TYPICAL WIRING DIAGRAM
DEEP SEA ELECTRONICS
053-013 ISSUE 1
Model 710 Configuration and installation instructions
ACCESSING THE CONFIG EDITOR
Press the Stop/Reset
and Info buttons
simultaneously.
The LED beside the AUTO button will flash continuously to indicate that configuration mode has been entered.
The first configuration
setting is displayed:
From the configuration table, this example is displaying Start Delay (parameter 0). It is currently set to 5 seconds.
EDITING A PARAMETER
Enter the editor as described above.
Press + / - to scroll through the parameters to
the one you want to change.
Press 9 to enter edit mode. The
will flash on the display to indicate that edit mode has been entered.
Press + / - to change the value to the desired parameter.
Press 9 to save the value and exit edit mode for this parameter.
The symbol will be removed from the display to indicate that edit mode has been exited.
To select another value to edit, press the + / ­buttons. Continuing to press the + and – buttons will cycle through the adjustable parameters as shown in the following lists.
symbol
SETTINGS
Factory default settings are in bold italicised text.
Timers
0 - Start Delay 0-60m (5s) 1 - Preheat 0-60s (0s) 2 - Cranking Time 3-60s (10s) 3 - Crank Rest Time 3-60s (10s) 4 - Safety On Delay 8-60s (8s) 5 - Warm Up Time 0-10m (0s) 6 - Gen transient delay 0-10s (0s) 7 – Return Delay 0-60m (30s) 8 - Cooling Time 0-30m (1m) 9 - ETS Hold Time 0-60s (0s) 10 - Fail To Stop Delay Time 10-60s (60s) 11 - Low DC Voltage Alarm Delay 0-60m (5m)
NOTE:- Setting a timer to 0 will disable it (where applicable)
Generator
12 - Under Frequency 0-60Hz (40Hz) 13 - Loading Frequency 20-60Hz (47Hz) 14 - Over Frequency 50-72Hz (57Hz) 15 - Loading Voltage 50-333V (212V) 16 - Over Current Alarm 50-120% (110%) 17 - Over Current Alarm Type 0 - Warning 1 - Shutdown 2 - Electrical Trip
Engine
18 - Low DC Voltage Alarm 0-25V (8V) 19 - Charge Fail Voltage Alarm 0-25V (8V)
Fixed Input settings
20 - Low Oil Pressure 5-150PSI (15 PSI) 21 - High Engine Temperature 22 - Remote Start input 0 - Remote start
90-150°C
close to activate
1 - Remote start,
open to activate
95°C)
NOTE: To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes you have made by pressing the 9 button first
Deep Sea Electronics Plc.
Highfield House, Hunmanby Industrial Estate,
North Yorkshire. YO14 0PH. ENGLAND
Tel:+44 (0)1723 890099.
Fax: +44 (0)1723 893303.
Email: sales@deepseaplc.com
Web: www.deepseaplc.com
Deep Sea Electronics inc.
3230 Williams Avenue
Rockford, IL 61101-2668. U.S.A.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316-8708
Email: dsesales@deepseausa.com
Web: www.deepseausa.com
DIMENSIONS
MOUNTING
PANEL CUT-OUT
209mm x 146mm (8.23” x 5.75”)
Mounting holes suitable for 4 x 4mm screws Mounting Hole spacing 196.0mm x 103.5mm (7.717” x 4.075”)
182mm x 137mm (7.17” x 5.39”) Maximum panel thickness – 8mm (0.3”)
Factory default settings are in bold italicised text.
r
p
g
r
p
g
Auxiliary Input settings
23 - Input 1 0 - Delayed, warning, close to activate 2 - Immediate, warning, close to activate
3 - Immediate, warning, open to activate 4 - Delayed, shutdown, close to activate 5 - Delayed, shutdown, open to activate 6 - Immediate, shutdown, close to activate 7 - Immediate, shutdown, open to activate 8 - Lamp test, close to activate 9 - Lamp test, open to activate 24 - I/P 1 delay 0-10s (0s) 25 - Input 2 0 - Delayed, warning, close to activate
2 - Immediate, warning, close to activate 3 - Immediate, warning, open to activate 4 - Delayed, shutdown, close to activate 5 - Delayed, shutdown. Open to activate 6 - Immediate, shutdown, close to activate 7 - Immediate, shutdown, open to activate 8 - Electrical trip, close to activate 9 - Electrical trip, open to activate 26 - I/P 2 delay 0-10s (0s)
1 - Delayed, warning, open to active
1 - Delayed, warning, open to active
Outputs
27 - Output 1 0 - Unused 2 - Air Flap
3 - Close Generato 4 - Energise to sto 5 - Engine Runnin 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start 28 - Output 2 0 - Unused
2 - Air Flap 3 - Close Generato 4 - Energise to sto 5 - Engine Runnin 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start
1 - Preheat Mode 0
1 - Preheat Mode 0
Outputs cont’d
29 - Output 3 0 - Unused
1 - Preheat Mode 0 2 - Air Flap 3 - Close Generator 4 - Energise to stop 5 - Engine Running 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start 30 - Output 4 0 - Unused
1 - Preheat Mode 0 2 - Air Flap 3 - Close Generator 4 - Energise to stop 5 - Engine Running 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start
LCD Indicators
31 - Indicator 1 0 - Unused
1 - Preheat Mode 0 2 - Air Flap 3 - Close Generator 4 - Energise to stop 5 - Engine Running 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start
Factory default settings are in bold italicised text.
LCD Indicators cont’d
32 - Indicator 2 0 - Unused
1 - Preheat Mode 0 2 - Air Flap 3 - Close Generator 4 - Energise to stop 5 - Engine Running 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start 33 - Indicator 3 0 - Unused
1 - Preheat Mode 0 2 - Air Flap 3 - Close Generator 4 - Energise to stop 5 - Engine Running 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start 34 - Indicator 4 0 - Unused
1 - Preheat Mode 0 2 - Air Flap 3 - Close Generator 4 - Energise to stop 5 - Engine Running 6 - Shutdown Alarm 7 - System in auto 8 - Auxiliary input 1 active 9 - Auxiliary input 2 active 10 - Preheat mode 1 11 - Preheat mode 2 12 - Preheat mode 3 13 - Warning Alarm 14 - Common Alarm 15 - Fail to start
`
Misc
35 - Full Load Current Rating 36 - Current Transformer Primary 37 - Alternator Poles 2,4,6,8 (4) 38 - AC Topology 0 - 3 phase, 4 wire
39 - Oil Pressure Display Units
40 - Oil pressure sender type 1 - Digital closed for low oil
2 - Digital open for low oil 3 - VDO 5 bar
4 - VDO 10 bar 5 - Datcon 5 bar 6 - Datcon 10 bar 7 - Datcon 7 bar 8 - Murphy 7 bar 9 - User configured 41 - Coolant temperature sender type 2 - Digital open for high
4 - Datcon high 5 - Datcon low 6 - Murphy 7 - Cummins 8 - PT100 9 - User configured
NOTE:- The ‘preheat modes’ selectable for configurable outputs and LCD indicators perform the following actions :
Preheat mode 0 - Preheat during preheat timer,
ceasing at end of preheat timer.
Preheat mode 1 - Preheat during preheat timer
and continue until engine stops cranking.
Preheat mode 2 - Preheat during preheat timer
and continue until the safety delay timer has expired.
Preheat mode 3 - Preheat during preheat timer
and continue until the warming timer has expired.
In addition, in all preheat modes, preheat takes place during the crank rest timer between crank cycles.
5-6000A (500A) 10-6000A (500A)
1 - Single phase, 2 wire
0 - Bar / PSI
1 - Kpa
0 - Not used
pressure pressure
1 - Digital closed for high temperature
temperature 3 - VDO 120
°