Deep SEA Electronics 7210 User Manual

DEEP S E A E L E C T R O NI C S
TYPICAL WIRING DIAGRAM
7210 INSTALL AT ION IN ST RUCTIONS
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset button.
Press the Stop/Reset and Info buttons simultaneously.
If a module security PIN has been set, the PIN number request is then
shown :
053-026
ISSUE 8
Press , the first ‘#’ changes to ‘0’. Press correct value.
Press (right) when the first digit is correctly entered. The digit you have just entered will now show ‘#’ for security.
Repeat this process for the other digits of the PIN number. You can press move back to adjust one of the previous digits.
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN.
(up) or
(down) to adjust it to the
(left) if you need to
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed :
EDITING A PARAMETER
Enter the editor as described above.
Press the left or right buttons to cycle to the section you wish to view/change.
Press the up or down buttons to select the parameter you wish to view/change within the currently selected section.
To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value.
Press the up or down buttons to change the parameter to the required value.
Press to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor at any time, press and hold the button.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
Email: support@deepseaplc.com
Web: www.deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: dsesales@deepseausa.com
Web: www.deepseausa.com
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: More comprehensive module configuration is possible using the 7xxx series PC configuration software. Please contact us for further details
ADJUSTABLE PARAMETERS
(Configuration editor)
Section Parameter as shown on display
DISPLAY
EDITOR
ENGINE
GENERATOR
Section
Parameter as shown on display
Factory Settings
TIM
ERS
SCHEDULE
Contrast Language LCD Page Timer Auto Scroll Delay Current Date and time Alt Config Oil Pressure Low Shutdown Oil Pressure Low Pre Alarm Coolant Temperature Low Warning Coolant Temperature High Pre Alarm Coolant Temperature High Shutdown Start Delay Off Load Start Delay On Load Start Delay Mains Fail Start Delay Telemetry Pre Heat Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Time Engine Under Speed Shutdown Engine Under Speed Shutdown Engine Under Speed Warning Engine Under Speed Warning Engine Over Speed Warning Engine Over Speed Warning Engine Over Speed Shutdown Engine Speed Overshoot Delay Engine Speed Overshoot Fail To Stop Delay Battery Under Voltage Warning Battery Under voltage Warning Delay Battery Under Voltage Battery Over Voltage Warning Battery Over Voltage Warning Delay Battery Over Voltage Warning Charge Alternator Failure Warning Charge Alternator Failure Warning Charge Alternator Warning Delay Charge Alternator Failure Shutdown Charge Alternator Failure Shutdown Charge Alternator Shutdown Delay DPTC Auto Regeneration Inhibit Fuel Usage Alarm (Running Rate) Fuel Usage Alarm (Stopped Rate) Droop control Droop control Generator Under Voltage Shutdown Generator Under Voltage Pre Alarm Generator Nominal Voltage Generator Over Voltage Pre Alarm Generator Over Voltage Shutdown Generator Under Frequency Shutdown Generator Under Frequency Pre Alarm Generator Nominal Frequency Generator Over Frequency Pre Alarm Generator Over Frequency Shutdown Full Load Rating KW Overload Trip Delayed Over Current Delayed Over Current AC System 3 Phase, 4 Wire CT Primary CT Secondary Generator transient delay
Front Panel Configuration Editor (continued)
Factory Settings
0% English 0h 0m 0s 0h 0m 0s hh:mm Default Config
0.00bar
0.00bar 0ºC (if configured) 0ºC 0ºC 0h 0m 0s 0h 0m 0s 0h 0m 0s 0h 0m 0s 0h 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0h 0m 0s Active / Inactive 0 rpm Active / Inactive 0 rpm Active / Inactive 0 rpm 0 rpm 0m 0s 0% 0m 0s Active / Inactive 0h 0m 0s 0 V Active / Inactive 0h 0m 0s 0 V Active / Inactive 0 V 0h 0m 0s Active / Inactive
0.0 V 0h 0m 0s Active / Inactive 0% - 100% 0% - 100% Active / Inactive 0% 0 V 0 V 0 V 0 V 0 V 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 A (If Configured) 0% Active / Inactive 0%
0 A 0 A 0s
Section Parameter as shown on display Factory Settings
LCD Page Timer Auto Scroll Delay
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
Pre Heat Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Timer Speed Overshoot Delay Fail To Stop Delay Battery voltage Low Warning Delay Battery Voltage High Warning Delay Return Delay Generator Transient Delay Mains Transient Delay Mains Transfer Time Schedule Schedule On Load Schedule Period
Schedule time and Date Selection (1-16)
0h 0m 0s 0h 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0m 0s 0h 0m 0s 0h 0m 0s 0m 0s 0m 0s 0h 0m 0s 0h 0m 0s 0h 0m 0s 0s 0m 0s
0.0s Active / Inactive Active / Inactive (only available when Scheduler is active) Weekly, Monthly, (only available when Scheduler is active
Press to begin editing then up or down when selecting the different parameters in the scheduler.
The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
Press and hold the button to enter the running editor.
EDITING A PARAMETER
Enter the editor as described above.
Press the left or right buttons to cycle to the section you wish to view/change.
Press the up or down buttons to select the parameter you wish to view/change within the currently selected section.
To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value.
Press the up or down buttons to change the parameter to the required value.
Press to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor at any time, press and hold the button.
ADJUSTABLE PARAMETERS (Running editor)
DISPLAY Contrast
ENGINE Droop Droop DPTC Auto Regen Inhibit DPTC Manual Regen
Language Manual Frequency Trim
DIMENSIONS AND MOUNTING
For flat surface mounting in a Type 1 enclosure to meet UL requirements
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT: 220mm x 160mm (8.7” x 6.3”)