/against the blue ABS liner.
Do not throw items into the storage area. Failure to
follow these recommendations could result in damage
to the interior of the cabinet or to the blower coil.
Overloading the storage area, restricting the airflow,
and continuous opening and closing of the doors and
drawers will hamper the units ability to maintain
operational temperature.
Refrigerated rail units
Product in the rail should be removed to the refrigerated base at the
end of the day. This allows you to turn the rail off at night to save
energy and to defrost the rail. It also helps maintain product quality.
The standard wrapped refrigerated rail units are controlled by a lowpressure control that is set to maintain the proper rail temperature.
An on/off switch is also provided for the rail and is required to be shut
off at night. With a LiquiTec rail a thermostat is provided to maintain
rail temperature as well as the rail on/off switch. The LiquiTec rail
is required to be shut off at night as well to allow for defrosting. To
ensure product quality in the rail it is recommended that product be
rotated every four hours.
If adding any item to the unit, be sure to keep in mind
the location of the refrigeration lines on wrapped rail
units. A refrigeration leak in a rail is extremely difficult
and costly to repair. In some cases it cannot be repaired
at all.
Preventing blower coil corrosion
To help prevent corrosion of the blower coil, store all acidic items,
such as pickles and tomatoes, in sealable containers. Immediately
wipe up all spills.
Units with pans should be operated with pans in place.
Operating the unit without all pans in place will lower
efficiency and may damage the unit.
Continuous opening and closing of the doors will hamper the unit’s
ability to maintain optimum refrigeration temperature. Top section is
not intended for overnight storage. Product should be removed from
pans. Pans can remain in unit while empty.
18600 and CTP-NB Series Service and Installation Manual
Operation: 18600PTBM & PTL Series
Product should be loaded into the unit with care.
Failure to heed these recommendations could result
in damage to the interior of the cabinet or the blower
coil.
This unit is equipped with two ON/OFF switches located behind the
louvered machine compartment panel. The unit’s compressor and all
evaporator fans will begin operating when the main power switch is
turned to the ON position. Temperature ranges for the base are 36°F
to 40°F.
The switch labeled rail is for the raised rail. The rail switch is
accessible through a 1.5” diameter hole in the louvered panel.
Turning this switch to the ON position will activate the refrigeration
for the rail. Temperature ranges for the raised rail are 33°F to 41°F.
Product located in the rail must be removed at the end of
day. This allows you to turn the rail off at night to save
energy and the rail will have time to defrost as needed.
A minimum of one hour of off time per day with the pans removed
from the rail is required to properly defrost the rail.
All R404A models have a high pressure limiting device. Under
severe overloading conditions, or in the event of a condenser fan
failure or a plugged or blocked condenser, this device may shut
down the refrigeration system. This device will automatically reset,
but determining the cause of the high pressure condition should be
investigated by a qualified refrigeration technician.
Operation: 18600BUCM & BSTM Series
The power must be turned to OFF and the unit
disconnected from the power source whenever
performing service or maintenance functions.
Never operate the unit without the louvered panel in
place!
After turning the ON/OFF switch to ON, the units compressor will
begin operating. Delfield refrigerated bases are designed to maintain
an operational temperature of 36°F to 40°F.
Product should be loaded into the unit with care.
Failure to heed these recommendations could result
in damage to the interior of the cabinet or the blower
coil.
Overloading the storage area, restricting the air flow
and continuous opening and closing of the doors and
drawers will hamper the units ability to maintain
operational temperature.
18600 and CTP-NB Series Service and Installation Manual
Product should be loaded into the unit with care.
Failure to heed these recommendations could result
in damage to the interior of the cabinet or the blower
coil.
This unit is equipped with two ON/OFF switches located behind the
louvered machine compartment panel. The unit’s compressor and all
evaporator fans will begin operating when the main power switch is
turned to the ON position. Temperature ranges for the base are 36°F
to 40°F (2°C to 4°C).
The switch labeled rail is for the raised rails. The rail switch is
accessible through a 1.5” (3.8cm) diameter hole in the louvered
panel. Turning this switch to the ON position will activate the
refrigeration for the rails. Temperature ranges for the raised rails are
33°F to 41°F (0.5°C to 5°C).
Product located in the rails must be removed at the end
of day. This allows you to turn the rails off at night to
save energy and the rails will have time to defrost as
needed.
A minimum of one hour of off time per day with the pans removed
from the rails is required to properly defrost the rails.
The power must be turned to OFF and the unit
disconnected from the power source whenever
performing service or maintenance functions.
Never operate the unit without the louvered panel in
place!
All R404A models have a high pressure limiting device. Under
severe overloading conditions, or in the event of a condenser fan
failure or a plugged or blocked condenser, this device may shut
down the refrigeration system. This device will automatically reset,
but determining the cause of the high pressure condition should be
investigated by a qualified refrigeration technician.
Operation: CTP-NB Series
The unit is equipped with one ON/OFF switch located on the right
end of the unit. The unit’s compressor will begin operating when
this switch is turned to the ON position. Temperature ranges for
the rail are 33°F to 41°F.
Product located in the rail must be removed at the
end of day. This allows you to turn the rail OFF at
night to save energy and the rail will have time to
defrost as needed.
A minimum of one hour of off time per day with the pans removed
from the rail is required to properly defrost the rail.
The power switch must be turned to OFF and the
unit disconnected from the power source whenever
performing service or maintenance functions.
Never operate the unit without the louvered panel in
place!
The factory recommended low-pressure control settings for 18600PTBM’s are: 55psi cut-in and 30psi cut-out to maintain
proper temperature for product in the rail. The interior temperature is controlled by the thermostat mounted on the
evaporator coil housing.
The factory recommended low-pressure control settings for 18600PDL’s & PTL’s are: 20psi (1.38bar) cut-in and 10psi
(0.70bar) cut-out to maintain proper temperature for product in the base. The rail temperature is controlled by the
thermostat mounted in the machine compartment.
The factory recommended low-pressure control settings for 18600BUCM’s & BSTM’s are: 82psi cut-in and 57psi cut-out
to maintain proper temperature.
Pressure Control
The temperature is controlled by an adjustable pressure control
located in the machine compartment. An adjustable control has
the word COLDER near the knob, with an arrow to indicate the
adjustment direction. These controls are field adjustable and do
not require a service agent.
In attempting to adjust the pressure control, you can
do damage to your unit by accidentally adjusting
the differential. Please make small incremental
adjustments if a temperature adjustment is necessary,
please contact the service department at Delfield
(800) 733-8829 or your local service agent. Delfield
is not responsible for charges incurred while having
the pressure control adjusted.
Thermostat Settings - PTL & PDL
The 18600PTL & 18600PDL models use a thermostat located in the mechanical section to control product temperature in
the LiquiTec rails.
18600 and CTP-NB Series Service and Installation Manual
Standard Labor Guidelines To Repair Or Replace Parts On Delfield Equipment
Advice and recommendations given by Delfield Service Technicians do not constitute or guarantee any special coverage.
• A maximum of 1-hour is allowed to
• A maximum of 1-hour is allowed for
• A maximum
• Overtime, installation/start-up, normal control adjustments, general maintenance, glass breakage, freight damage, and/or
correcting and end-user installation error will not be reimbursed under warranty unless pre-approved with a Service Work
Authorization from Delfield. You must submit the number with the service claim.
LABOR OF 1-HOUR IS ALLOWED TO REPLACE:
• Thermostat
• Evaporator/Condenser Fan Motor and Blade
• Door Hinges, Locks, and Gaskets
• Compressor Start Components and Overload Protector
• Thermometer
• Solenoid Coil
LABOR OF 2 HOURS TO REPLACE:
• Drawer Tracks/Cartridges • Pressure Control
• Solenoid Valve • Locate/Repair Leak
LABOR OF 3 HOURS TO REPLACE:
• Condenser or Evaporator Coil
• Expansion Valve
travel distance of 100 miles round trip and 2-hours will be reimbursed.
diagnose a defective component.
retrieval of parts not in stock.
LABOR OF 4 HOURS TO REPLACE
• Compressor
This includes recovery of refrigerant and leak check.
$55.00 maximum reimbursement for refrigerant recovery (includes recovery machine, pump, torch, oil, flux, minor fittings,
solder, brazing rod, nitrogen or similar fees.)
REFRIGERANTS
• R404A A maximum of $15.00/lb. or$1.00/oz. will be reimbursed.
18600 and CTP-NB Series Service and Installation Manual
Standard One Year Warranty (One year parts, 90 days labor.)
The Delfield Company (“Delfield”) warrants to the Original Purchaser of
the Delfield product (herein called the “Unit”) that such Unit, and all
parts thereof, will be free from defects in material and workmanship
under normal use and service for a period of one (1) year from the date
of shipment of the Unit to the Original Purchaser or, if the Original
Purchaser returns the warranty card completely filled out including the
date of installation within thirty (30) days of receipt of the Unit, one (1)
year from the date of installation. During this one year warranty period,
Delfield will repair or replace any defective part or portion there of returned
to Delfield by the Original Purchaser which Delfield determines was
defective due to faulty material or workmanship. The Original purchaser
will pay all labor, crating, freight and related costs incurred in the removal
of the Unit of defective component and shipment to Delfield, except that
during a period of either ninety (90) days from the date of shipment of
the Unit to the Original Purchaser or, if the Original Purchaser returns
the warranty card completely filled out including the date of installation
within thirty (30) days of receipt of the Unit, ninety (90) days from the
date of installation Delfield will pay all related labor costs. Delfield will
pay the return costs if the Unit or part thereof was defective.
The term “Original Purchaser” as used herein means that person, firm,
association, or corporation for whom the Unit was originally installed.
This warranty does not apply to any Unit or part thereof that has been
subjected to misuse, neglect, alteration, or accident, such as accidental
damage to the exterior finish, operated contrary to the recommendations
specified by Delfield; or repaired or altered by anyone other than Delfield
in any way so as to, in Delfield’s sole judgement, affect its quality or
efficiency. This warranty does not apply to any Unit that has been moved
from the location where it was originally installed. This warranty also
does not cover the refrigerator drier or the light bulbs used in the Unit.
The warranty is subject to the user’s normal maintenance and care
responsibility as set forth in the Service and Installation Manual, such
as cleaning the condenser coil, and is in lieu of all other obligations
of Delfield. Delfield neither assumes, nor authorizes any other person
to assume for Delfield, any other liability in connection with Delfield’s
products.
Removal or defacement of the original Serial Number or Model Number
from any Unit shall be deemed to release Delfield from all obligations
hereunder or any other obligations, express or implied.
Parts furnished by suppliers to Delfield are guaranteed by Delfield only
to the extent of the original manufacturer’s express warranty to Delfield.
Failure of the Original Purchaser to receive such manufacturer’s express
warranty to Delfield. Failure of the Original Purchaser to receive such
manufacturers warranty shall in no way create any warranty, expressed
or implied, or any other obligation or liability on Delfield’s part in respect
thereof.
IF THE CUSTOMER IS USING A PART THAT RESULTS IN A VOIDED
WARRANTY AND A DELFIELD AUTHORIZED REPRESENTATIVE
TRAVELS TO THE INSTALLATION ADDRESS TO PERFORM WARRANTY
SERVICE, THE SERVICE REPRESENTATIVE WILL ADVISE CUSTOMER
THE WARRANTY IS VOID. SUCH SERVICE CALLS WILL BE BILLED
TO CUSTOMER AT THE AUTHORIZED SERVICE CENTER’S THEN
APPLICABLE TIME AND MATERIALS RATES. CONSIDER: CUSTOMER
MAY INITIATE A SERVICE AGREEMENT WITHOUT PARTS COVERAGE.
If shipment of a replacement part is requested prior to the arrival in the
Delfield factory of the part claimed to be defective, the Original Purchaser
must accept delivery of the replacement part of a C.O.D. basis, with credit
being issued after the part has been received and inspected at Delfield’s
plant and determined by Delfield to be within this warranty.
Under no condition does this warranty give the Original Purchaser the
right to replace the defective Unit with a complete Unit of the same
manufacturer or of another make. Unless authorized by Delfield in
writing, this warranty does not permit the replacement of any part,
including the motor-compressor, to be made with the part of another
make or manufacturer.
No claims can be made under this warranty for spoilage of any products
for any reason, including system failure.
The installation contractor shall be responsible for building access,
entrance and field conditions to insure sufficient clearance to allow any
hood(s), vent(s), or Unit(s) if necessary, to be brought into the building.
Delfield will not be responsible for structural changes or damages
incurred during installation of the Unit or any exhaust system.
Delfield shall not be liable in any manner for any default or delay in
performance hereunder caused by or resulting from any contingency
beyond Delfield’s control, including, but not limited to, war, governmental
restrictions or restraints, strike, lockouts, injunctions, fire, flood, acts
of nature, short or reduced supply of raw materials, or discontinuance
of the parts by the original part manufacturer.
Except as provided in any Additional Four Year Protection Plan,
if applicable, and the Service Labor Contract, if applicable, the
foregoing is exclusive and in lieu of all other warranties, whether
written or oral, express or implied. This warranty supersedes
and excludes any prior oral or written representations or
warranties. Delfield expressly disclaims any implied warranties
of merchantability, fitness for a particular purpose of compliance
with any law, treaty, rule or regulation relating to the discharge of
substances into the environment. The sole and exclusive remedies
of any person relating to the Unit, and the full liability of Delfield for
any breach of this warranty, will be as provided in this warranty.
Other than this Delfield Standard One Year Limited Warranty, any
applicable Delfield Additional Four Year Protection Plan or applicable
Delfield Service Labor Contract, the Original Purchaser agrees and
acknowledges that no other warranties are offered or provided in
connection with or for the unit or any other part thereof.
In no event will Delfield be liable for special, incidental or consequential
damages, or for damages in the nature of penalties.
IF DURING THE WARRANTY PERIOD, CUSTOMER USES A PART FOR
THIS DELFIELD EQUIPMENT OTHER THAN AN UNMODIFIED NEW
OR RECYCLED PART PURCHASED DIRECTLY FROM DELFIELD OR
ANY OF ITS AUTHORIZED SERVICE CENTERS AND/OR THE PART
BEING USED IS MODIFIED FROM ITS ORIGINAL CONFIGURATION,
THIS WARRANTY WILL BE VOID. FURTHER, DELFIELD AND ITS
AFFILIATES WILL NOT BE LIABLE FOR ANY CLAIMS DAMAGES OR
EXPENSES INCURRED BY THE CUSTOMER WHICH ARISE DIRECTLY
OR INDIRECTLY, IN WHOLE OR IN PART, DUE TO THE INSTALLATION
OF ANY MODIFIED PART AND/OR PART RECEIVED FROM AN
UNAUTHORIZED SERVICE CENTER. If the warranty becomes void,
Customer may purchase from Delfield, if available, a Service
Agreement or service at the then current time and materials rate.
For more information on Delfield warranty’s log on and check out the
service section of our web site at www.delfield.com.
18600 and CTP-NB Series Service and Installation Manual
18600PDL One Limited Year Warranty (One Year Parts And Labor)
Delfield warrants to the Original Purchaser of the Delfield product
(herein called the “Unit”) that such Unit, and all parts thereof, will be
free from defects in material and workmanship under normal use and
service for a period of one (1) year from the date of shipment of the
Unit to the Original Purchaser or, if the Original Purchaser returns the
warranty card completely filled out including the date of installation
within thirty (30) days of receipt of the Unit, one (1) year from the
date of installation. During this one year warranty period, Delfield
will pay labor, crating and freight incurred in the removal of the Unit
or defective component and shipment to Delfield. Reimbursement is
subject to the following limitations: A maximum of 1-hour is allowed to
diagnose a defective component; A maximum of 1-hour is allowed for
retrieval of parts not in stock; A maximum travel distance of 100 miles
round trip and 2-hours will be reimbursed. Overtime, installation/startup, normal control adjustments, general maintenance, glass breakage,
freight damage, and/or correcting an end-user installation error will not
be reimbursed under warranty unless pre-approved with a Service Work
Authorization from Delfield. Delfield will pay the return costs if the Unit
or part thereof was defective.
The term “Original Purchaser” as used herein means that person, firm,
association, or corporation for whom the Unit was originally installed.
This warranty does not apply to any Unit or part thereof that has
been subjected to misuse, neglect, alteration, or accident, such as
accidental damage to the exterior finish, operated contrary to the
recommendations specified by Delfield; or repaired or altered by anyone
other than Delfield in any way so as to, in Delfield’s sole judgement,
affect its quality or efficiency. This warranty does not apply to any Unit
that has been moved from the location where it was originally installed.
This warranty also does not cover the refrigerator drier or the light
bulbs used in the Unit. The warranty is subject to the user’s normal
maintenance and care responsibility as set forth in the Service and
Installation Manual, such as cleaning the condenser coil, and is in
lieu of all other obligations of Delfield. Delfield neither assumes, nor
authorizes any other person to assume for Delfield, any other liability
in connection with Delfield’s products.
Removal or defacement of the original Serial Number or Model Number
from any Unit shall be deemed to release Delfield from all obligations
hereunder or any other obligations, express or implied.
Parts furnished by suppliers to Delfield are guaranteed by Delfield only
to the extent of the original manufacturer’s express warranty to Delfield.
Failure of the Original Purchaser to receive such manufacturers warranty
shall in no way create any warranty, expressed or implied, or any other
obligation or liability on Delfield’s part in respect thereof.
If shipment of a replacement part is requested prior to the arrival in the
Delfield factory of the part claimed to be defective, the Original Purchaser
must accept delivery of the replacement part on a C.O.D. basis, with
credit being issued after the part has been received and inspected at
Delfield’s plant and determined by Delfield to be within this warranty.
Under no condition does this warranty give the Original Purchaser the
right to replace the defective Unit with a complete Unit of the same
manufacturer or of another make. Unless authorized by Delfield in
writing, this warranty does not permit the replacement of any part,
including the motor-compressor, to be made with the part of another
make or manufacturer.
No claims can be made under this warranty for spoilage of any products
for any reason, including system failure.
The installation contractor shall be responsible for building access,
entrance and field conditions to insure sufficient clearance to allow any
hood(s), vent(s), or Unit(s) if necessary, to be brought into the building.
Delfield will not be responsible for structural changes or damages
incurred during installation of the Unit or any exhaust system.
Delfield shall not be liable in any manner for any default or delay in
performance hereunder caused by or resulting from any contingency
beyond Delfield’s control, including, but not limited to, war, governmental
restrictions or restraints, strike, lockouts, injunctions, fire, flood, acts of
nature, short or reduced supply of raw materials, or discontinuance of
the parts by the original part manufacturer.
Except as provided in any Additional Four Year Protection Plan, if
applicable, and the Service Labor Contract, if applicable, the foregoing
is exclusive and in lieu of all other warranties, whether written or
oral, express or implied. This warranty supersedes and excludes
any prior oral or written representations or warranties. Delfield
expressly disclaims any implied warranties of merchantability,
fitness for a particular purpose or compliance with any law, treaty,
rule or regulation relating to the discharge of substances into
the environment. The sole and exclusive remedies of any person
relating to the Unit, and the full liability of Delfield for any breach of
this warranty, will be as provided in this warranty.
Other than this Delfield Standard One Year Limited Warranty, any
applicable Delfield Additional Four Year Protection Plan or applicable
Delfield Service Labor Contract, the Original Purchaser agrees and
acknowledges that no other warranties are offered or provided in
connection with or for the Unit or any other part thereof.
In no event will Delfield be liable for special, incidental or consequential
damages, or for damages in the nature of penalties.
18600 and CTP-NB Series Service and Installation Manual
Additional Four Year Protection Plan (for Motor-Compressor only)
Installation
Delfield Model# Serial # Date
General Conditions
Delfield shall not be liable in any manner for any default or delay in
performance hereunder caused by or resulting from any contingency
beyond Delfield’s control, including, but not limited to, war,
In addition to the Standard One Year Warranty on the MotorCompressor contained in the above listed Delfield product (the
“Unit”), The Delfield Company (“Delfield”) also agrees to repair, or
exchange with similar or interchangeable parts in design and capacity
at Delfield’s option, the defective Motor-Compressor contained in the
Unit (the “Motor-Compressor), or any part thereof, for the Original
Purchaser only, at any time during the four (4) years following the
initial one (1) year period commencing on the date of installation for the
Original Purchaser. Failure of the Original Purchaser to register the
registration card containing the Original Purchasers name, address,
date of installation, model number and serial number of the Unit
containing the Motor-Compressor within 30 days from the date of
installation shall void this warranty. This additional warranty is only
available if the Motor-Compressor is inoperative due to defects in
material or factory workmanship, as determined by Delfield in its sole
judgement and discretion. The Original Purchaser shall be responsible
for returning the defective Motor-Compressor to Delfield prepaid, F.O.B.
at the address shown on the back cover of this manual.
The term “Original Purchaser” as used herein means that person, firm,
association, or corporation for whom the Unit was originally installed.
The term “Motor-Compressor” as used herein does not include unit
base, air or water cooled condenser, receiver, electrical accessories
such as relay, capacitors, refrigerant controls, or condenser fan/motor
assembly. This warranty does not cover labor charges incidental to
the replacement of parts. This warranty further does not include
any equipment to which said condensing unit is connected, such as
cooling coils, temperature controls or refrigerant metering devices.
This warranty shall be void if the Motor-Compressor, in Delfield’s
sole judgement, has been subjected to misuse, neglect, alteration or
accident, operated contrary to the recommendations specified by the
Unit manufacturer, repaired or altered by anyone other than Delfield
in any way so as, in Delfield’s sole judgment, to affect its quality or
efficiency or if the serial number has been altered, defaced or removed.
This Warranty does not apply to a Motor-Compressor in any Unit that
has been moved from the location where it was originally installed.
The addition of methyl chloride to the condensing unit or refrigeration
system shall void this warranty.
governmental restrictions or restraints, strike, lockouts, injunctions,
fire, flood, acts of nature, short or reduced supply of raw materials,
or discontinuance of any part or the Motor-Compressor by the unit
manufacturer.
Replacement of a defective Motor-Compressor is limited to one (1)
Motor-Compressor by us during the four (4) year period. Delfield
shall replace the Motor-Compressor at no charge.
This warranty does not give the Original Purchaser of the Motor-
Compressor the right to purchase a complete replacement Motor-
Compressor of the same make or of another make. It further does
not permit the replacement to be made with a Motor-Compressor
of another kind unless authorized by Delfield. In the event Delfield
authorizes the Original Purchaser to purchase a replacement Motor-
Compressor locally, only the wholesale cost of the Motor-Compressor
is refundable.
Expressly excluded from this warranty are damages resulting from
spoilage of goods.
Except as provided in any applicable Standard One Year Limited
Warranty or applicable Service Labor Contract, the foregoing is
exclusive and in lieu of all other warranties, whether written or
oral, express or implied. This Warranty supersedes and excludes
any prior oral or written representations or warranties. Delfield
expressly disclaims any implied warranties of merchantability,
fitness for a particular purpose or compliance with any law, treaty,
rule or regulation relating to the Motor-Compressor, and the full
liability of Delfield for any breach of this warranty, will be as
provided in this warranty.
Other than any applicable Delfield Standard One year Limited
Warranty, this Delfield Additional Four Year Protection Plan and any
applicable Delfield Service Labor Contract, the Original Purchaser
agrees and acknowledges that no other warranties are offered or
provided in connection with or for the Motor-Compressor or any
part thereof.
In no event will Delfield be liable for special, incidental or consequential
damages, or for damages in the nature of penalties.