Deep Sea Electronics DSE7400 Operator Manual

DEEP SEA ELECTRONICS PLC
DSE7400 Operator Manual
Author: Ashley Senior
DSE7400 Operator Manual ISSUE 1
DSE7400 Operator Manual
DEEP SEA ELECTRONICS PLC
Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND
Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303
E-mail : sales@deepseaplc.com Website : www.deepseaplc.com
DSE7400 Operator Manual
© Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above.
The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective
companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments List
Issue Comments Minimum
1 Initial release V1.0.0 2011.10v1.0.7
Module version
required
Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
Clarification of notation used within this publication.
Highlights an essential element of a procedure to ensure correctness.
NOTE:
Indicates a procedure or practice, which, if not strictly observed, could result in
CAUTION!
damage or destruction of equipment. Indicates a procedure or practice, which could result in injury to personnel or loss
WARNING!
of life if not followed correctly.
Minimum
Configuration Suite
Version required
2
DSE7400 Operator Manual
TABLE OF CONTENTS
Section Page
1 BIBLIOGRAPHY .............................................................................................. 7
1.1 INSTALLATION INSTRUCTIONS ....................................................................................... 7
1.2 TRAINING GUIDES ............................................................................................................. 7
1.3 MANUALS ........................................................................................................................... 7
1.4 THIRD PARTY DOCUMENTS ............................................................................................. 7
2 INTRODUCTION .............................................................................................. 8
3 SPECIFICATIONS ............................................................................................ 9
3.1 PART NUMBERING ............................................................................................................ 9
3.1.1 SHORT NAMES ............................................................................................................ 9
3.2 TERMINAL SPECIFICATION ............................................................................................ 10
3.3 POWER SUPPLY REQUIREMENTS ................................................................................ 10
3.4 GENERATOR VOLTAGE / FREQUENCY SENSING ....................................................... 10
3.5 GENERATOR CURRENT SENSING ................................................................................ 11
3.5.1 VA RATING OF THE CTS .......................................................................................... 11
3.5.2 CT POLARITY ............................................................................................................ 12
3.5.3 CT PHASING .............................................................................................................. 12
3.5.4 CT CLASS .................................................................................................................. 12
3.6 INPUTS .............................................................................................................................. 13
3.6.1 DIGITAL INPUTS ........................................................................................................ 13
3.6.2 ANALOGUE INPUTS .................................................................................................. 13
3.6.2.1 OIL PRESSURE .................................................................................................. 13
3.6.2.2 COOLANT TEMPERATURE ............................................................................... 13
3.6.2.3 FUEL LEVEL ....................................................................................................... 13
3.6.2.4 FLEXIBLE SENSOR ............................................................................................ 14
3.6.3 CHARGE FAIL INPUT ................................................................................................ 14
3.6.4 MAGNETIC PICKUP ................................................................................................... 14
3.7 OUTPUTS .......................................................................................................................... 15
3.7.1 OUTPUTS A & B ......................................................................................................... 15
3.7.2 CONFIGURABLE OUTPUTS C & D (LOAD SWITCHING) ....................................... 15
3.7.2.1 CONTACTOR COILS .......................................................................................... 15
3.7.2.2 UNDERVOLTAGE (UV COILS) ........................................................................... 15
3.7.2.3 CLOSING COILS ................................................................................................. 16
3.7.2.4 OPENING COILS / SHUNT TRIP COILS ............................................................ 16
3.7.3 OUTPUTS E,F,G,H, I & J ........................................................................................... 16
3.8 COMMUNICATION PORTS .............................................................................................. 17
3.9 COMMUNICATION PORT USAGE .................................................................................. 17
3.9.1 CAN INTERFACE ...................................................................................................... 17
3.9.2 USB CONNECTION ................................................................................................... 18
3.9.3 USB HOST-MASTER (USB DRIVE CONNECTION) ................................................. 18
3.9.4 RS232 ......................................................................................................................... 19
3.9.4.1 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS ................................... 19
3.9.4.2 RECOMMENDED EXTERNAL MODEMS: ......................................................... 20
3.9.5 RS485 ......................................................................................................................... 21
3.9.5.1 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS ................................... 21
3.9.6 ETHERNET ................................................................................................................. 22
3.9.6.1 DIRECT PC CONNECTION ................................................................................ 22
3.9.6.2 CONNECTION TO BASIC ETHERNET .............................................................. 23
3.9.6.3 CONNECTION TO COMPANY INFRASTRUCTURE ETHERNET..................... 24
3.9.6.4 CONNECTION TO THE INTERNET ................................................................... 25
3.9.6.5 FIREWALL CONFIGURATION FOR INTERNET ACCESS ................................ 27
3.10
DSENET® FOR EXPANSION MODULES.................................................................... 28
3.10.1 DSENET® USED FOR MODBUS ENGINE CONNECTION ...................................... 28
3.11
SOUNDER ...................................................................................................................... 29
3
DSE7400 Operator Manual
3.11.1 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION .................................. 29
3.12
ACCUMULATED INSTRUMENTATION ........................................................................ 29
3.13
DIMENSIONS AND MOUNTING ................................................................................... 30
3.13.1 DIMENSIONS ............................................................................................................. 30
3.13.2 PANEL CUTOUT ........................................................................................................ 30
3.13.3 WEIGHT ..................................................................................................................... 30
3.13.4 FIXING CLIPS ............................................................................................................. 31
3.13.5 CABLE TIE FIXING POINTS ...................................................................................... 32
3.13.6 SILICON SEALING GASKET ..................................................................................... 32
3.14
APPLICABLE STANDARDS ......................................................................................... 33
3.14.1 ENCLOSURE CLASSIFICATIONS ............................................................................. 35
3.14.2 NEMA CLASSIFICATIONS ......................................................................................... 36
4 INSTALLATION ............................................................................................. 37
4.1 TERMINAL DESCRIPTION ............................................................................................... 37
4.1.1 DC SUPPLY, FUEL AND START OUTPUTS, OUTPUTS E-J ................................... 38
4.1.2 ANALOGUE SENSOR ................................................................................................ 39
4.1.3 MAGNETIC PICKUP, CAN AND EXPANSION .......................................................... 40
4.1.4 LOAD SWITCHING AND V1 GENERATOR VOLTAGE SENSING ........................... 41
4.1.5 V2 BUS/MAINS VOLTAGE SENSING ........................................................................ 41
4.1.6 GENERATOR CURRENT TRANSFORMERS ........................................................... 42
4.1.7 CONFIGURABLE DIGITAL INPUTS .......................................................................... 44
4.1.8 PC CONFIGURATION INTERFACE CONNECTOR .................................................. 44
4.1.9 RS485 CONNECTOR ................................................................................................. 45
4.1.10 RS232 CONNECTOR ................................................................................................. 45
4.2 TYPICAL WIRING DIAGRAMS ......................................................................................... 46
4.2.1 DSE7410 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION . 47
4.2.2 DSE7420 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION . 48
4.3 ALTERNATIVE TOPOLOGIES ......................................................................................... 49
4.3.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION .................................. 49
4.3.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT ............................................. 50
4.3.3 SINGLE PHASE WITHOUT EARTH FAULT .............................................................. 50
4.3.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT ........................... 51
4.3.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT ............................................ 51
4.3.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT ........................... 52
4.3.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING ..................... 52
4.3.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING ............... 53
4.4 EARTH SYSTEMS ............................................................................................................. 54
4.4.1 NEGATIVE EARTH ..................................................................................................... 54
4.4.2 POSITIVE EARTH ...................................................................................................... 54
4.4.3 FLOATING EARTH ..................................................................................................... 54
4.5 TYPICAL ARRANGEMENT OF DSENET® ...................................................................... 54
5 DESCRIPTION OF CONTROLS .................................................................... 55
5.1 DSE7410 AUTO START CONTROL MODULE ................................................................ 55
5.2 DSE7420 AUTO START CONTROL MODULE ................................................................ 56
5.3 QUICKSTART GUIDE ....................................................................................................... 57
5.3.1 STARTING THE ENGINE ........................................................................................... 57
5.3.2 STOPPING THE ENGINE .......................................................................................... 57
5.4 VIEWING THE INSTRUMENT PAGES ............................................................................. 58
5.4.1 STATUS ...................................................................................................................... 59
5.4.2 ENGINE ...................................................................................................................... 60
5.4.3 GENERATOR ............................................................................................................. 61
5.4.4 BUS (DSE7410 ONLY) ............................................................................................... 62
5.4.5 MAINS (DSE7420 ONLY) ........................................................................................... 62
5.4.6 RS232 SERIAL PORT ................................................................................................ 62
5.4.7 RS485 SERIAL PORT ................................................................................................ 65
5.4.8 ABOUT ........................................................................................................................ 66
5.4.8.1 ETHERNET PAGES ............................................................................................ 67
5.4.8.2 DATA LOGGING PAGES .................................................................................... 68
5.4.9 CAN ERROR MESSAGES ......................................................................................... 69
4
DSE7400 Operator Manual
5.5 VIEWING THE EVENT LOG.............................................................................................. 70
5.6 USER CONFIGURABLE INDICATORS ............................................................................ 71
6 OPERATION .................................................................................................. 72
6.1 CONTROL ......................................................................................................................... 72
6.2 CONTROL PUSH-BUTTONS ............................................................................................ 73
6.3 ALTERNATIVE CONFIGURATIONS ................................................................................ 74
6.4 DUMMY LOAD / LOAD SHEDDING CONTROL .............................................................. 75
6.5 STOP MODE ...................................................................................................................... 76
6.5.1 ECU OVERRIDE ......................................................................................................... 77
6.6 MANUAL MODE ................................................................................................................ 78
6.6.1 WAITING IN MANUAL MODE .................................................................................... 78
6.6.2 STARTING SEQUENCE............................................................................................. 78
6.6.3 ENGINE RUNNING .................................................................................................... 79
6.6.4 MANUAL FUEL PUMP CONTROL ............................................................................. 79
6.6.5 MANUAL SPEED CONTROL ..................................................................................... 79
6.6.6 STOPPING SEQUENCE ............................................................................................ 80
6.7 TEST MODE ...................................................................................................................... 80
6.7.1 WAITING IN TEST MODE .......................................................................................... 80
6.7.2 STARTING SEQUENCE............................................................................................. 80
6.7.3 ENGINE RUNNING .................................................................................................... 81
6.8 AUTOMATIC MODE .......................................................................................................... 82
6.8.1 WAITING IN AUTO MODE ......................................................................................... 82
6.8.2 STARTING SEQUENCE............................................................................................. 82
6.8.3 ENGINE RUNNING .................................................................................................... 83
6.8.4 STOPPING SEQUENCE ............................................................................................ 83
7 PROTECTIONS .............................................................................................. 84
7.1 PROTECTIONS DISABLED .............................................................................................. 85
7.1.1 INDICATION / WARNING ALARMS ........................................................................... 85
7.1.2 SHUTDOWN / ELECTRICAL TRIP ALARMS ............................................................ 85
7.1.3 CAN ALARMS ............................................................................................................. 86
7.2 INDICATIONS .................................................................................................................... 87
7.3 WARNINGS ....................................................................................................................... 88
7.4 HIGH CURRENT WARNING ALARM ............................................................................... 89
7.5 SHUTDOWNS .................................................................................................................... 90
7.6 ELECTRICAL TRIPS ......................................................................................................... 92
7.7 HIGH CURRENT SHUTDOWN / ELECTRICAL TRIP ALARM ........................................ 93
7.7.1 IMMEDIATE WARNING ............................................................................................. 93
7.7.2 IDMT ALARM .............................................................................................................. 93
7.8 EARTH FAULT SHUTDOWN / ELECTRICAL TRIP ALARM ........................................... 96
7.9 SHORT CIRCUIT ALARM ................................................................................................. 97
7.10
MAINTENANCE ALARM ............................................................................................... 98
8 SCHEDULER ................................................................................................. 99
8.1.1 STOP MODE .............................................................................................................. 99
8.1.2 MANUAL MODE ......................................................................................................... 99
8.1.3 AUTO MODE .............................................................................................................. 99
9 FRONT PANEL CONFIGURATION ............................................................. 100
9.1 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR ......................... 101
9.1.1 EDITING A PARAMETER ......................................................................................... 102
9.2 ADJUSTABLE PARAMETERS ....................................................................................... 103
9.3 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR .......................................... 104
9.3.1 EDITING A PARAMETER ......................................................................................... 104
9.3.2 ADJUSTABLE PARAMETERS (RUNNING EDITOR) .............................................. 104
10 COMMISSIONING ..................................................................................... 105
10.1
PRE-COMMISSIONING ............................................................................................... 105
11 FAULT FINDING ....................................................................................... 106
5
11.1
11.2
11.3
11.4
11.5
11.6
DSE7400 Operator Manual
STARTING ................................................................................................................... 106
LOADING ..................................................................................................................... 106
ALARMS ...................................................................................................................... 107
COMMUNICATIONS .................................................................................................... 108
INSTRUMENTS ........................................................................................................... 109
MISCELLANEOUS ...................................................................................................... 109
12 MAINTENANCE, SPARES, REPAIR AND SERVICING ........................... 110
12.1
PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ............................. 110
12.1.1 PACK OF PLUGS ..................................................................................................... 110
12.1.2 INDIVIDUAL PLUGS ................................................................................................. 110
12.2
PURCHASING ADDITIONAL FIXING CLIPS FROM DSE .......................................... 110
12.3
PURCHASING ADDITIONAL SEALING GASKET FROM DSE ................................. 110
12.4
DSENET EXPANSION MODULES .............................................................................. 111
13 WARRANTY .............................................................................................. 112
14 DISPOSAL ................................................................................................ 112
14.1
WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ........................... 112
14.2
ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES) ........................................ 112
6
Bibliography
1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website: www.deepseaplc.com
1.1 INSTALLATION INSTRUCTIONS
Installation instructions are supplied with the product in the box and are intended as a ‘quick start’ guide only.
DSE PART DESCRIPTION
053-085 DSE7410 Installation Instructions 053-088 DSE7420 Installation Instructions 053-032 DSE2548 LED Expansion Annunciator Installation Instructions 053-033 DSE2130 Input Expansion Installation Instructions 053-034 DSE2157 Output Expansion Installation Instructions 053-125 DSE2131 Ratio-metric Input Expansion Installation Instructions 053-126 DSE2133 RTD/Thermocouple Input Expansion Installation Instructions 053-134 DSE2152 Ratio-metric Output Expansion Installation Instructions
1.2 TRAINING GUIDES
Training Guides are produced to give ‘handout’ sheets on specific subjects during training sessions
DSE PART DESCRIPTION
056-005 Using CTs With DSE Products 056-010 Overcurrent Protection 056-018 Negative Phase Sequence 056-019 Earth Fault Protection 056-020 Loss of Excitation 056-022 Breaker Control 056-024 GSM Modem 056-026 kW & kVAr 056-029 Smoke Limiting 056-030 Module PIN Codes
1.3 MANUALS
Product manuals are can be downloaded from the DSE website: www.deepseaplc.com
DSE PART DESCRIPTION
057-004 Electronic Engines and DSE Wiring 057-160 DSE7400 Series Configuration Software Manual 057-082 DSE2130 Input Expansion Manual 057-083 DSE2157 Output Expansion Manual 057-084 DSE2548 Annunciator Expansion Manual 057-139 DSE2131 Ratio-metric Input Expansion Manual 057-140 DSE2133 RTD/Thermocouple Expansion Manual 057-141 DSE2152 Ratio-metric Output Expansion Manual
1.4 THIRD PARTY DOCUMENTS
The following third party documents are also referred to:
REFERENCE DESCRIPTION
ISBN 1-55937-879-4 IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function
Numbers and Contact Designations. Institute of Electrical and Electronics Engineers Inc ISBN 0-7506-1147-2 Diesel generator handbook. L.L.J.Mahon ISBN 0-9625949-3-8 On-Site Power Generation. EGSA Education Committee.
7
Introduction
2 INTRODUCTION
This document details the installation and operation requirements of the DSE7400 Series modules, part of the DSEGenset® range of products.
The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or supplied to another party, ensure that this document is passed to them for reference purposes. This is not a controlled document. You will not be automatically informed of updates. Any future updates of this document will be included on the DSE website at www.deepseaplc.com
The DSE7400 series is designed to provide differing levels of functionality across a common platform. This allows the generator OEM greater flexibility in the choice of controller to use for a specific application.
The DSE7400 series module has been designed to allow the operator to start and stop the generator, and if required, transfer the load to the generator either manually (via fascia mounted push-buttons) or automatically. Additionally, the DSE7420 automatically starts and stops the generator set depending upon the status of the mains (utility) supply. The user also has the facility to view the system operating parameters via the LCD display.
The DSE7400 module monitors the engine, indicating the operational status and fault conditions, automatically shutting down the engine and giving a true first up fault condition of an engine failure by a COMMON AUDIBLE ALARM. The LCD display indicates the fault.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of complex features:
Text based LCD display (supporting multiple languages).
True RMS Voltage, Current and Power monitoring.
Communications capability (RS485, RS232 or Ethernet)
Engine parameter monitoring.
Fully configurable inputs for use as alarms or a range of different functions.
Engine ECU interface to electronic engines.
Using a PC and the DSE Configuration Suite software allows alteration of selected operational sequences, timers, alarms and operational sequences. Additionally, the module’s integral fascia configuration editor allows adjustment of a subset of this information.
A robust plastic case designed for front panel mounting houses the module. Connections are via locking plug and sockets..
Access to critical operational sequences and timers for use by qualified engineers, can be protected by a security code. Module access can also be protected by PIN code. Selected parameters can be changed from the module’s front panel.
The module is housed in a robust plastic case suitable for panel mounting. Connections to the module are via locking plug and sockets.
8
Specification
Failure Module
3 SPECIFICATIONS
3.1 PART NUMBERING
7410 - 001 - 01
Product type
DSE7410 Autostart Module
DSE7420 Automatic Mains
At the time of this document production, there have been no revisions to the module hardware.
7410
7420
3.1.1 SHORT NAMES
Short name Description
DSE7000,DSE7xxx All modules in the DSE7000 range. DSE7400,DSE74xx All modules in the DSE7400 range. DSE7410 DSE7410 module/controller DSE7420 DSE7420 module/controller
Variant
Standard version
Hardware revision
Initial Release
01
001
9
Specification
3.2 TERMINAL SPECIFICATION
Connection type Two part connector.
Male part fitted to module
Female part supplied in module packing case ­Screw terminal, rising clamp, no internal spring.
Example showing cable entry and screw
terminals of a 10 way connector
Minimum cable size 0.5mm² (AWG 24) Maximum cable size 2.5mm² (AWG 10)
NOTE:
NOTE: ---- For purchasing additional connector plugs from DSE, please see the sec
NOTE: NOTE:
entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.
entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.
entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.
For purchasing additional connector plugs from DSE, please see the section
For purchasing additional connector plugs from DSE, please see the secFor purchasing additional connector plugs from DSE, please see the sec
tion
tion tion
3.3 POWER SUPPLY REQUIREMENTS
Minimum supply voltage 8V continuous Cranking dropouts
Able to survive 0V for 50mS providing the supply was at least 10V
before the dropout and recovers to 5V afterwards. Maximum supply voltage 35V continuous (60V protection) Reverse polarity protection -35V continuous
Maximum operating current Maximum standby current
130mA at 24V
260mA at 12V
65mA at 24V
120mA at 12V
Plant supply instrumentation display
Range 0V-70V DC (note Maximum continuous operating voltage of 35V DC) Resolution 0.1V Accuracy 1% full scale (±0.7V)
3.4 GENERATOR VOLTAGE / FREQUENCY SENSING
Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 10th or better Input Impedance Phase to Neutral 15V
Phase to Phase 26V
Common mode offset from Earth Resolution 1V AC phase to neutral
Accuracy ±1% of full scale phase to neutral Minimum frequency 3.5Hz
Maximum frequency 75.0Hz Frequency resolution 0.1Hz Frequency accuracy ±0.2Hz
300K ph-N
(minimum required for sensing frequency
)
to 333V AC
Suitable for 110V to 277V nominal
(±20% for under/overvoltage detection)
(minimum required for sensing frequency
)
to 576V AC
Suitable for 190V ph-ph to 479V ph-ph nominal
(±20% for under/overvoltage detection)
100V AC (max)
2V AC phase to phase
±2% of full scale phase to phase
(absolute maximum)
(absolute maximum)
10
Specification
3.5 GENERATOR CURRENT SENSING
Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 10th or better Nominal CT secondary rating 1A or 5A (5A recommended) Maximum continuous current 5A Overload Measurement 3 x Nominal Range setting Absolute maximum overload 50A for 1 second Burden common mode offset ±2V peak plant ground to CT common terminal Resolution 0.5% of 5A Accuracy ±1% of Nominal (1A or 5A) (excluding CT error)
3.5.1 VA RATING OF THE CTS
The VA burden of the module on the CTs is 0.5VA. However depending upon the type and length of cabling between the CTs and the module, CTs with a greater VA rating than the module are required.
The distance between the CTs and the measuring module should be estimated and cross-referenced against the chart opposite to find the VA burden of the cable itself.
If the CTs are fitted within the alternator top box, the star point (common) of the CTs should be connected to system ground (earth) as close as possible to the CTs. This minimises the length of cable used to connect the CTs to the DSE module.
Example. If 1.5mm² cable is used and the distance from the CT to the measuring module is 20m, then the burden of the cable alone is approximately 15VA. As the burden of the DSE controller is
0.5VA, then a CT with a rating of at least 15+0.5V = 15.5VA must be used. If 2.5mm² cables are used over the same distance of 20m, then the burden of the cable on the CT is approximately 7VA. CT’s required in this instance is at least 7.5VA (7+0.5).
0.5VA (0.02 current shunts)
NOTE:
NOTE: ---- Details for 4mm² cables are shown for reference only.
NOTE: NOTE:
DSE modules are only suitable for cables up to 2.5mm².
DSE modules are only suitable for cables up to 2.5mm².
DSE modules are only suitable for cables up to 2.5mm².DSE modules are only suitable for cables up to 2.5mm².
NOTE:
NOTE: ---- CTs with 5A secondary windings are recommended with DSE modules. 1A CTs
NOTE: NOTE:
can be used if necessary however, the resolution of the readings is 5 times better when
can be used if necessary however, the resolution of the readings is 5 times better when
can be used if necessary however, the resolution of the readings is 5 times better when can be used if necessary however, the resolution of the readings is 5 times better when using 5A
using 5A CTs.
using 5Ausing 5A
Details for 4mm² cables are shown for reference only. The connectors on the
Details for 4mm² cables are shown for reference only.Details for 4mm² cables are shown for reference only.
CTs with 5A secondary windings are recommended with DSE modules. 1A CTs
CTs with 5A secondary windings are recommended with DSE modules. 1A CTs CTs with 5A secondary windings are recommended with DSE modules. 1A CTs
CTs.
CTs.CTs.
The connectors on the
The connectors on the The connectors on the
11
Specification
3.5.2 CT POLARITY
Take care to ensure the correct polarity of the CTs. Incorrect CT orientation will lead to negative kW readings when the set is supplying power. Take note that paper stick-on labels on CTs that show the orientation are often incorrectly placed on the CT (!). It is more reliable to use the labelling in the case moulding as an indicator to orientation (if available). To test orientation, run the generator in island mode (not in parallel with any other supply) and load the generator to around 10% of the set rating. Ensure the DSE module shows positive kW for all three individual phase readings.
labelled as p1,
k
or K
labelled as p2,
l
or L
TO GENERATOR
NOTE:
NOTE:----
NOTE:NOTE:
doubt, check with the CT supplier.
doubt, check with the CT supplier.
doubt, check with the CT supplier.doubt, check with the CT supplier.
Take care to ensure correct polarity of the CT primary as show
Take care to ensure correct polarity of the CT primary as shown above. If in
Take care to ensure correct polarity of the CT primary as showTake care to ensure correct polarity of the CT primary as show
POLARITY OF CT PRIMARY
TO LOAD SWITCH DEVICE
n above. If in
n above. If in n above. If in
3.5.3 CT PHASING
Take particular care that the CTs are connected to the correct phases. For instance, ensure that the CT on phase 1 is connected to the terminal on the DSE module intended for connection to the CT for phase 1. Additionally ensure that the voltage sensing for phase 1 is actually connected to generator phase 1. Incorrect connection of the phases as described above will result in incorrect power factor (pf) measurements, which in turn results in incorrect kW measurements. One way to check for this is to make use of a single-phase load. Place the load on each phase in turn, run the generator and ensure the kW value appears in the correct phase. For instance if the load is connected to phase 3, ensure the kW figure appears in phase 3 display and not in the display for phase 1 or 2.
3.5.4 CT CLASS
Ensure the correct CT type is chosen. For instance if the DSE module is providing overcurrent protection, ensure the CT is capable of measuring the overload level you wish to protect against, and at the accuracy level you require. For instance, this may mean fitting a protection class CT (P10 type) to maintain high accuracy while the CT is measuring overload currents. Conversely, if the DSE module is using the CT for instrumentation only (current protection is disabled or not fitted to the controller), then measurement class CTs can be used. Again, bear in mind the accuracy you require. The DSE module is accurate to better than 1% of the full-scale current reading. To maintain this accuracy you should fit Class 0.5 or Class 1 CTs.
You should check with your CT manufacturer for further advice on selecting your CTs
12
Specification
3.6 INPUTS
3.6.1 DIGITAL INPUTS
Number 11 configurable inputs Arrangement Contact between terminal and ground Low level threshold 2.1V minimum High level threshold 6.6V maximum Maximum input voltage +50V DC with respect to plant supply negative Minimum input voltage -24V DC with respect to plant supply negative Contact wetting current 7mA typical Open circuit voltage 12V typical
3.6.2 ANALOGUE INPUTS
3.6.2.1 OIL PRESSURE
Configurable if engine ECU link provides oil pressure measurement Measurement type Resistance measurement by measuring voltage across sensor with
a fixed current applied Arrangement Differential resistance measurement input Measurement current 15mA Full scale Over range / fail Resolution 0.1 Bar (1-2 PSI) Accuracy Max common mode voltage ±2V Display range 13.7 bar (0-200 PSI) subject to limits of the sensor
3.6.2.2 COOLANT TEMPERATURE
Configurable if engine ECU link provides coolant temp measurement Measurement type Resistance measurement by measuring voltage across sensor with a fixed
current applied Arrangement Differential resistance measurement input Measurement current Full scale Over range / fail Resolution Accuracy Max common mode voltage Display range
3.6.2.3 FUEL LEVEL
Measurement type Resistance measurement by measuring voltage across sensor with a fixed Arrangement Differential resistance measurement input
Measurement current Full scale
Over range / fail Resolution Accuracy Max common
mode voltage Display range 0-250%
10mA
480
540
1°C (2°F)
+/-2% of full scale resistance (±9.6) excluding transducer error
±2V
0°C -140°C (32°F - 284°F) subject to limits of the sensor
current applied
10mA
480
540
1°C (2°F)
+/-2% of full scale resistance (±9.6) excluding transducer error
±2V
240 270
±2% of full scale resistance (±4.8) excluding transducer error
13
Specification
3.6.2.4 FLEXIBLE SENSOR
Number 2 Measurement type Resistance measurement by measuring voltage across sensor with a
fixed current applied Arrangement Differential resistance measurement input Measurement current 10mA Full scale Over range / fail Resolution 1% Accuracy Max common mode voltage ±2V Display range 0-250%
480
540
±2% of full scale resistance (±9.6) excluding transducer error
3.6.3 CHARGE FAIL INPUT
Minimum voltage 0V Maximum voltage 35V (plant supply) Resolution 0.2V Accuracy ± 1% of max measured voltage Excitation Active circuit constant power output Output Power 2.5W Nominal @12V and 24V Current at 12V 210mA Current at 24V 105mA
The charge fail input is actually a combined input and output. Whenever the generator is required to run, the terminal provides excitation current to the charge alternator field winding. When the charge alternator is correctly charging the battery, the voltage of the terminal is close to the plant battery supply voltage. In a failed charge situation, the voltage of this terminal is pulled down to a low voltage. It is this drop in voltage that triggers the charge failure alarm. The level at which this operates and whether this triggers a warning or shutdown alarm is configurable using the DSE Config Suite Software.
3.6.4 MAGNETIC PICKUP
Type Single ended input, capacitive coupled Minimum voltage 0.5V RMS Max common mode voltage ±2V Maximum voltage Clamped to ±70V by transient suppressers, dissipation not to
exceed 1W. Maximum frequency 10,000Hz Resolution 6.25 RPM Accuracy ±25 RPM Flywheel teeth 10 to 500
NOTE : DSE can supply a suitable magnetic pickup device, available in two body thread lengths : DSE Part number 020-012 - Magnetic Pickup probe 5/8 UNF 2½” thread length DSE Part number 020-013 - Magnetic Pickup probe 5/8 UNF 4” thread length
Magnetic Pickup devices can often be ‘shared’ between two or more devices. For example, one device can often supply the signal to both the module and the engine governor. The possibility of this depends upon the amount of current that the magnetic pickup can supply.
14
Specification
3.7 OUTPUTS
Ten (10) outputs are fitted to the controller.
3.7.1 OUTPUTS A & B
Type Normally used for Fuel / Start outputs. Fully configurable for other purposes if the
module is configured to control an electronic engine. Supplied from Emergency Stop terminal 3.
Rating 15A resistive @ 35V
3.7.2 CONFIGURABLE OUTPUTS C & D (LOAD SWITCHING)
Type Fully configurable volts free relays. Output C – Normally Closed, Output D – Normally
Open Rating 8A resistive@ 250V AC Protection Protected against over current & over temperature. Built in load dump feature.
3.7.2.1 CONTACTOR COILS
Use output D, the normally open relay:
Generator
DSE output drives the contactor coil, via external slave relay if required. When the DSE module requires the contactor closed, the output energises (closing the internal relay) When the DSE module requires the contactor to be open, the output is de-energised (opening the internal relay)
3.7.2.2 UNDERVOLTAGE (UV COILS)
Use output C, the normally closed relay :
Generator
DSE output drives the UV coil, via external slave relay if required. When the generator starts, the UV is powered via the normally closed relay. The breaker is now ready for the close signal to be given. When the breaker is to be opened, the Open Generator Pulse relay is operated, removing power from the UV coil for one second. This causes the breaker to trip (open) as the UV is no longer powered. The Open Generator Pulse relay switches back to its closed state, ready to power the UV coil the next time the
15
Specification
3.7.2.3 CLOSING COILS
For continuous closing signals (close signal is present continuously when the breaker is closed), follow the instructions above as for Contactor Coils. For momentary (pulsed) closing signals, use OUTPUT D, the normally open relay:
Generator
When the DSE module requires the breaker closed, the output energises (closing the internal relay) for the period of the Breaker Close Pulse timer after which the output is de-energised (opening the internal relay).
3.7.2.4 OPENING COILS / SHUNT TRIP COILS
For Continuous opening signal, use output D, the normally open relay:
Generator:
When the DSE module requires the breaker open, the output energises (closing the internal relay).
For momentary (pulsed) closing signals, use a normally open relay:
Generator:
When the DSE module requires the breaker open, the output energises (closing the internal relay) for the period of the breaker trip pulse.
3.7.3 OUTPUTS E,F,G,H, I & J
Number 6 Type Fully configurable, supplied from DC supply terminal 2. Rating 3A resistive @ 35V
16
Specification
3.8 COMMUNICATION PORTS
USB Port USB2.0 Device for connection to PC running DSE configuration
suite only Max distance 6m (yards)
Serial Communication RS232 and RS485 are both fitted but and provide independent
operation
RS232 Serial port
RS485 Serial port
CAN Port Engine CAN Port
Non – Isolated port Max Baud rate 115K baud subject to S/W TX, RX, RTS, CTS, DSR, DTR, DCD Male 9 way D type connector Max distance 15m (50 feet) Isolated Data connection 2 wire + common Half Duplex Data direction control for Transmit (by s/w protocol) Max Baud Rate 19200 External termination required (120) Max common mode offset 70V (on board protection transorb) Max distance 1.2km (¾ mile)
Standard implementation of ‘Slow mode’, up to 250K bits/s Non-Isolated. Internal Termination provided (120) Max distance 40m (133 feet)
NOTE:- For additional length, the DSE124 CAN Extender is available. Please refer to DSE Publication: 057-116 DSE124 Operator Manual for more information.
Ethernet Auto detecting 10/100 Ethernet port.
3.9 COMMUNICATION PORT USAGE
3.9.1 CAN INTERFACE
Modules are fitted with the CAN interface as standard and are capable of receiving engine data from engine CAN controllers compliant with the CAN standard. CAN enabled engine controllers monitor the engine’s operating
parameters such as engine speed, oil pressure, engine temperature (among others) in order to closely monitor and control the engine. The industry standard communications interface (CAN) transports data gathered by the engine controller interface. This allows generator controllers to access these engine parameters with no physical connection to the sensor device.
NOTE:- For further details for connections to CAN enabled engines and the functions available with each engine type, refer to the manual Electronic Engines and DSE Wiring. Part No. 057-004
17
Specification
3.9.2 USB CONNECTION
The USB port is provided to give a simple means of connection between a PC and the controller. Using the DSE Configuration Suite Software, the operator is then able to control the module, starting or stopping the generator, selecting operating modes, etc. Additionally, the various operating parameters (such as output volts, oil pressure, etc.) of the remote generator are available to be viewed or changed.
To connect a module to a PC by USB, the following items are required:
DSE7400 series module
DSE Configuration Suite PC Software
(Supplied on configuration suite software CD or available from www.deepseaplc.com).
USB cable Type A to Type B. (This is the same cable as often used between a PC and a USB printer)
DSE can supply this cable if required : PC Configuration interface lead (USB type A – type B) DSE Part No 016-125
NOTE:- The DC supply must be connected to the module for configuration by PC.
NOTE:- Refer to DSE7400 Series Configuration Suite Manual (DSE part 057-160) for further
details on configuring, monitoring and control.
3.9.3 USB HOST-MASTER (USB DRIVE CONNECTION)
USB Type A connection for USB Host facility for USB storage device for data recording. Maximum size of externally storage device is 16Gb.(see viewing the instrument pages)
NOTE:- Refer to DSE7400 Series Configuration Suite Manual (DSE part 057-160) for further
details on configuring, monitoring and control.
18
Specification
3.9.4 RS232
The RS232 port on the controller supports the Modbus RTU protocol. The Gencomm register table for the controller is available upon request from the DSE Technical Support Department.
RS232 is for short distance communication (max 15m) and is typically used to connect the controller to a telephone or GSM modem for more remote communications.
Many PCs are not fitted with an internal RS232 serial port. DSE DOES NOT recommend the use of USB to RS232 convertors but can recommend PC add-ons to provide the computer with an RS232 port.
3.9.4.1 RECOMMENDED PC RS232 SERIAL PORT ADD-ONS
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
Brainboxes PM143 PCMCIA RS232 card (for laptop PCs)
Brainboxes VX-001 Express Card RS232 (for laptops and nettops PCs)
Brainboxes UC246 PCI RS232 card (for desktop PCs)
Brainboxes PX-246 PCI Express 1 Port RS232 1 x 9 Pin (for desktop
PCs)
Supplier:
Brainboxes Tel: +44 (0)151 220 2500 Web: http://www.brainboxes.com Email: Sales: sales@brainboxes.com
NB DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these
products and are happy to recommend them.
19
Specification
3.9.4.2 RECOMMENDED EXTERNAL MODEMS:
Multitech Global Modem – MultiModem ZBA (PSTN) DSE Part Number 020-252 (Contact DSE Sales for details of localisation kits for these modems)
Sierra Fastrak Xtend GSM modem kit (PSU, Antenna and modem)* DSE Part number 0830-001-01
NOTE: *For GSM modems a SIM card is required, supplied by your GSM network provider :
For SMS only, a ‘normal’ voice SIM card is required. This enables the controller to send SMS messages to designated mobile phones upon status and alarm conditions.
For a data connection to a PC running DSE Configuration Suite Software, a ‘special’ CSD (Circuit Switched Data) SIM card is required that will enable the modem to answer an incoming data call. Many ‘pay as you go’ services will not provide a CSD (Circuit Switched Data) SIM card.
20
Specification
3.9.5 RS485
The RS485 port on the series controller supports the Modbus RTU protocol. The DSE Gencomm register table for the controller is available upon request from the DSE Technical Support Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices) and allows for connection to PCs, PLCs and Building Management Systems (to name just a few devices).
One advantage of the RS485 interface is the large distance specification (1.2km when using Belden 9841 (or equivalent) cable. This allows for a large distance between the module and a PC running the DSE Configuration Suite software. The operator is then able to control the module, starting or stopping the generator, selecting operating modes, etc. The various operating parameters (such as output volts, oil pressure, etc.) of the remote generator can be viewed or changed.
NOTE:- For a single module to PC connection and distances up to 6m (8yds) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which is more suited to longer distance connections).
3.9.5.1 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
Brainboxes PM154 PCMCIA RS485 card (for laptops PCs) Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and nettop PCs)
Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs) Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)
Supplier:
Brainboxes Tel: +44 (0)151 220 2500 Web: http://www.brainboxes.com Email: Sales: sales@brainboxes.com
NB DSE have no business tie to Brainboxes. Over many years,our own engineers have used these products and are happy to recommend them.
21
Specification
3.9.6 ETHERNET
The module is fitted with ETHERNET socket for connection to LAN (local area networks)
1 2 3 4 5 6 7 8
3.9.6.1 DIRECT PC CONNECTION Requirements
DSE7400 series module
Crossover Ethernet cable (see Below)
PC with Ethernet port
Description
TX+ TX­RX+ Do not connect Do not connect RX­Do not connect Do not connect
Crossover network cable
22
Crossover cable wiring detail
Two pairs crossed, two pairs uncrossed 10baseT/100baseTX crossover
Pin
1 2
Connection 1 (T568A)
white/green stripe green solid
Specification
Connection 2 (T568B)
white/orange stripe orange solid
For the advanced Engineer, a crossover cable is a CAT5 cable with one end terminated as T568A and the other end terminated as T568B.
3 4 5 6 7 8
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
white/green stripe blue solid white/blue stripe green solid white/brown stripe brown solid
NOTE:- This cable can be purchased from any good PC or IT store.
3.9.6.2 CONNECTION TO BASIC ETHERNET Requirements
DSE7400 series module
Ethernet cable (see below)
Working Ethernet (company or home network)
PC with Ethernet port
Ethernet router or ADSL router
Ethernet cable
23
Ethernet cable wiring detail
.
10baseT/100baseT
Pin
1 2
Connection 1 (T568A)
white/green stripe green solid
Specification
For the advanced Engineer, this cable
Connection 2 (T568A)
white/green stripe green solid
has both ends terminated as T568A (as shown below) or T568B.
3 4 5 6
7 8
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
NOTE:- DSE Stock a 2m (2yds) Ethernet Cable – Part number 016-137. Alternatively they
can be purchased from any good PC or IT store.
3.9.6.3 CONNECTION TO COMPANY INFRASTRUCTURE ETHERNET Requirements
DSE7400 series module
Ethernet cable (see below)
Working Ethernet (company or home network)
PC with Ethernet port
Ethernet router or ADSL router
PC Network wall connection sockets
Ethernet cable
24
Ethernet cable wiring detail
10baseT/100baseT
Pin
1 2
Connection 1 (T568A)
white/green stripe green solid
Specification
For the advanced Engineer, this cable has both ends terminated as T568A
Connection 2 (T568A)
white/green stripe green solid
(as shown below) or T568B.
3 4 5 6 7 8
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
NOTE:- DSE Stock a 2m (2yds) Ethernet Cable – Part number 016-137. Alternatively they
can be purchased from any good PC or IT store.
3.9.6.4 CONNECTION TO THE INTERNET
Requirements
Ethernet cable (see below)
Working Ethernet (company or home network)
Working Internet connection (ADSL or DSL recommended)
INTERNET
DSL or ADSL
router
Ethernet cable
DSL or ADSL
router
The DSL/ADSL router will route external network traffic.
PC remote
from generator
Optional ‘Local’
site PC
25
Ethernet cable wiring detail
10baseT/100baseT
Pin
1 2
Connection 1 (T568A)
white/green stripe green solid
Specification
For the advanced Engineer, this cable
Connection 2 (T568A)
white/green stripe green solid
has both ends terminated as T568A (as shown below) or T568B.
3 4 5 6 7 8
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
white/orange stripe blue solid white/blue stripe orange solid white/brown stripe brown solid
NOTE:- DSE Stock a 2m (2yds) Ethernet Cable – Part number 016-137. Alternatively they
can be purchased from any good PC or IT store.
26
Specification
3.9.6.5 FIREWALL CONFIGURATION FOR INTERNET ACCESS
As modem/routers differ enormously in their configuration, it is not possible for DSE to give a complete guide to their use with the module. However it is possible to give a description of the requirements in generic terms. For details of how to achieve the connection to your modem/router you are referred to the supplier of your modem/router equipment.
The module makes its data available over Modbus TCP and as such communicates over the Ethernet using a Port configured via the DSE Configuration Suite software..
You must configure your modem/router to allow inbound traffic on this port. For more information you are referred to your WAN interface device (modem/router) manufacturer.
It is also important to note that if the port assigned (setting from software “Modbus Port Number”) is already in use on the LAN, the module cannot be used and another port must be used .
Outgoing Firewall rule
As the module makes its user interface available to standard web browsers, all communication uses the chosen port. It is usual for a firewall to make the same port outgoing open for communication.
Incoming traffic (virtual server)
Network Address and Port Translation (NAPT) allows a single device, such as the modem/router gateway, to act as an agent between the Internet (or "public external network") and a local (or "internal private") network. This means that only a single, unique IP address is required to represent an entire group of computers.
For our application, this means that the WAN IP address of the modem/router is the IP address we need to access the site from an external (internet) location.
When the requests reach the modem/router, we want this passed to a ‘virtual server’ for handling, in our case this is the module.
Result : Traffic arriving from the WAN (internet) on port xxx is automatically sent to IP address set within the configuration software on the LAN for handling.
NOTE:- Refer to DSE7400 Series Configuration Suite Manual (DSE part 057-160) for further
details on configuring, monitoring and control.
27
Specification
3.10 DSENET® FOR EXPANSION MODULES
DSENet® is the interconnection cable between the host controller and the expansion module(s) and must not be connect to any device other than DSE equipment designed for connection to the DSENet®
Cable type Two core screened twisted pair Cable characteristic impedance Recommended cable Belden 9841
Maximum cable length 1200m (¾ mile) when using Belden 9841 or direct equivalent. DSENet® topology “Daisy Chain” Bus with no stubs (spurs)
DSENet® termination Maximum expansion
modules
120
Belden 9271 600m (666 yds) when using Belden 9271 or direct equivalent.
120. Fitted internally to host controller. Must be fitted externally to the ‘last’ expansion module by the customer. Total 20 devices made up of DSE2130 (up to 4), DSE2131 (up to 4), DSE2133 (up to 4), DSE2152 (up to 4), DSE2157 (up to 10), DSE2548 (up to 10)
This gives the possibility of : Maximum 32 additional 0-10V or 4-20mA outputs (DSE2152) Maximum 80 additional relay outputs (DSE2157) Maximum 80 additional LED indicators Maximum 24 additional Ratio-metric or Thermocouple inputs (DSE2133). Maximum 40 additional inputs (All can be configured as either digital, resistive, 0-10V or 4-20mA when using DSE2131)
NOTE: As a termination resistor is internally fitted to the host controller, the host controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to the ‘last’ unit on the DSENet®. For connection details, you are referred to the section entitled ‘typical wiring diagram’ elsewhere in this document.
NOTE : DSE7400 series module does not support the DSE2510/2520 display modules.
3.10.1 DSENET® USED FOR MODBUS ENGINE CONNECTION
As DSENet® utilises an RS485 hardware interface, this port can be configured for connection to Cummins Modbus engines (Engines fitted with Cummins GCS). This leaves the RS485 interface free for connection to remote monitoring equipment (i.e. Building Management System, PLC or PC RS485 port).
While this is a very useful feature in some applications, the obvious drawback is that the DSENet® interface is no longer available for connection to expansion devices.
Example of configuring the DSENet® for connection to Cummins QST GCS using the DSE Configuration Suite Software:
28
Specification
3.11 SOUNDER
The module features an internal sounder to draw attention to warning, shutdown and electrical trip alarms.
Sounder level 64db @ 1m
3.11.1 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION
Should an external alarm or indicator be required, this can be achieved by using the DSE Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by configuring an auxiliary input for “Alarm Mute” (if required). The audible alarm output activates and de-activates at the same time as the module’s internal sounder. The Alarm mute input and internal alarm mute button activate ‘in parallel’ with each other. Either signal will mute both the internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
3.12 ACCUMULATED INSTRUMENTATION
NOTE: When an accumulated instrumentation value exceeds the maximum number as listed below, it will reset and begin counting from zero again.
Engine hours run Maximum 99999 hrs 59 minutes (approximately 11yrs 4months) Number of starts 1,000,000 (1 million)
The number of logged Engine Hours and Number of Starts can be set/reset using the DSE Configuration Suite PC software. Depending upon module configuration, this may have been PIN number locked by your generator supplier
29
3.13 DIMENSIONS AND MOUNTING
3.13.1 DIMENSIONS
240.0mm x 181.1mm x 41.7mm
3.13.2 PANEL CUTOUT
220mm x 160mm
(8.7” x 6.3”)
3.13.3 WEIGHT
0.7kg (1.4lb)
(9.4” x 7.1” x 1.6”)
Specification
30
Specification
3.13.4 FIXING CLIPS
The module is held into the panel fascia using the supplied fixing clips.
Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the
clip are inside their allotted slots.
Turn the fixing clip screws clockwise until they make contact with the panel fascia.
Turn the screws a little more to secure the module into the panel fascia. Care should be taken
not to over tighten the fixing clip screws.
Fixing clip
Fixing clip fitted to module
NOTE:- In conditions of excessive vibration, mount the module on suitable anti-vibration
mountings.
31
Specification
3.13.5 CABLE TIE FIXING POINTS
Integral cable tie fixing points are included on the rear of the module’s case to aid wiring. This additionally provides strain relief to the cable loom by removing the weight of the loom from the screw connectors, thus reducing the chance of future connection failures. Care should be taken not to over tighten the cable tie (for instance with cable tie tools) to prevent the risk of damage to the module case.
Cable tie fixing point With cable and tie in place
3.13.6 SILICON SEALING GASKET
The supplied silicon gasket provides improved sealing between module and the panel fascia. The gasket is fitted to the module before installation into the panel fascia. Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.
Sealing gasket
Gasket fitted to module
32
3.14 APPLICABLE STANDARDS
BS 4884-1 BS 4884-2
BS 4884-3 BS EN 60068-2-1
(Minimum temperature)
BS EN 60068-2-2
(Maximum temperature)
BS EN 60950 BS EN 61000-6-2
BS EN 61000-6-4 BS EN 60529
(Degrees of protection provided by enclosures)
UL508 NEMA rating
(Approximate)
IEEE C37.2
(Standard Electrical Power System Device Function Numbers and Contact Designations)
Continued overleaf.
This document conforms to BS4884-1 1992 Specification for presentation of essential information. This document conforms to BS4884-2 1993 Guide to content This document conforms to BS4884-3 1993 Guide to presentation
-30°C (-22°F)
+70°C (158°F) Safety of information technology equipment, including electrical business
equipment EMC Generic Immunity Standard (Industrial) EMC Generic Emission Standard (Industrial) IP65 (front of module when installed into the control panel with the supplied sealing gasket) IP42 (front of module when installed into the control panel WITHOUT being sealed to the panel) 12 (Front of module when installed into the control panel with the supplied sealing gasket). 2 (Front of module when installed into the control panel WITHOUT being sealed to the panel) Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor devices and software programs. The controller is device number 11L-8000 (Multifunction device protecting Line (generator) –module).
As the module is configurable by the generator OEM, the functions covered by the module will vary. Under the module’s factory configuration, the device numbers included within the module are :
2 – Time delay starting or closing relay 3 – Checking or interlocking relay 5 – Stopping Device 6 – Starting circuit breaker 8 – Control power disconnecting device 10 – Unit sequence switch 11 – Multifunction device 12 – Overspeed device 14 – Underspeed device 23 – Temperature control device 26 – Apparatus thermal device 27AC – AC undervoltage relay 27DC – DC undervoltage relay 29 – Isolating contactor or switch 30 – Annunciator relay 31 – Separate Excitation Device 37 – Undercurrent or underpower relay (USING INTERNAL PLC EDITOR) 41 – Field circuit breaker 42 – Running circuit breaker 44 – Unit sequence relay 46 – Reverse-phase or phase-balance current relay 48 – Incomplete sequence relay 49 – Machine or transformer thermal relay
Specification
33
Specification
IEEE C37.2
(Standard Electrical Power System Device Function Numbers and Contact Designations)
Continued… 50 – Instantaneous overcurrent relay
51 – AC time overcurrent relay 52 – AC circuit breaker 53 – Exciter or DC generator relay 54 – Turning gear engaging device 55 – Power factor relay (USING INTERNAL PLC EDITOR) 59AC – AC overvoltage relay 59DC – DC overvoltage relay 62 – Time delay stopping or opening relay 63 – Pressure switch 71 – Level switch 74 – Alarm relay 78 – Phase-angle measuring relay 79 – Reclosing relay (USING INTERNAL PLC EDITOR) 81 – Frequency relay 83 – Automatic selective control or transfer relay 86 – Lockout relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
34
Specification
3.14.1 ENCLOSURE CLASSIFICATIONS
IP CLASSIFICATIONS
The modules specification under BS EN 60529 Degrees of protection provided by enclosures
IP65 (Front of module when module is installed into the control panel with the optional sealing gasket).
IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
First Digit Second Digit
Protection against contact and ingress of solid objects Protection against ingress of water 0 No protection 0 No protection
1 Protected against ingress solid objects with a diameter
of more than 50 mm. No protection against deliberate access, e.g. with a hand, but large surfaces of the body are prevented from approach.
2 Protected against penetration by solid objects with a
diameter of more than 12 mm. Fingers or similar objects prevented from approach.
3 Protected against ingress of solid objects with a
diameter of more than 2.5 mm. Tools, wires etc. with a thickness of more than 2.5 mm are prevented from approach.
4 Protected against ingress of solid objects with a
diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach.
5 Protected against harmful dust deposits. Ingress of
dust is not totally prevented but the dust must not enter in sufficient quantity to interface with satisfactory operation of the equipment. Complete protection against contact.
6 Protection against ingress of dust (dust tight).
Complete protection against contact.
1 Protection against dripping water falling vertically. No
harmful effect must be produced (vertically falling drops).
2 Protection against dripping water falling vertically. There
must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15° from its normal pos ition (drops falling at an angle).
3 Protection against water falling at any angle up to 60° from
the vertical. There must be no harmful effect (spray water).
4 Protection against water splashed against the equipment
(enclosure) from any direction. There must be no harmful effect (splashing water).
5 Protection against water projected from a nozzle against
the equipment (enclosure) from any direction. There must be no harmful effect (water jet).
6 Protection against heavy seas or powerful water jets.
Water must not enter the equipment (enclosure) in harmful quantities (splashing over).
35
Specification
3.14.2 NEMA CLASSIFICATIONS
The modules NEMA Rating (Approximate)
12 (Front of module when module is installed into the control panel with the optional sealing gasket).
2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.
1
IP30
Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.
2
IP31
3
IP64
3R
IP32
4 (X)
IP66
12/12K
IP65
13
IP65
Provides a degree of protection against limited amounts of falling water and dirt.
Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure.
Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.
Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.
36
Installation – Terminal Description
4 INSTALLATION
The module is designed to be mounted on the panel fascia. For dimension and mounting details, see the section entitled Specification, Dimension and mounting elsewhere in this document.
4.1 TERMINAL DESCRIPTION
To aid user connection, icons are used on the rear of the module to help identify terminal functions. An example of this is shown below.
NOTE : Availability of some terminals depends upon module version. Full details are given
in the section entitled Terminal Description elsewhere in this manual.
Terminals 39-46 Terminals 47-50 Terminals 51-57 Terminals 60-68
Serial and part number label
Terminals 1-13 Terminals 15-19 Terminals 22-36
USB Host Data Logging
Ethernet
USB PC Configuration
37
Installation – Terminal Description
4.1.1 DC SUPPLY, FUEL AND START OUTPUTS, OUTPUTS E-J
PIN
No
1
2
3 Emergency Stop Input
4 Output relay A (FUEL)
5 Output relay B (START)
6 Charge fail / excite
7 Functional Earth
8 Output relay E
9 Output relay F
10 Output relay G
11 Output relay H
12 Output relay I
13 Output relay J
DESCRIPTION CABLE
DC Plant Supply Input (Negative)
DC Plant Supply Input (Positive)
SIZE
2.5mm²
AWG 13
2.5 mm² AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
1.0mm²
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
NOTES
(Recommended Maximum Fuse 15A anti-surge) Supplies the module (2A anti-surge requirement) and Output relays E,F,G & H
Plant Supply Positive. Also supplies outputs 1 & 2. (Recommended Maximum Fuse 20A)
Plant Supply Positive from terminal 3. 15 Amp rated. Fixed as FUEL relay if electronic engine is not configured. Plant Supply Positive from terminal 3. 15 Amp rated. Fixed as START relay if electronic engine is not configured. Do not connect to ground (battery negative). If charge alternator is not fitted, leave this terminal disconnected.
Connect to a good clean earth point.
Plant Supply Positive from terminal 2. 2 Amp rated.
Plant Supply Positive from terminal 2. 2 Amp rated.
Plant Supply Positive.from terminal 2. 2 Amp rated.
Plant Supply Positive from terminal 2. 2 Amp rated.
Plant Supply Positive from terminal 2. 2 Amp rated.
Plant Supply Positive from terminal 2. 2 Amp rated.
NOTE:- Terminal 14 is not fitted to the controller.
NOTE:- When the module is configured for operation with an electronic engine, FUEL and START output requirements may be different. Refer to Electronic Engines and DSE Wiring for further information. Part No. 057-004.
38
Installation – Terminal Description
4.1.2 ANALOGUE SENSOR
PIN
No
15 Sensor Common Return
16 Oil Pressure Input
17 Coolant Temperature Input
18 Fuel Level input
19 Flexible sensor
NOTE:- Terminals 20 and 21 are not fitted to the controller.
NOTE: - It is VERY important that terminal 15 (sensor common) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel, and must be a sound electrical connection to the sensor bodies. This connection MUST NOT be used to provide an earth connection for other terminals or devices. The simplest way to achieve this is to run a SEPARATE earth connection from the system earth star point, to terminal 15 directly, and not use this earth for other connections.
DESCRIPTION CABLE
SIZE
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
NOTES
Return feed for sensors*
Connect to Oil pressure sensor
Connect to Coolant Temperature sensor
Connect to Fuel Level sensor
Connect to additional sensor (user configurable)
NOTE: - If you use PTFE insulating tape on the sensor thread when using earth return sensors, ensure you do not insulate the entire thread, as this will prevent the sensor body from being earthed via the engine block.
39
Installation – Terminal Description
4.1.3 MAGNETIC PICKUP, CAN AND EXPANSION
PIN
MSC
No
22 Magnetic pickup Positive 23 Magnetic pickup Negative 24 Magnetic pickup screen Shield Connect to ground at one end only 25 CAN port H 26 CAN port L 27 CAN port Common 28 DSENet expansion + 29 DSENet expansion ­30 DSENet expansion SCR 31 Multiset Comms (MSC) Link H 32 Multiset Comms (MSC) Link L 33
DESCRIPTION CABLE
Multiset Comms (MSC) Link SCR
SIZE
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
Connect to Magnetic Pickup device Connect to Magnetic Pickup device
Use only 120 CAN approved cable Use only 120 CAN approved cable Use only 120 CAN approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable Use only 120 RS485 approved cable
NOTES
NOTE:- Terminal 34 to 38 are not fitted to the controller
NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is earthed at one end ONLY.
NOTE:- Screened 120ΩΩΩ impedance cable specified for use with CAN must be used for the CAN link and the Multiset comms link. DSE stock and supply Belden cable 9841 which is a high quality 120ΩΩΩ impedance cable suitable for CAN use (DSE part number 016-030)
NOTE:- When the module is configured for CAN operation, terminals 22, 23 & 24 should be left unconnected. Engine speed is transmitted to the controller on the CAN link. Refer to Electronic Engines and DSE Wiring for further information. Part No. 057-004.
40
Installation – Terminal Description
4.1.4 LOAD SWITCHING AND V1 GENERATOR VOLTAGE SENSING
PIN
No
39 Output relay C 40 Output relay C 41 Output relay D 42 Output relay D 43 44
V1
45 46 Generator Neutral (N) input
DESCRIPTION CABLE
Generator L1 (U) voltage monitoring Generator L2 (V) voltage monitoring input Generator L3 (W) voltage monitoring input
SIZE
1.0mm
AWG 18
1.0mm
AWG 18
1.0mm
AWG 18
1.0mm
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
1.0mm²
AWG 18
NOTES
Normally configured to control mains contactor coil (Recommend 10A fuse)
Normally configured to control mains contactor coil Normally configured to control generator contactor coil
(Recommend 10A fuse) Normally configured to control generator contactor coil Connect to generator L1 (U) output (AC)
(Recommend 2A fuse) Connect to generator L2 (V) output (AC) (Recommend 2A fuse) Connect to generator L3 (W) output (AC) (Recommend 2A fuse)
Connect to generator Neutral terminal (AC)
NOTE:- The above table describes connections to a three phase, four wire alternator. For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.
4.1.5 V2 BUS/MAINS VOLTAGE SENSING
PIN
No
47 48
V2
49 50 Bus/Mains Neutral (N) input
DESCRIPTION CABLE
Bus/Mains L1 (R) voltage monitoring Bus/Mains L2 (S) voltage monitoring Bus/Mains L3 (T) voltage monitoring
SIZE
1.0mm
AWG 18
1.0mm
AWG 18
1.0mm
AWG 18
1.0mm
AWG 18
NOTES
Connect to Mains L1 (R) incoming supply (AC) (Recommend 2A fuse) Connect to Mains L1 (S) incoming supply (AC) (Recommend 2A fuse) Connect to Mains L1 (T) incoming supply (AC) (Recommend 2A fuse) Connect to Mains N incoming supply (AC)
41
Installation – Terminal Description
4.1.6 GENERATOR CURRENT TRANSFORMERS
WARNING!:- Do not disconnect this plug when the CTs are carrying current. Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may then develop. Always ensure the CTs are not carrying current and the CTs are short circuit connected before making or breaking connections to the module.
NOTE:- The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the burden of the controller, the cable length being used and any other equipment sharing the CT. If in doubt, consult your CT supplier.
PIN
No
51 CT Secondary for Gen L1 52 CT Secondary for Gen L2 53 CT Secondary for Gen L3
Connection to terminals 54 & 55
The function of terminals 54 and 55 change position depending upon wiring topology as follows:
Topology Pin
No earth fault measuring
Restricted earth fault measuring
Un-restricted earth fault measuring (Earth fault CT is fitted in the neutral to earth link)
DESCRIPTION CABLE
SIZE
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
No
54 DO NOT CONNECT 55 54 55 54
55
NOTES
Connect to s1 secondary of L1 monitoring CT Connect to s1 secondary of L2 monitoring CT Connect to s1 secondary of L3 monitoring CT
Description CABLE
Connect to s2 of the CTs connected to L1,L2,L3,N
Connect to s2 of the CTs connected to L1,L2,L3,N
Connect to s1 of the CT on the neutral conductor
Connect to s1 of the CT on the neutral to earth conductor. Connect to s2 of the CT on the neutral to earth link. Also connect to the s2 of CTs connected to L1, L2, L3.
SIZE
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
2.5mm²
AWG 13
NOTE: - Terminals 56 to 59 are not fitted to the controller.
42
Installation – Terminal Description
CT CONNECTIONS
p1, k or K is the primary of the CT that ‘points’ towards the GENERATOR
p2, l or L is the primary of the CT that ‘points’ towards the LOAD s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring
(I1,I2,I3)
s2 is the secondary of the CT that should be commoned with the s2 connections of all the other CTs and connected to the CT common terminal of the module.
CT labelled as p1, k or K
To Supply
To Load
CT labelled as p2, l or L
43
Installation – Terminal Description
4.1.7 CONFIGURABLE DIGITAL INPUTS
PIN
No
60 Configurable digital input A 61 Configurable digital input B 62 Configurable digital input C 63 Configurable digital input D 64 Configurable digital input E 65 Configurable digital input F 66 Configurable digital input G 67 Configurable digital input H 68 Configurable digital input I 69 Configurable digital input J 70 Configurable digital input K
DESCRIPTION CABLE
SIZE
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
0.5mm²
AWG 20
NOTES
Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative Switch to negative
NOTE:- See the software manual for full range of configurable outputs available.
4.1.8 PC CONFIGURATION INTERFACE CONNECTOR
DESCRIPTION CABLE
SIZE
Socket for connection to PC with DSE Configuration Suite Software
0.5mm²
AWG 20
This is a standard USB type A to type B connector.
NOTE:- The USB connection cable between the PC and the module must not be extended beyond 5m (yards). For distances over 5m, it is possible to use a third party USB extender. Typically, they extend USB up to 50m (yards). The supply and support of this type of equipment is outside the scope of Deep Sea Electronics PLC.
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more than the recommended number of USB devices to the PC. For further information, consult your PC supplier.
NOTES
CAUTION!: This socket must not be used for any other purpose.
44
4.1.9 RS485 CONNECTOR
PIN No NOTES
Installation – Terminal Description
A (-)
B (+)
SCR
Two core screened twisted pair cable. 120 impedance suitable for RS485 use. Recommended cable type - Belden 9841 Max distance 1200m (1.2km) when using Belden 9841 or direct equivalent.
Location of RS485 connector
4.1.10 RS232 CONNECTOR
PIN No NOTES
1 Received Line Signal Detector (Data Carrier Detect) 2 Received Data 3 Transmit Data 4 Data Terminal Ready 5 Signal Ground 6 Data Set Ready 7 Request To Send 8 Clear To Send 9 Ring Indicator
Location of RS232
connector
View looking into the male connector on the module
45
Installation – Typical Wiring Diagrams
4.2 TYPICAL WIRING DIAGRAMS
As every system has different requirements, these diagrams show only a TYPICAL system and do not intend to show a complete system.
Genset manufacturers and panel builders may use these diagrams as a starting point; however, you are referred to the completed system diagram provided by your system manufacturer for complete wiring detail.
Further wiring suggestions are available in the following DSE publications, available at www.deepseaplc.com to website members.
DSE PART DESCRIPTION
056-022 Breaker Control (Training guide) 057-004 Electronic Engines and DSE Wiring
46
Installation – Typical Wiring Diagrams
4.2.1 DSE7410 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION
NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to generator / upstream of the CT)
47
Installation – Typical Wiring Diagrams
4.2.2 DSE7420 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION
NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to generator / upstream of the CT)
48
Installation – Typical Wiring Diagrams
4.3 ALTERNATIVE TOPOLOGIES
The controller is factory configured to connect to a 3 phase, 4 wire Star connected alternator. This section details connections for alternative AC topologies. Ensure to configure the controller to suit the required topology.
NOTE:- Refer to DSE7400 Series Configuration Suite Manual (DSE part 057-160) for further details on configuring, monitoring and control.
4.3.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION
49
Installation – Typical Wiring Diagrams
4.3.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT
NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to generator / upstream of the CT)
4.3.3 SINGLE PHASE WITHOUT EARTH FAULT
50
Installation – Typical Wiring Diagrams
4.3.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT
NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to generator / upstream of the CT)
4.3.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT
51
Installation – Typical Wiring Diagrams
4.3.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT
NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults ‘after’ the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT only (Restricted to generator / upstream of the CT)
4.3.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING
52
Installation – Typical Wiring Diagrams
4.3.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING
NOTE:- Unrestricted Earth Fault Protection detects earth faults in the load and in the generator. Be sure to measure the natural earth fault of the site before deciding upon an earth fault alarm trip level.
53
Installation – Typical Wiring Diagrams
4.4 EARTH SYSTEMS
4.4.1 NEGATIVE EARTH
The typical wiring diagrams located within this document show connections for a negative earth system (the battery negative connects to Earth)
4.4.2 POSITIVE EARTH
When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the following points must be followed:
Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
All points shown as Earth on the typical wiring diagram should connect to BATTERY
NEGATIVE (not earth).
4.4.3 FLOATING EARTH
Where neither the battery positive nor battery negative terminals are connected to earth the following points must to be followed
Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
All points shown as Earth on the typical wiring diagram should connect to BATTERY
NEGATIVE (not earth).
4.5 TYPICAL ARRANGEMENT OF DSENET®
Twenty (20) devices can be connected to the DSENet®, made up of the following devices :
Device Max Number Supported
DSE2130 Input Expansion 4 DSE2131 Ratio-metric Input Expansion 4 DSE2133 RTD/Thermocouple Intput Expansion 4 DSE2152 Ratio-metric Output Expansion 4 DSE2157 Relay Output Expansion 10 DSE2548 LED Expansion 10
For part numbers of the expansion modules and their documentation, see section entitled DSENet Expansion Modules elsewhere in this manual.
54
Description Of Controls
mode
mode
mode
L
amp test
mode
5 DESCRIPTION OF CONTROLS
5.1 DSE7410 AUTO START CONTROL MODULE
Menu navigation buttons
Open Generator (manual mode only)
Select Stop
Select Manual
Close Mains LED. On When The Mains Is On Load.
Main status and instrumentation display
Select Test
Four configurable LEDs
Close Generator (manual mode only)
Start engine (when in manual)
Mute alarm /
Select Auto
Generator Available LED. On when the generator is within limits and able to take load.
55
Description Of Controls
mode
mode
mode
Lamp test
mode
5.2 DSE7420 AUTO START CONTROL MODULE
Menu navigation buttons
Transfer to Mains (manual mode only)
Select Stop
Mains Available LED. On when the mains is within limits and able to take load.
Select Manual
Close Mains LED. On When The Mains Is On Load.
Main status and instrumentation display
Select Test
Select Auto
Close Bus LED. On When The Bus Is On Load.
Four configurable LEDs
Transfer to Generator (manual mode only)
Start engine (when in manual or Testmode)
Mute alarm /
Generator Available LED. On when the generator is within limits and able to take load.
56
Description Of Controls
5.3 QUICKSTART GUIDE
This section provides a quick start guide to the module’s operation.
5.3.1 STARTING THE ENGINE
First, select manual mode…
…then press the Start button to crank the engine.
NOTE:- For further details, see the section entitled ‘OPERATION’ elsewhere in this manual.
5.3.2 STOPPING THE ENGINE
Select Stop/Reset mode. The generator is stopped.
NOTE:- For further details, see the section entitled ‘OPERATION’ elsewhere in this manual.
57
Viewing The Instrument Pages
instruments
rather than down!
the
pages
rather than
right!
5.4 VIEWING THE INSTRUMENT PAGES
It is possible to scroll to display the different pages of information by repeatedly operating the next /
previous page buttons .
Example
Example
ExampleExample
If you want to view one of the instrument pages towards the end of the list, it may be quicker to scroll left through
And so on until the last page is reached.
Status
Engine
Generator
A Further press of the scroll right button returns the display to the Status page.
The complete order and contents of each information page are given in the following sections
Once selected the page will remain on the LCD display until the user selects a different page, or after an extended period of inactivity (LCD Page Timer), the module will revert to the status display.
If no buttons are pressed upon entering an instrumentation page, the instruments will be displayed automatically subject to the setting of the LCD Scroll Timer.
The LCD Page and LCD Scroll timers are configurable using the DSE Configuration Suite Software or by using the Front Panel Editor.
The screenshot shows the factory settings for the timers, taken from the DSE Configuration Suite Software.
Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll
buttons. The ‘autoscroll’ is disabled.
If you want to view one of the instruments towards the end of the list, it may be quicker to scroll up through the
To re-enable ‘autoscroll’ press the scroll buttons to scroll to the ‘title’ of the instrumentation page (ie Engine). A short time later (the duration of the LCD Scroll Timer), the instrumentation display will begin to autoscroll.
When scrolling manually, the display will automatically return to the Status page if no buttons are pressed for the duration of the configurable LCD Page Timer.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the operator’s attention to the alarm condition.
58
Viewing The Instrument Pages
5.4.1 STATUS
This is the ‘home’ page, the page that is displayed when no other page has been selected, and the page that is automatically displayed after a period of inactivity (LCD Page Timer) of the module control buttons.
This page will change with the action of the controller , when on gen generator parameters will be seen and when changing to mains the mains parameters will be shown.
Status 22:31
Status 22:31
Status 22:31Status 22:31
Generator at Rest
Generator at Rest
Generator at RestGenerator at Rest
Stop Mode
Stop Mode
Stop ModeStop Mode
Safety on Delay 00:04
Safety on Delay 00:04
Safety on Delay 00:04Safety on Delay 00:04
LLLL----N 215V 43A
N 215V 43A
N 215V 43AN 215V 43A
LLLL----L 373V 47.5Hz
L 373V 47.5Hz
L 373V 47.5HzL 373V 47.5Hz
0kW 0.0pf
The contents of this display may vary depending upon configuration by the generator manufacturer / supplier.
The display above is achieved with the factory settings, shown below in the DSE Configuration suite software:
0kW 0.0pf
0kW 0.0pf0kW 0.0pf
Factory setting of Status screen showing engine stopped...
...and engine running
‘Stop Mode’ etc is displayed on the Home Page
With a summary of the instrumentation shown when the engine is running.
Other pages can be configured to be shown, automatically scrolling when the set is running.
NOTE:- The following sections detail instrumentation pages, accessible using the scroll left and right buttons, regardless of what pages are configured to be displayed on the ‘status’ screen.
59
Viewing The Instrument Pages
5.4.2 ENGINE
Contains instrumentation gathered about the engine itself, some of which may be obtained using the CAN or other electronic engine link.
Engine Speed
Oil Pressure
Coolant Temperature
Engine Battery Volts
Engine Run Time
Engine Fuel Level
Oil Temperature*
Coolant Pressure*
Inlet Temperature*
Exhaust Temperature*
Fuel Temperature*
Turbo Pressure*
Fuel Pressure*
Fuel Consumption*
Fuel Used*
Fuel Level*
Auxiliary Sensors (If fitted and configured)
Engine Maintenance Due (If configured)
Engine ECU Link*
*When connected to suitably configured and compatible engine ECU. For details of supported engines see ‘Electronic Engines and DSE wiring’ (DSE Part number 057-004).
Tier 4 engine information will also be available if used with a Tier 4 suitable engine / ECU.
Depending upon configuration and instrument function, some of the instrumentation items may include a tick icon beside them. This denotes a further function is available, detailed in the ‘operation’
section of this document.
Example:
The tick icon denotes that manual fuel pump control is enabled in this system. Press and hold to start the fuel transfer pump, release to stop the pump. This is detailed further in the section entitled ‘operation’ elsewhere in this document.
60
Viewing The Instrument Pages
5.4.3 GENERATOR
Contains electrical values of the generator (alternator), measured or derived from the module’s voltage and current inputs.
Generator Voltage (ph-N)
Generator Voltage (ph-ph)
Generator Frequency
Generator Current
Generator Earth Current
Generator Load %
Generator Load (kW)
Generator Load (kVA)
Generator Power Factor
Generator Power Factor Average
Generator Load (kVAr)
Generator Load (kWh, kVAh, kVArh)
Generator Phase Sequence
Generator Config (Nominals)
Generator Active Config
61
Viewing The Instrument Pages
5.4.4 BUS (DSE7410 ONLY)
Bus Voltage (ph-N)
Bus Voltage (ph-ph)
Bus Frequency
5.4.5 MAINS (DSE7420 ONLY)
Mains Voltage (ph-N)
Mains Voltage (ph-ph)
Mains Frequency
5.4.6 RS232 SERIAL PORT
This section is included to give information about the RS232 serial port and external modem (if connected). The items displayed on this page will change depending upon configuration of the module. You are referred to your system supplier for further details.
NOTE:- Factory Default settings are for the RS232 port to be enabled with no modem connected, operating at 19200 baud, modbus slave address 10.
Example 1 – Module connected to an RS232 telephone modem.
When the module is powered up, it will send ‘initialisation strings’ to the connected modem. It is important therefore that the modem is already powered, or is powered up at the same time as the module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, then if the modem is dialled, it will answer after two rings (using the factory setting ‘initialisation strings)’. Once the call is established, all data is passed from the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module will dial out whenever an alarm is generated. Note that not all alarms will generate a dial out; this is dependant upon module configuration of the event log. Any item configured to appear in the event log will cause a dial out.
Press down to view the modem status....
Indicates that a modem is configured. Shows ‘RS232’ if no modem is configured.
62
Viewing The Instrument Pages
Example 1 continued – Modem diagnostics
Modem diagnostic screens are included; press when viewing the RS232 Serial Port instrument to cycle the available screens. If you are experiencing modem communication problems, this information will aid troubleshooting.
Serial Port
Serial Port
Serial PortSerial Port
RTS
RTS
RTSRTS
CTS
CTS
CTSCTS
DSR
DSR
DSRDSR
DTR
DTR
DTRDTR DCD
DCD
DCDDCD
Shows the state of the modem communication lines. These can help diagnose connection problems.
Example:
RTS A dark background shows the line is active. RTS a grey background shows that the line is toggling high and
low. RTS No background indicates that the line is inactive
Line Description
RTS Request To Send Flow control CTS Clear To Send Flow control DSR Data Set Ready Ready to communicate DTR Data Terminal Ready Ready to communicate DCD Data Carrier Detect Modem is connected
Modem Commands
Modem Commands
Modem CommandsModem Commands
Rx: OK
Rx: OK
Rx: OKRx: OK Tx: AT+IPR=9600
Tx: AT+IPR=9600
Tx: AT+IPR=9600Tx: AT+IPR=9600 Rx: OK
Rx: OK
Rx: OKRx: OK
Shows the last command sent to the modem and the result of the command.
63
Viewing The Instrument Pages
Modem Setup Sequence
1)
If the Modem and module communicate successfully:
2)
In case of communication failure between the modem and module, the modem is automatically reset and initialisation is attempted once more:
3) In the case of a module that is unable to communicate with the modem, the display will
continuously cycle between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and attempts to communicate with it again, this will continue until correct communication is established with the modem. In this instance, you should check connections and verify the modem operation.
Example 2 – Module connected to a modem.
Example 3 – Modem status of a GSM modem
Currently connected GSM operator and signal strength.
Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator. These can be a useful troubleshooting tool.
In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an ordinary telephone. There should be two rings, followed by the modem answering the call and then ‘squealing’. If this does not happen, you should check all modem connections and double check with the SIM provider that it is a DATA SIM and can operate as a data modem. DATA is NOT the same as FAX or GPRS and is often called Circuit Switched Data (CSD) by the SIM provider.
NOTE:
NOTE: In the case of G
NOTE:NOTE:
This is often a different number than the ‘voice number’
This is often a different number than the ‘voice number’ and is often called Circuit Switched
This is often a different number than the ‘voice number’This is often a different number than the ‘voice number’ Data (CSD) by the SIM provider
Data (CSD) by the SIM provider....
Data (CSD) by the SIM providerData (CSD) by the SIM provider
In the case of GSM modems, it is important that a DATA ENABLED SIM is used.
In the case of GIn the case of G
SM modems, it is important that a DATA ENABLED SIM is used.
SM modems, it is important that a DATA ENABLED SIM is used. SM modems, it is important that a DATA ENABLED SIM is used.
and is often called Circuit Switched
and is often called Circuit Switched and is often called Circuit Switched
If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at 9600 baud.
64
Viewing The Instrument Pages
5.4.7 RS485 SERIAL PORT
This section is included to give information about the currently selected serial port and external modem (if connected). The items displayed on this page will change depending upon configuration of the module. You are referred to your system supplier for further details.
NOTE:- Factory Default settings are for the RS485 port to operating at 19200 baud, modbus
slave address 10.
Module RS485 port configured for connection to a modbus master.
The modules operate as a modbus RTU slave device. In a modbus system, there can be only one Master, typically a PLC, HMI system or PC SCADA system.
This master requests for information from the modbus slave (The module) and may (in control systems) also send request to change operating modes etc. Unless the Master makes a request, the slave is ‘quiet’ on the data link.
The factory settings are for the module to communicate at 19200 baud, modbus slave address 10. To use the RS485 port, ensure that ‘port usage’ is correctly set using the DSE Configuration Suite Software. Required settings are shown below.
‘Master inactivity timeout’ should be set to at least twice the value of the system scan time. For example if a modbus master PLC requests data from the module once per second, the timeout should be set to at least 2 seconds.
The DSE Modbus Gencomm document containing register mappings inside the DSE module is available upon request from support@deepseaplc.com. Email your request along with the serial number of your DSE module to ensure the correct information is sent to you.
65
Viewing The Instrument Pages
• Version
– Engine type file version.
Typical requests (using Pseudo code)
BatteryVoltage=ReadRegister(10,0405,1)
: reads register (hex) 0405 as a single register (battery volts)
from slave address 10.
WriteRegister(10,1008,2,35701, 65535-35701)
: Puts the module into AUTO mode by writing to (hex) register 1008, the values 35701 (auto mode) and register 1009 the value 65535-35701 (the bitwise opposite of auto mode)
Shutdown=(ReadRegister(10,0306,1) >> 12) & 1)
: reads (hex) 0306 and looks at bit 13 (shutdown alarm
present)
Warning=(ReadRegister(10,0306,1) >> 11) & 1)
: reads (hex) 0306 and looks at bit 12 (Warning alarm
present)
ElectricalTrip=(ReadRegister(10,0306,1) >> 10) & 1)
: reads (hex) 0306 and looks at bit 11 (Electrical
Trip alarm present)
ControlMode=ReadRegister(10,0304,2);
reads (hex) register 0304 (control mode).
5.4.8 ABOUT
Contains important information about the module and the firmware versions. This information may be asked for when contacting DSE Technical Support Department for advice.
About
Variant 7420 Application V4.4.6 USB ID BC614E
Variant (7410 or 7420)
Application Version – The version of the module’s main
firmware file (Updatable using the Firmware Update Wizard in the DSE Configuration Suite Software).
USB ID – Unique identifier for PC USB connection
Press to access more information about the module.
About
Bootloader V1.3.4
Bootloader - Firmware Update bootloader software version
Analogue – Analogue measurements software version
Analogue V2.0.0
Press to access more information about the module.
About
Engine Type – The type of engine or ECU file which is
Engine Type Volvo EMS2b
configured within the module.
Version V1.18
66
Viewing The Instrument Pages
• Pref IP
– The preferred IP address.
5.4.8.1 ETHERNET PAGES
Whilst in the ‘ABOUT’ section, press to access more information about the network settings. Network settings change be configured using DSE Configuration Suite Software. The module must be rebooted for the changes to take effect.
Network
IP Address
192.168.50.76
DHCP Disabled
Press to access more information about the network settings.
Network
Subnet Mask
255.255.255.0
Network
Gateway Address
192.168.49.76
Network
DNS Address
192.168.88.99
Network
MAC Address
E8.A4.C1.0.A.C2
DHCP
Host Domain Vender
MODBUS Over IP
TCP Port 502 Pref IP 192.168.20.11
IP Address – The configured network IP address of the module
DHCP – Dynamic Host Configuration Protocol (DHCP) has been enabled or disabled in the modules configuration.
Subnet Mask – The configured network subnet mask of the module.
Gateway Address – The configured network gateway address of the module.
DNS Address – The configured network DNS address of the module.
MAC Address – The MAC address of the module, this cannot be changed and is unique to each module.
DHCP – The DHCP settings of module if configured.
TCP Port – The MODBUS TCP communication port
number.
67
Viewing The Instrument Pages
USB memory.
5.4.8.2 DATA LOGGING PAGES
Whilst in the ‘ABOUT’ section, press to access more information about the data logging settings.
Data Logging
Log to internal memory Logging active No USB drive present
Inserting a USB drive to the host USB will display the following change to the page.
Data Logging
Log to USB drive Logging active Do not remove USB drive
Location of stored data. Internal module memory or external
If data logging is active or inactive
NOTE:- Removal of the USB drive should only be carried out using the following method.
Press and hold the tick button until “Ok to remove USB drive” is displayed.
Data Logging
Log to USB drive Logging active Ok to remove USB drive
It is now safe to remove the USB drive. This ensures the logging data file will save to memory complete and will not become corrupt.
Press down
Time remaining xxxx h xx m
Press down
Memory remaining
.
to view the next page.
Data Logging
to view the next page.
Data Logging
xxxx
Remaining time available for logging information. xxxx hours xx minutes
Memory space remaining, this depends what size memory drive is fitted (Max 16Gb) or allocated internal (2Mb) memory left available.
68
Viewing The Instrument Pages
5.4.9 CAN ERROR MESSAGES
When connected to a suitable CAN engine the controller displays alarm status messages from the ECU.
Alarm
ECU Warning Warning
Press to access the list of current active Engine DTCs (Diagnostic Trouble Codes).
Engine DTCs
Water Level Low Xxx,xxx,xxx
The code interpreted by the module shows on the display as a text message. Additionally, the manufacturer’s code is shown.
Type of alarm that is triggered in the DSE module (i.e. Warning or Shutdown)
NOTE: - For details on these code meanings, refer to the ECU instructions provided by the
engine manufacturer, or contact the engine manufacturer for further assistance.
NOTE: - For further details on connection to electronic engines please refer to Electronic
engines and DSE wiring. Part No. 057-004
69
Viewing The Instrument Pages
5.5 VIEWING THE EVENT LOG
The module maintains a log of past alarms and/or selected status changes. The log size has been increased in the module over past module updates and is always subject to change. At the time of writing, the modules log is capable of storing the last 250 log entries.
Under default factory settings, the event log only includes shutdown and electrical trip alarms logged (The event log does not contain Warning alarms); however, this is configurable by the system designer using the DSE Configuration Suite software.
Example showing the possible configuration of the modules event log (DSE Configuration Suite Software) This also shows the factory settings of the module (Only shutdown alarms and the mains status are logged).
Once the log is full, any subsequent shutdown alarms will overwrite the oldest entry in the log. Hence, the log will always contain the most recent shutdown alarms. The module logs the alarm, along with the date and time of the event (or engine running hours if configured to do so). If the module is configured and connected to send SMS text
To view the event log, repeatedly press the next page button until the LCD screen displays the Event log :
Event log 1
Oil Pressure Low Shutdown
12 Sep 2007, 08:25:46
Press down
Continuing to press down most recent alarm and the cycle begins again.
to view the next most recent shutdown alarm:
This is event 1.
cycles through the past alarms after which the display shows the
To exit the event log and return to viewing the instruments, press the next page button to select the next instrumentation page.
70
Control and Indications
5.6 USER CONFIGURABLE INDICATORS
These LEDs can be configured by the user to indicate any one of 100+ different functions based around the following:-
Indications - Monitoring of a digital input and indicating associated functioning user’s equipment - Such as Battery Charger On or Louvres Open, etc.
WARNINGS, ELECTRICAL TRIPS & SHUTDOWNS - Specific indication of a particular warning or shutdown condition, backed up by LCD indication - Such as Low Oil Pressure Shutdown, Low Coolant
level, etc.
Status Indications - Indication of specific functions or sequences derived from the modules operating state - Such as Safety On, Pre-
heating, Panel Locked, Generator Available, etc.
User configurable LEDs
71
Operation
6 OPERATION
6.1 CONTROL
Control of the module is via push buttons mounted on the front of the module with STOP/RESET, MANUAL, TEST, AUTO, ALARM MUTE and START functions. For normal operation, these are the
only controls which need to be operated. The smaller push buttons are used to access further information such as mains voltage or to change the state of the load switching devices when in manual mode. Details of their operation are provided later in this document.
The following descriptions detail the sequences followed by a module containing the standard ‘factory configuration’. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field.
CAUTION:
CAUTION: ---- The module may i
CAUTION: CAUTION:
Therefore, it is possible for the engine to start at any time without warning. Prior to
Therefore, it is possible for the engine to start at any time without warning. Prior to
Therefore, it is possible for the engine to start at any time without warning. Prior to Therefore, it is possible for the engine to start at any time without warning. Prior to performing any maintenance on the system, it is recommended that steps are taken to
performing any maintenance on the system, it is recommended that steps are taken to
performing any maintenance on the system, it is recommended that steps are taken to performing any maintenance on the system, it is recommended that steps are taken to remove the battery and iso
remove the battery and isolate supplies.
remove the battery and isoremove the battery and iso
NOTE:
NOTE: ---- This control
NOTE: NOTE:
standard operation when used.
standard operation when used. ((((Default configuration the no PLC is set. See software
standard operation when used.standard operation when used. manual for more information)
manual for more information)
manual for more information)manual for more information)
The module may instruct an engine start event due to external influences.
The module may iThe module may i
late supplies.
late supplies.late supplies.
This control module
This controlThis control
module has PLC functionality built in.
modulemodule
nstruct an engine start event due to external influences.
nstruct an engine start event due to external influences. nstruct an engine start event due to external influences.
has PLC functionality built in. This can have change the
has PLC functionality built in.has PLC functionality built in.
Default configuration the no PLC is set. See software
Default configuration the no PLC is set. See software Default configuration the no PLC is set. See software
72
This can have change the
This can have change the This can have change the
Operation
6.2 CONTROL PUSH-BUTTONS
Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and the module is in Stop mode, the module will automatically instruct the changeover device to unload the generator (‘Close Generator becomes inactive (if used)). The fuel supply de-energises and the engine comes to a standstill. Should a remote start signal be present while operating in this mode, a remote start will not occur. Manual This mode allows manual control of the generator functions. Once in Manual
mode the module will respond to the start button, start the engine, and
run off load. If the engine is running off-load in the Manual mode and a remote start signal becomes present, the module will automatically instruct the changeover device to place the generator on load (‘Close Generatorbecomes active (if used)). Upon removal of the remote start signal, the generator
remains on load until either selection of the ‘STOP/RESET or ‘AUTO modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this manual.
Test (DSE7420 only)
This button places the module into its ‘Test’ mode. This allows an on load test of the generator.
Once in Test mode the module will respond to the start button, start the engine, and run on load.
For further details, please see the more detailed description of ‘Test operation’ elsewhere in this manual.
Auto This button places the module into its ‘Automatic’ mode. This mode allows the module to control the function of the generator automatically. The module will monitor the remote start input and mains supply status and once a start request is made, the set will be automatically started and placed on load. Upon removal of the starting signal, the module will automatically transfer the load from the generator and shut the set down observing the stop delay timer and cooling timer as necessary. The module will then await the next start event.
For further details, please see the more detailed description of ‘Auto operation’ elsewhere in this manual.
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test feature/ When correctly configured and fitted to a compatible engine ECU, pressing this
button in STOP/RESET mode after pressing the START button (to power the ECU) will cancel any “passive” alarms on the engine ECU.
Start
This button is only active in STOP/RESET or MANUAL mode. Pressing this button in manual or test mode will start the engine and run off load (manual) or on load (test).
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly configured and fitted to a compatible engine ECU)
NOT
NOTE:
E:---- Different modes of operation are possible
NOTNOT
Different modes of operation are possible ---- Please refer to
E:E:
Different modes of operation are possible Different modes of operation are possible
73
Please refer to
Please refer to Please refer to
Operation
your configuration source for details.
your configuration source for details.
your configuration source for details.your configuration source for details.
Transfer to generator
Operative in Manual Mode only ‘Normal’ breaker button control
Allows the operator to transfer the load to the generator
‘Alternative’ breaker button control
If mains is on load, transfers the load to the generator.
If generator is on load, opens the generator breaker
If generator and mains are off load, closes the generator breaker.
Open generator (DSE7410 only) Allows the operator to open the generator (when in Manual mode only)
Transfer to mains (DSE7420 only)
Operative in Manual Mode only ‘Normal’ breaker button control
Allows the operator to transfer the load to the mains
‘Alternative’ breaker button control
If generator is on load, transfers the load to the mains.
If mains is on load, opens the mains breaker
If generator and mains are off load, closes the mains breaker.
Menu navigation Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this manual.
6.3 ALTERNATIVE CONFIGURATIONS
Depending upon the configuration of your system by the generator supplier, the system may have selectable configurations (for example to select between 50Hz and 60Hz running). If this has been enabled your generator supplier will advise how this selection can be made (usually by externally operated selector switch or by selecting the required configuration file in the module front panel configuration editor).
74
Operation
6.4 DUMMY LOAD / LOAD SHEDDING CONTROL
This feature may be enabled by the system designer to ensure the loading on the generator is kept to a nominal amount. If the load is low, ‘dummy loads’ (typically static load banks) can be introduced to ensure the engine is not too lightly loaded. Conversely as the load increases towards the maximum rating of the set, non-essential loads can be shed to prevent overload of the generator.
6.2.1 DUMMY LOAD CONTROL
The dummy load control feature (if enabled) allows for a maximum of five dummy load steps. When the set is first started, all configured Dummy Load Control outputs are de-energised. Once the generator is placed onto load, the generator loading is monitored by the Dummy Load Control scheme.
If the generator loading falls below the Dummy Load Control Trip setting (kW), the Dummy Load Control Trip Delay is displayed on the module display. If the generator loading remains at this low level for the duration of the timer, the first Dummy Load Control output is energised. This is used to energise external circuits to switch in (for instance) a static load bank.
The generator loading has now been increased by the first dummy load. Again the generator loading is monitored. This continues until all configured Dummy Load Control outputs are energised. Should the generator loading rise above the Dummy Load Return level, the Dummy Load Return Delay begins. If the loading remains at these levels after the completion of the timer, the ‘highest’ active Dummy Load Control output is de-energised. This continues until all Dummy Load Control outputs have been de-energised.
6.2.2 LOAD SHEDDING CONTROL
The Load Shedding Control feature (if enabled) allows for a maximum of five load shedding steps. When the generator is about to take load, the configured number of Load Shedding Control Outputs at Startup will energise. This configurable setting allows (for instance) certain loads to be removed from the generator prior to the set’s load switch being closed. This can be used to ensure the initial loading of the set is kept to a minimum, below the Load Acceptance specification of the generating set.
The generator is then placed on load. The Load Shedding Control scheme begins. When the load reaches the Load Shedding Trip level the Trip Delay timer will start. If the generator loading is still high when the timer expires, the first Load shedding Control output will energise. When the load has been above the trip level for the duration of the timer the ‘next’ Load shedding Control output will energise and so on until all Load Shedding Control outputs are energised.
If at any time the load falls back below the Load Shedding Return level, the Return Time will start. If the load remains below the return level when the timer has expired the ‘highest’ Load Shedding Control output that has been energised will be de-energised. This process will continue until all outputs have been de-energised. When the set enters a stopping sequence for any reason the Load Shedding control’ outputs will de­energise at the same time as the generator load switch is signalled to open.
NOTE:- Refer to DSE7400 Series Configuration Suite Manual (DSE part 057-160) for further
details on configuration.
75
Operation
6.5 STOP MODE
STOP mode is activated by pressing the button.
In STOP mode, the module will remove the generator from load (if necessary) before stopping the engine if it is already running.
If the engine does not stop when requested, the FAIL TO STOP alarm is activated (subject to the setting of the Fail to Stop timer). To detect the engine at rest the following must occur :
Engine speed is zero as detected by the Magnetic Pickup or CANbus ECU (depending upon module variant).
Generator frequency must be zero.
Oil pressure switch must be closed to indicate low oil pressure (MPU version only)
When the engine has stopped, it is possible to send configuration files to the module from DSE Configuration Suite PC software and to enter the Front Panel Editor to change parameters.
Any latched alarms that have been cleared will be reset when STOP mode is entered.
The engine will not be started when in STOP mode. If remote start signals are given, the input is ignored until AUTO mode is entered.
When configured to do so, When left in STOP mode for five minutes with no presses of the fascia buttons, the module enters low power mode. To ‘wake’ the module, press the button or any other
fascia control button.
Sleep mode configuration in the DSE Configuration Suite Software
76
Operation
6.5.1 ECU OVERRIDE
NOTE:- ECU Override function is only applicable when the controller is configured for a
CAN engine.
NOTE:- Depending upon system design, the ECU may be powered or unpowered when the module is in STOP mode. ECU override is only applicable if the ECU is unpowered when in STOP mode.
When the ECU powered down (as is normal when in STOP mode), it is not possible to read the diagnostic trouble codes or instrumentation. Additionally, it is not possible to use the engine manufacturers’ configuration tools.
As the ECU is usually unpowered when the engine is not running, it must be turned on manually as follows :
Select STOP mode on the DSE controller.
Press and hold the START button to power the ECU. As the controller is in STOP mode,
the engine will not be started.
.
The ECU will remain powered 2 minutes after the START button is released.
This is also useful if the engine manufacturer’s tools need to be connected to the engine, for instance to configure the engine as the ECU needs to be powered up to perform this operation.
77
Operation
6.6 MANUAL MODE
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate Manual mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Manual mode allows the operator to start and stop the set manually, and if required change the state of the load switching devices.
6.6.1 WAITING IN MANUAL MODE
When in manual mode, the set will not start automatically. To begin the starting sequence, press the
button.
6.6.2 STARTING SEQUENCE
NOTE:- There is no start delay in this mode of operation.
The fuel relay is energised and the engine is cranked.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start command via CAN.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration after which the next start attempt is made. Should this sequence continue beyond the set
number of attempts, the start sequence will be terminated and the display shows Fail to Start. When the engine fires, the starter motor is disengaged. Speed detection is factory configured to be
derived from the main alternator output frequency but can additionally be measured from a Magnetic Pickup mounted on the flywheel (Selected by the configuration software).
Additionally, rising oil pressure can be used disconnect the starter motor (but cannot detect underspeed or overspeed).
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
78
Operation
6.6.3 ENGINE RUNNING
In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made. A loading request can come from a number of sources.
Pressing the transfer to generator button
Mains supply out of limits (DSE7420 only)
Activation of an auxiliary input that has been configured to remote start on load
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the engine.
Once the load has been transferred to the generator, it will not be automatically transferred back to the mains supply. To manually transfer the load back to the mains either:
Press the Transfer to Mains button (DSE7420 only)
Press the Open Generator button (DSE7410 only)
Press the Auto Mode button to return to automatic mode.
For further details of breaker control, see the section entitled “controls and indications” elsewhere in this manual.
6.6.4 MANUAL FUEL PUMP CONTROL
Navigate to the instruments page using the buttons and locate FUEL LEVEL. is shown on the module display to indicate that this feature is available.
Press and hold the button to energise the transfer pump. The pump starts two seconds after the button is pressed.
Release the button to de-energise the transfer pump.
6.6.5 MANUAL SPEED CONTROL
Navigate to the instruments page using the buttons and locate ENGINE SPEED. is shown on the module display to indicate that this feature is available.
Press the button to enter edit mode
Press (up or down) to change the engine speed.
Press the button again to exit the editor and leave the engine running at the newly selected
speed.
79
Operation
6.6.6 STOPPING SEQUENCE
In manual mode the set will continue to run until either :
The stop button
The auto button is pressed. The set will observe all auto mode start requests and stopping
timers before beginning the Auto mode stopping sequence.
is pressed – The set will immediately stop
6.7 TEST MODE
NOTE:- Test Mode is only applicable to DSE7420 controller.
NOTE:- If a digital input configured to panel lock is active, changing module modes will
not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate test mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Test mode will start the set and transfer the load to the generator to provide a Test on load function.
6.7.1 WAITING IN TEST MODE
When in test mode, the set will not start automatically. To begin the starting sequence, press the
6.7.2 STARTING SEQUENCE
The set begins to crank.
button.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start
command via CAN.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration after which the next start attempt is made. Should this sequence continue beyond the set
number of attempts, the start sequence will be terminated and the display shows Fail to Start. When the engine fires, the starter motor is disengaged. Speed detection is factory configured to be
derived from the main alternator output frequency but can additionally be measured from a Magnetic Pickup mounted on the flywheel (Selected by PC using the configuration software).
Additionally, rising oil pressure can be used disconnect the starter motor (but cannot detect underspeed or overspeed).
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
80
Operation
6.7.3 ENGINE RUNNING
Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before accepting the load.
Load will be automatically transferred from the mains supply to the generator.
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
In test mode, the set will continue to run on load until either:
The stop button is pressed – The set will immediately stop
The auto button is pressed. The set will observe all auto mode start requests and stopping
timers before beginning the Auto mode stopping sequence.
81
Operation
6.8 AUTOMATIC MODE
NOTE:- If a digital input configured to panel lock is active, changing module modes will
not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate auto mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Auto mode will allow the generator to operate fully automatically, starting and stopping as required with no user intervention.
6.8.1 WAITING IN AUTO MODE
If a starting request is made, the starting sequence will begin. Starting requests can be from the following sources:
Mains supply out of limits (DSE7420 only)
Activation of an auxiliary input that has been configured to remote start on load or remote
start off load.
Activation of the inbuilt exercise scheduler.
Instruction from external remote telemetry devices using the RS232 or RS485 interface
6.8.2 STARTING SEQUENCE
To allow for ‘false’ start requests such as mains brownouts, the start delay timer begins. There are individual start delay timers for each of the different start request types.
Should all start requests be removed during the start delay timer, the unit will return to a stand-by state.
If a start request is still present at the end of the start delay timer, the fuel relay is energised and the engine will be cranked.
NOTE:- If the unit has been configured for CAN, compatible ECU’s will receive the start
command via CAN.
If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the crank rest duration after which the next start attempt begins. Should this sequence continue beyond the set
number of attempts, the start sequence will be terminated and the display shows Fail to Start. The starter motor is disengaged when the engine fires. Speed detection is factory configured to be
derived from the main alternator output frequency, but can additionally be measured from a Magnetic Pickup mounted on the flywheel (Selected by PC using the configuration software).
Additionally, rising oil pressure can be used to disconnect the starter motor (but cannot detect underspeed or overspeed).
NOTE:- If the unit has been configured for CAN, speed sensing is via CAN.
After the starter motor has disengaged, the Safety On timer activates, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
82
Operation
6.8.3 ENGINE RUNNING
Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before accepting the load.
DSE7410 - The generator will be placed on load. DSE7420 - Load will be transferred from the mains supply to the generator
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
As the load increases and decreases, the module may (depending upon configuration) add dummy loads or remove non-essential loads. This is configured as part of the Load Shedding and Dummy Load control settings in the DSE Configuration Suite Software. See section entitled Dummy Load / Load Shedding elsewhere in this document for further details.
If all start requests are removed, the stopping sequence will begin.
6.8.4 STOPPING SEQUENCE
The return delay timer operates to ensure that the starting request has been permanently removed and isn’t just a short term removal. Should another start request be made during the cooling down period, the set will return on load.
If there are no starting requests at the end of the return delay timer, the load is transferred back from the generator to the mains supply and the cooling timer is initiated.
The cooling timer allows the set to run off load and cool sufficiently before being stopped. This is particularly important where turbo chargers are fitted to the engine.
After the cooling timer has expired, the set is stopped.
83
Protections
7 PROTECTIONS
When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configured will illuminate.
The audible alarm can be silenced by pressing the Mute button The LCD display will jump from the ‘Information page’ to display the Alarm Page
Alarm 1/2
Warning Low oil pressure
The LCD will display multiple alarms E.g. “High Engine Temperature shutdown”, “Emergency Stop” and “Low Coolant Warning”. These will automatically scroll in the order that they occurred.
In the event of a warning alarm, the LCD will display the appropriate text. If a shutdown then occurs, the module will again display the appropriate text. Example:-
Alarm 1/2
Warning Oil pressure Low
Number of present alarms. This is alarm 1 of a total of 2 present alarms
The type of alarm. E.g. Shutdown or warning
The nature of alarm, e.g. Low oil pressure
Alarm 2/2
Shutdown Coolant Temperature High
84
Protections
7.1 PROTECTIONS DISABLED
User configuration is possible to prevent Shutdown / Electrical Trip alarms from stopping the engine. Under such conditions, Protections Disabled will appear on the module display to inform the operator of this status.
This feature is provided to assist the system designer in meeting specifications for “Warning only”, “Protections Disabled”, “Run to Destruction”, “War mode” or other similar wording.
When configuring this feature in the PC software, the system designer chooses to make the feature either permanently active, or only active upon operation of an external switch. The system designer provides this switch (not DSE) so its location will vary depending upon manufacturer, however it normally takes the form of a key operated switch to prevent inadvertent activation. Depending upon configuration, a warning alarm may be generated when the switch is operated.
The feature is configurable in the PC configuration software for the module. Writing a configuration to the controller that has “Protections Disabled” configured, results in a warning message appearing on the PC screen for the user to acknowledge before the controller’s configuration is changed. This prevents inadvertent activation of the feature.
7.1.1 INDICATION / WARNING ALARMS
Under Indication or Warning alarms:
The module operation is unaffected by the Protections Disabled feature. See sections entitled Indications and Warnings elsewhere in this document.
7.1.2 SHUTDOWN / ELECTRICAL TRIP ALARMS
NOTE:- The EMERGENCY STOP input and shutdown alarm continues to operate even
when Protections Disabled has been activated.
Under Shutdown or Electrical Trip alarm conditions (excluding Emergency Stop):
The alarm is displayed on the screen as detailed in the section entitled Shutdown alarms elsewhere in this document.
The set continues to run.
The load switch maintains its current position (it is not opened if already closed)
Shutdown Blocked also appears on the LCD screen to inform the operator that the
Protections Disabled feature has blocked the shutdown of the engine under the normally critical fault.
The ‘shutdown’ alarm is logged by the controllers Event Log (if configured to log shutdown alarms) and logs that the Shutdown was prevented.
85
Protections
7.1.3 CAN ALARMS
NOTE:- Please refer to the engine manufacturer’s documentation for ECU CAN error
message information.
CAN alarms are messages sent from the CAN ECU to the DSE controller and displayed as follows in the below tables.
Display Reason
CAN ECU WARNING
ECU SHUTDOWN
ECU DATA FAIL
DM1 Signals. Messages from the CAN ECU that are configurable within the DSE module for:-
Display Reason
Amber Warning Red Shutdown Malfunction Protect
Advanced CAN alarms Allows configuration of additional can messages from the engine ECU.
Display Reason
Water in Fuel After Treatment
The engine ECU has detected a warning alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display and action taken depending upon the setting for the DM1 signals The engine ECU has detected a shutdown alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display. The module is configured for CAN operation and does not detect data on the engine CAN datalink, the engine shuts down.
Warning, Electrical Trip, shutdown or None
The CAN ECU has detected a Amber warning. The CAN ECU has detected a Red Shutdown. The CAN ECU has detected a Malfunction message. The CAN ECU has detected a Protect message
The ECU has detected water in the fuel action taken is set by settings in advanced. The ECU has detected “After Treatment alarm” consult engine manufacturer for details” action taken by DSE controller is set by settings in advanced
NOTE:- For CAN ECU error code meanings, refer to the ECU documentation provided by
the engine manufacturer, or contact the engine manufacturer for further assistance.
86
Protections
7.2 INDICATIONS
Indications are non-critical and often status conditions. They do not appear on the LCD of the module as a text message. However, an output or LED indicator can be configured to draw the operator’s attention to the event.
Example
Input configured for indication.
The LCD text will not appear on the module display but can be added in the configuration to remind the system designer what the input is used for.
As the input is configured to Indication there is no alarm generated.
LED Indicator to make LED1 illuminate when Digital Input A is active.
The Insert Card Text allows the system designer to print an insert card detailing the LED function.
Sample showing operation of the LED.
87
Protections
7.3 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition.
Example
Alarm 1/1
Charge Failure Warning
In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However enabling ‘all warnings are latched’ will cause warning alarms to latch until reset manually. This is enabled using the DSE Configuration Suite in conjunction with a compatible PC.
Display Reason
AUXILIARY INPUTS
CHARGE FAILURE BATTERY UNDER
VOLTAGE BATTERY OVER VOLTAGE FAIL TO STOP
If an auxiliary input has been configured as a warning the appropriate LCD message will be displayed and the COMMON ALARM LED will illuminate. The auxiliary charge alternator voltage is low as measured from the W/L terminal. The DC supply has fallen below the low volts setting level for the duration of the low battery volts timer
The DC supply has risen above the high volts setting level for the duration of the high battery volts timer
The module has detected a condition that indicates that the engine is running when it has been instructed to stop.
FUEL USAGE
LOW FUEL LEVEL CAN ECU ERROR
kW OVERLOAD EARTH FAULT NEGATIVE PHASE
SEQUENCE MAINTENANCE DUE
LOADING VOLTAGE NOT REACHED
LOADING FREQUENCY NOT REACHED
NOTE:
NOTE:---- ‘Fail to Stop’ could indicate a faulty oil pressure
NOTE:NOTE:
sensor or switch
sensor or switch ---- If the engine is at rest check oil sensor wiring
sensor or switch sensor or switch and configuration.
and configuration.
and configuration.and configuration.
Indicates the amount of fuel measured by the fuel level sensor is in excess of the Fuel Usage alarm settings. This often indicates a fuel leak or potential fuel theft. The level detected by the fuel level sensor is below the low fuel level setting. The engine ECU has detected a warning alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display. The measured Total kW is above the setting of the kW overload warning alarm The measured Earth Fault Current has been in excess of the earth fault trip and has surpassed the IDMT curve of the Earth Fault alarm. Indicates ‘out of balance’ current loading of the generator. Sometimes also called Negative Sequence Current or Symmetry Fault
Indicates that the maintenance alarm has triggered. A visit is required by the Generator service company. Indicates that the generator voltage is not above the configured loading voltage. The generator will not take load when the alarm is present after the safety timer. Indicates that the generator frequency is not above the configured loading frequency. The generator will not take load when the alarm is present after the safety timer.
‘Fail to Stop’ could indicate a faulty oil pressure
‘Fail to Stop’ could indicate a faulty oil pressure ‘Fail to Stop’ could indicate a faulty oil pressure
If the engine is at rest check oil sensor wiring
If the engine is at rest check oil sensor wiring If the engine is at rest check oil sensor wiring
88
Protections
Display Reason
PROTECTIONS DISABLED
LOW OIL PRESSURE
ENGINE HIGH TEMPERATURE
ENGINE LOW TEMPERATURE OVERSPEED UNDERSPEED GENERATOR OVER FREQUENCY GENERATOR UNDER FREQUENCY GENERATOR OVER VOLTAGE GENERATOR UNDER VOLTAGE INSUFFICIENT CAPACITY
MAINS FAILED TO CLOSE
MAINS FAILED TO OPEN
ECU WARNING
If the module is configured for, CAN and receives an “error” message from the engine control unit, ‘CAN ECU Warning” is shown on the module’s display and a warning alarm is generated.
Shutdown and electrical trip alarms can be disabled by user configuration. In this case, Protections Disabled will appear on the module display; The alarm text is displayed but the engine will continue to run. This is ‘logged’ by the module to allow DSE Technical Staff to check if the protections have been disabled on the module at any time. The module detects that the engine oil pressure has fallen below the low oil pressure pre-alarm setting level after the Safety On timer has expired. The module detects that the engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired. The module detects that the engine coolant temperature has fallen below the high engine temperature pre-alarm setting level.
The engine speed has risen above the overspeed pre alarm setting The engine speed has fallen below the underspeed pre alarm setting The generator output frequency has risen above the pre-set pre-alarm setting. The generator output frequency has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. The generator output voltage has risen above the pre-set pre-alarm setting. The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. f the generator reach full load when they are in parallel with the mains (utility). The LCD will indicate ‘INSUFFICIENT CAPACITY’ and the COMMON ALARM LED will illuminate. If the mains breaker fails to close, a warning is initiated. The LCD will indicate ‘MAINS FAILED TO CLOSE’ and the COMMON ALARM LED will illuminate. If the mains breaker fails to open, a warning is initiated. The LCD will indicate ‘MAINS FAILED TO OPEN’ and the COMMON ALARM LED will illuminate. The engine ECU has detected a warning alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display.
7.4 HIGH CURRENT WARNING ALARM
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-
set trip a warning alarm initiates. The module shows Alarm Warning High Current. If this high current condition continues for an excess period, then the alarm escalates to a shutdown condition. For further details of the high current alarm, please see High Current Shutdown Alarm.
By default, High Current Warning Alarm is self-resetting when the overcurrent condition is removed. However enabling ‘all warnings are latched’ will cause the alarm to latch until reset manually. This is enabled using the DSE Configuration Suite in conjunction with a compatible PC.
89
Protections
7.5 SHUTDOWNS
NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. See
the section entitled Protections Disabled elsewhere in this document.
Shutdowns are latching alarms and stop the Generator. Clear the alarm and remove the fault then press Stop/Reset to reset the module.
Example
Alarm 1/1
Oil Pressure Low Shutdown
NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition remains, it will not be possible to reset the unit (The exception to this is the Low Oil Pressure alarm and similar ‘active from safety on’ alarms, as the oil pressure will be low with the engine at rest).
Display Reason
EARTH FAULT
FAIL TO START EMERGENCY STOP
The measured Earth Fault Current has been in excess of the earth fault trip and has surpassed the IDMT curve of the Earth Fault alarm. The engine has not fired after the preset number of start attempts The emergency stop button has been depressed. This a failsafe (normally closed to battery positive) input and will immediately stop the set should the signal be removed. Removal of the battery positive supply from the emergency stop input will also remove DC supply from the Fuel and Start outputs of the controller.
LOW OIL PRESSURE
ENGINE HIGH TEMPERATURE
FUEL USAGE
PHASE ROTATION
OVERSPEED
UNDERSPEED
NOTE:- The Emergency Stop Positive signal must be
present otherwise the unit will shutdown.
The engine oil pressure has fallen below the low oil pressure trip setting level after the Safety On timer has expired. The engine coolant temperature has exceeded the high engine temperature trip setting level after the Safety On timer has expired. Indicates the amount of fuel measured by the fuel level sensor is in excess of the Fuel Usage alarm settings. This often indicates a fuel leak or potential fuel theft. The phase rotation is measured as being different to the configured direction.
The engine speed has exceeded the pre-set trip
NOTE:-During the start-up sequence, the overspeed trip logic can be configured to allow an extra trip level margin. This is used to prevent nuisance tripping on start­up - Refer to the DSE7400 series configuration software manual under heading ‘Overspeed Overshoot’ for details.
The engine speed has fallen below the pre-set trip after the Safety On timer has expired.
90
Display Reason
GENERATOR OVER
The generator output frequency has risen above the preset level
FREQUENCY GENERATOR UNDER
The generator output frequency has fallen below the preset level
FREQUENCY GENERATOR OVER VOLTAGE GENERATOR UNDER VOLTAGE OIL PRESSURE SENSOR OPEN CIRCUIT AUXILIARY INPUTS
The generator output voltage has risen above the preset level The generator output voltage has fallen below the preset level The oil pressure sensor is detected as not being present (open circuit) An active auxiliary input configured as a shutdown will cause the engine to shut down. The display shows the text as configured by the user.
LOSS OF SPEED SIGNAL
The speed signal from the magnetic pickup is not being received by the DSE controller.
ECU DATA FAIL
The module is configured for CAN operation and does not detect data on the engine Can datalink, the engine shuts down.
ECU SHUTDOWN
The engine ECU has detected a shutdown alarm and has informed the DSE module of this situation. The exact error is also indicated on the module’s display.
kW OVERLOAD
The measured Total kW is above the setting of the kW overload shutdown alarm
NEGATIVE PHASE SEQUENCE
Indicates ‘out of balance’ current loading of the generator. Sometimes also called Negative Sequence Current or Symmetry Fault
MAINTENANCE DUE
Indicates that the maintenance alarm has triggered. A visit is required by the Generator service company.
GENERATOR HIGH CURRENT
A High Current condition has continued for an excess period, then the alarm escalates to either a shutdown or electrical trip condition (depending upon module configuration). For further details of the high current alarm, please see High Current Shutdown / Electrical Trip Alarm.
LOADING VOLTAGE NOT REACHED
Indicates that the generator voltage is not above the configured loading voltage after the safety timer. The generator will shutdown.
LOADING FREQUENCY NOT REACHED
Indicates that the generator frequency is not above the configured loading frequency after the safety timer. The generator will shutdown.
PROTECTIONS DISABLED
Shutdown and electrical trip alarms can be disabled by user configuration. In this case, Protections Disabled will appear on the module display; The alarm text will be displayed but the engine will continue to run. This is ‘logged’ by the module to allow DSE Technical Staff to check if the protections have been disabled on the module at any time.
Protections
91
Protections
7.6 ELECTRICAL TRIPS
NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. See
the section entitled Protections Disabled elsewhere in this document.
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the module will de-energise the ‘Close Generator’ Output to remove the load from the generator. Once this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down the engine. The alarm must be accepted and cleared, and the fault removed to reset the module.
Example
Alarm 1/1
Generator Current High Electrical Trip
Electrical trips are latching alarms and stop the Generator. Remove the fault then press Stop/Reset
to reset the module.
Display Reason
GENERATOR HIGH CURRENT
AUXILIARY INPUTS kW OVERLOAD EARTH FAULT
NEGATIVE PHASE SEQUENCE FUEL USAGE
LOADING VOLTAGE NOT REACHED LOADING FREQUENCY NOT REACHED PROTECTIONS DISABLED
GENERATOR UNDER FREQUENCY GENERATOR UNDER VOLTAGE INSUFFICIENT CAPACITY
UNDERSPEED
If a generator output in excess of the high current alarm point, a warning alarm occurs. If this high current condition continues for an excess period, then the alarm escalates to either a shutdown or electrical trip condition (depending upon module configuration). For further details of the high current alarm, please see High Current Shutdown / Electrical Trip Alarm. If an auxiliary input configured as an electrical trip is active, the user configured message shows on the display. The measured Total kW is above the setting of the kW overload Electrical Trip alarm The measured Earth Current is above the setting of the Earth fault alarm. Indicates ‘out of balance’ current loading of the generator. Sometimes also called Negative Sequence Current or Symmetry Fault
Indicates the amount of fuel used is in excess of the Fuel Usage alarm settings. This often indicates a fuel leak or potential fuel theft. Indicates that the generator voltage is not above the configured loading voltage after the safety timer. The generator will shutdown.
Indicates that the generator frequency is not above the configured loading frequency after the safety timer. The generator will shutdown.
Shutdown and electrical trip alarms is disabled by user configuration. In this case, Protections Disabled will appear on the module display; The alarm text is displayed but the engine will continue to run. This is ‘logged’ by the module to allow DSE Technical Staff to check if the protections have been disabled on the module at any time. The generator output frequency has fallen below the preset level
The generator output voltage has fallen below the preset level If the module is configured for Mains CT and the load levels are so high
that the generator is unable to supply enough load to maintain the configured mains level, insufficient capacity will be displayed and the COMMON ALARM LED will flash. The generator will provide 100% of its capacity and the loading on the mains will increase. The engine speed has fallen below the underspeed setting
92
Protections
7.7 HIGH CURRENT SHUTDOWN / ELECTRICAL TRIP ALARM
The overcurrent alarm combines a simple warning trip level with a fully functioning IDMT curve for thermal protection.
7.7.1 IMMEDIATE WARNING
If the Immediate Warning is enabled, the controller generates a warning alarm as soon as the Trip level is reached. The alarm automatically resets once the generator loading current falls below the Trip level (unless All Warnings are latched is enabled). For further advice, consult your generator supplier.
7.7.2 IDMT ALARM
If the IDMT Alarm is enabled, the controller begins following the IDMT ‘curve’ when the trip level is passed.
If the Trip is surpassed for an excess amount of time the IDMT Alarm triggers (Shutdown or Electric trip as selected in Action).
High current shutdown is a latching alarm and stops the Generator. Remove the fault then press Stop/Reset to reset the module.
High current electrical trip is a latching alarm and removes the generator from the load, before stopping the Generator after the off load cooling timer.
Remove the fault then press Stop/Reset to reset the module.
The higher the overload, the faster the trip. The speed of the trip is dependent upon the fixed formula:
T = t / ((IA / I T) – 1)
Where: T is the tripping time in seconds
IA is the actual current of the most highly loaded line (L1 or L2 or L3) IT is the delayed over-current trip point t is the time multiplier setting and also represents the tripping time in seconds at twice full load (when IA / IT = 2).
2
93
Protections
Factory settings for the IDMT Alarm when used on a brushless alternator are as follows (screen capture from the DSE Configuration Suite PC software :
I
(Trip setting value)
T
t
(time multiplier)
These settings provide for normal running of the generator up to 100% full load. If full load is surpassed, the Immediate Warning alarm is triggered, the set continues to run. The effect of an overload on the generator is that the alternator windings begin to overheat; the aim of the IDMT alarm is to prevent the windings being overload (heated) too much. The amount of time that the set can be safely overloaded is governed by how high the overload condition is.
With typical settings as above, the tripping curve is followed as shown below. This allows for overload of the set to the limits of the Typical Brushless Alternator whereby 110%
overload is permitted for 1 hour. If the set load reduces, the controller then follows a cooling curve. This means that a second overload
condition may trip much sooner than the first as the controller knows if the windings have not cooled sufficiently.
For further details on the Thermal damage curve of your alternator, you are referred to your alternator manufacturer and generator supplier.
94
Protections
Slower than Factory setting
(Time Multiplier = 72
Faster than Factory setting
(Time Multiplier = 18
Factory setting
‘Fastest’ trip setting
(Time Multiplier = 1
(Time Multiplier = 36
95
Protections
7.8 EARTH FAULT SHUTDOWN / ELECTRICAL TRIP ALARM
When the module is suitably connected using the ‘Earth Fault CT’. The module measures Earth Fault and can optionally be configured to generate an alarm condition (shutdown or electrical trip) when a specified level is surpassed.
If the Earth Fault alarm is enabled, the controller begins following the IDMT ‘curve’. If the Trip is surpassed for an excess amount of time the Alarm triggers (Shutdown or Electric trip as selected in Action).
The higher the Earth Fault, the faster the trip. The speed of the trip is dependent upon the fixed formula :
T = K x 0.14 / ((I / Is)
Where: T is the tripping time in seconds (accurate to +/- 5% or +/- 50ms (whichever is the greater)
K is the time multiplier setting I is the actual earth current measured
0.02
-1)
IS (Trip setting
Is is the trip setting value
K (time multiplier setting)
The settings shown in the example above are a screen capture of the DSE factory settings, taken from the DSE Configuration Suite software.
96
Protections
7.9 SHORT CIRCUIT ALARM
If the Short Circuit alarm is enabled, the controller begins following the IDMT ‘curve’. If the Trip is surpassed for an excess amount of time the Alarm triggers (Shutdown or Electrical trip as selected in Action).
The higher the Short Circuit, the faster the trip. The speed of the trip is dependent upon the fixed formula :
T = K x 0.14 / ((I / Is)
Where: T is the tripping time in seconds (accurate to +/- 5% or +/- 50ms (whichever is the greater)
K is the time multiplier setting I is the actual current measured Is is the trip setting value
0.02
-1)
IS (Trip setting
K (time multiplier setting)
The settings shown in the example above are a screen capture of the DSE factory settings, taken from the DSE Configuration Suite software.
97
Maintenance Alarm
7.10 MAINTENANCE ALARM
Depending upon module configuration one or more levels of maintenance alarm may occur based upon a configurable schedule.
Example 1 Screen capture from DSE Configuration Suite
Software showing the configuration of Maintenance Alarm 1 and Maintenance Alarm
2. When activated, the maintenance alarm can
be either a warning (set continues to run) or shutdown (running the set is not possible). Resetting the maintenance alarm is normally actioned by the site service engineer after performing the required maintenance. The method of reset is either by:
Activating a input that has been configured to maintenance x reset, where x is the number of the maintenance alarm (1 to 3).
Pressing the maintenance reset button in the DSE Configuration Suite, Maintenance section.
Example 2
Screen capture from DSE Configuration Suite Software showing the configuration of a digital input for Reset Maintenance Alarm 1.
Example 3
Screen capture from DSE Configuration Suite Software showing the Maintenance Alarm Reset ‘button’ in the DSE Configuration Suite SCADA | MAINTENANCE section.
98
Scheduler
8 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and stopping the set. Up to 16 scheduled start/stop sequences can be configured to repeat on a 7-day or 28-day cycle. Scheduled runs may be on load or off load depending upon module configuration.
Example
Screen capture from DSE Configuration Suite Software showing the configuration of the Exercise Scheduler.
In this example the set will start at 09:00 on Monday and run for 5 hours, then start at 13:30 on Tuesday and run for 30 minutes.
8.1.1 STOP MODE
Scheduled runs will not occur when the module is in STOP/RESET mode.
8.1.2 MANUAL MODE
Scheduled runs will not occur when the module is in MANUAL mode.
Activation of a Scheduled Run ‘On Load’ when the module is operating OFF LOAD in Manual
mode will have no effect, the set continues to run OFF LOAD
8.1.3 AUTO MODE
Scheduled runs will operate ONLY if the module is in AUTO mode with no Shutdown or Electrical Trip alarm present.
If the module is in STOP or MANUAL mode when a scheduled run begins, the engine will not be started. However, if the module is moved into AUTO mode during a scheduled
run, the engine will be called to start.
Depending upon configuration by the system designer, an external input can be used to inhibit a scheduled run.
If the engine is running OFF LOAD in AUTO mode and a scheduled run configured to ‘On Load’ begins, the set is placed ON LOAD for the duration of the Schedule.
99
Front Panel Configuration
9 FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customising of the way the module operates. Use the module’s navigation buttons to traverse the menu and make value changes to the parameters:
Previous page
Increase value / next item
Decrease value / next item
100
Loading...