TYPICAL WIRING DIAGRAM
Deep Sea Electronics Inc.
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator
manual, refer to DSE Publication: 057-276 DSE8003 MKII Operator Manual available from
www.deepseaplc.com for more information.
053-231 ISSUE: 1
DSE8003 MKII INSTALLATION INSTRUCTIONS
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
• The ‘Running’ Configuration Editor for the DSE8003 MKII or connected modules is accessible
without stopping the generators. All protections remain active whilst the ‘Running’ Configuration
Editor is accessed.
• Press the (Up) or (Down) button or press the screen to select which DSE module’s
‘Running’ Configuration Editor is to be entered. A green border appears to indicate that module has
been selected.
• Press and hold the (Tick) button or press the (Config) icon on the top right of the screen
to enter the ‘Running’ Configuration Editor of the selected DSE module. If no DSE module is
selected, the ‘Running’ Configuration Editor for the DSE8003 MKII is entered.
• Once entered, press the (Left) or (Right) button to change between the
DSE8003 MKII or connected module’s ‘Running’ Configuration Editor.
EDITING A PARAMETER
• Enter the ‘running’ configuration editor as described above.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
Email: support@deepseaplc.com
Web: www.deepseaplc.com
Tel: +1 (815) 316 8706
Fax: +1 (815) 316 8708
Email: support@deepseausa.com
Web: www.deepseausa.com
• Press the (Up) or (Down) buttons to select the section to view/change. The current
selected section/parameter highlights in green.
• Press the appropriate combination of navigation buttons to select to required subsection or
parameter to view/change.
• To edit the parameter, press the (Tick) button to enter the edit mode. The parameter is no
longer highlighted green to indicate editing.
• Press the (Up) or (Down) buttons to change the parameter to the required value.
• Press the (Tick) button to save the value. The parameter highlights green to indicate that it
has been saved.
• To exit the editor and save the changes, press and hold the (Tick) button.
NOTE: Configuration of the Layout File used for Multiset Mode is achieved using the DSE
SCADA Suite PC software and then uploaded to the DSE8003 MKII using a USB memory device.
For more information, refer to DSE publication 057-128 DSE8005 SCADA Suite PC Software
Manual available from www.deepseaplc.com.
DSE8003 MKII ‘RUNNING’ CONFIGURATION EDITOR (SYSTEM SECTION)
Language English
Units Pressure kPA / bar / psi
Temperature
Volume Litres / Imperial Gallons / US Gallons
Display Options Graphics Bars / Meters
Commissioning Screen Enable / Disable
Bus Breaker Present Enable / Disable
Tier 4 Screen Enable / Disable
Backlight Backlight Level 0 %
Alarms External Alarm Alert Enable / Disable
Mode Config Source Layout File (Multiset Mode) / Internal Config (Singleset Mode)
Slave Setup Channel RS232 / RS485 / Ethernet
Slave ID 0
RS232 / RS485 Baud Rate 9600 to 115200
Slave IP Setup Slave Port 0
Slave IP 000.000.000.000
Host IP Setup Host Port 0
DHCP Enable Enable / Disable
Host IP 000.000.000.000
Subnet Mask 000.000.000.000
Gateway IP 000.000.000.000
DNS IP 000.000.000.000
Advanced Inactivity Timeout 0 s
Packet Timeout 0 ms
Multiset Control 000.000.000.000
MAC Address
Sounder Multiset Sounder Enable / Disable
Output C Output Source Communications Link Lost / Emergency Stop / Common Warning /
Output D
Module Time hh:mm:ss
Module Date MM/DD/YYYY
Date Format YYYY/MM/DD / MM/DD/YYYY / DD/MM/YYYY
Time Synchronise Enable / Disable
Version Select Version
Files Select File
°C / °F
Common Shutdown / Common Electrical Trip / Common Alarm /
Combined Maintenance Alarm / Audible Alarm / Not Used
CONNECTED DSE MODULE ‘RUNNING’ CONFIGURATION EDITOR (SLAVE SECTION)
CONFIGURATION FOR MULTISET MODE (GRAPHICAL USER INTERFACE SETUP)
NOTE: Configuration of the Layout File used for Multiset Mode is achieved using the DSE
SCADA Suite software and then uploaded to the DSE8003 MKII using a USB memory device. For
more information, refer to DSE publication 057-128 DSE8005 SCADA Suite PC Software Manual
available from www.deepseaplc.com.
The Layout File is configured using the DSE8005 SCADA Suite PC Software in conjunction with a USB
storage device. To configure and install the Layout File:
• Use the DSE8005 SCADA Suite PC Software to design the graphical user interface for the Multiset
Mode.
• Save the file to the root directory of a USB storage device with the filename layout.xml.
• Insert the USB storage device into the USB host socket on the rear of the DSE8003 MKII.
• Access the DSE8003 MKII ‘Running’ Configuration Editor as documented overleaf.
• Navigate to the Layout Update section in ‘Running’ Configuration Editor and select the layout file by
pressing the (Tick) button when the file is highlighted.
• Once the file is selected, the display prompts a power cycle.
• Turn the DSE8003 MKII off and then on, the configuration file is loaded automatically.
DIMENSIONS AND MOUNTING
Dimensions 317 mm X 169 mm X 43 mm (12.47” X 6.65” X 1.69”)
Panel Cutout 282 mm X 136 mm (11.10” X 5.35”)
Weight 1.0 kg (2.20 lb)
Operating Temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Storage Temperature -40 ºC to +80 ºC (-40 ºF to +176 ºF)
NOTE: The available parameters in the ‘Running’ Configuration Editor change depending
upon the connected DSE module. For more information, refer to DSE module’s installation
instructions or operator manual available from www.deepseaplc.com.
REQUIREMENTS FOR UL CERTIFICATION
Screw Terminal Tightening
Torque
Conductors
Communication Circuits
DC Output Pilot Duty
Mounting
Operating Temperature
• 4.5 lb-in (0.5 Nm)
Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²).
• Conductor protection must be provided in accordance with NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated
secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to
maintain at least ¼” (6 mm) separation from the generator and mains connected circuit conductors unless
all conductors are rated 600 V or greater.
Must be connected to communication circuits of UL Listed equipment
0.5 A
Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding air temperature -22 ºF
to +122 ºF (-30 ºC to +50 ºC)
• Suitable for pollution degree 3 environments
-22 ºF to +122 ºF (-30 ºC to +50 ºC)