DE DIETRICH MCR-P 24 User Manual

Vivadens
Wall-hung gas condensing boilers
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
EN
User Guide
127684-01
Contents
1.1 Symbols used .......................................................4
1.2 Abbreviations ........................................................4
1.3 General ..................................................................5
1.3.1 Manufacturer’s liability .............................................5
1.3.2 Installer’s liability .....................................................5
1.4 Homologations ......................................................5
1.4.1 Certifications ...........................................................5
1.4.2 Gas categories ........................................................6
1.4.3 Additional Directives ................................................6
1.4.4 Factory test .............................................................6
2 Safety instructions and recommendations ..............................................7
2.1 Safety instructions ...............................................7
2.2 Recommendations ................................................7
3 Description ..................................................................................................9
3.1 General description ..............................................9
3.2 Main parts ..............................................................9
3.3 Control panel .......................................................10
4 Operating the appliance ..........................................................................11
4.1 Start the boiler ....................................................11
4.2 Reading out measured values ...........................12
4.3 Changing the settings ........................................13
4.3.1 Changing the heating temperature ........................13
4.3.2 Changing the domestic hot water
temperature ...........................................................14
4.3.3 Modifying the comfort setting (ECO) .....................14
4.3.4 Stopping the central heating or activating the Summer
mode .....................................................................15
4.3.5 Stopping domestic hot water production ...............16
4.3.6 Other settings ........................................................16
1
070513 - 127684-01
Contents
4.4 Installation shutdown .........................................17
4.5 Turning on the antifreeze function ....................18
5 Checking and maintenance .....................................................................19
5.1 General instructions ...........................................19
5.2 Periodic checks ..................................................19
5.3 Filling the system ...............................................20
5.4 Bleeding the heating system .............................21
5.5 Draining the installation .....................................23
6 Troubleshooting .......................................................................................25
6.1 Error codes ..........................................................25
6.1.1 e01 - e02 - e07 - e09 ......................25
6.1.2 e04 ...................................................................25
6.1.3 Other error codes ..................................................25
6.1.4 Before contacting the installer ...............................26
6.2 Incidents and solutions ......................................26
7 Technical specifications ..........................................................................28
7.1 Technical specifications ....................................28
8 Energy savings .........................................................................................30
8.1 Energy savings ...................................................30
8.1.1 Energy-saving advice ............................................30
8.1.2 Room thermostat and settings ..............................30
9 Warranty ....................................................................................................32
9.1 General ................................................................32
9.2 Warranty terms ...................................................32
2
070513 - 127684-01
3
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
1 Introduction
1.1 Symbols used
In these instructions, various danger levels are employed to draw the user’s attention to particular information. In so doing, we wish to safeguard the user’s safety, obviate hazards and guarantee correct operation of the appliance.
1. Introduction
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
1.2 Abbreviations
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the instructions.
4 DHW: Domestic hot water.
4 PPS: Polypropylene hardly inflammable.
4 3CE: Collective conduit for sealed boiler.
4 IRC: Interactive remote control.
4 CRC: Communicating remote controller.
4 Hi: Lower heating value LHV (Nett).
4 Hs: Higher heating value HHV (Gross).
070513 - 127684-01
4
1. Introduction MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
1.3 General
1.3.1. Manufacturer’s liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
1.4 Homologations
1.3.2. Installer’s liability
The installer is responsible for the installation and inital start up of the appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.4.1. Certifications
CE identification no
NOx < 70 mg/kWh
Type of connection Chimney: B
5
PIN 0063BQ3009
23
Flue gas outlet: C13,C33,C43,C53,C63,C83, C
070513 - 127684-01
93
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
1.4.2. Gas categories
Gas category Gas type Connection pressure (mbar) Countries
II
2H3P
I
2H
Natural gas H (G20) 20 All countries except China
Propane (G31) 50 Bulgaria, Romania
37/50 Czech Republic, Spain
30 Finland, Norway, Slovenia
30/37 Greece, Italy
37 Portugal
30/50 Russia
Natural gas H (G20) 20 China
The boiler is preset in the factory to operate on natural gas H (G20).
1.4.3. Additional Directives
Apart from the legal provisions and Directives, the additional Directives described in these instructions must also be observed.
1. Introduction
For all provisions and Directives referred to in these instructions, it is agreed that all addenda or subsequent provisions will apply at the time of installation.
WARNING
Installation of the appliance must be done by a qualified engineer in accordance with prevailing local and national regulations.
1.4.4. Factory test
Before leaving the factory, each boiler is set for optimum performance and tested to check the following items:
4 Electrical safety
4 Adjustment (CO2)
4 Domestic hot water mode (Only on models with domestic hot water
production)
4 Water tightness
4 Gas tightness
4 Parameter settings
070513 - 127684-01
6
2. Safety instructions and recommendations
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
2 Safety instructions and
recommendations
2.1 Safety instructions
DANGER
If you smell gas:
1. Do not use a naked flame, do not smoke, do not operate electrical contacts or switches ( doorbell, light, motor, lift, etc..).
2. Shut off the gas supply.
3. Open the windows.
4. Trace possible leaks and seal them immediately.
5. If the gas leak is before the gas meter, contact the gas supplier.
2.2 Recommendations
DANGER
If you smell flue gases:
1. Switch the appliance off.
2. Open the windows.
3. Trace possible leaks and seal them immediately.
WARNING
4 Installation and maintenance of the boiler must be
carried out by a qualified professional in compliance with prevailing local and national regulations.
4 When working on the boiler, always disconnect the
boiler from the mains and close the main gas inlet valve.
4 After maintenance or repair work, check all
installations to ensure that there are no leaks.
CAUTION
The boiler must be installed in a frost-free environment.
Keep this document close to the place where the boiler is installed.
Casing components
7
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 2. Safety instructions and recommendations
Only remove the casing for maintenance and repair operations. Put the casing back in place after maintenance and repair operations.
Instructions stickers
The instructions and warnings affixed to the appliance must never be removed or covered and must remain legible during the entire lifespan of the appliance. Immediately replace damaged or illegible instructions and warning stickers.
Modifications
Modifications may only be made to the boiler after the written permission of De Dietrich Thermique to do so.
070513 - 127684-01
8
R000232-A
13
15
16
14
12
11
4
2
1
3
5
6
7
8
9
10
3. Description MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
3 Description
3.1 General description
Wall-hung gas condensing boilers
4 MCR-P 24 - Heating only.
4 MCR-P ... MI - Heating and instantaneous domestic hot water
production.
4 Low pollutant emissions.
4 Flue gas discharge via a forced flue, chimney, bi-flow or 3CE type
connection.
The MCR-P 24 boiler can be connected to a 80 or 130 litre tank to produce domestic hot water.
3.2 Main parts
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Automatic air vent
Flue gas discharge pipe / Combustive air
Outlet for measuring combustion gases
Heat exchanger
Air/gaz canal
Fan air inlet
Water pressure sensor
Gas block
Display
Control panel
Pressure gauge
Circulating pump
Ignition transformer
Expansion vessel heating circuit (Except MCR-P 34/39 MI model )
Ignition/ionization electrode
Stand-off frame (optional)
9
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 3. Description
3.3 Control panel
A
B
C
D
E
F
G
H
J
The display indicates the state of the boiler and any errors. The symbols located above the function keys indicate their current function.
Pressing on any key will display the current status of the boiler and the current command code. If there is a fault, the corresponding code continues to be displayed.
Menu key
Display
Main ON/OFF switch
Pressure gauge
Sweep key
( or RESET key
Heating temperature key or -
DHW temperature key or +
SERVICE or U key
070513 - 127684-01
10
A000785-A
A000787-A
4. Operating the appliance MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
4 Operating the appliance
4.1 Start the boiler
1. Check the water pressure in the installation.
2. Open the gas valve.
3. Throw the boiler’s ON / OFF switch.
4. The start-up cycle begins. It lasts 2 minutes and cannot be interrupted. During the start-up cycle, the display shows the following information:
fK[xx pK[xx
The version numbers are displayed alternately.
5. When the start-up cycle is finished, the display shows 0. The
boiler is now operational.
: Software version
: Parameter version
11
070513 - 127684-01
T000138-A
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 4. Operating the appliance
4.2 Reading out measured values
The following values can be displayed in the information menu Q:
4 t1 = Flow temperature (°C) 4 t2 = Return temperature (°C) 4 t3 = Domestic hot water temperature (°C) 4 t4 = Outside temperature (°C)
fl = Ionization current (μA)
4 4 Mf = Fan speed (rpm)
1. Press the f key. The symbol Q flashes.
2. To access the parameters, press key S.
3. Press the [+] key successively to scroll down the various parameters.
4. Press the
key 2 times to return to the current operating mode
>
070513 - 127684-01
12
T000147-A
GA,
HF,
4. Operating the appliance MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
4.3 Changing the settings
4.3.1. Changing the heating temperature
If an outside temperature sensor or an OpenTherm control system is fitted, the heating flow temperature is adjusted automatically.
In summer, it is possible to reduce the heating flow temperature whilst maintaining comfort. To do this, proceed as follows:
1. Press the D key. The symbol D and the current temperature are displayed.
2. Use the [+] and [-] keys to change the parameter value.
3. To confirm the new value, press the key S.
It also possible to modify this setting using the parameter
p1. ¼
See chapter: "Other settings", page 16.
13
070513 - 127684-01
T000143-A
Ajj
2x
T000148-B
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 4. Operating the appliance
4.3.2. Changing the domestic hot water
temperature
1. Press the N key. The symbol N and the current temperature are displayed.
2. Use the [+] and [-] keys to change the parameter value.
3. To confirm the new value, press the key S.
It also possible to modify this setting using the parameter
p2. ¼
See chapter: "Other settings", page 16.
4.3.3. Modifying the comfort setting (ECO)
The user can consult or modify the following 3 settings:
4 ON = Activation of the energy-saving setting.
4 OFF = Activation of the comfort setting.
4 AUTO = Setting dependent on the control unit (Factory setting).
1. Press the f key 1 times. The symbol Q flashes.
2. Press the f key a second time. The symbol ECO flashes.
3. To confirm, press the S key.
4. The current operating status is shown on the display:AUTO.
5. Use the + and - keys to change the parameter value.
6. To confirm, press the S key.
7. Press the mode.
It also possible to modify this setting using the parameter p4. ¼See chapter: "Other settings", page 16.
key 2 times to return to the current operating
>
070513 - 127684-01
14
HF,
Ajj
T000141-A
4. Operating the appliance MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
4.3.4. Stopping the central heating or activating
the Summer mode
1. Press the D key. The symbol D and the current temperature are displayed.
2. Press the key [-] several times until the value
3. To confirm the new value, press the key S. The symbol C appears.
4 It also possible to modify this setting using the
parameter p3. ¼See chapter: Unresolved Cha
internal-destination[ 1834] .
4 Domestic hot water production is maintained.
0ff
is displayed.
15
070513 - 127684-01
GA,
Ajj
T000142-A
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 4. Operating the appliance
4.3.5. Stopping domestic hot water production
1. Press the N key. The symbol N and the current temperature are displayed.
2. Press the key [-] several times until the value
3. To confirm the new value, press the key S. The symbol T appears.
It also possible to modify this setting using the parameter p3. ¼See chapter: Unresolved Cha internal-
destination[ 1834] .
0ff
is displayed.
Parameter
p1
p2
p3
070513 - 127684-01
Description Adjustment range
Flow temperature 20 to 85 °C 75 °C 75 °C 75 °C 75 °C
Domestic hot water temperature
Heating / DHW mode
4.3.6. Other settings
Factory setting
MCR-P 24
40 to 65 °C 55 °C 55 °C 55 °C 55 °C 0 = Heating deactivated (C) / DHW
deactivated (T) 1 = Heating activated (D) / DHW
activated (N) 2 = Heating activated (D) / DHW
deactivated (T) 3 = Heating deactivated (C) / DHW
activated (N)
2 1 1 1
MCR-P 24/28 MI
MCR-P 30/35 MI
MCR-P 34/39 MI
16
2x
3x
T000307-A
4. Operating the appliance
Parameter Description Adjustment range
0 = Comfort mode
p4
p5
p6
ECO mode
Anticipation resistance
Display screen
1 = Energy-saving mode
2 = Management using a programmable thermostat
0 = No anticipation resistance for the ON/OFF thermostat
1 = Anticipation resistance for the ON/ OFF thermostat
0 = The screen stays off
1 = The screen stays on
2 = The screen switches off automatically after 3 minutes
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
Factory setting
MCR-P 24
2 2 2 2
0 0 0 0
2 2 2 2
MCR-P 24/28 MI
MCR-P 30/35 MI
MCR-P 34/39 MI
To change these parameters, proceed as follows:
1. Press key f several times until the symbol W flashes on the menu bar.
2. Press the S key to enter the "User" menu. The symbol
p[1
appears.
3. Use the + and - keys to select to parameter to be changed.
4. Press the S key to display the parameter value selected.
5. Use the + and - keys to change the parameter value.
6. To confirm the new value, press the key S. The name of the modified parameter is displayed.
7. If necessary, set other parameters by selecting them using the + or - keys.
8. To exit the User menu, press the
>
key 2 times.
4.4 Installation shutdown
If no selections are made in the various modes for 10 minutes, the boiler resumes the settings prior to manipulation.
If the central heating system is not used for a long period, we recommend switching the boiler off.
1. Switch the boiler off.
2. Switch off the boiler electrical power supply.
3. Close the gas valve.
4. Ensure that the boiler and system are protected against frost damage.
17
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 4. Operating the appliance
4.5 Turning on the antifreeze function
We recommend setting the boiler thermostat to a value off 10°C if using a classic installation.
Define parameter p4 as 1 (energy-saving mode), the heat retention function will be deactivated.
Installation and room antifreeze protection is guaranteed if you are absent.
If the temperature of the central heating water in the boiler falls too much, the integrated protection device switches itself on:
4 If the water temperature is lower than 7°C, the circulating pump is
activated.
4 If the water temperature is lower than 3°C, the boiler is activated.
4 When the water temperature is above 10 °C, the boiler is switched
off and the circulation pump runs for another 15 minutes.
CAUTION
This function is a protection device for the boiler only, not for the system or buiding fabric.
CAUTION
If a room thermostat, connected via connectors 7 and 8, is activated, the boiler will operate permanently until it reaches the flow setting point.
070513 - 127684-01
18
1
2
3
4
T000181-B
5. Checking and maintenance MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
5 Checking and maintenance
5.1 General instructions
CAUTION
4 An annual inspection is compulsory.
4 We recommend taking out a maintenance contract.
4 Maintenance operations must be done by a qualified
engineer.
4 Only original spare parts must be used.
4 Make certain that the flues and chimneys are
connected, in good condition and not blocked.
4 Do not modify nor block the condensate outlet(s).
4 If a neutralisation system is installed, follow the
instructions delivered with the neutralisation system for cleaning and servicing of this system.
5.2 Periodic checks
4 Check the water pressure in the installation. If the water pressure
is too low, add more water to the installation. ¼See chapter: "Filling the system", page 20.
4 Carry out a visual check for the presence of any water leaks.
4 Open and close the radiator valves several times a year (this
prevents the valves from seizing up).
19
070513 - 127684-01
1
2
3
4
T000181-B
T000182-A
T000155-A
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
4 Clean the outside of the boiler using a damp cloth and a light
detergent.
5. Checking and maintenance
CAUTION
Only a qualified professional is authorised to clean the inside of the boiler.
5.3 Filling the system
The water pressure in the boiler must be between 1,5 and 2 bar. Add water to the installation if necessary. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
2. Set the room thermostat to as low a temperature as possible.
070513 - 127684-01
3. Switch off the boiler electrical power supply.
20
T000185-A
T000847-A
1
2
3
4
T000181-B
T000183-A
T000184-A
5. Checking and maintenance
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
4. Wait until the temperature drops below 40°C and the radiators seem cold before filling the central heating system.
5. Open the valve.
6. Close the valve.
7. After filling the installation, switch the boiler on.
8. Set the room thermostat or the regulator.
9. Set the radiator valves.
CAUTION
Filling and bleeding the installation 2 times a year should be sufficient to obtain an adequate hydraulic pressure. If it is often necessary to top up the installation with water, contact your fitter.
5.4 Bleeding the heating system
It is essential that you bleed any air in the calorifier, the conduits or the taps to prevent the annoying noises likely to be produced during heating or when tapping water. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
2. Set the room thermostat as high as possible.
21
3. Wait until the radiators are hot.
070513 - 127684-01
T000155-A
T000185-A
T000216-A
3
1
4
5
2
T000217-A
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 5. Checking and maintenance
4. Switch the boiler off.
5. Wait around 10 minutes until the radiators are cold.
6. Bleed the radiators. Start with the lower floors.
7. Open the bleed connection using the bleed key provided whilst keeping a rag pressed against the connection.
070513 - 127684-01
22
T000218-A
T000228-A
1,5 ... 2 bar
T000183-A
1
2
3
4
T000181-B
5. Checking and maintenance
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
8. Wait until water comes out of the bleed valve and then close the bleed connection.
CAUTION
The water may still be hot.
9. After venting, check whether the pressure in the installation is still sufficient. Add water to the installation if necessary.
10.Switch on the boiler. A vent cycle of a duration of around 3 minutes is carried out automatically.
5.5 Draining the installation
11.Set the room thermostat or the regulator.
It may become necessary to empty the water from the heating system when the radiators have to be replaced, should there be a major water leak or a risk of frost. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
23
2. Switch off the boiler electrical power supply.
070513 - 127684-01
T000185-A
T000858-A
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 5. Checking and maintenance
3. Wait around 10 minutes until the radiators are cold.
4. Connect an evacuation hose to the plug located at the lowest level. Place the end of the hose in a discharge sump or in a place where the water discharged from the valve can not do any damage.
5. Open the filling/draw-off valve on the heating system. Vent the heating installation.
WARNING
The water may still be hot.
6. When no more water comes out of the drainage plug, close the drainage valve.
070513 - 127684-01
24
6. Troubleshooting
6 Troubleshooting
6.1 Error codes
6.1.1. e01 - e02 - e07 - e09
If one of the breakdown codes opposite is dispayed, check the hydraulic pressure:
Case 1: Pressure higher than or equal to 1 bar
4 Press the RESET key to reset the appliance. Wait a few seconds.
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
- If the display shows 0, the boiler is again operating normally.
- If the display again shows e1, e2 or e7, contact the
installer.
Case 2: Pressure lower than 1 bar
4 Top up the installation with water. ¼See chapter: "Filling the
system", page 20.
4 Press the RESET key to reset the appliance. Wait a few seconds.
- If the display shows 0, the boiler is again operating normally.
- If the display again shows e1, e2, e7 or e9, contact the
installer.
6.1.2.
If the breakdown code opposite is shown:
4 Check the position of the gas valve. Open the gas valve if it is
closed.
4 Press the RESET key to reset the appliance. Wait a few seconds.
- If the display shows 0, the boiler is again operating normally.
- If the display again shows e4, contact the installer.
e04
6.1.3. Other error codes
25
If another error code is displayed, contact the installer.
070513 - 127684-01
C000655-B
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 6. Troubleshooting
6.1.4. Before contacting the installer
Before contacting the installer
Note the following information on the appliance’s rating plate:
4 Type of gas used
4 Boiler type
4 Manufacturing date
4 Serial no. of the appliance
6.2 Incidents and solutions
Problem
There is no domestic hot water.
The radiators are cold.
Probable causes Solution
4 Check that the boiler is switched on.
The boiler is not switched on.
The DHW mode is deactivated.
4 Check the fuses and switches.
4 Check that the gas valve is fully opened.
Activate the DHW mode.
¼See chapter: "Stopping domestic hot water production", page 16.
The water pressure is too low (< 1 bar).
The energy-saving shower head is restricting the water flow.
The heating temperature setting is too low.
Top up the installation with water. ¼See chapter:
"Filling the system", page 20.
Clean the shower head; replace if necessary.
Increase the value of parameter p1 or, if a room thermostat is connected, increase the temperature.
¼See chapter: "Changing the heating temperature", page 13.
Activate the heating mode.
The heating mode is deactivated.
¼See chapter: "Stopping the central heating or activating the Summer mode", page 15.
The radiator valves are closed. Open the valves on all radiators connected to the heating
system.
4 Check that the boiler is switched on.
The boiler is not switched on.
The water pressure is too low (< 1 bar).
4 Check the fuses and switches.
4 Check that the gas valve is fully opened.
Top up the installation with water. ¼See chapter:
"Filling the system", page 20.
070513 - 127684-01
26
6. Troubleshooting MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
Problem Probable causes Solution
The heating temperature setting is too low.
Increase the value of parameter p1 or, if a room thermostat is connected, increase the temperature.
¼See chapter: "Changing the heating temperature", page 13.
4 Check that the boiler is switched on.
The boiler is not switched on.
The boiler is not working.
The water pressure is too low (< 1 bar).
An error code appears on the display.
4 Check the fuses and switches.
4 Check that the gas valve is fully opened.
Top up the installation with water. ¼See chapter:
"Filling the system", page 20.
4 Press the Reset button for 2 seconds. 4 Correct the error if possible. ¼See chapter:
"Error codes", page 25.
The gas pressure is too low. Open the gas valve.
The water pressure is too low (< 1 bar).
Significant variations in domestic hot water temperature.
Clicking in the central heating pipes
Significant water leak under or close to the boiler
Not enough water in the installation.
Water leak. Contact the fitter.
Insufficient water supply. Open the valve.
The central heating pipe connections are too tight.
There is air in the heating pipes. It is essential that you bleed any air in the calorifier, the
The water is circulating too quickly in the central heating system.
The boiler or central heating pipes are damaged.
Top up the installation with water. ¼See chapter:
"Filling the system", page 20.
Contact the fitter.
conduits or the taps to prevent the annoying noises likely to be produced during heating or when tapping water.
Contact the fitter.
Close the water supply. Contact the fitter.
27
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI 7. Technical specifications
7 Technical specifications
7.1 Technical specifications
Boiler type MCR-P 24 MCR-P
24/28 MI
Heating mode Nominal useful output 40/30
(min / max)
Nominal useful output 80/60 (min / max)
Nominal input power kW 24 24/28 30/35 34/39
Minimum input power kW 5.8 5.8 6.1 6.3
Domestic hot water mode Nominal useful output kW - 27.4 34.3 38.2
Nominal input power kW 24 24/28 30/35 34/39
Minimum input power kW 5.8 5.8 6.1 6.3
Gas flow rate at nominal output (15 °C ­1013 mbar)
LHV efficiency 100% of nominal output and
HHV efficiency 100% of nominal output and
Maximum temperature (Safety thermostat cut-off) °C 110 110 110 110
Casing losses W 57 57 57 57
Water content litres 1.7 1.8 2 2.2
Weight empty, without mounting frame, without front cover kg 29 30.5 32 31.5
Heating circuit
Nominal water flow (ΔT = 20 K)
Manometric height (ΔT = 20 K)
Flow temperature °C 75/85 75/85 75 75
Maximum pressure bar 3 3 3 3
Expansion vessel litres 8 8 8 -
Initial pressure of the expansion vessel bar 1 1 1 1
Minimum operating pressure bar 0.8 0.8 0.8 0.8
Domestic hot water circuit
Instruction set outlet temperature °C 55 55 55 55
Specific hot water flow (ΔT = 30 K)
(1) 1 mbar = 100 Pa, 1 daPa = 1 mmWG (2) Cold water inlet temperature: 10 °C
Natural gas H (G20)
Propane (G31) Kg/h 1.9 1.9 2.7 3.0
average water temperature in the boiler of 70°C
100% of nominal output and return temperature of 30°C
30% of nominal output and return temperature of 30°C
average water temperature in the boiler of 70°C
100% of nominal output and return temperature of 30°C
30% of nominal output and return temperature of 30°C
(2)
kW 6.3 /25 6.3 /25 6.6 /31.3 6.8 /35.5
kW 5.5 / 23.6 5.5 / 23.6 5.7 / 29.5 5.9 / 33.3
m3/h
% 98.3 98.3 98.2 98
% 104.4 104.4 104.4 104.4
% 108.7 108.7 109.7 110.5
% 88.5 88.5 88.4 88.2
% 94 94 94 94
% 97.9 97.9 98.8 99.5
m3/h
(1)
mbar
litres per min.
2.4 2.4 3.5 3.9
1.03 1.03 1.29 1.47
> 250 > 250 > 200 > 200
- 14 16 19
MCR-P 30/35 MI
MCR-P 34/39 MI
070513 - 127684-01
28
7. Technical specifications MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
Boiler type MCR-P 24 MCR-P
24/28 MI
Nominal max cold water pressure
Minimum pressure for 11 l/min
(2)
(2)
bar 8 8 8 8
bar - 1.4 0.4 0.4
MCR-P 30/35 MI
MCR-P 34/39 MI
Water capacity litres - 0.5 0.5 0.5
Combustion products circuit
Connection diameter mm 80/125 80/125 80/125 80/125
Mass flue gas flow rate (min / max) Kg/h 10/37 10/47 10/59 10/66
Flue gas temperature 80/60 °C 78 78 74 71.5
Pa
(1)
50 100 100 140
1 - 7 1 - 7 1 - 7 1 - 7
Pressure available at the flue gas nozzle
Condensation water pH 50/30
Electricity characteristics
Power supply voltage (50 Hz) V 230 230 230 230
Power consumption W 115 115 150 180
Electrical power circulating pump W 90 90 125 135
Auxiliary electrical power (nominal output, ex heating
W 25 25 25 25
pump)
Electrical protection index
(1) 1 mbar = 100 Pa, 1 daPa = 1 mmWG (2) Cold water inlet temperature: 10 °C
IPX4D IPX4D IPX4D IPX4D
29
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
8 Energy savings
8.1 Energy savings
This chapter contains:
4 Energy-saving advice
4 Advice on setting the room thermostat correctly
8.1.1. Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated. Do
not block ventilation outlets. Install reflective panels behind the radiators to prevent heat losses.
4 Do not cover the radiators. Do not hang curtains in front of the
radiators.
4 Insulate the pipes in rooms that are not heated (cellars and lofts).
4 Close the radiators in rooms not in use.
4 Do not run hot (or cold) water pointlessly.
4 Install a water-saving shower head to save up to 40 % energy.
4 Take showers rather than baths. A bath consumes twice as much
water and energy.
8. Energy savings
8.1.2. Room thermostat and settings
The room thermostat is available in the following versions:
4 2-wire ON/OFF thermostat
4 Modulating thermostat
4 Programmable room temperature thermostat
The type of thermostat and its settings have a considerable influence on energy consumption.
A few tips:
4 A modulating thermostat, possibly in combination with
thermostatic valve radiators, saves energy and offers considerable comfort. This combination allows you to set the temperature on each flow.
4 Completely closing and opening thermostatic valve radiators
causes undesirable temperature fluctuations. Open and close thermostatic valves in small steps.
4 Lower the thermostat to around 20°C. This reduces heating costs
and energy consumption.
4 Lower the room thermostat when you air the rooms.
070513 - 127684-01
30
8. Energy savings MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
4 If you are using an ON/OFF type thermostat, reduce the water
temperature value (p1) in summer (e.g. 60 in summer and 80 in winter).
4 When setting an hourly programmable thermostat, keep in mind
the days you are absent or on vacation.
31
070513 - 127684-01
MCR-P 24 MCR-P 24/28 MI MCR-P 30/35 MI MCR-P 34/39 MI
9 Warranty
9.1 General
You have just purchased one of our appliances and we thank you for the trust you have placed in our products.
Please note that your appliance will provide good service for a longer period of time if it is regularly checked and maintained.
Your fitter and our customer support network are at your disposal at all times.
9.2 Warranty terms
The following provisions are not exclusive of the buyer being able benefit from the legal provisions applicable regarding hidden defects in the buyer’s country.
9. Warranty
Starting from the purchase date shown on the original fitter’s invoice, your appliance has a contractual guarantee against any manufacturing defect.
The length of the guarantee is mentioned in the price catalogue. The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified engineer).
In particular, the manufacturer shall not be held responsible for any damage, loss or injury caused by installations which do not comply with the following:
4 applicable local laws and regulations,
4 specific requirements relating to the installation, such as national
and/or local regulations,
4 the manufacturer’s instructions, in particular those relating to the
regular maintenance of the unit,
4 the rules of the profession.
The warranty is limited to the exchange or repair of such parts as have been recognised to be faulty by our technical department and does not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts damaged by normal wear and tear, negligence, repairs by unqualified parties, faulty or insufficient monitoring and maintenance, faulty power supply or the use of unsuitable fuel.
070513 - 127684-01
Sub-assemblies such as motors, pumps, electric valves etc. are guaranteed only if they have never been dismantled.
The legislation laid down by european directive 99/44/EEC, transposed by legislative decree No. 24 of 2 February 2002 published in O.J. No. 57 of 8 March 2002, continues to apply.
32
AD001-AH
DUEDI S.r.l.
DE DIETRICH SERVICE
BDR Thermea (Czech republic) s.r.o
www.duediclima.it
www.dedietrich.cz
Distributore Ufficiale Esclusivo
De Dietrich-Thermique Italia
www.dedietrich-heiztechnik.com
Freecall 0800 / 201608
Jeseniova 2770/56
130 00 Praha 3
+49 (0)25 72 / 9161-0
+49 (0)25 72 / 9161-102
info@remeha.de
Via Passatore, 12 - 12010 San Defendente di Cervasca CUNEO
+39 0171 857170 +39 0171 687875 info@duediclima.it
+420 271 001 627 info@dedietrich.cz
IT
DE DIETRICH THERMIQUE S.A.S
DE DIETRICH THERMIQUE Iberia S.L.U.
www.dedietrich-calefaccion.es
Av. Princep d’Astúries 43-45
08012 BARCELONA
+34 932 920 520 +34 932 184 709
ES
129164, Россия, г. Москва
Зубарев переулок, д. 15/1
Бизнес-центр «Чайка Плаза»,
офис 309
+7 (495) 221-31-51
CZ
127684- 001-01
DEDIETRICH THERMIQUE 57,ruedelaGareF-67580MERTZWILLER-BP 30
© Copyright All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing.
070513
Loading...