1. Do not use naked flames, do not smoke and
do not operate electrical contacts or switches
(doorbell, lighting, motor, lift etc).
2. Shut off the gas supply.
3. Open the windows.
4. Trace possible leaks and seal them off
immediately.
5. If the leak is upstream of the gas meter, notify
the gas company.
Danger
If you smell flue gases:
1. Switch the boiler off.
2. Open the windows.
3. Trace possible leaks and seal them off
immediately.
Caution
After maintenance or repair work, check the
entire heating installation to ensure that there are
no leaks.
For the end user:
1 Safety
67600532 - v.11 - 13122018
Danger
If you smell gas:
1. Do not use naked flames, do not smoke and
do not operate electrical contacts or switches
(doorbell, lighting, motor, lift etc).
2. Shut off the gas supply.
3. Open the windows.
4. Evacuate the property.
5. Contact a qualified installer.
Danger
If you smell flue gases:
1. Switch the boiler off.
2. Open the windows.
3. Evacuate the property.
4. Contact a qualified installer.
Warning
Do not touch the flue gas pipes. Depending on
the boiler settings, the temperature of the flue gas
pipes can rise to over 60°C.
Warning
Do not touch radiators for long periods.
Depending on the boiler settings, the temperature
of the radiators can rise to over 60°C.
Warning
Be careful when using the domestic hot water.
Depending on the boiler settings, the temperature
of domestic hot water can rise to over 65°C.
Warning
The use of the boiler and the installation by you
as the end-user must be limited to the operations
described in this manual. All other actions may
only be undertaken by a qualified fitter/engineer.
Warning
The condensation drain must not be changed or
sealed. If a condensate neutralisation system is
used, the system must be cleaned regularly in
accordance with the instructions provided by the
manufacturer.
Caution
Ensure that the boiler is regularly serviced.
Contact a qualified installer or arrange a
maintenance contract for the servicing of the
boiler.
1.2 Recommendations
7600532 - v.11 - 131220187
1 Safety
Caution
Only genuine spare parts may be used.
Important
Regularly check for the presence of water and
pressure in the heating installation.
Danger
This appliance can be used by children aged
eight and above and people with a physical,
sensory or mental disability, or with a lack of
experience and knowledge, provided they are
supervised and instructed in how to use the
appliance in a safe manner and understand the
associated dangers. Children must not be
allowed to play with the appliance. Cleaning and
user maintenance should not be carried out by
children without adult supervision.
Warning
Installation and maintenance of the boiler must be
carried out by a qualified installer in accordance
with local and national regulations.
Warning
The installation and maintenance of the boiler
must be undertaken by a qualified installer in
accordance with the information in the supplied
manual, doing otherwise may result in dangerous
situations and/or bodily injury.
Warning
Removal and disposal of the boiler must be
carried out by a qualified installer in accordance
with local and national regulations.
Warning
If the mains lead is damaged, it must be replaced
by the original manufacturer, the manufacturer's
dealer or another suitably skilled person to
prevent hazardous situations from arising.
Warning
Always disconnect the mains supply and close
the main gas tap when working on the boiler.
Warning
Check the entire system for leaks after
maintenance and servicing work.
1 Safety
87600532 - v.11 - 13122018
Danger
For safety reasons, we recommend fitting smoke
and CO alarms at suitable places in your home.
Caution
Make sure the boiler can be reached at all
times.
The boiler must be installed in a frost-free area.
If the power cord is permanently connected, you
must always install a main bipolar switch with
an opening gap of at least 3 mm (EN 60335-1).
Drain the boiler and central heating system if
you are not going to use your home for a long
time and there is a chance of frost.
The frost protection does not work if the boiler is
out of operation.
The boiler protection only protects the boiler,
not the system.
Check the water pressure in the system
regularly. If the water pressure is lower than 0.8
bar, the system must be topped up
(recommended water pressure between 1.5 and
2 bar).
1.3
Important
Keep this document near to the boiler.
Important
Only remove the casing for maintenance and
repair operations. Refit all panels when
maintenance work and servicing are complete.
Important
Instruction and warning labels must never be
removed or covered and must be clearly legible
throughout the entire service life of the boiler.
Damaged or illegible instructions and warning
stickers must be replaced immediately.
Important
Modifications to the boiler require the written
approval of De Dietrich.
Liabilities
1.3.1 Manufacturer's liability
Our products are manufactured in compliance with the
requirements of the various Directives applicable. They
are therefore delivered with the
marking and any
1 Safety
7600532 - v.11 - 131220189
documents necessary. In the interests of the quality of
our products, we strive constantly to improve them. We
therefore reserve the right to modify the specifications
given in this document.
Our liability as manufacturer may not be invoked in the
following cases:
Failure to abide by the instructions on installing and
maintaining the appliance.
Failure to abide by the instructions on using the
appliance.
Faulty or insufficient maintenance of the appliance.
1.3.2
Installer's liability
The installer is responsible for the installation and initial
commissioning of the appliance. The installer must
observe the following instructions:
Read and follow the instructions given in the manuals
provided with the appliance.
Install the appliance in compliance with prevailing
legislation and standards.
Carry out initial commissioning and any checks
necessary.
Explain the installation to the user.
If maintenance is necessary, warn the user of the
obligation to check the appliance and keep it in good
working order.
Give all the instruction manuals to the user.
1.3.3 User's liability
To guarantee optimum operation of the system, you
must abide by the following instructions:
Read and follow the instructions given in the manuals
provided with the appliance.
Call on a qualified professional to carry out installation
and initial commissioning.
Get your installer to explain your installation to you.
Have the required inspections and maintenance
carried out by a qualified installer.
Keep the instruction manuals in good condition close
to the appliance.
2 About this manual
107600532 - v.11 - 13122018
2 About this manual
2.1 Additional documentation
The boiler can be fitted with various control panels. The selected control
panel is supplied with its corresponding manual.
2.2
Symbols used
2.2.1 Symbols used in the manual
This manual uses various danger levels to draw attention to special
instructions. We do this to improve user safety, to prevent problems and to
guarantee correct operation of the appliance.
Danger
Risk of dangerous situations that may result in serious personal
injury.
Danger of electric shock
Risk of electric shock.
Warning
Risk of dangerous situations that may result in minor personal
injury.
Caution
Risk of material damage.
Important
Please note: important information.
See
Reference to other manuals or pages in this manual.
3 Technical specifications
7600532 - v.11 - 1312201811
3.1 Homologations
3.1.1 Certifications
Tab.1Certifications
CE identification numberPIN 0063CL3613
Class NOx
(1)
Type of flue gas connection
6
B23, B
23P
(2)
C33, C53, C63, C
(1) EN 15502–1
(2) When installing a boiler with connection type B23, B
boiler is lowered to
IP20.
3.1.2 Unit categories
3 Technical specifications
93
, the IP rating of the
23P
3.2
Technical data
Tab.2Unit categories
CategoryGas typeConnection pressure
(mbar)
I
2H
G20 (H gas)20
3.1.3 Directives
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines
specified in this manual.
3.1.4 Factory test
Before leaving the factory, each boiler is optimally set and tested for:
Electrical safety.
Adjustment of (O2).
Water tightness.
Gas tightness.
Parameter setting.
3.2.1 C 330 ECO technical data
Tab.3General
C 330 ECO280350430500570650
Number of sections5678910
Nominal output (Pn)
(80/60 °C)
Nominal output (Pn)
(50/30 °C)
Nominal load (Qnh)
(Hi)
min
max
max
min
max
(1)
(1)
kW279350425497574651
261
kW54
kW51
(1)
266
65
327
68
333
79
395
82
402
92
461
95
469
106
530
109
539
119
601
122
610
3 Technical specifications
127600532 - v.11 - 13122018
C 330 ECO280350430500570650
Nominal load (Qnh)
(Hs)
Full load central heating efficiency
min
max
(1)
kW60
295
75
369
96
445
105
520
121
598
135
677
%98.098.198.298.398.498.5
(Hi) (80/60 °C) (92/42/EEC)
Full load central heating efficiency
%104.8105.2105.6106.0106.4106.8
(Hi) (50/30 °C) (EN15502)
Central heating efficiency under
%94.795.395.896.396.897.3
part load (Hi)
(Return temperature 60 °C)
Annual efficiency G20 (DIN 4702,
%109.6109.5109.4109.3109.2109.1
Part 8)
Part load central heating efficiency
%109.2109.0108.8108.6108.3108.1
(92/42 EEC)
(Return temperature 30 °C)
(1)
Factory setting
Tab.4Gas and flue gas data
C 330 ECO280350430500570650
Gas inlet pressure G20 (H gas)min
max
Gas inlet pressure G25 (L gas)min
max
Gas consumption G20 (H gas)min
max
Gas consumption G25 (L gas)min
max
NOx annual emissions G20
O2 = 0%ppm28.931.730.628.930.627
mbar17
30
mbar17
30
m3/h
5.7
28.1
m3/h
6.6
32.7
17
30
17
30
7.2
35.2
8.4
41.0
17
100
17
100
8.7
42.5
10.1
49.5
17
100
17
100
10.1
49.6
11.7
57.7
17
100
17
100
11.5
57.0
13.4
66.3
17
30
17
30
12.9
64.6
15.0
75.1
EN15502
NOx annual emissions G20
H
i
mg/kWh51.056.054.051.054.047.6
EN15502
NOx annual emissions G20
H
s
mg/kWh46.050.049.046.049.043.0
EN15502
Flue gas mass flow ratemin
max
Flue gas temperaturemin
max
Maximum counter pressure for flue
Pa
gas outlet
kg/h91
448
°C30
80
130120130150150150
114
560
30
80
138
676
30
80
160
789
30
80
183
907
30
80
205
1026
30
80
Chimney losses80/60 °C%2.32.32.32.32.32.3
Stoppage loss (EN15502)
(Including heat exchanger insula
tion kit)
(ΔT = 30K)
(1)
W
%
464
0.17
479
0.14
493
0.12
508
0.11
522
0.10
537
0.09
Number of stars (92/42/EEC)444444
(1) ΔT = (boiler temperature – ambient temperature).
Power consumption – full loadmaxW558668852108615261446
Power consumption – part loadminW9292116122124110
Power consumption – standbyminW121212121214
Electrical protection index
(1)
IPX1BX1BX1BX1BX1BX1B
Fuse – main fuse F2(A)101010101010
Fuse – PCB F1(A)222222
(1) For a room-sealed system.
Tab.13Other data
C 630 ECO560700860100011401300
Total weight (empty)kg70777183795710251095
Average acoustic level
(1)
at a dis
dB(A)585858585858
tance of 1 metre from the boiler
Ambient temperaturemax°C404040404040
(1) For a sealed installation
AD-0000485-01
22
1500
1023
130
366320
1477
447
1293
310
706
592
716
155
2
Ø 250
C
L
920
B
A
Ø 250
1310
353
3 Technical specifications
167600532 - v.11 - 13122018
3.3 Dimensions and connections
Fig.1Dimensions C 330 ECO
3.3.1 Boiler type C 330 ECO
C 330 ECO280350430500570650
A1833 mm1833 mm1833 mm2142 mm2142 mm2142 mm
B1635 mm1635 mm1635 mm1944 mm1944 mm1944 mm
C1862 mm1862 mm1862 mm2172 mm2172 mm2172 mm
L1490 mm1490 mm1490 mm1800 mm1800 mm1800 mm
Central heating circuit flowFlange NW
Central heating circuit return Flange NW
Gas connectionG2"G2"G2"G2"G2"G2"
Condensation outletØ 32 mm (in
80 (DIN
2576)
80 (DIN
2576)
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flue gas outletØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mm
Air supplyØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mm
Second return (optional)Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
65 (DIN
2576)
Fig.2DimensionsC 630 ECO
AD-0000509-01
B
920
869
A
641
L
C
592592
366320
22
1023
1760
1477
1293
310
155
1500
130
1726
1310
8
8353353
722
1460
7600532 - v.11 - 1312201817
3 Technical specifications
3.3.2 Boiler type C 630 ECO
C 630 ECO560700860100011401300
A1833 mm1833 mm1833 mm2142 mm2142 mm2142 mm
B1582 mm1582 mm1582 mm1892 mm1892 mm1892 mm
C1862 mm1862 mm1862 mm2172 mm2172 mm2172 mm
L1490 mm1490 mm1490 mm1800 mm1800 mm1800 mm
Central heating circuit flowFlange NW
80 (DIN
2576)
Central heating circuit return Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Gas connectionG2"G2"G2"G2"G2"G2"
Condensation outletØ 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Flue gas outletØ 350 mmØ 350 mmØ 350 mmØ 350 mmØ 350 mmØ 350 mm
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
AD-3001123-01
PCU-06
X06
1 2 3 4
NLL
BL
BR
BR
X07
1 2 3
ION
LN
GY
BL
BK
X02
1 2
Pump
3
LN
P
X50
10 AT
LN
X04 X05
1 10
X11
1 2 3 4
14 25
WH
BR
GN
YW
X09
1 2 3 4 5 6
OT
1
On / Off
bL
3 4
RL
5 62
X08
X51
X01
1 2 3
Mains
YW/
GN
BL
BK
BL
BR
BK
BL
YW/
GN
X03
192 3 4 510 116 7 812
WHBL
RD
BK
OR
OR
YW/
WH
BR/
WH
BK/
WH
BL/
WH
SU-01
X10
SCU-D4
J6J2
N
TS + BB
LN LN
Alim
230 V - 50 Hz
L
NN L
A
+
0-10V
- 4
SCAMB S AMBB S AMPA
3 2 1 2 1 2 1 2 12
S SYST
1 2
+S ECS S EXTTA -S DEP C S DEPB
1 2 1 2 1 2 1 2 1
J9J8J8
X06
X07
X08
X02
X03
X11
X09
X04
X10
X05
X01
SU-01
J5
J2
J1
J10
J8
J9
J6
J4
J7
SU-01
3
4
5
1
2
678910 1112131415
16
3 Technical specifications
187600532 - v.11 - 13122018
C 630 ECO560700860100011401300
Air supply
Air supply manifold
Second return (optional)Flange NW
Ø 250 mm
Ø 350 mm
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
3.4
Electrical diagram
Fig.3Electrical diagram
1
2
3
4
5
6
7
8
Extended PCB (SCU-D4)
Standard PCB (PCU-06)
Safety PCB (SU-01)
On/Off switch (AU)
Power supply (P)
Flow sensor (Fs)
Heat exchanger temperature sensor (HEs)
Return temperature sensor (RTs)
9
Parameter storage (PSU)
10
High limit switch (HLs)
11
Air pressure differential switch (PS)
12
Computer connection (PC)
13
Control panel (HMI)
14
Gas valve unit (GB)
15
Ignition transformer (IT)
16
Fan (FAN)
4 Description of the product
7600532 - v.11 - 1312201819
4.1 General description
4 Description of the product
The C 330 ECO / C 630 ECO is a freestanding gas boiler with the
following characteristics:
High-efficiency heating.
Heat exchanger made of cast aluminium sections.
Limited emissions of polluted substances.
Has transport wheels as standard.
Left- or right-hand version of the water and flue gas side connections
possible.
Separable for assembly in boiler room.
DIEMATIC iSystem or IniControl control panel.
The C 630 ECO comprises a left-hand and a right-hand module. These
are combined on the flue gas side (optionally on the air side) and also in
terms of their casing.
The following boiler types are available:
4.2
Operating principle
C 330 ECO 280
C 330 ECO 350
C 330 ECO 430
C 330 ECO 500
C 330 ECO 570
C 330 ECO 650
C 630 ECO 560
C 630 ECO 700
C 630 ECO 860
C 630 ECO 1000
C 630 ECO 1140
C 630 ECO 1300
The boiler is fitted with an electronic temperature control with a flow and
return temperature sensor. The flow temperature can be adjusted between
20°C and 90°C. The boiler modulates back when the set flow temperature
is reached. The switch-off temperature is the set flow temperature + 5°C.
4.2.2 Protection against shortage of water
The boiler is fitted with protection against a shortage of water that is based
on temperature differences (difference in temperature between flow and
return). From ΔT = 25K (factory setting) the boiler reduces its output by
modulating to remain in operation as long as possible. At ΔT ≥ 25K, the
boiler goes into part load. At ΔT > 25 + 5K, the boiler goes into a normal
control stop (blocking).
4.2.3 Maximum protection
The maximum temperature protection shuts the boiler down in the event
that an excessively high water temperature (110 °C) is reached. Once the
cause of the fault has been remedied, the boiler can be unlocked by
pressing the button for 2 seconds.
4.2.4 Air pressure differential switch
Before a start and when the boiler is in operation, the air pressure
differential switch PS measures the difference in pressure between the
measuring points on the back of the heat exchanger p+ and the air box p-.
AD-0000521-01
2
1
3
4
5
6
7
8
27
40
28
29
30
32
34
31
33
35
36
37
38
39
11
12
14
13
15
16
17
18
19
20
22
24
26
21
23
25
10
9
4 Description of the product
207600532 - v.11 - 13122018
If the pressure difference is greater than 6 mbar, then the boiler will lock
out. Once the cause of the fault has been remedied, the boiler can be
unlocked by pressing the button for 2 seconds.
4.2.5 Circulating pump
The boiler does not have a built-in pump. A circulating pump can be
installed on the connector of the standard control PCB. This can be an
on/off pump or a modulating pump (with 0 - 10 V control).
The pump settings can be changed.
See
Manual for the control panel.
For more information, see
Analogue output (Ctrl), page 44
4.3
Main components
4.3.1 Main components C 330 ECO
Fig.4
C 330 ECO
1
Flow connection
2
Air pressure differential switch
3
Flue gas outlet
4
Return connection
5
Flue gas measuring point
6
Flue gas thermostat (if present)
7
Condensate collector sealant cap
8
Pivoting castor
9
Adjustment bolt
10
Frame
11
Second return connection
12
Heat exchanger insulation kit (if present)
13
Boiler casing
14
Air supply
15
Burner
16
Adapter
17
Ignition/ionisation electrode
18
Heat exchanger
19
Inspection trap
20
Temperature sensor for heat exchanger
21
Return temperature sensor
22
Gas filter
23
Data plate
24
Siphon
25
Transport wheels
26
Adjustment bolt
27
Gas connection
28
Gas pressure measuring point
29
Control panel
30
Installation option for weather-compensated boiler
control
31
Pressure measurement point
32
Flame inspection window
33
Non-return valve
34
Fan
35
Extension piece
36
Venturi
37
Gas valve unit
38
Air supply hose
39
Document holder
40
Ignition transformer
Fig.5C 630 ECO
AD-0000522-01
1
3
4
5
2
6
7
8
27
28
29
30
32
34
31
33
35
36
14
13
15
16
17
18
19
20
22
24
26
21
23
25
10
41
11
12
9
37
38
39
40
7600532 - v.11 - 1312201821
4 Description of the product
4.3.2 Main components C 630 ECO
1
Flow connection
2
Air pressure differential switch
3
Flue gas outlet
4
Return connection
5
Flue gas measuring point
6
Flue gas thermostat (if present)
7
Condensate collector sealant cap
8
Pivoting castor
9
Adjustment bolt
10
Frame
11
Heat exchanger insulation kit (if present)
12
Flue gas collector
13
Boiler casing
14
Air supply
15
Burner
16
Adapter
17
Ignition/ionisation electrode
18
Heat exchanger
19
Inspection trap
20
Temperature sensor for heat exchanger
21
Return temperature sensor
4.4
Control panel description
The boiler is supplied with a DIEMATIC iSystem or IniControl control
panel. The control panel is mounted in the boiler.
See
Assembly instructions for the control panel.
Manual for the control panel.
Important
For operation of the C 630 ECO boiler: each module has its own
control panel.
22
Gas filter
23
Data plate
24
Siphon
25
Transport wheels
26
Adjustment bolt
27
Gas connection
28
Gas pressure measuring point
29
Control panel
30
Installation option for weather-compensated boiler
control
31
Pressure measurement point
32
Flame inspection window
33
Non-return valve
34
Fan
35
Extension piece
36
Venturi
37
Gas valve unit
38
Air supply hose
39
Document holder
40
Ignition transformer
41
Second return connection
4 Description of the product
227600532 - v.11 - 13122018
4.5 Standard delivery
The delivery includes:
The boiler
Complete siphon
Filling and drain valve
Gas filter
Documentation
Water quality instructions
Please fit these components in the order described in this manual.
Important
This manual only deals with the standard scope of supply. For the
installation or mounting of any accessories delivered with the
boiler, refer to the corresponding mounting instructions.
4.6
Accessories and options
Various accessories can be obtained for the boiler.
Important
Contact us for more information.
5 Before installation
AD-0000487-01
7600532 - v.11 - 1312201823
5.1 Installation regulations
5 Before installation
Warning
The boiler must be installed by a qualified installer in accordance
with local and national regulations.
5.2
Fig.6
Choice of the location
Position of data plate
5.2.1 Data plate
The identification plate is located behind the boiler casing on the frame,
near the syphon connection. The data plate provides important information
on the boiler specifications such as the model and the device category.
5.2.2
Use the guidelines and the required installation space as a basis for
determining the correct place to install the boiler.
When determining the correct installation area, take account of the
permitted position of the flue gas outlet and/or air supply outlet.
Ensure that there is sufficient space around the boiler for good access
and ease of maintenance.
A technical clearance of at least 80 cm is required at the front (service
side) of the boiler. However, we recommend that the clearance is at
least 100 cm. Above the boiler, we recommend a clearance of at least
40 cm (when using an air inlet filter, the clearance must be at least 65
cm). A minimum of 30 cm is required on the side of the flue gas outlet,
and a minimum of 30 cm is also required on the other side (or 80 cm, if
this is operating side).
Installing the boiler C 330 ECO
AD-0000515-01
L
R
I
I
AD-0000486-01
5555
5555
66321,5
53187,5
673
55
A
5 Before installation
247600532 - v.11 - 13122018
Danger
It is forbidden to store, even temporarily, combustible products
and substances in or near the boiler.
Caution
The boiler must be installed in a frost-free area.
An earthed electrical connection must be available close to the
boiler.
A connection to the drain must be present for the condensate
drain close to the boiler.
Fig.7Left-hand and right-hand versions
Fig.8Position of the adjustment bolts
L
Left-hand version
R
Right-hand version
I
Inspection trap (service side)
The service side with the inspection trap on the heat exchanger is
considered to be the front of the boiler. The boiler is available in both a
'left-hand' and 'right-hand' version. This means that the hydraulic
connections and the flue gas discharge are situated on either the left or
the right-hand side of the boiler. The control panel is on the front as
standard, but can easily be rotated so that it is on the short side.
The adjustment bolts must be used to make the boiler level and to raise
the wheels off the floor. Turn the adjustment bolts outwards as soon as the
boiler is placed in the correct position. The figure shows the support
surface of the boiler (this is the position of the adjustment bolts).
Tab.14Dimensions A (mm)
C 330 ECOA (mm)
280723
350723
430723
5001032
5701032
6501032
Fig.9Clearance required
AD-0000506-02
CC
C
800
300
600
800800
720
1670
800150
720720
3190
800
800
150
720
1670
800150
C
800
300
7600532 - v.11 - 1312201825
5 Before installation
For the dimensions of C:
See
Boiler type C 330 ECO, page 16
5.2.3 Installing the boiler C 630 ECO
Use the guidelines and the required installation space as a basis for
determining the correct place to install the boiler.
When determining the correct installation area, take account of the
permitted position of the flue gas outlet and/or air supply outlet.
Ensure that there is sufficient space around the boiler for good access
and ease of maintenance.
A technical clearance of at least 80 cm is required at the front (service
side) of the boiler. However, we recommend that the clearance is at
least 100 cm. Above the boiler, we recommend a clearance of at least
40 cm (when using an air inlet filter, the clearance must be at least 65
cm). A minimum of 30 cm is required on the side of the flue gas outlet,
and a minimum of 30 cm is also required on the other side (or 80 cm, if
this is operating side).
AD-0000514-02
AD-0000510-01
5555
55
55
21,5
21,5
87,5531
663663
53187,5
673
A
55
55
55
55
55
55
55
5 Before installation
267600532 - v.11 - 13122018
Danger
It is forbidden to store, even temporarily, combustible products
and substances in or near the boiler.
Caution
The boiler must be installed in a frost-free area.
An earthed electrical connection must be available close to the
boiler.
A connection to the drain must be present for the condensate
drain close to the boiler.
Fig.10Position of the control panel
Fig.11Position of the adjustment bolts
The boiler is not available with a choice between 'left-hand' and 'righthand' versions. The control panel is on the front as standard, but can
easily be rotated so that it is on the short side.
The adjustment bolts must be used to make the boiler level and to raise
the wheels off the floor. Turn the adjustment bolts outwards as soon as the
boiler is placed in the correct position. The figure shows the support
surface of the boiler (this is the position of the adjustment bolts).
Tab.15Dimensions A (mm)
C 630 ECOA (mm)
560723
700723
860723
10001032
11401032
13001032
Fig.12Clearance required
AD-0000511-02
C
C
C
800
300
600
800
800
1450
3050
800800
1450
3050
800800
7600532 - v.11 - 1312201827
5 Before installation
For the dimensions of C:
See
Boiler type C 630 ECO, page 17
5.2.4 Rotating the control panel
The control panel is on the front as standard, but can easily be rotated so
that it is on the short side.
AD-0000523-01
3 2x
4
90º
5
6
72x
8
9
1
2
AD-0000519-01
1789
800
L
5 Before installation
287600532 - v.11 - 13122018
Fig.13Rotating the control panel
1. Unscrew the 4 lateral retaining screws in the control panel.
2. Remove the protective cover.
3. Unscrew the 2 bottom plate screws.
4. Lift up the control panel with the bottom plate.
5. Turn the control panel and the bottom plate into position on the short
side.
6. Slide the lips of the bottom plate into the appropriate slots.
7. Tighten the 2 bottom plate screws.
8. Replace the protective cover.
9. Tighten the 4 lateral retaining screws again.
5.3
Transport
Fig.14Boiler package
Tab.16Boiler package dimensions
C 330 ECOL (mm)
2801920
3501920
4301920
5002230
5702230
6502230
Important
For work on the C 630 ECO boilers: The features and instructions
described apply to each boiler module.
The boiler is supplied fully assembled on a pallet. See the diagram and
table for the dimensions. The base of the package is a pallet 80 cm wide.
This means that it can be transported with a pallet truck or using fourwheel transport boards. Without the packaging, the boiler is 720 mm wide,