TYPICAL WIRING DIAGRAM
DEEP SEA ELECTRONICS
053-013
ISSUE 1
Model 710 Configuration and installation instructions
ACCESSING THE CONFIG EDITOR
Press the Stop/Reset
and Info buttons
simultaneously.
• The LED beside the AUTO button will
flash continuously to indicate that
configuration mode has been entered.
• The first configuration
setting is displayed:
From the configuration table, this example is
displaying Start Delay (parameter 0). It is currently
set to 5 seconds.
EDITING A PARAMETER
• Enter the editor as described above.
• Press + / - to scroll through the parameters to
the one you want to change.
• Press 9 to enter edit
mode. The
will flash on the display
to indicate that edit
mode has been entered.
• Press + / - to change the value to the desired
parameter.
• Press 9 to save the value and exit edit mode for
this parameter.
• The symbol will be removed from the display
to indicate that edit mode has been exited.
• To select another value to edit, press the + / buttons. Continuing to press the + and – buttons
will cycle through the adjustable parameters as
shown in the following lists.
symbol
SETTINGS
Factory default settings are in bold italicised text.
Timers
0 - Start Delay 0-60m (5s)
1 - Preheat 0-60s (0s)
2 - Cranking Time 3-60s (10s)
3 - Crank Rest Time 3-60s (10s)
4 - Safety On Delay 8-60s (8s)
5 - Warm Up Time 0-10m (0s)
6 - Gen transient delay 0-10s (0s)
7 – Return Delay 0-60m (30s)
8 - Cooling Time 0-30m (1m)
9 - ETS Hold Time 0-60s (0s)
10 - Fail To Stop Delay Time 10-60s (60s)
11 - Low DC Voltage Alarm Delay 0-60m (5m)
NOTE:- Setting a timer to 0 will disable it (where applicable)
Generator
12 - Under Frequency 0-60Hz (40Hz)
13 - Loading Frequency 20-60Hz (47Hz)
14 - Over Frequency 50-72Hz (57Hz)
15 - Loading Voltage 50-333V (212V)
16 - Over Current Alarm 50-120% (110%)
17 - Over Current Alarm Type 0 - Warning
1 - Shutdown
2 - Electrical Trip
Engine
18 - Low DC Voltage Alarm 0-25V (8V)
19 - Charge Fail Voltage Alarm 0-25V (8V)
Fixed Input settings
20 - Low Oil Pressure 5-150PSI (15 PSI)
21 - High Engine Temperature
22 - Remote Start input 0 - Remote start
90-150°C
close to activate
1 - Remote start,
open to activate
95°C)
NOTE: To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes you have made by pressing the 9 button first
Deep Sea Electronics Plc.
Highfield House, Hunmanby Industrial Estate,
North Yorkshire. YO14 0PH. ENGLAND
Tel:+44 (0)1723 890099.
Fax: +44 (0)1723 893303.
Email: sales@deepseaplc.com
Web: www.deepseaplc.com
Deep Sea Electronics inc.
3230 Williams Avenue
Rockford, IL 61101-2668. U.S.A.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316-8708
Email: dsesales@deepseausa.com
Web: www.deepseausa.com
DIMENSIONS
MOUNTING
PANEL CUT-OUT
209mm x 146mm (8.23” x 5.75”)
Mounting holes suitable for 4 x 4mm screws
Mounting Hole spacing 196.0mm x 103.5mm (7.717” x 4.075”)
182mm x 137mm (7.17” x 5.39”)
Maximum panel thickness – 8mm (0.3”)
Factory default settings are in bold italicised text.
Auxiliary Input settings
23 - Input 1 0 - Delayed, warning, close to activate
2 - Immediate, warning, close to activate
3 - Immediate, warning, open to activate
4 - Delayed, shutdown, close to activate
5 - Delayed, shutdown, open to activate
6 - Immediate, shutdown, close to activate
7 - Immediate, shutdown, open to activate
8 - Lamp test, close to activate
9 - Lamp test, open to activate
24 - I/P 1 delay 0-10s (0s)
25 - Input 2 0 - Delayed, warning, close to activate
2 - Immediate, warning, close to activate
3 - Immediate, warning, open to activate
4 - Delayed, shutdown, close to activate
5 - Delayed, shutdown. Open to activate
6 - Immediate, shutdown, close to activate
7 - Immediate, shutdown, open to activate
8 - Electrical trip, close to activate
9 - Electrical trip, open to activate
26 - I/P 2 delay 0-10s (0s)
1 - Delayed, warning, open to active
1 - Delayed, warning, open to active
Outputs
27 - Output 1 0 - Unused
2 - Air Flap
3 - Close Generato
4 - Energise to sto
5 - Engine Runnin
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
28 - Output 2 0 - Unused
2 - Air Flap
3 - Close Generato
4 - Energise to sto
5 - Engine Runnin
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
1 - Preheat Mode 0
1 - Preheat Mode 0
Outputs cont’d
29 - Output 3 0 - Unused
1 - Preheat Mode 0
2 - Air Flap
3 - Close Generator
4 - Energise to stop
5 - Engine Running
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
30 - Output 4 0 - Unused
1 - Preheat Mode 0
2 - Air Flap
3 - Close Generator
4 - Energise to stop
5 - Engine Running
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
LCD Indicators
31 - Indicator 1 0 - Unused
1 - Preheat Mode 0
2 - Air Flap
3 - Close Generator
4 - Energise to stop
5 - Engine Running
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
Factory default settings are in bold italicised text.
LCD Indicators cont’d
32 - Indicator 2 0 - Unused
1 - Preheat Mode 0
2 - Air Flap
3 - Close Generator
4 - Energise to stop
5 - Engine Running
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
33 - Indicator 3 0 - Unused
1 - Preheat Mode 0
2 - Air Flap
3 - Close Generator
4 - Energise to stop
5 - Engine Running
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
34 - Indicator 4 0 - Unused
1 - Preheat Mode 0
2 - Air Flap
3 - Close Generator
4 - Energise to stop
5 - Engine Running
6 - Shutdown Alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Preheat mode 1
11 - Preheat mode 2
12 - Preheat mode 3
13 - Warning Alarm
14 - Common Alarm
15 - Fail to start
`
Misc
35 - Full Load Current
Rating
36 - Current
Transformer Primary
37 - Alternator Poles 2,4,6,8 (4)
38 - AC Topology 0 - 3 phase, 4 wire
39 - Oil Pressure
Display Units
40 - Oil pressure
sender type
1 - Digital closed for low oil
2 - Digital open for low oil
3 - VDO 5 bar
4 - VDO 10 bar
5 - Datcon 5 bar
6 - Datcon 10 bar
7 - Datcon 7 bar
8 - Murphy 7 bar
9 - User configured
41 - Coolant
temperature sender
type
2 - Digital open for high
4 - Datcon high
5 - Datcon low
6 - Murphy
7 - Cummins
8 - PT100
9 - User configured
NOTE:- The ‘preheat modes’ selectable for
configurable outputs and LCD indicators perform the
following actions :
• Preheat mode 0 - Preheat during preheat timer,
ceasing at end of preheat timer.
• Preheat mode 1 - Preheat during preheat timer
and continue until engine stops cranking.
• Preheat mode 2 - Preheat during preheat timer
and continue until the safety delay timer has
expired.
• Preheat mode 3 - Preheat during preheat timer
and continue until the warming timer has
expired.
In addition, in all preheat modes, preheat takes place
during the crank rest timer between crank cycles.
5-6000A (500A)
10-6000A (500A)
1 - Single phase, 2 wire
0 - Bar / PSI
1 - Kpa
0 - Not used
pressure
pressure
1 - Digital closed for high
temperature
temperature
3 - VDO 120
°
C