Deep SEA Electronics DSE7420 Mkii, DSE7410 Mkii User Manual

TYPICAL WIRING DIAGR AM
NOTE: Terminals 41, 42, 43 & 44 are not fitted to the DSE7410 MKII.
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator manual, refer to DSE Publication: 057-263 DSE7410 MKII & DSE7420 MKII Operator Manual available from www.deepseaelectronics.com for more information.
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Fax: +1 (815) 316 8708
Email: support@deepseausa.com
Web: www.deepseausa.com
D E E P S E A E L E C T R O N I C S
DSE7410 MKII & DSE7420 MKII Installation Instructions
053-191
ISSUE 3
ACCESSING THE MAIN CONFIGURATION EDITOR
Ensure the engine is at rest and the module is in STOP mode by pressing the (Stop/Reset) button.
Press the (Stop/Reset) and (Tick) buttons simultaneously.
If a module security PIN has been set, the PIN number request is then shown:
The first ‘#’ changes to ‘0’. Press the (Up) or (Down) button to adjust it to the correct value.
Press the (Right) button when the first digit is correctly entered. The digit previously entered now shows ‘#’ for security.
Repeat this process for the other digits of the PIN number. Press the (Left) button to move back to adjust one of the previous
digits.
When the (Tick) button i s pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, the PIN must be re-entered.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed:
EDITING A PARAMETER
Enter the editor as described above.
Press the (Right) or (Left) buttons to cycle to the section to view/change.
Press the (Up) or (Dow n) buttons to select the parameter to view/change within the currently selected section.
To edit the parameter, press the (Tick) button to enter edit mode. The parameter begins to flash to indicate editing.
Press the (Up) or (Dow n) buttons to change the parameter to the required value.
Press the (Tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor and save the changes, press and hold the (Tick) button.
To exit the editor and not save the changes, press and hold the (Stop/Reset) button.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE publication 057-262 DSE7410 MKII & DSE7420 MKII Configuration Suite PC Software Manual available from www.deepseaelectronics.com.
DSE7410 MKII & DSE7420 MKII
MAIN CONFIGURATION EDITOR PARAMETERS
NOTE: Depending upon module configuration, some values in the Main & Running Configuration Editors may not be available. For more information refer to DSE publication 057-262 DSE7410 MKII & DSE7420 MKII Configuration Suite PC Software Manual available from www.deepseaelectronics.com
Section
Parameter As Shown On Display
Value
Display
Contrast
0 % Language
English
Current Date and Time
dd:mm:yyyy hh:mm:ss
Dual Mutual Mode
Set Priority / Run Time / Engine Hours
Dual Mutual Priority
0 Dual Mutual Duty Time
0 h 0 m
Alt Config
Config to Edit
Main Configuration / Alt Config 1, 2, 3, 4 or 5
Default Configuration
Main Configuration / Alt Config 1, 2, 3, 4 or 5
Engine
Oil Pressure Low Shutdown
0.00 bar 0 psi 0 kPa
Oil Pressure Low Pre Alarm
0.00 bar 0 psi 0 kPa
Coolant Temperature Low Warning
0 ºC 0 ºF
Coolant Temperature High Pre Alarm
0 ºC 0 ºF
Coolant Temperature High Electrical Trip
0 ºC 0 ºF
Coolant Temperature High Shutdown
0 ºC 0 ºF
Fuel Usage Running Rate
0 % Fuel Usage Stopped Rate
0 % Specific Gravity
0.00 Pre Heat Temp
0 ºC 0 ºF
Pre Heat Timer
0 h 0 m 0 s
Post Heat Temp
0 ºC 0 ºF
Post Heat Timer
0 h 0 m 0 s
Droop
Active / Inactive
Droop
0.0 % Crank Disconnect Oil Pressure Delay
0.0 s Crank Disconnect
0 V Under Speed Shutdown
Active / Inactive
Under Speed Shutdown
0 RPM Under Speed Warning
Active / Inactive
Under Speed Warning
0 RPM Under Speed Delay
0.0 s Over Speed Warning
Active / Inactive
Over Speed Warning
0 RPM Over Speed Shutdown
0 RPM Over Speed Delay
0.0 s Overspeed Overshoot
0 % Overspeed Overshoot Delay
0.0 s Battery Under Voltage Warning
Active / Inactive
Battery Under Voltage Warning
0 V
Battery Under voltage Warning Delay
0 h 0 m 0 s
Battery Over Voltage Warning
Active / Inactive
Battery Over Voltage Warning
0 V Battery Over Voltage Warning Delay
0 h 0 m 0 s
Charge Alternator Failure Warning
Active / Inactive
Charge Alternator Failure Warning
0 V Charge Alternator Warning Delay
0 h 0 m 0 s
Charge Alternator Failure Shutdown
Active / Inactive
Charge Alternator Failure Shutdown
0.0 V Charge Alternator Shutdown Delay
0 h 0 m 0 s
Inlet Temperature Alarm
0 ºC 0 ºF
Inlet Temperature Pre-Alarm
0 ºC 0 ºF
Generator
AC System
3 Phase, 4 Wire
Under Voltage Shutdown
0 V Under Voltage Pre Alarm
0 V Under Voltage Delay
0.0 s Nominal Voltage
0 V Over Voltage Pre Alarm
0 V Over Voltage Shutdown
0 V Over Voltage Delay
0.0 s Under Frequency Shutdown
0.0 Hz Under Frequency Pre Alarm
0.0 Hz Under Frequency Delay
0.0 s
MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED)
Section
Parameter As Shown On Display
Value
Generator
Nominal Frequency
0.0 Hz
(Continued)
Over Frequency Pre Alarm
0.0 Hz Over Frequency Shutdown
0.0 Hz Over Frequency Delay
0.0 s Frequency Overshoot
0 % Frequency Overshoot Delay
0 m 0.0 s
CT Primary
0 A CT Secondary
0 A Earth CT Primary
0 A Full Load Rating
0 A Delayed Over Current
Active / Inactive
Delayed Over Current
0 % Earth Fault Trip
Active / Inactive
Earth Fault Trip
0 % kW Overload Trip
0 %
Mains
AC System
3 Phase, 4 Wire
DSE7420 MKII
Under Voltage Trip
0 V
Only
Over Voltage Trip
0 V Under Frequency Trip
0.0 Hz Over Frequency Trip
0.0 Hz
Timers
Start Delay Off Load
0 h 0 m 0 s
Start Delay On Load
0 h 0 m 0 s
Start Delay Mains Fail
0 h 0 m 0 s
Start Delay Telemetry
0 h 0 m 0 s
Mains Transient Delay
0 m 0 s
Engine Cranking
0 m 0 s
Engine Cranking Rest
0 m 0 s
Engine Smoke Limiting
0 m 0 s
Engine Smoke Limiting Off
0 m 0 s
Engine Safety On Delay
0 m 0 s
Engine Warming
0 h 0 m 0 s
ECU Override
0 m 0 s
(Mains) Transfer Time
0 m 0.0 s
Return Delay
0 h 0 m 0 s
Engine Cooling
0 h 0 m 0 s
Engine Fail To Stop Delay
0 m 0 s
LCD Page Delay
0 h 0 m 0 s
LCD Scroll Delay
0 h 0 m 0 s
Sleep Timer
0 h 0 m 0 s
Backlight Timer
0 h 0 m 0 s
Schedule
Schedule
Active / Inactive
Schedule Period Bank 1
Weekly / Monthly
On Load / Off Load / Auto Start Inhibit, Week, On, Run Time and Day Selection (1 to 8)
Press Tick to begin editing then up or down when selecting the different parameters in the scheduler.
Schedule Period Bank 2
Weekly / Monthly
On Load / Off Load / Auto Start Inhibit, Week, On, Run Time and Day Selection (1 to 8)
Press Tick to begin editing then up or down when selecting the different parameters in the scheduler.
DIMENSIONS AND MOUNTING
Parameter
Specification
Dimensions
245 mm x 184 mm x 51 mm (9.6 ” x 7.2 ” x 2.0 ”)
Panel Cut-out
220 mm x 160 mm (8.7 ” x 6.3 ”)
Weight
0.98 kg (2.16 lb)
Operating Temperature With Standard Display
-30 ºC to +70 ºC (-22 ºF to +158 ºF)
Operating Temperature With Heated Display
-40 ºC to +70 ºC (-40 ºF to +158 ºF) Storage Temperature
-40 ºC to +80 ºC (-40 ºF to +176 ºF)
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
The ‘running’ editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered.
Press and hold the (Tick) button to enter the running editor.
RUNNING CONFIGURATION EDITOR PARAMETERS
Section
Parameter As Shown On Display
Value
Display
Contrast
0% Language
English
Dual Mutual Status
Set Priority (1 to 8)
Engine
Manual Frequency Trim
0.0 Hz
Speed Bias
0.0 Unit
Governor Gain
0.0 Frequency Adjust
0 % DPF Auto Regeneration Inhibit
Active / Inactive
DPF Manual Regeneration Request
Active / Inactive
ECU Service Mode
Active / Inactive
Escape Mode
Active / Inactive
AVR
Droop (% of Set Point)
0.0 Proportional Set Point
0.0 Integral Set Point
0.0 Derivative Set Point
0.0 Off Load Duty Cycle
0.0 Maximum Duty Cycle
0.0 Soft Start Ramp Start Point
0.0 Soft Start Ramp Rate (%/Hz)
0.0 Alternative Configuration
0 Stability Selection
0
REQUIREMENTS FOR UL CERTIFICATION
WARNING!: More than one live circuit exists, see diagram overleaf for further
information.
Specification
Description
Screw Terminal Tightening Torque
4.5 lb-in (0.5 Nm)
Conductors
Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²).
Conductor protection must be provided in accordance with NFPA 70, Article 240
Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit.
The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least
¼” (6 mm) separation from the generator and mains connected
circuit conductors unless all conductors are rated 600 V or greater.
Current Inputs
Must be connected through UL Listed or Recognized isolating current transformers with the secondary rating of 5 A max.
Communication Circuits
Must be connected to communication circuits of UL Listed equipment
DC Output Pilot Duty
0.5 A
Mounting
Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be installed in an unventilated or filtered ventilation enclosure to maintain a pollution degree 2 environment.
Operating Temperature
-22 ºF to +122 ºF (-30 ºC to +50 ºC)