TYPICAL WIRING DIAGRAM
NOTE: Larger versions of the Typical Wiring Diagrams are available in the products’
operator manuals, refer to DSE Publication: 057-310 DSE8910 Operator Manual & 057-311
DSE8920 Operator Manual, both available from www.deepseaelectronics.com.
Deep Sea Electronics Ltd.
Tel:+44 (0)1723 890099
Email: support@deepseaelectronics.com
Web: www.deepseaelectronics.com
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Email: USAsupport@deepseaelectronics.com
Web: www.deepseaelectronics.com
DEEP SEA ELECTRONI CS
DSE8910 & DSE8920 Installation Instructions
ACCESSING THE RUNNING CONFIGURATION EDITOR
• The Running Configuration Editor is accessible without stopping the generator. All protections
remain active whilst the ‘Running Configuration Editor is accessed.
• Press and hold the Tick button to enter the Running Configuration Editor.
EDITING A PARAMETER
• Enter the Running Configuration Editor as described above.
• Press the Up or Down buttons to select the section to view/change. The current selected
section highlights in green.
• Press the Left or Right buttons to select the Subsection/Parameter to be edited. The
current selected item highlights in green.
• To edit the parameter, press the Tick button to enter the edit mode. The parameter is no
longer highlighted green to indicate editing.
• Press the Up or Down buttons to change the parameter to the required value.
• Press the Tick button to save the value. The parameter highlights green to indicate that it has
been saved.
• To exit the editor and save the changes, press and hold the Tick button.
SELECTING THE DSE8910 OR DSE8920 SOFTWARE APPLICATION
• Ensure the generator is at rest and the module by pressing the Stop/Reset Mode button.
• Enter the Running Configuration Editor as described above.
• Press the Up or Down buttons to navigate to the MODEL TYPE section. The section
highlights in green when selected.
• Press the Right button to select the MODEL SELECTION parameter. The parameter
highlights in green when selected.
• To edit the parameter, press the Tick button to enter the edit mode. The parameter is no
longer highlighted green to indicate editing.
• Press the Up or Down buttons to change between DSE8910 and DSE8920, by default
DSE8920 is selected.
• Press the Tick button to change the software application, a confirmation box appears.
• Press the Left or Right buttons to select YES to confirm software application change.
When prompted, remove the power supply to the module and then reapply the power supply. The
module powers up in the newly selected software application.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically
exited to ensure security.
RUNNING CONFIGURATION EDITOR
8910: Home / Engine / Generator /
Bus / I/O / PLC / Status
8920: Home / Engine / Generator /
Mains / I/O / PLC / Status
Display Options
Page Timer
Mains Decoupling Test
Mode
Enable / Disable
External Alarm Alert
Adjustments
Frequency Adjust
Litres / Imp Gal / US Gal
Do Not Remove / Safe to Remove
/ Not Detected / Unknown
Maintenance Alarm 1, 2 & 3
Control Mode
Power Control Mode
Const Power / Frequency Power /
Voltage Power
Const Reactive / Voltage-Reactive
Power / Power-Power Factor
Mains
Mains Stability Timer
310 mm X 162 mm X 51.3 mm (12.2 ” X 6.38 ” X 2.02 ”)
282 mm X 136 mm (11.10” X 5.35”)
-40 ºC to +70 ºC (-40 ºF to +158 ºF)
-40 ºC to +80 ºC (-40 ºF to +176 ºF)
PANEL FASCIA FIXING CLIPS
NOTE: In conditions of excessive vibration, mount the module on suitable anti-vibration
mountings.
The module is held into the panel fascia using the supplied fixing clips:
• Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the
clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip
are inside their allotted slots.
• Turn the fixing clip screws clockwise until they make contact with the panel fascia.
• Turn the screw a quarter of a turn to secure the module into the panel fascia. Care must be taken
not to over tighten the fixing clip screws.
REQUIREMENTS FOR UL CERTIFICATION
WARNING!: More than one live circuit exists, see diagram overleaf for further information.
ATTENTION!: Il existe plusieurs circuits sous tension. Voir le schéma au verso pour plus
d'informations.
Screw Terminal Tightening
Torque
• Terminals suitable for connection of conductor size 13 AWG to 20
AWG (0.5 mm² to 2.5 mm²).
• Conductor protection must be provided in accordance with NFPA 70,
Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine
starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit
conductors shall be separated and secured to maintain at least ¼ ”
(6 mm) separation from the generator and mains connected circuit
conductors unless all conductors are rated 600 V or greater.
• Must be connected through UL Listed or Recognized isolating
current transformers with the secondary rating of 5 A max.
• Must be connected to communication circuits of UL Listed equipment
• Suitable for flat surface mounting in Type 1 Enclosure Type rating
with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
• Suitable for pollution degree 3 environments when voltage sensing
inputs do not exceed 300 V. When used to monitor voltages over
300 V device to be installed in an unventilated or filtered ventilation
enclosure to maintain a pollution degree 2 environment.
• -22 ºF to +122 ºF (-30 ºC to +50 ºC)