DE DIETRICH GTU C 330 User Manual

Oil-fired condensing boiler
GTU C 330
EN
C001933-C
User Guide
300017846-001-B
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1 Symbols and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.2 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2 Safety instructions and recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.2 Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3.2 Boiler and Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.3 Description of the S3 control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.4 Description of the B3 control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.5 Description of the K3 control panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4 Changing the settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5 Start the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6 Arrêter le chauffage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.1 Stopping the central heating or activating the Summer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.2 Prolonged absence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
7 Checking and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7.1 Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7.2 Hydraulic pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7.3 Draining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
8.1 Rating plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
8.2 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
8.3 Incidents and solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
9 Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
10 Energy savings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
2
GTU C 330 24/11/08 - 300017846-001-B

1Introduction

1.1 Symbols and abbreviations

1. Introduction
In these instructions, various markings and pictograms are used to draw your attention to particular information. In so doing, De Dietrich Thermique wishes to safeguard the user's safety, obviate hazards and guarantee correct operation of the boiler.
Danger
Risk of a dangerous situation causing serious physical injury.
Warning
Risk of a dangerous situation causing slight physical injury.

1.2 General

1.2.1 Manufacturer's liability

De Dietrich Thermique S.A.S manufactures products in compliance
with the standard 1. Products are delivered with 1 marking and all documents required.
In the interest of customers, De Dietrich Thermique S.A.S are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Caution
Risk of material damage.
Specific information.
Reference
Z
Refer to another manual or other pages in this instruction manual.
` DHW: Domestic hot water.
The liability of De Dietrich Thermique S.A.S as the manufacturer may not be invoked in the following cases:
` Incorrect use of the appliance.
` Faulty or insufficient maintenance of the appliance.
` Incorrect installation of the appliance.

1.2.2 Installer's liability

The installer is responsible for the installation and inital start up of the appliance. The installer must respect the following instructions:
` Read and follow the instructions given in the manuals provided
with the appliance.
` Carry out installation in compliance with the prevailing
legislation and standards.

1.2.3 User's liability

To guarantee optimum operation of the appliance, the user must respect the following instructions:
` Read and abide by the instructions given in the user manual.
` Call on qualified professionals to carry out installation and initial
start up.
` Get your fitter to explain your installation to you.
` Have the required checks and services done.
` Keep the instruction manuals in good condition close to the
appliance.
` Perform the initial start up and carry out any checks necessary.
` Explain the installation to the user.
` Warn the user of the obligation to check the appliance and
maintain it in good working order.
` Give all the instruction manuals to the user.
24/11/08 - 300017846-001-B GTU C 330
3
2. Safety instructions and recommendations

2 Safety instructions and recommendations

2.1 Safety instructions

For a proper operating of the boiler, follow carefully the
instructions.
Only qualified professionals are authorised to work on the
appliance and the instalation.
Incorrect use or unauthorised modifications to the
installation or the equipment itself invalidate any right to claim.
The condensates in oil-fired condensing boilers are acidic
(2 < pH < 3): The installation of a condensates neutralisation system is recommended.
Before any work, switch off the mains supply to the
appliance.
Keep to the polarity shown on the terminals: phase (L),
neutral (N) and earth
Keep children away from the boiler.
Fire hazard
It is forbidden to store inflammable products and materials
in the boiler room or close to the boiler, even temporarily.
4
.
Risk of intoxication
Do not obstruct the air inlets in the room (even partially).
If you smell flue gases
1.Switch the appliance off
2.Open the windows
3.Evacuate the premises
4.Contact a qualified professional
Risk of being burnt
Depending on the settings of the appliance:
- The temperature of the flue gas conduits may exceed 65°C
- The temperature of the radiators may reach 95°C
- The temperature of the domestic hot water may reach 65°C
Risk of damage
Do not stock chloride or fluoride compounds close to the
appliance.
.Install the appliance in premises sheltered from rain, snow
and frost.
Do not neglect to service the appliance: Contact a qualified
professional or take out a maintenance contract for the annual servicing of the appliance.

2.2 Recommendations

Check regularly that the installation contains water and is pressurised.
Keep the appliance accessible at all times.
Avoid draining the installation.
Use only original spare parts.
Never remove or cover labels and rating plates affixed to the appliance.
Boiler with DIEMATIC-m3 control panel: The appliance should be on Summer or Antrifreeze mode rather than switched off to guarantee the following functions:
- Cleaning the pumps
- Antifreeze protection
- Protection against corrosion on domestic hot water tanks fitted
with a titanium anode
4
GTU C 330 24/11/08 - 300017846-001-B

3 Description

3.1 General description

3. Description
GTU C 330 boilers are intended for central heating using radiators or underfloor heating. These boilers have the following characteristics:
- Hot water condensing boilers,
- Heating body in cast iron,
- Condenser
- Pressurised boiler,
- Atomisation burner using domestic fuel oil
- Connecting to a chimney
- S3, B3, K3 or DIEMATIC-m3 control panel (See below)
Control panel S3
l
TEST
0
STB
10A
Control panel K3
- Production of domestic hot water can be ensured by a separate hot water calorifier.
The boiler, condenser and burner enable the use of all types of
oil :
- Standard fuel oil
- Oil with low sulphur content.
30
C001967
Control panel DIEMATIC-m3
Control panel B3
24/11/08 - 300017846-001-B GTU C 330
5
3. Description

3.2 Boiler and Condenser

2
5
6
7
8
6
10
5
3
4
11
C001936-B
4
3
1
2
7
9
8
Burner
1
Control panel
2
Heating flow pipe
3
Boiler flue gas system / condenser connection pipe
4
Condenser
5
Condenser safety control box. The box comprises ;
6
- 80°C limiter thermostat
- Safety thermostat with manual reset, set to 120 °C. This thermostat monitors the temperature of the combustion products.
10
11
C001937-B
Boiler / condenser hydraulic connecting kit
7
Adjustable feet
8
Condensates evacuation pipe
9
Heating return pipe
10
Recycling kit (Option)
11
1
6
GTU C 330 24/11/08 - 300017846-001-B

3.3 Description of the S3 control panel

3. Description
76 1234
TEST STB
10A
1. General ON (1) / OFF (0) switch
2. Switch Test-STB
Temporary action to test the safety thermostat
3. Boiler thermostats (30 to 90 °C)
The boiler thermostat regulates the boiler operating temperature.
4. Boiler thermometer
5. Location for flue gas thermometer (optional)
6. Timed circuit breaker (10 A) with delayed action and manual reset
7. Safety thermostat with manual reset
(set to 110 °C)
The safety thermostat with manual reset ensures that the boiler operates safely.
In the event that there is an abnormal rise in the
temperature in the boiler 110° C. Advise your installation engineer.
l
0
5
30
M000484
24/11/08 - 300017846-001-B GTU C 330
7
3. Description

3.4 Description of the B3 control panel

1. General ON (1) / OFF (0) switch
2. Alarm indicator
This indicator lights up when the burner is on safety (faulty).
3. Switch TEST-STB/
Position .: DHW + Heating
Position
Position TEST-STB: Temporary action to test the safety thermostat
4. Safety thermostat with manual reset
Set at 110° C
5. Timed circuit breaker (10 A) with delayed action and manual reset
6. Pump shutdown switch
7. Electronic thermostat
Set the boiler temperature between 30° C and 90° C using manual setting.
8. Indicator lights up
Boiler temperature display
%
./%
: DHW
When preparing domestic hot water
11. Electronic thermostat
Regulating the storage temperature of domestic hot water between 10° C and 80° C.
12. Indicator lights up
Domestic hot water display
After switching on, the system performs an automatic purge of
the accumulator interchanger for one minute by intermittently operating the domestic load pump and the heating pump. This purge sequence is deactivated if the temperature in the accumulator is above 25º C.
13. Location for hour run meter (Option)
9. Location for flue gas thermometer (optional)
10. Switch for selecting the number of burner stages
8
GTU C 330 24/11/08 - 300017846-001-B

3.5 Description of the K3 control panel

1. General ON (1) / OFF (0) switch
2. Burner alarm indicator
This indicator lights up when the burner is on safety (faulty).
3. Description
3. Switch AUTO/
Position AUTO: This position enables automatic operation of the installation in accordance with DIEMATIC-m 3 regulation controls.
Position
DIEMATIC-m 3 regulation into account. The boiler is regulated by the boiler thermostat(s).
Position TEST-STB: Temporary action to test the safety thermostat
4. Safety thermostat with manual reset
Set at 110° C
5. Timed circuit breaker (10 A) with delayed action and manual reset
6. Pump shutdown switch
7. Boiler thermostat (30 to 90 °C)
A factory-set stop limits the maximum temperature to 75 °C. The stop may be moved if necessary.
Z
8. Boiler thermometer. Boiler temperature display.
!
See "Moving the thermostat stop".
/TEST-STB
!
: The boiler no longer takes orders from the
9. Switch for selecting the number of burner stages
10. Connector for the programming tool
24/11/08 - 300017846-001-B GTU C 330
9
3. Description

3.6 Description of the DIEMATIC-m3 control panel

Electromechanical components
1. General ON (1) / OFF (0) switch
2. Burner alarm indicator
This indicator lights up when the burner is on safety (faulty).
3. Switch AUTO/
Position AUTO: Automatic control Position
Position TEST-STB: Temporary action to test the safety thermostat
4. Safety thermostat with manual reset
Set at 110° C
5. Timed circuit breaker (10 A) with delayed action and manual reset
6. Pump shutdown switch
7. Boiler thermostat (30 to 90 °C)
A factory-set stop limits the maximum temperature to 75 °C. The stop may be moved if necessary.
Z
8. Boiler thermometer. Boiler temperature display.
!
See "Moving the thermostat stop".
/TEST-STB
!
: Manual control
The panel must always be supplied with 230V voltage:
- to ensure the anti-grip of the heating pump,
- to ensure Titan Active System® operation when a titanium anode is protecting the DHW tank.
Use the mode:
- "summer" to shut down the heating.
- "antifreeze" to shut down the boiler if you are to be absent.
Furthermore, if an interactive remote control (CDI 2) is connected and the 1 switch is in the off the CDI 2.
position, there will be no display on
7
9. Switch for selecting the number of burner stages
10. Connector for the programming tool
14. "Boiler" heat curve
15.
DIEMATIC-m3 regulator
16. Display
10
GTU C 330 24/11/08 - 300017846-001-B
Display
1 Text and numerical display
2 Graphic display bar for the programme in circuit A, B or C
3 Light area: Reduced temperature heating period or tank load disabled
4 Dark area: Comfort temperature heating period or tank load enabled
5 Flashing cursor showing the current time
6 Number display (current time, adjusted values, parameters, etc.)
7 Number of the boiler for which the parameters are displayed
8 The arrows flash when setting values can be modified using the + and - keys
9 Circuit operation symbols
3 4 5 6 7
2
024681012141618202224
1
SUNDAY
bar
3. Description
8
A
BC
91011
>
=
:
A B C Name of the circuit displayed
10
11 Symbols indicating that the following inputs/outputs are active
 #
D
Opening the 3-way valve
Closing the 3-way valve
Displayed circuit pump on
Arrows indicating the chosen time programme (P1, P2, P3 or P4) for the circuit displayed, A, B, C, or the activation of the manual summer mode
DHW load pump on
Summer mode (Automatic or Manual)
Burner on
D Burner on with 1 stage
Burner on with 2 stages
Y
24/11/08 - 300017846-001-B GTU C 330
11
3. Description
DIEMATIC-m3 regulator
Keys accessible when the flap is closed
Adjustment keys
MODE Various operating modes can be selected by successively
pressing key MODE:
` AUTOMATIQUE ` DAY 7/7: Forced operation at permanent Day temperature ` DAY (Until midnight): Forced operation at temporary Day
temperature
` NIGHT 7/7: Forced operation at permanent Night
temperature
` NIGHT (Until midnight): Forced operation at temporary
Night temperature
` DAYS ANTIFREEZ: Antifreeze mode for the number of
days set
` ANTIFREEZ 7/7: Permanent antifreeze mode
Restart key for a DHW calorifier load
` AUTOMATIQUE ` DHW: Restarts DHW load until midnight ` DHW 7/7: DHW load is forced permanently
After a few seconds, the display disappears but the mode is
activated.
Display key for the various counters (number of burner start-ups,
+
number of burner operating hours, etc.)
Adjustment keys
%O
$P
STANDARD
S J I
*
#
K
M
Enter (per 1/2 hour) the comfort temperature period or tank load enabled (dark area).
Enter (per 1/2 hour) the reduced temperature period or tank load disabled (light area).
Simultaneously pressing the 2 keys,
, resets all of the time programmes.
$P
Return key
Page scrolling
Line scrolling
Scroll of boilers connected
Manual "Summer" shutdown key. The heating is switched off and DHW production is ensured.
Fitter settings access key
DO NOT USE
%O
and
Set temperatures Day (Heating / DHW / Pool)
2%
Set temperatures Night (Heating / DHW)
2$
Access key to the slave boilers (Panel K3) in a cascade
*
(
)
+/-
Keys accessible when the flap is open
If using only one boiler, this key is inactive.
Setting the gradients for circuits A, B and C
Setting the parallel offsets DECAL.// DEP.A, DECAL.// DEP.B or DECAL.// DEP.C for the heating curves on circuits A, B or C. If the Day setting for one of the circuits, A, B or C, is above 30°C, you no longer have access parallel offset on this circuit.
Adjustment keys
12
GTU C 330 24/11/08 - 300017846-001-B

4 Changing the settings

To change the temperature of the heating water or to change the programming:
` Refer to the connection instructions supplied with the control
panel.
` Refer to the description of the installation
4. Changing the settings
24/11/08 - 300017846-001-B GTU C 330
13
5. Start the boiler

5 Start the boiler

` Fill the siphon with water,
` Check the water pressure in the installation.
pressure must be a minimum of 0.8 bars
. Adjust the pressure if
The hydraulic
necessary, avoiding a sudden influx of cold water into the boiler when it is hot.
` Switch on the appliance
` Open the valves on the heating circuit
` Open the fuel supply
` Provoke a heating request: see below (depending on the type
of control panel)
Control panel S3
`Set the boiler thermostats 3 to the desired position. The 2nd
stage thermostat must be set to a value at least 5°C lower than the 1st stage thermostat.
Control panel B3
- Place the boiler thermostat 7 in the required position.
- When preparing domestic hot water, Place thermostat 11 on the required setting. Setting 6 (approx 60° C) recommended.
This value must always be below the temperature limiter for the domestic hot water load.
- Set the On/Off switch to 1.
0
l
t
TEST
Control panel K3
STB
05C0196
Place the boiler thermostat 7 in the required position. The boiler is managed by the boiler fitted with the DIEMATIC-m3 control panel.
Control panel DIEMATIC-m3
` Set switch 3 to the AUTO position.
` Check that safety thermostat 4 is properly set. To do so,
unscrew the hexagonal cap and press the reset button with a screwdriver.
` Set main On/Off switch 1 to
8
.
If there is no control unit, we advise you never to set the
boiler thermostat below mark 4 (approx. 40°C) in order to avoid the risk of combustion products condensing on the walls of the boiler.
` Control unit in boiler room electrical cabinet:
- See the instructions supplied with the control unit and any remote control unit used.
` Set the On/Off switch to 1.
0
l
t
TEST
STB
05C 0196
` The boiler starts to operate.
0
l
t
TEST
STB
When the boiler is switched on, the tank exchanger is purged
for one minute if a tank is connected and its temperature is
05C 0196
lower than 25°C. If disgassing has already taken place, press the MODE key to suspend disgassing.
See:
Z
- Control panel instructions
- Burner instructions
- Domestic hot water calorifier instructions
14
GTU C 330 24/11/08 - 300017846-001-B

6 Switching off the central heating

l
0
t
TEST
STB
05C0196

6.1 Stopping the central heating or activating the Summer mode

6. Switching off the central heating
Control panels DIEMATIC-m3 and K3:
The panel must always be supplied with 230V voltage:
- to ensure the anti-grip of the heating pump,
- to ensure Titan Active System® operation when a titanium anode is protecting the DHW tank.
Use the mode:
- "summer" to shut down the heating.
- "antifreeze" to shut down the boiler if you are to be absent.

6.2 Prolonged absence

Control panels S3 and B3
1. Set the On/Off switch to O.
See: Control panel instructions
Z
See: Burner instructions
Z
2. Switch off the boiler electrical power supply
3. Close the fuel supply.

6.2.1 Precautions required in the case of long boiler stops (one or more years)

The boiler and the chimney must be swept carefully.
Close all the doors of the boiler to prevent air from circulating inside the boiler.
We advise removing the pipe which connects the boiler to the chimney and to close off the nozzle with a cover.

6.2.2 Precautions required if the heating is stopped when there is a risk of freezing

We recommend the use of a correctly dosed antifreeze agent to prevent to the heating circuit from freezing.
If this cannot be done, drain the system completely.
24/11/08 - 300017846-001-B GTU C 330
15
7. Checking and maintenance

7 Checking and maintenance

7.1 Checks

Make the following checks at least 1 time a year:
- Safety devices
-
System pressure
- Checking burner safety
- Checking the safety thermostat
- Condensates neutralisation system

7.2 Hydraulic pressure

Checking the hydraulic pressure. The hydraulic pressure must be a minimum of 0.8 bars. Adjust the pressure if necessary, avoiding a sudden influx of cold water into the boiler when it is hot. This operation should be required only a few times in each heating season, with very low quantities of water; otherwise, look for the leak and repair it.

7.3 Draining

We advise you against draining the system unless it is absolutely necessary.
Carry out the following maintenance at least 1 time a year:
- Cleaning the burner
- Cleaning of the heating body
- Cleaning of the condenser
- Cleaning the siphon
- Cleaning the flue gas circuit

7.4 Maintenance

The boiler will only operate efficiently if the exchange
surfaces are kept clean.
Have the required checks and services done.
` The boiler must be serviced and fully cleaned and the flue gas
conduit swept by a qualified professional at least 1 times per year.
` The condenser and the condensates neutralisation station must
serviced at least once a year by a qualified professional.
The siphon and the condensates evacuation conduit must imperatively be checked and cleaned at least once a year.
16
GTU C 330 24/11/08 - 300017846-001-B

8 Troubleshooting

` Carry out the checks mentioned in the burner instructions.
` Contact a qualified professional

8.1 Rating plate

Before informing the fitter of a fault, make a note of the following information:
1. The type of control panel,
8. Troubleshooting
4. Burner rating plate:
2. Condenser rating plate:
- Serial no. of the appliance
- Date of manufacture
3. Boiler rating plate:
- Boiler type
- Serial no. of the appliance
- Date of manufacture
- Burner type
- Type of combustible
- Burner serial number
- Date of manufacture
2
C001966
1
3
24/11/08 - 300017846-001-B GTU C 330
4
17
8. Troubleshooting

8.2 Error messages

8.2.1 Control panel B3

In the event of a fault, the display may show the following messages:
Message Faults Probable causes Action
AL 50 Boiler sensor
AL 52 Domestic hot water sensor The sensor is cut
AL td
Titanium anode
AL tc

8.2.2 Control panel K3

The sensor circuit has been broken or short circuited.
The titanium anode is on an open circuit or the tank is empty.
A short circuit has occurred on the titanium anode or connection reversed.
The installation is stopped. Advise the installer.
The installation continues to operate but domestic hot water heating is no longer covered. Advise the installer.
Production of domestic hot water is stopped. This may be reactivated for 24 hours by disconnecting and reconnecting the power supply to the boiler.
Advise the installer.
No error messages displayed.
See DIEMATIC-m3 control panel display.
18
GTU C 330 24/11/08 - 300017846-001-B

8.2.3 Control panel DIEMATIC-m3

Message Probable causes Action
SHOW REM. CTRL
REVISION Boiler service required. Advise the installer.
DISGAS
AUX1.SENS.FAIL AUX2.SENS.FAIL
UNIV.SENS.FAIL
DHW 2 S. FAIL
BOILER S.FAIL.
OUTSI. S.FAIL.
DHW S. FAILURE
OUTL S.A FAIL. OUTL S.B FAIL. OUTL S.C FAIL.
ROOM S.A FAIL. ROOM S.B FAIL. ROOM S.C FAIL.
SMOKE S. FAIL.
SWIM.P.A S.FAIL SWIM.P.B. S.FAIL SWIM.P.C. S.FAIL
SOLAR S. FAIL
ST.TANK S.FAIL
TA-S SHORT-CIR The Titan Active System® is short-circuited.
TA-S DISCONNEC The Titan Active System® is on an open circuit.
TA-S FAILURE Internal problem.
The message SHOW REM.CTRL indicates the presence of an override on a remote control.
When connecting voltage, if the hot water tank temperature is below 25 ºC, the boiler carries out a domestic water exchanger purge cycle.
The sensor circuit has been broken or short circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
The sensor circuit has been broken or short
circuited.
To cancel the overrides on all remote controls, press the AUTO key for 5 seconds.
Wait 1 minute.
Advise the installer.
If the boiler sensor fails, the burner is controlled by the boiler thermostat and the heating and DHW circuits operate normally. Advise the installer.
The boiler setting is equal to BOILER MAX. but can be limited by the boiler thermostat to a lower value.
- The valve setting is no longer ensured but monitoring the maximum temperature of the circuit after the valve is ensured.
- Valves may be manually operated.
- Reheating the domestic hot water remains ensured. Advise the installer.
To ensure domestic hot water production, set the switch AUTO/
STB to
Advise the installer.
The circuit concerned goes from automatic to manual mode: The pump operates. Advise the installer.
The circuit concerned operates without any influence from the room sensor. Advise the installer.
This failure has no impact on the operating modes. Advise the installer.
Pool reheating is independent of its temperature. Advise the installer.
Reheating domestic hot water using the solar panel is no longer ensured. Advise the installer.
The hot water storage tank reheating operation is no longer assured. Advise the installer.
Domestic hot water production is shut down and can be restarted using key
Advise the installer.
Domestic hot water production is shut down and can be restarted using key
Advise the installer.
Switch off the current. Advise the installer.
.
!
. The tank is no longer protected.
. The tank is no longer protected.
8. Troubleshooting
/TEST-
!
24/11/08 - 300017846-001-B GTU C 330
19
8. Troubleshooting

8.3 Incidents and solutions

The burner is not working:
` Check the boiler thermostat settings.
` Carry out the checks mentioned in the burner instructions.
` Shutdown by the safety thermostat due to accidental
overheating:
Boiler: Check that the safety thermostat has not triggered. To restart the boiler, reset the safety thermostat. Remove the safety thermostat hood and press the reset button with a screwdriver.
Condenser: Check that the safety thermostat has not triggered:
- Unscrew the protection cap
- Press the resetting button of the burner
The burner is operating but the radiators are cold:
` Bleed the radiators.
` Checking the hydraulic pressure. The hydraulic pressure must
be a minimum of 0.8 bars. Adjust the pressure if necessary, avoiding a sudden influx of cold water into the boiler when it is hot. If it is often necessary to top up the installation with water, contact your fitter.
` Check that the heating pumps are working correctly
` Check the position of the 3 position switch.
Control panel B3: TEST-STB/ Control panel DIEMATIC-m3: AUTO/ AUTO. Control panel K3: AUTO/
` Check the settings on the boiler thermostat(s).
/TEST STB on AUTO
!
./%
on ..
/TEST STB on
!
C001951
1
2
` Carry out the start-up operations again. Call your fitter.
` Check the circuit breaker
20
GTU C 330 24/11/08 - 300017846-001-B
9. Technical characteristics

9 Technical characteristics

Conditions of use: Test conditions:
Maximum operating temperature: 90 °C
Maximum operating pressure: 4 bar Ambient temperature: 20 °C
Thermostat adjustable from 30 to 90°C
Safety thermostat: 110 °C
80°C limiter thermostat - Condenser
Flue gas temperature safety thermostat: 120 °C
Boiler GTU C 334 335 336 337 338 339
Nominal output Pn by 50/30°C kW 93.4 120.3 157.3 192.7 239.7 291.2
PCI efficiency - 100 % Pn - Average temperature: 70 °C
PCI efficiency - 30 % Pn - Return temperature:
50 °C
PCI efficiency - 30 % Pn - Return temperature:
30 °C
Nominal water flow (Nominal output) - T = 20K
Stand-by losses (1) , T =
30K
Losses through the outer casing (2)
Auxiliary electrical power (3) W 325 435 650 625 625 1100
Useful output range by 50/30°C kW 56.7-93.4 93.7-120.3 120.2-157.3 155.4-192.7 191.7-239.7 238.4-291.2
Useful output range by 80/60°C kW 55-90 90-115 115-150 150-185 185-230 230-280
Water content l 113 133 153 177 197 217
T = 10K (1) mbar 11 18 31 46 68 105
Loss of load hydraulic circuit
Combustion chamber
Number of sections 4 5 6 7 8 9
Number of baffle plates 6 10 10 10 12 12
Mass flue gas flow rate (3) - by 50/30°C Kg/h 149 191 248 306 381 463
Flue gas temperature (3) °C 50 55 61 62 63 65
Pressure available at the flue gas nozzle mbar 1.0 0.6 1.8 1.9 1.6 1.7
Loss of load flue gas side mbar 0.45 0.8 1.0 1.3 1.6 2.3
Maintenance consumption (4) T = 30K % 0.38 0.32 0.25 0.28 0.23 0.19
Burner type M202-2S M302-1S M302-3S M302-3S M302-4S M302-5S
Weight (empty) kg 678 802 912 1117 1239 1366
T = 15K (1) mbar 4.6 7.4 14.2 19.5 30.1 46
T = 20K (1) mbar 2.6 4.2 8.0 11 17 26
Inscribed diameter mm 377 377 377 377 377 377
Length mm 613 718 854 993 1117 1245
Volume
% 97.8 96.9 96.4 98.1 97.7 97.6
% 101.5 101.4 101.1 102.2 101.8 101.5
% 103.0 102.8 103.0 104.7 104.0 103.8
3
m
/h
4.019 5.178 6.769 8.293 10.312 12.530
W 315 335 350 495 500 510
%697378838793
3
0.096 0.122 0.148 0.174 0.200 0.226
m
CO² Fuel oil = 13%
(1) Stand-by losses, according to the standard EN 304
(2) as a % of stand-by losses
(3) At nominal output
(4) Maintenance consumption, as a % of the input - according to the standard EN15034
1 mbar = 10 mmCE = 10 daPa.
24/11/08 - 300017846-001-B GTU C 330
21
10. Energy savings

10 Energy savings

Here are a few tips for saving energy:
- Install reflector panels behind the radiators.
- Do not cover the radiators. Do not hang curtains in front of the radiators.
- Insulate pipes to prevent thermal losses and condensation.
- Do not obstruct aeration grates (even partially). They help to reduce humidity in the home. The more humid a home, the more heating it consumes.
- Turn heating off when airing a room (5 minutes a day is sufficient) Avoid deregulating the thermostat. Place the start/stop switch on Off.
- Do not shut down heating completely if you are absent. Lower the thermostat by 3-4°C.
- Use the sun's heat as much as possible.
- Take showers rather than baths. Use a water-saving shower head.
22
GTU C 330 24/11/08 - 300017846-001-B
11
Warranty
11.
You have just purchased one of our appliances and we thank you for the trust you have placed in our products.
Please note that your appliance will provide good service for a longer period of time if it is regularly checked and maintained.
Your fitter and our customer support network are at your disposal at all times.
Warranty terms
Starting from the purchase date shown on the original fitter's invoice, your appliance has a contractual guarantee against any manufacturing defect.
The length of the guarantee is mentioned in the price catalogue.
The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified fitter).
In particular, the manufacturer shall not be held responsible for any damage, loss or injury caused by installations which do not comply with the following:
- applicable local laws and regulations
- specific requirements relating to the installation, such as national and/or local regulations
- the manufacturer's instructions, in particular those relating to the regular maintenance of the unit
- the rules of the profession
France
The preceding dispositions are not exclusive of benefits for the purchaser of the legal guarantee as stated in Civil Code articles 1641 to 1648.
Belgium
The preceding dispositions about the contractual guarantee are not exclusive of profit if the need arises for the purchaser in Belgium of the applicable legal dispositions on hidden defects.
Switzerland
The application of the warranty is subject to the terms and conditions of sale, delivery and warranty of the company marketing our products.
Poland
Warranty conditions are included in the warranty card.
Other countries
The above provisions do not restrict the benefit of the legal laws regarding hidden defects applicable in the buyer's country.
The warranty is limited to the exchange or repair of such parts as have been recognised to be faulty by our technical department and does not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts damaged by normal wear and tear, negligence, repairs by unqualified parties, faulty or insufficient monitoring and maintenance, faulty power supply or the use of unsuitable fuel.
Sub-assemblies such as motors, pumps, electric valves etc. are guaranteed only if they have never been dismantled.
24/11/08 - 300017846-001-B GTU C 330
23
FR
DE DIETRICH THERMIQUE S.A.S.
www.dedietrich-thermique.fr
Direction des Ven te s France
57, rue de la Gare
F- 67580 MERTZWILLER
+33 (0)3 88 80 27 00 +33 (0)3 88 80 27 99
DE
BE
CN
DE DIETRICH REMEHA GmbH
www.dedietrich-remeha.de
Rheiner Strasse 151
D- 48282 EMSDETTEN
+49 (0)25 72 / 23-5
+49 (0)25 72 / 23-102
info@dedietrich.de
VAN MARCKE
www.vanmarcke.be
Weggevoerdenlaan 5
B- 8500 KORTRIJK
+32 (0)56/23 75 11
DE DIETRICH
www.dedietrich-heating.com
Room 512, Tower A, Kelun Building 12A Guanghua Rd, Chaoyang District
C-100020 BEIJING +86 (0)106.581.4017 +86 (0)106.581.4018 +86 (0)106.581.7056 +86 (0)106.581.4019
contactBJ@dedietrich.com.cn
LU
RU
AT
NEUBERG S.A.
www.dedietrich-heating.com
39 rue Jacques Stas
L- 2010 LUXEMBOURG
+352 (0)2 401 401
DE DIETRICH
www.dedietrich-otoplenie.ru
Россия
109044 г. Москва
ул. Крутицкий Вал, д. 3
корп. 2, оф. 35
+7 495 988-43-04 +7 495 988-43-04 dedietrich@nnt.ru
ÖAG AG
www.oeag.at
Schemmerlstrasse 66-70
A-1110 WIEN
+43 (0)50406 - 61624
+43 (0)50406 - 61569
dedietrich@oeag.at
CH
WALTER MEIER (Klima Schweiz) AG
www.waltermeier.com
Bahnstrasse 24
CH-8603 SCHWERZENBACH
+41 (0) 44 806 44 24
Serviceline +41 (0)8 00 846 846
+41 (0) 44 806 44 25
ch.klima@waltermeier.com
WALTER MEIER (Climat Suisse) SA
www.waltermeier.com
Z.I. de la Veyre B, St-Légier
CH-1800 VEVEY 1
+41 (0) 21 943 02 22
Serviceline +41 (0)8 00 846 846
+41 (0) 21 943 02 33
ch.climat@waltermeier.com
© Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing.
Subject to alterations.
24/11/08
AD001NU-AB
DE DIETRICH THERMIQUE 57, rue de la Gare F- 67580 MERTZWILLER - BP 30
Loading...