1. Do not use naked flames, do not smoke and
do not operate electrical contacts or switches
(doorbell, lighting, motor, lift etc).
2. Shut off the gas supply.
3. Open the windows.
4. Trace possible leaks and seal them off
immediately.
5. If the leak is upstream of the gas meter, notify
the gas company.
Danger
If you smell flue gases:
1. Switch the boiler off.
2. Open the windows.
3. Trace possible leaks and seal them off
immediately.
Caution
After maintenance or repair work, check the
entire heating installation to ensure that there are
no leaks.
For the end user:
Page 6
1 Safety
67600532 - v.11 - 13122018
Danger
If you smell gas:
1. Do not use naked flames, do not smoke and
do not operate electrical contacts or switches
(doorbell, lighting, motor, lift etc).
2. Shut off the gas supply.
3. Open the windows.
4. Evacuate the property.
5. Contact a qualified installer.
Danger
If you smell flue gases:
1. Switch the boiler off.
2. Open the windows.
3. Evacuate the property.
4. Contact a qualified installer.
Warning
Do not touch the flue gas pipes. Depending on
the boiler settings, the temperature of the flue gas
pipes can rise to over 60°C.
Warning
Do not touch radiators for long periods.
Depending on the boiler settings, the temperature
of the radiators can rise to over 60°C.
Warning
Be careful when using the domestic hot water.
Depending on the boiler settings, the temperature
of domestic hot water can rise to over 65°C.
Warning
The use of the boiler and the installation by you
as the end-user must be limited to the operations
described in this manual. All other actions may
only be undertaken by a qualified fitter/engineer.
Warning
The condensation drain must not be changed or
sealed. If a condensate neutralisation system is
used, the system must be cleaned regularly in
accordance with the instructions provided by the
manufacturer.
Caution
Ensure that the boiler is regularly serviced.
Contact a qualified installer or arrange a
maintenance contract for the servicing of the
boiler.
Page 7
1.2 Recommendations
7600532 - v.11 - 131220187
1 Safety
Caution
Only genuine spare parts may be used.
Important
Regularly check for the presence of water and
pressure in the heating installation.
Danger
This appliance can be used by children aged
eight and above and people with a physical,
sensory or mental disability, or with a lack of
experience and knowledge, provided they are
supervised and instructed in how to use the
appliance in a safe manner and understand the
associated dangers. Children must not be
allowed to play with the appliance. Cleaning and
user maintenance should not be carried out by
children without adult supervision.
Warning
Installation and maintenance of the boiler must be
carried out by a qualified installer in accordance
with local and national regulations.
Warning
The installation and maintenance of the boiler
must be undertaken by a qualified installer in
accordance with the information in the supplied
manual, doing otherwise may result in dangerous
situations and/or bodily injury.
Warning
Removal and disposal of the boiler must be
carried out by a qualified installer in accordance
with local and national regulations.
Warning
If the mains lead is damaged, it must be replaced
by the original manufacturer, the manufacturer's
dealer or another suitably skilled person to
prevent hazardous situations from arising.
Warning
Always disconnect the mains supply and close
the main gas tap when working on the boiler.
Warning
Check the entire system for leaks after
maintenance and servicing work.
Page 8
1 Safety
87600532 - v.11 - 13122018
Danger
For safety reasons, we recommend fitting smoke
and CO alarms at suitable places in your home.
Caution
Make sure the boiler can be reached at all
times.
The boiler must be installed in a frost-free area.
If the power cord is permanently connected, you
must always install a main bipolar switch with
an opening gap of at least 3 mm (EN 60335-1).
Drain the boiler and central heating system if
you are not going to use your home for a long
time and there is a chance of frost.
The frost protection does not work if the boiler is
out of operation.
The boiler protection only protects the boiler,
not the system.
Check the water pressure in the system
regularly. If the water pressure is lower than 0.8
bar, the system must be topped up
(recommended water pressure between 1.5 and
2 bar).
1.3
Important
Keep this document near to the boiler.
Important
Only remove the casing for maintenance and
repair operations. Refit all panels when
maintenance work and servicing are complete.
Important
Instruction and warning labels must never be
removed or covered and must be clearly legible
throughout the entire service life of the boiler.
Damaged or illegible instructions and warning
stickers must be replaced immediately.
Important
Modifications to the boiler require the written
approval of De Dietrich.
Liabilities
1.3.1 Manufacturer's liability
Our products are manufactured in compliance with the
requirements of the various Directives applicable. They
are therefore delivered with the
marking and any
Page 9
1 Safety
7600532 - v.11 - 131220189
documents necessary. In the interests of the quality of
our products, we strive constantly to improve them. We
therefore reserve the right to modify the specifications
given in this document.
Our liability as manufacturer may not be invoked in the
following cases:
Failure to abide by the instructions on installing and
maintaining the appliance.
Failure to abide by the instructions on using the
appliance.
Faulty or insufficient maintenance of the appliance.
1.3.2
Installer's liability
The installer is responsible for the installation and initial
commissioning of the appliance. The installer must
observe the following instructions:
Read and follow the instructions given in the manuals
provided with the appliance.
Install the appliance in compliance with prevailing
legislation and standards.
Carry out initial commissioning and any checks
necessary.
Explain the installation to the user.
If maintenance is necessary, warn the user of the
obligation to check the appliance and keep it in good
working order.
Give all the instruction manuals to the user.
1.3.3 User's liability
To guarantee optimum operation of the system, you
must abide by the following instructions:
Read and follow the instructions given in the manuals
provided with the appliance.
Call on a qualified professional to carry out installation
and initial commissioning.
Get your installer to explain your installation to you.
Have the required inspections and maintenance
carried out by a qualified installer.
Keep the instruction manuals in good condition close
to the appliance.
Page 10
2 About this manual
107600532 - v.11 - 13122018
2 About this manual
2.1 Additional documentation
The boiler can be fitted with various control panels. The selected control
panel is supplied with its corresponding manual.
2.2
Symbols used
2.2.1 Symbols used in the manual
This manual uses various danger levels to draw attention to special
instructions. We do this to improve user safety, to prevent problems and to
guarantee correct operation of the appliance.
Danger
Risk of dangerous situations that may result in serious personal
injury.
Danger of electric shock
Risk of electric shock.
Warning
Risk of dangerous situations that may result in minor personal
injury.
Caution
Risk of material damage.
Important
Please note: important information.
See
Reference to other manuals or pages in this manual.
Page 11
3 Technical specifications
7600532 - v.11 - 1312201811
3.1 Homologations
3.1.1 Certifications
Tab.1Certifications
CE identification numberPIN 0063CL3613
Class NOx
(1)
Type of flue gas connection
6
B23, B
23P
(2)
C33, C53, C63, C
(1) EN 15502–1
(2) When installing a boiler with connection type B23, B
boiler is lowered to
IP20.
3.1.2 Unit categories
3 Technical specifications
93
, the IP rating of the
23P
3.2
Technical data
Tab.2Unit categories
CategoryGas typeConnection pressure
(mbar)
I
2H
G20 (H gas)20
3.1.3 Directives
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines
specified in this manual.
3.1.4 Factory test
Before leaving the factory, each boiler is optimally set and tested for:
Electrical safety.
Adjustment of (O2).
Water tightness.
Gas tightness.
Parameter setting.
3.2.1 C 330 ECO technical data
Tab.3General
C 330 ECO280350430500570650
Number of sections5678910
Nominal output (Pn)
(80/60 °C)
Nominal output (Pn)
(50/30 °C)
Nominal load (Qnh)
(Hi)
min
max
max
min
max
(1)
(1)
kW279350425497574651
261
kW54
kW51
(1)
266
65
327
68
333
79
395
82
402
92
461
95
469
106
530
109
539
119
601
122
610
Page 12
3 Technical specifications
127600532 - v.11 - 13122018
C 330 ECO280350430500570650
Nominal load (Qnh)
(Hs)
Full load central heating efficiency
min
max
(1)
kW60
295
75
369
96
445
105
520
121
598
135
677
%98.098.198.298.398.498.5
(Hi) (80/60 °C) (92/42/EEC)
Full load central heating efficiency
%104.8105.2105.6106.0106.4106.8
(Hi) (50/30 °C) (EN15502)
Central heating efficiency under
%94.795.395.896.396.897.3
part load (Hi)
(Return temperature 60 °C)
Annual efficiency G20 (DIN 4702,
%109.6109.5109.4109.3109.2109.1
Part 8)
Part load central heating efficiency
%109.2109.0108.8108.6108.3108.1
(92/42 EEC)
(Return temperature 30 °C)
(1)
Factory setting
Tab.4Gas and flue gas data
C 330 ECO280350430500570650
Gas inlet pressure G20 (H gas)min
max
Gas inlet pressure G25 (L gas)min
max
Gas consumption G20 (H gas)min
max
Gas consumption G25 (L gas)min
max
NOx annual emissions G20
O2 = 0%ppm28.931.730.628.930.627
mbar17
30
mbar17
30
m3/h
5.7
28.1
m3/h
6.6
32.7
17
30
17
30
7.2
35.2
8.4
41.0
17
100
17
100
8.7
42.5
10.1
49.5
17
100
17
100
10.1
49.6
11.7
57.7
17
100
17
100
11.5
57.0
13.4
66.3
17
30
17
30
12.9
64.6
15.0
75.1
EN15502
NOx annual emissions G20
H
i
mg/kWh51.056.054.051.054.047.6
EN15502
NOx annual emissions G20
H
s
mg/kWh46.050.049.046.049.043.0
EN15502
Flue gas mass flow ratemin
max
Flue gas temperaturemin
max
Maximum counter pressure for flue
Pa
gas outlet
kg/h91
448
°C30
80
130120130150150150
114
560
30
80
138
676
30
80
160
789
30
80
183
907
30
80
205
1026
30
80
Chimney losses80/60 °C%2.32.32.32.32.32.3
Stoppage loss (EN15502)
(Including heat exchanger insula
tion kit)
(ΔT = 30K)
(1)
W
%
464
0.17
479
0.14
493
0.12
508
0.11
522
0.10
537
0.09
Number of stars (92/42/EEC)444444
(1) ΔT = (boiler temperature – ambient temperature).
Power consumption – full loadmaxW558668852108615261446
Power consumption – part loadminW9292116122124110
Power consumption – standbyminW121212121214
Electrical protection index
(1)
IPX1BX1BX1BX1BX1BX1B
Fuse – main fuse F2(A)101010101010
Fuse – PCB F1(A)222222
(1) For a room-sealed system.
Tab.13Other data
C 630 ECO560700860100011401300
Total weight (empty)kg70777183795710251095
Average acoustic level
(1)
at a dis
dB(A)585858585858
tance of 1 metre from the boiler
Ambient temperaturemax°C404040404040
(1) For a sealed installation
Page 16
AD-0000485-01
22
1500
1023
130
366320
1477
447
1293
310
706
592
716
155
2
Ø 250
C
L
920
B
A
Ø 250
1310
353
3 Technical specifications
167600532 - v.11 - 13122018
3.3 Dimensions and connections
Fig.1Dimensions C 330 ECO
3.3.1 Boiler type C 330 ECO
C 330 ECO280350430500570650
A1833 mm1833 mm1833 mm2142 mm2142 mm2142 mm
B1635 mm1635 mm1635 mm1944 mm1944 mm1944 mm
C1862 mm1862 mm1862 mm2172 mm2172 mm2172 mm
L1490 mm1490 mm1490 mm1800 mm1800 mm1800 mm
Central heating circuit flowFlange NW
Central heating circuit return Flange NW
Gas connectionG2"G2"G2"G2"G2"G2"
Condensation outletØ 32 mm (in
80 (DIN
2576)
80 (DIN
2576)
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flue gas outletØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mm
Air supplyØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mmØ 250 mm
Second return (optional)Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
65 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Flange NW
65 (DIN
2576)
Page 17
Fig.2DimensionsC 630 ECO
AD-0000509-01
B
920
869
A
641
L
C
592592
366320
22
1023
1760
1477
1293
310
155
1500
130
1726
1310
8
8353353
722
1460
7600532 - v.11 - 1312201817
3 Technical specifications
3.3.2 Boiler type C 630 ECO
C 630 ECO560700860100011401300
A1833 mm1833 mm1833 mm2142 mm2142 mm2142 mm
B1582 mm1582 mm1582 mm1892 mm1892 mm1892 mm
C1862 mm1862 mm1862 mm2172 mm2172 mm2172 mm
L1490 mm1490 mm1490 mm1800 mm1800 mm1800 mm
Central heating circuit flowFlange NW
80 (DIN
2576)
Central heating circuit return Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Gas connectionG2"G2"G2"G2"G2"G2"
Condensation outletØ 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Ø 32 mm (in
ternal)
Flue gas outletØ 350 mmØ 350 mmØ 350 mmØ 350 mmØ 350 mmØ 350 mm
Flange NW
80 (DIN
2576)
Flange NW
80 (DIN
2576)
Ø 32 mm (in
ternal)
Page 18
AD-3001123-01
PCU-06
X06
1 2 3 4
NLL
BL
BR
BR
X07
1 2 3
ION
LN
GY
BL
BK
X02
1 2
Pump
3
LN
P
X50
10 AT
LN
X04 X05
1 10
X11
1 2 3 4
14 25
WH
BR
GN
YW
X09
1 2 3 4 5 6
OT
1
On / Off
bL
3 4
RL
5 62
X08
X51
X01
1 2 3
Mains
YW/
GN
BL
BK
BL
BR
BK
BL
YW/
GN
X03
192 3 4 510 116 7 812
WHBL
RD
BK
OR
OR
YW/
WH
BR/
WH
BK/
WH
BL/
WH
SU-01
X10
SCU-D4
J6J2
N
TS + BB
LN LN
Alim
230 V - 50 Hz
L
NN L
A
+
0-10V
- 4
SCAMB S AMBB S AMPA
3 2 1 2 1 2 1 2 12
S SYST
1 2
+S ECS S EXTTA -S DEP C S DEPB
1 2 1 2 1 2 1 2 1
J9J8J8
X06
X07
X08
X02
X03
X11
X09
X04
X10
X05
X01
SU-01
J5
J2
J1
J10
J8
J9
J6
J4
J7
SU-01
3
4
5
1
2
678910 1112131415
16
3 Technical specifications
187600532 - v.11 - 13122018
C 630 ECO560700860100011401300
Air supply
Air supply manifold
Second return (optional)Flange NW
Ø 250 mm
Ø 350 mm
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
Ø 250 mm
Ø 350 mm
Flange NW
65 (DIN
2576)
3.4
Electrical diagram
Fig.3Electrical diagram
1
2
3
4
5
6
7
8
Extended PCB (SCU-D4)
Standard PCB (PCU-06)
Safety PCB (SU-01)
On/Off switch (AU)
Power supply (P)
Flow sensor (Fs)
Heat exchanger temperature sensor (HEs)
Return temperature sensor (RTs)
9
Parameter storage (PSU)
10
High limit switch (HLs)
11
Air pressure differential switch (PS)
12
Computer connection (PC)
13
Control panel (HMI)
14
Gas valve unit (GB)
15
Ignition transformer (IT)
16
Fan (FAN)
Page 19
4 Description of the product
7600532 - v.11 - 1312201819
4.1 General description
4 Description of the product
The C 330 ECO / C 630 ECO is a freestanding gas boiler with the
following characteristics:
High-efficiency heating.
Heat exchanger made of cast aluminium sections.
Limited emissions of polluted substances.
Has transport wheels as standard.
Left- or right-hand version of the water and flue gas side connections
possible.
Separable for assembly in boiler room.
DIEMATIC iSystem or IniControl control panel.
The C 630 ECO comprises a left-hand and a right-hand module. These
are combined on the flue gas side (optionally on the air side) and also in
terms of their casing.
The following boiler types are available:
4.2
Operating principle
C 330 ECO 280
C 330 ECO 350
C 330 ECO 430
C 330 ECO 500
C 330 ECO 570
C 330 ECO 650
C 630 ECO 560
C 630 ECO 700
C 630 ECO 860
C 630 ECO 1000
C 630 ECO 1140
C 630 ECO 1300
The boiler is fitted with an electronic temperature control with a flow and
return temperature sensor. The flow temperature can be adjusted between
20°C and 90°C. The boiler modulates back when the set flow temperature
is reached. The switch-off temperature is the set flow temperature + 5°C.
4.2.2 Protection against shortage of water
The boiler is fitted with protection against a shortage of water that is based
on temperature differences (difference in temperature between flow and
return). From ΔT = 25K (factory setting) the boiler reduces its output by
modulating to remain in operation as long as possible. At ΔT ≥ 25K, the
boiler goes into part load. At ΔT > 25 + 5K, the boiler goes into a normal
control stop (blocking).
4.2.3 Maximum protection
The maximum temperature protection shuts the boiler down in the event
that an excessively high water temperature (110 °C) is reached. Once the
cause of the fault has been remedied, the boiler can be unlocked by
pressing the button for 2 seconds.
4.2.4 Air pressure differential switch
Before a start and when the boiler is in operation, the air pressure
differential switch PS measures the difference in pressure between the
measuring points on the back of the heat exchanger p+ and the air box p-.
Page 20
AD-0000521-01
2
1
3
4
5
6
7
8
27
40
28
29
30
32
34
31
33
35
36
37
38
39
11
12
14
13
15
16
17
18
19
20
22
24
26
21
23
25
10
9
4 Description of the product
207600532 - v.11 - 13122018
If the pressure difference is greater than 6 mbar, then the boiler will lock
out. Once the cause of the fault has been remedied, the boiler can be
unlocked by pressing the button for 2 seconds.
4.2.5 Circulating pump
The boiler does not have a built-in pump. A circulating pump can be
installed on the connector of the standard control PCB. This can be an
on/off pump or a modulating pump (with 0 - 10 V control).
The pump settings can be changed.
See
Manual for the control panel.
For more information, see
Analogue output (Ctrl), page 44
4.3
Main components
4.3.1 Main components C 330 ECO
Fig.4
C 330 ECO
1
Flow connection
2
Air pressure differential switch
3
Flue gas outlet
4
Return connection
5
Flue gas measuring point
6
Flue gas thermostat (if present)
7
Condensate collector sealant cap
8
Pivoting castor
9
Adjustment bolt
10
Frame
11
Second return connection
12
Heat exchanger insulation kit (if present)
13
Boiler casing
14
Air supply
15
Burner
16
Adapter
17
Ignition/ionisation electrode
18
Heat exchanger
19
Inspection trap
20
Temperature sensor for heat exchanger
21
Return temperature sensor
22
Gas filter
23
Data plate
24
Siphon
25
Transport wheels
26
Adjustment bolt
27
Gas connection
28
Gas pressure measuring point
29
Control panel
30
Installation option for weather-compensated boiler
control
31
Pressure measurement point
32
Flame inspection window
33
Non-return valve
34
Fan
35
Extension piece
36
Venturi
37
Gas valve unit
38
Air supply hose
39
Document holder
40
Ignition transformer
Page 21
Fig.5C 630 ECO
AD-0000522-01
1
3
4
5
2
6
7
8
27
28
29
30
32
34
31
33
35
36
14
13
15
16
17
18
19
20
22
24
26
21
23
25
10
41
11
12
9
37
38
39
40
7600532 - v.11 - 1312201821
4 Description of the product
4.3.2 Main components C 630 ECO
1
Flow connection
2
Air pressure differential switch
3
Flue gas outlet
4
Return connection
5
Flue gas measuring point
6
Flue gas thermostat (if present)
7
Condensate collector sealant cap
8
Pivoting castor
9
Adjustment bolt
10
Frame
11
Heat exchanger insulation kit (if present)
12
Flue gas collector
13
Boiler casing
14
Air supply
15
Burner
16
Adapter
17
Ignition/ionisation electrode
18
Heat exchanger
19
Inspection trap
20
Temperature sensor for heat exchanger
21
Return temperature sensor
4.4
Control panel description
The boiler is supplied with a DIEMATIC iSystem or IniControl control
panel. The control panel is mounted in the boiler.
See
Assembly instructions for the control panel.
Manual for the control panel.
Important
For operation of the C 630 ECO boiler: each module has its own
control panel.
22
Gas filter
23
Data plate
24
Siphon
25
Transport wheels
26
Adjustment bolt
27
Gas connection
28
Gas pressure measuring point
29
Control panel
30
Installation option for weather-compensated boiler
control
31
Pressure measurement point
32
Flame inspection window
33
Non-return valve
34
Fan
35
Extension piece
36
Venturi
37
Gas valve unit
38
Air supply hose
39
Document holder
40
Ignition transformer
41
Second return connection
Page 22
4 Description of the product
227600532 - v.11 - 13122018
4.5 Standard delivery
The delivery includes:
The boiler
Complete siphon
Filling and drain valve
Gas filter
Documentation
Water quality instructions
Please fit these components in the order described in this manual.
Important
This manual only deals with the standard scope of supply. For the
installation or mounting of any accessories delivered with the
boiler, refer to the corresponding mounting instructions.
4.6
Accessories and options
Various accessories can be obtained for the boiler.
Important
Contact us for more information.
Page 23
5 Before installation
AD-0000487-01
7600532 - v.11 - 1312201823
5.1 Installation regulations
5 Before installation
Warning
The boiler must be installed by a qualified installer in accordance
with local and national regulations.
5.2
Fig.6
Choice of the location
Position of data plate
5.2.1 Data plate
The identification plate is located behind the boiler casing on the frame,
near the syphon connection. The data plate provides important information
on the boiler specifications such as the model and the device category.
5.2.2
Use the guidelines and the required installation space as a basis for
determining the correct place to install the boiler.
When determining the correct installation area, take account of the
permitted position of the flue gas outlet and/or air supply outlet.
Ensure that there is sufficient space around the boiler for good access
and ease of maintenance.
A technical clearance of at least 80 cm is required at the front (service
side) of the boiler. However, we recommend that the clearance is at
least 100 cm. Above the boiler, we recommend a clearance of at least
40 cm (when using an air inlet filter, the clearance must be at least 65
cm). A minimum of 30 cm is required on the side of the flue gas outlet,
and a minimum of 30 cm is also required on the other side (or 80 cm, if
this is operating side).
Installing the boiler C 330 ECO
Page 24
AD-0000515-01
L
R
I
I
AD-0000486-01
5555
5555
66321,5
53187,5
673
55
A
5 Before installation
247600532 - v.11 - 13122018
Danger
It is forbidden to store, even temporarily, combustible products
and substances in or near the boiler.
Caution
The boiler must be installed in a frost-free area.
An earthed electrical connection must be available close to the
boiler.
A connection to the drain must be present for the condensate
drain close to the boiler.
Fig.7Left-hand and right-hand versions
Fig.8Position of the adjustment bolts
L
Left-hand version
R
Right-hand version
I
Inspection trap (service side)
The service side with the inspection trap on the heat exchanger is
considered to be the front of the boiler. The boiler is available in both a
'left-hand' and 'right-hand' version. This means that the hydraulic
connections and the flue gas discharge are situated on either the left or
the right-hand side of the boiler. The control panel is on the front as
standard, but can easily be rotated so that it is on the short side.
The adjustment bolts must be used to make the boiler level and to raise
the wheels off the floor. Turn the adjustment bolts outwards as soon as the
boiler is placed in the correct position. The figure shows the support
surface of the boiler (this is the position of the adjustment bolts).
Tab.14Dimensions A (mm)
C 330 ECOA (mm)
280723
350723
430723
5001032
5701032
6501032
Page 25
Fig.9Clearance required
AD-0000506-02
CC
C
800
300
600
800800
720
1670
800150
720720
3190
800
800
150
720
1670
800150
C
800
300
7600532 - v.11 - 1312201825
5 Before installation
For the dimensions of C:
See
Boiler type C 330 ECO, page 16
5.2.3 Installing the boiler C 630 ECO
Use the guidelines and the required installation space as a basis for
determining the correct place to install the boiler.
When determining the correct installation area, take account of the
permitted position of the flue gas outlet and/or air supply outlet.
Ensure that there is sufficient space around the boiler for good access
and ease of maintenance.
A technical clearance of at least 80 cm is required at the front (service
side) of the boiler. However, we recommend that the clearance is at
least 100 cm. Above the boiler, we recommend a clearance of at least
40 cm (when using an air inlet filter, the clearance must be at least 65
cm). A minimum of 30 cm is required on the side of the flue gas outlet,
and a minimum of 30 cm is also required on the other side (or 80 cm, if
this is operating side).
Page 26
AD-0000514-02
AD-0000510-01
5555
55
55
21,5
21,5
87,5531
663663
53187,5
673
A
55
55
55
55
55
55
55
5 Before installation
267600532 - v.11 - 13122018
Danger
It is forbidden to store, even temporarily, combustible products
and substances in or near the boiler.
Caution
The boiler must be installed in a frost-free area.
An earthed electrical connection must be available close to the
boiler.
A connection to the drain must be present for the condensate
drain close to the boiler.
Fig.10Position of the control panel
Fig.11Position of the adjustment bolts
The boiler is not available with a choice between 'left-hand' and 'righthand' versions. The control panel is on the front as standard, but can
easily be rotated so that it is on the short side.
The adjustment bolts must be used to make the boiler level and to raise
the wheels off the floor. Turn the adjustment bolts outwards as soon as the
boiler is placed in the correct position. The figure shows the support
surface of the boiler (this is the position of the adjustment bolts).
Tab.15Dimensions A (mm)
C 630 ECOA (mm)
560723
700723
860723
10001032
11401032
13001032
Page 27
Fig.12Clearance required
AD-0000511-02
C
C
C
800
300
600
800
800
1450
3050
800800
1450
3050
800800
7600532 - v.11 - 1312201827
5 Before installation
For the dimensions of C:
See
Boiler type C 630 ECO, page 17
5.2.4 Rotating the control panel
The control panel is on the front as standard, but can easily be rotated so
that it is on the short side.
Page 28
AD-0000523-01
3 2x
4
90º
5
6
72x
8
9
1
2
AD-0000519-01
1789
800
L
5 Before installation
287600532 - v.11 - 13122018
Fig.13Rotating the control panel
1. Unscrew the 4 lateral retaining screws in the control panel.
2. Remove the protective cover.
3. Unscrew the 2 bottom plate screws.
4. Lift up the control panel with the bottom plate.
5. Turn the control panel and the bottom plate into position on the short
side.
6. Slide the lips of the bottom plate into the appropriate slots.
7. Tighten the 2 bottom plate screws.
8. Replace the protective cover.
9. Tighten the 4 lateral retaining screws again.
5.3
Transport
Fig.14Boiler package
Tab.16Boiler package dimensions
C 330 ECOL (mm)
2801920
3501920
4301920
5002230
5702230
6502230
Important
For work on the C 630 ECO boilers: The features and instructions
described apply to each boiler module.
The boiler is supplied fully assembled on a pallet. See the diagram and
table for the dimensions. The base of the package is a pallet 80 cm wide.
This means that it can be transported with a pallet truck or using fourwheel transport boards. Without the packaging, the boiler is 720 mm wide,
Page 29
Fig.15Transport element
AD-0000507-01
1107
1000
700
L
1000
7600532 - v.11 - 1312201829
5 Before installation
(without casing 700 mm), meaning that it will fit through all standard
doorways. The boiler has wheels so that, once the packaging has been
removed, it can easily be moved around.
Caution
The wheels are designed for transport purposes only and not for
use when the boiler is in its final position.
If required for internal transport, the boiler can be dismantled into smaller
parts for transport. The boiler can be stripped of:
Casing panels
Gas/air components
The frame section on the control panel side
See drawing and table for the dimensions and weight of the largest
remaining transport element (frame element with heat exchanger and
water connections).
Tab.17Boiler dimensions and weight
C 330 ECOL (mm)Weight (kg)
2801160249
3501160283
4301160317
5001469356
5701469390
6501469424
See
Refer to the installation manual supplied for information on how to
install the boiler parts.
Page 30
AD-0000488-01
1
3
2
6
4
5
6 Installation
307600532 - v.11 - 13122018
6 Installation
6.1 General
Warning
The boiler must be installed by a qualified installer in accordance
with local and national regulations.
6.2
Hydraulic connections
6.2.1 Rinsing the system
Installation must be carried out in accordance with the prevailing
regulations, codes of practice and the recommendations in this manual.
Before a new boiler can be connected to an existing or new system, the
entire system must be thoroughly cleaned and flushed. This step is
absolutely crucial. The flushing helps to remove residue from the
installation process (weld slag, fixing products etc.) and accumulations of
dirt (silt, mud etc.)
Important
Flush the system with a volume of water equivalent to at least
three times the volume of the system.
Flush the DHW pipes with at least 20 times the volume of the
pipes.
6.2.2 Connecting the heating circuit
Important
For C 630 ECO: the properties described and the instructions
apply to each boiler module.
1. Remove the dust caps from the CH flow connection and CH
return connection .
2. Fit the outlet pipe for CH water to the CH flow .
3. Fit the inlet pipe for CH water to the CH return .
4. Connect a safety valve to the boiler's flow connection.
5. Connect the pump to the boiler's return connection.
Always connect the boiler in a way that will guarantee the water flow
through the unit during operation. When the boiler is used in a system with
two return pipes, the return pipe must be used as a cold return. The
second return pipe (if connected) is then used as a hot return. Contact us
for more information.
The flow pipe is fitted with the following components:
Fig.16Flow pipe
1 Immersion tube for a temperature sensor for an external control
Caution
If using synthetic pipes, follow the manufacturer's (connection)
instructions.
6.2.3 Connecting the condensate discharge pipe
Important
For C 630 ECO: the properties described and the instructions
apply to each boiler module.
1. Fit a plastic drain pipe of Ø 32 mm or larger to the siphon, terminating
in the drain.
Caution
Use only plastic material for the discharge pipe due to the
acidity (pH 2 to 5) of the condensate.
Do not make a fixed connection in order to prevent an
overpressure in the siphon.
2. Fit a stench-trap or siphon in the drain pipe.
Caution
Never seal the condensate drain.
The drain pipe must slope down at least 5 - 10 mm per metre,
the maximum horizontal length is 5 metres.
Condensed water must not be discharged into a gutter.
6.3
6.4
Gas connection
Important
For C 630 ECO: the properties described and the instructions
apply to each boiler module.
Warning
Before starting work on the gas pipes, turn off the main gas tap.
Before installing, check that the gas meter has sufficient
capacity. Take into account the consumption of all appliances.
Notify the local energy company if the gas meter has insufficient
capacity.
1. Remove the dust cap on the gas connection .
2. Fit the gas supply pipe to the gas supply .
3. Also fit a gas isolation valve in this pipe, near the boiler.
Caution
Remove dirt and dust from the gas pipe.
Always perform welding work at a sufficient distance from the
boiler.
The boiler is fitted with a gas filter as standard.
Air supply/flue gas connections
The boiler is suitable for the following types of flue gas connections:
See
Certifications, page 11.
Follow applicable local guidelines when connecting the flue gas discharge
and air supply pipes to the boiler. The diameters of the pipes must be
defined in accordance with the standards in force in your country. The total
resistance of the flue gas outlet and air inlet must not exceed the
maximum acceptable resistance.
Page 32
AD-3001120-01
EN 14471 - T120 P1 W 1 O50 LI E U0
EN 1856-1 - T120 P1 W VxL40045 G(xx)
1
3
2
4
5
6 Installation
327600532 - v.11 - 13122018
Important
With room-sealed operation, make sure the dirt trap in the boiler
air supply remains accessible. For example, fit a T piece with an
inspection trap in the air supply pipe directly above the boiler.
With a flue gas connection of two or more C 330 ECO boilers,
certain fan speeds need to be changed. Change the values of
relevant parameters for each boiler in the flue gas connection.
Set them to the values as specified in the parameter table for
the C 630 ECO boiler.
6.4.1 Material
Use the string on the flue gas outlet material to check whether it is suitable
for use on this appliance.
Fig.17Sample string
1
EN 14471 of EN 1856–1: The material is CE approved according to
this standard. For plastic this is EN 14471, For aluminium and
stainless steel this is EN 1856-1.
2
T120: The material has temperature class T120. A higher number
is also allowed, but not lower.
3
P1: The material falls into pressure class P1. H1 is also allowed.
4
W: The material is suitable for draining condensation water
(W=’wet’). D is not allowed (D=’dry’).
5
E: The material falls into fire resistance class E. Class A to D are
also allowed, F is not allowed. Only applicable to plastic.
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof feed-throughs and common channels.
The materials used must comply with the prevailing regulations
and standards.
Temperature class T120 or
higher
Condensate class W (wet)
Plastic
Stainless steel
Aluminium
Pressure class P1 or H1
Fire resistance class E or bet
(3)
ter
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
With CE marking
Pressure class P1 or H1
Fire resistance class E or bet
(3)
ter
Page 33
6.4.2 Dimensions of flue gas outlet pipe
AD-3001094-01
ød
1
AD-0000562-01
L =
7600532 - v.11 - 1312201833
Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
6 Installation
Fig.18Dimensions of open connection
d
External dimensions of flue gas outlet pipe
1
Tab.19Dimensions of pipe
d1 (min-max)
250 mm249 - 251 mm
350 mm349 - 351 mm
6.4.3 Length of the air and flue gas pipes
The maximum length of the flue gas outlet and air supply channel vary
depending on the appliance type; consult the relevant chapter for the
correct lengths.
Important
When using bends, the maximum chimney length (L) must be
shortened according to the reduction table.
For adaptation to another diameter use approved transitions
Room-ventilated model (B23, B
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler
obtains the necessary combustion air directly from the installation area.
23P
)
Fig.19Room-ventilated version C 330
ECO
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
If the boiler, in room-ventilated operation, has been set up in a
(very) dusty room, use the air supply filter (accessory).
Use of the air inlet filter is compulsory when the boiler is
exposed to building dust.
L
Length of the flue gas outlet channel to roof feed-through
Flue gas outlet
Tab.20Maximum length for open design
C 330 ECO
Maximum length L (in metres)
Ø 150 mm Ø 180 mm Ø 200 mm Ø 250 mm
(1)
28020505050
35011305050
4308223950
5007183250
5705132450
6505122150
(1) Calculated with rigid tube and discharge without cover ( "free" opening)
Page 34
AD-0000560-01
L =
AD-0000557-01
L = +
AD-0000561-01
L = +
6 Installation
347600532 - v.11 - 13122018
Fig.20
Room-ventilated version C 630
ECO
Fig.21Room-sealed version C 330 ECO
L
Length of the flue gas outlet channel to roof feed-through
Flue gas outlet
Tab.21Maximum length for open design
C 630 ECO
Maximum length L (in metres)
Ø 250 mmØ 300 mmØ 350 mm
(1)
560505050
700315050
860205050
1000113950
114052650
130031950
(1) Calculated with rigid tube and discharge without cover ( "free" opening)
Room-sealed model (C33, C63, C93)
With a room-sealed version, both the flue gas outlet and the air supply
openings are connected (in parallel).
L
Combined length of the flue gas outlet and air supply channel to
the roof feed-through
Flue gas outlet
Air supply
Tab.22Maximum length for room-sealed operation
C 330 ECO
Maximum length L (in metres)
Ø 200 mmØ 250 mmØ 300 mm
280425050
350215050
430135050
500105050
57053450
65043050
(1) Calculated with rigid tube and discharge without cover ( "free" opening)
(1)
Fig.22Room-sealed version C 630 ECO
L
Combined length of the flue gas outlet and air supply channel to
the roof feed-through
Flue gas outlet
Air supply
Tab.23Maximum length for room-sealed operation
C 630 ECO
Maximum length L (in metres)
Ø 300 mmØ 350 mmØ 400 mm
(1)
560505050
700435050
860265050
1000133550
114051624
1300—1012
(1) Calculated with rigid tube and parallel 350 mm top conduit
Connection in different pressure areas (C53)
Combustion air supply and flue gas discharge are possible in different
pressure areas and semi-CLV systems, with the exception of the coastal
area. The maximum permitted height difference between the combustion
air supply and the flue gas outlet is 36 m.
Page 35
AD-0000558-01
L = +
AD-0000559-01
L = +
6 Installation
7600532 - v.11 - 1312201835
Fig.23
Various pressure zones C 330 ECO
Fig.24Various pressure zones C 630 ECO
L
Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
Tab.24Maximum length in the various pressure zones
C 330 ECO
Maximum length L (in metres)
Ø 250 mm
(1)
28050
35050
43050
50050
57049
65040
(1) Calculated with rigid tube and 90° bend and discharge without cover ( "free"
opening)
L
Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
Tab.25Maximum length in the various pressure zones
C 630 ECO
Maximum length L (in metres)
Ø 350 mmØ 400 mm
(1)
5605050
7005050
8605050
10003350
1140—22
1300——
(1) Calculated with rigid tube and 90° bend and discharge without cover ( "free"
opening)
Reduction table
Tab.26Pipe reduction for each element used
Diameter
Pipe reduction (in metres)
45° bend90° bend
150 mm1.22.1
180 mm1.42.5
200 mm1.62.8
250 mm2.03.5
300 mm2.44.2
350 mm2.84.9
400 mm3.25.6
6.4.4
Additional guidelines
Installation
For installing the flue gas outlet and air supply materials, refer to the
instructions of the manufacturer of the relevant material. After
installation, check at least all flue gas outlet and air supply parts for
tightness.
Page 36
6 Installation
367600532 - v.11 - 13122018
Warning
If the flue gas outlet and air supply materials are not installed in
accordance with the instructions (e.g. not leak-proof, not correctly
bracketed), this can result in dangerous situations and/or physical
injury.
Make sure that the flue gas outlet pipe towards the boiler has a sufficient
gradient (at least 50 mm per metre) and that there is a sufficient
condensate collector and discharge (at least 1 m before the outlet of the
boiler). The bends used must be larger than 90° to guarantee the
gradient and a good seal on the lip rings.
Condensation
Direct connection of the flue gas outlet to structural ducts is not
permitted because of condensation.
If condensate from a plastic or stainless steel pipe section can flow back
to an aluminium part in the flue gas outlet, this condensate must be
discharged via a collector before it reaches the aluminium.
Important
Contact us for more information.
6.4.5 Connecting the flue gas outlet
The boiler is equipped with a mechanical flue gas non-return valve as
standard. This prevents flue gases from flowing back into the boiler when
it is not in operation (cascade settings for example).
Proceed as follows to connect the flue gas outlet:
1. Fit the flue gas outlet pipe to the boiler.
2. Fit the subsequent flue gas outlet pipes in accordance with the
manufacturer's instructions.
Caution
The pipes must be flue gas-tight and corrosion-resistant.
The materials used must comply with the prevailing regulations
and standards.
The flue gas outlet pipe must be smooth and deburred.
Connect the pipes so that they are stress-free.
The pipes must not rest on the boiler or flue gas adapter.
Fit the horizontal parts sloping down towards the boiler, with a
slope of 50 mm per metre.
Maximum bracket spacing for vertical pipes is 2 m.
Maximum tilt of vertical pipes is 20 mm per meter.
Use a bracket at each connection for horizontal pipes.
6.4.6 Air supply connection
1. Fit the air supply pipe to the boiler.
2. Fit the subsequent air supply pipes in accordance with the
manufacturer's instructions.
Page 37
Caution
7600532 - v.11 - 1312201837
The pipes must be flue gas-tight and corrosion-resistant.
The air supply pipe must be smooth and deburred.
Connect the pipes so that they are stress-free.
Maximum bracket spacing for vertical pipes is 2 m.
Maximum tilt of vertical pipes is 20 mm per meter.
The pipes must not rest on the boiler or air supply adapter.
Fit the horizontal parts sloping down towards the air supply
outlet.
Use a bracket at each connection for horizontal pipes.
6 Installation
6.5
Electrical connections
6.5.1 General
Important
For connections for the C 630 ECO boiler: the properties
described and the instructions apply to each boiler module.
6.5.2 Recommendations
Warning
Electrical connections must always be made with the power
supply disconnected and only by qualified installers.
The boiler is completely pre-wired. Never change the internal
connections of the control panel.
Always connect the boiler to a well-earthed installation.
Establish the electrical connections in accordance with:
The instructions of the current standards.
The instructions of the wiring diagrams supplied with the boiler.
The recommendations in this manual.
Separate the sensor cables from the 230 V cables
Caution
Outside the central heating boiler: Use 2 cables spaced at least
10 cm apart.
6.5.3 Control unit
The table gives important connection values for the control unit.
Tab.27Connection values for control unit
Supply voltage230 VAC/50 Hz
Main fuse value F2 (230 VAC)10 AT
Fuse value F1 (230 VAC)2 AT
Fan230 VAC
Page 38
N L
Mains
N L
PUMP
ON/OFF
OT BL
3
1
2
4
AD-0000498-01
6 Installation
387600532 - v.11 - 13122018
Danger of electric shock
The following components of the boiler are connected to a 230 V
power supply:
(Electrical connection of) circulation pump on connector
(Electrical connection of) combined gas valve unit
(Electrical connection of) fan
The majority of components in the control unit
Ignition transformer
(Connection of) supply cable
Caution
Observe the polarities shown on the terminals: live (L), neutral (N)
and earth .
The boiler has phase detection. The boiler is completely pre-wired. The
boiler is suitable for a 230 VAC/50 Hz supply with live/neutral/earth. Other
connection values are only acceptable if an isolating transformer is
installed. Connect the wires of the mains lead to the correct terminal block.
This can be found on the left underneath the MAINS connector. (The
mains lead is not supplied).
Fig.25
Mains connection
1
Fuse (F1)
2
Pre-wired in the boiler (PW)
3
Main fuse (F2)
4
Three-wired mains lead (M)
Caution
Always order a replacement mains lead from De Dietrich. The
power supply cable should only be replaced by De Dietrich, or
by an installer certified by De Dietrich.
In the case of a fixed connection of the mains lead, you must
always install a main bipolar switch with a contact gap of at least
3 mm.
Important
The boiler has a unique boiler code. This, together with other data,
including the boiler type, counter readings, etc. is stored in what is
known as a PSU that belongs with the boiler. If the control unit is
replaced, the counter readings remain stored in it.
The boiler has several control, protection and regulation connection
options. The heat output of the boiler can be controlled as follows:
Modulating control: the output varies between the minimum and
maximum value on the basis of the value defined by the controller.
Analogue control: where the heat output or the temperature is controlled
by a 0-10 V signal.
(Standard with DIEMATIC iSystem – only available in combination with
the control PCB SCU-05 or IF-01 with IniControl.)
On/off control: where the heat output modulates between the minimum
and maximum value on the basis of the flow temperature set in the
boiler.
Page 39
6.5.4 Access to the connectors
AD-0000489-01
N L
Mains
N L
PUMP
ON/OFF
OT RLBL
14b
2
4a
3c
3c
3a
3b
3b
3b
3
N L
Mains
N L
PUMP
ON/OFF
OTRLBL
AD-0000494-01
7600532 - v.11 - 1312201839
6 Installation
Fig.26Access to the connectors
The SU protection PCB, which protects the boiler, is connected to the
standard PCU-06 PCB. Various thermostats and regulators can be
connected to the standard PCB.
Important
A clearance of 20 cm is required above the control panel to allow
the front cover to open fully. Bear this in mind when installing
cable ducts.
1. Unscrew the 4 lateral retaining screws in the control panel.
2. Remove the protective cover.
The detachable screw connectors are now accessible.
3. Secure the cable(s) using the traction clips (the traction clips are
supplied loose).
4. Screw the strain relief clamps securely into position and close the
control panel.
Fig.27Connecting the on/off thermostat
6.5.5 Connection options for the standard PCB
Connecting the on/off thermostat
Important
This function is only available with the IniControl control panel.
The boiler is suitable for connection to a 2-wire on/off thermostat.
1. Install the thermostat in a reference room.
2. Connect the two-wire cable of the thermostat to the On/Off OT
terminals of the connector. It does not matter which wire is connected
to which cable clamp.
Page 40
N L
Mains
N L
PUMP
ON/OFF
OTRLBL
AD-0000494-01
AD-0000495-01
N L
Mains
N L
PUMP
ON/OFF
OTRLBL
AD-0000496-01
N L
Mains
N L
PUMP
ON/OFF
OTRLBL
6 Installation
407600532 - v.11 - 13122018
Connecting the modulating thermostat
Important
This function is only available with the IniControl control panel
Fig.28Connecting the modulating
thermostat
Fig.29Blocking input
The boiler is fitted with an OpenTherm connection as standard. As a
result, modulating OpenTherm thermostats can be connected without any
further adjustments.
1. In the case of a room thermostat: install the thermostat in a reference
room.
2. Connect the two-wire cable of the thermostat to the On/Off OT
terminals of the connector. It does not matter which wire is connected
to which cable clamp.
Blocking input
The boiler has a blocking input (normally closed contact). If this contact is
opened, the boiler will be blocked or locked out. This input can be used for
example in combination with the flue gas thermostat (if present). This input
relates to the BL terminals of the connector.
Warning
Only suitable for potential-free contacts.
Important
First remove the bridge if this input is used.
Fig.30Release input
A parameter setting can be used to change the function of the input.
See
Manual for the control panel.
Release input
The boiler has a release input (normally open contact). If this contact is
closed when there is a heat demand, the burner will be blocked after a
waiting time. This input can be used, for example, in combination with the
limit switches on flue gas dampers, hydraulic shutter valves, etc. This input
relates to the RL terminals of the connector.
Warning
Only suitable for potential-free contacts.
A parameter setting can be used to change the input waiting time.
See
Manual for the control panel.
Page 41
Fig.31Connecting the pump
AD-0000497-01
N L
Mains
N L
PUMP
ON/OFF
OTRLBL
AD-0000503-01
7600532 - v.11 - 1312201841
6 Installation
Connecting the circulating pump
The boiler is supplied without a pump. An external CH pump may be
connected:
1. Connect an external CH pump to the Pump terminals of the
connector.
Maximum power consumption may be 300 VA.
For more information about controlling a modulating pump:
See
Connection options for the SCU-S05 control PCB, page 43
Connecting a PC/laptop
Fig.32Connecting a PC/laptop
A PC or laptop can be connected to the RS232 input using a USB cable.
Using the Recom PC/laptop service software, you can enter, change and
read out various boiler settings.
Page 42
AD-4000058-01
SCU-D4
N
TS + BB
LN LN
Alim
230 V - 50 Hz
LNN L
A
2
S SYST
1 2
+S ECS S EXTTA -S DEPC S DEP B
1 2 1 2 1 2 1 2 1
+
0-10V
- 4
SCAMB SAMBB S AMPA
3 2 1 2 1 2 1 2 1
J10
J7
J4
J6
J5
J2
J1
J9
J8
AD-0000530-01
54 +
4
14x
2
3
6 Installation
427600532 - v.11 - 13122018
6.5.6 PCBs
Fig.33Open housing for PCBs
The PCBs are positioned in the PCB housing behind the control panel.
1. Unscrew the 4 lateral retaining screws in the control panel.
2. Remove the protective cover.
3. Open the front cover.
4. Use both thumbs to press the top of the control panel downwards a
little.
5. While maintaining some of the pressure you are applying to the top of
the control panel, use both hands to tip the casing forwards and
upwards.
Fig.34SCU-D4 control PCB
Connection options for the SCU-D4 control PCB
For connection options to the SCU-D4 control PCB:
Page 43
See
AD-0000508-01
X2
SCU-S05
X1
X3
X7X6X4 X5
N L
N
L
EgV
N L
EgV
N L
HdV
N L
HdV
N L
FgV
FgV
X9
X8
+0 S
+0
Wps
S
Gps
Gps
VPS
VPS+0+0+0
+0
Ctrl0-10
Pump
N L
N
Pump
L
NoNc C
NoNc C
Status
NoNc C
NoNc C
Status
Tout
Tout
AD-0000546-01
N L
N L
FgV
FgV
AD-0000547-01
HdV
N L
HdV
N L
AD-0000548-01
EgV
N L
EgV
N L
AD-0000549-01
Pump
N L
N
Pump
L
AD-0000550-01
NoNc C
NoNc C
Status
NoNc C
NoNc C
Status
7600532 - v.11 - 1312201843
Manual for the control panel.
Connection options for the SCU-S05 control PCB
6 Installation
Fig.35SCU-S05 control PCB
Fig.36FgV connection
Fig.37Connecting the HdV
The extended SCU-S05 control PCB is available as an accessory.
Important
On removing this PCB, the boiler will display an error code. To
prevent this error, an auto-detect must be carried out after
removing this PCB.
See
Manual for the control panel.
Connecting the flue damper (FgV)
Not applicable.
Connecting the hydraulic valve (HdV)
In a cascade configuration, a hydraulic valve prevents heat loss in the
system when the boiler is not running.
1. Connect the hydraulic valve to the HdV terminals of terminal strip.
2. Change the hydraulic valve running time with a parameter setting.
See
Manual for the control panel.
Connecting the external gas valve (EgV)
Fig.38EgV connection
DIEMATIC iSystem: This function is available as standard.
IniControl: If there is a heat demand, an alternating voltage of 230 VAC, 1
A (maximum) becomes available at the EgV terminals of the connector to
control an external gas valve.
Connecting a shunt pump
Fig.39Connecting the pump
If required, a shunt pump may also be installed on the Pump terminals of
the connector. Only an on/off pump can be controlled. The maximum
power consumption is 300 VA. The pump is activated for certain
blockages.
See
Manual for the control panel.
Operation signal and error signal (status)
Fig.40Status of connections
DIEMATIC iSystem: Connect to the A.Tel output of the boiler.
IniControl: The choice of an alarm or operation signal can be set on
connectors X4 or X5 using a parameter setting.
See
Manual for the control panel.
Page 44
AD-0000551-01
+0
+0
Ctrl
AD-0000516-01
1 2 3 4 5 6 7 8 9 10
U
R
1
2
3
AD-0000517-01
R
1 2 3
4 5 6 7 8 9 10
1
2
3
U
6 Installation
447600532 - v.11 - 13122018
If the boiler is operating, the operation signal can be switched via a
potential-free contact (maximum 230 VAC, 1 A) on the No and C
terminals of the connector.
If the boiler is locked out, the alarm signal can be transmitted via a
potential-free contact (maximum 230 VAC, 1 A) on the Nc and C
terminals of the connector.
Analogue output (Ctrl)
Fig.41Ctrl connection
Fig.42Wilo pump
An outgoing 0 - 10 V signal can be used either to report the supplied heat
output or the supplied temperature.
An outgoing 0 - 10 V signal can be used to adjust the speed of the system
pump (possible only if the pump is suitable for this).
The function of the analogue output can be changed with a parameter
setting.
See
Manual for the control panel.
Control of the 0-10 V Wilo system pump
1
Maximum pump speed
2
Minimum pump speed
3
The pump is off
R
Pump speed
U
Output signal (V)
Tab.28Output signal
Output signal (V)Description
<1Pump off
1 - 2Hysteresis
2 - 3Pump on (minimum pump speed
3 - 10Pump modulating (linear)
Control of the 0-10 V Grundfos system pump
Fig.43Grundfos pump
1
Maximum pump speed
2
Nominal set-point
3
Minimum pump speed
R
Pump speed
U
Output signal (V)
Tab.29Output signal
Output signal (V)Description
< 0.5Pump on (minimum pump speed
> 0.5Pump modulating (linear)
Control of the PWM system pump
In this case, the 0 - 10 V signal controls the system pump linearly.
Tab.30Message about the supplied temperature
Output signal (V)Temperature in (°C)Description
0.5-Lock out
1 - 1010 - 100Supplied temperature
Page 45
Fig.440 - 10 V connection
AD-0000552-01
+0
+0
0-10
AD-0000553-01
+0 S
+0
Wps
S
7600532 - v.11 - 1312201845
6 Installation
Tab.31Message about the supplied heat output
Output signal (V)Heat output (%)Description
00Boiler off
0.5-Lock out
2.0 - 10
(1)
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
20 - 100Supplied heat output
Analogue input (0 - 10 V)
A choice can be made with this control between control based on
temperature or heat output. If this input is used for 0-10 V control, the OT
communication from the boiler is ignored.
1. DIEMATIC iSystem: Connect to the ING.0–10V input of the boiler. For
settings:
See
Manual for the control panel.
2. IniControl: Connect the input signal to terminals 0–10 of the
connector.
The function of the analogue input can be changed with a parameter
setting.
See
Manual for the control panel.
Tab.32Temperature-based control (°C)
Jumper 2 Input signal (V)Temperature °C Description
0–1.50–15Boiler off
1.5–1.815–18Hysteresis
1.8–1018–100Desired temperature
The 0–10 V signal controls the boiler supply temperature. This control
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
Tab.33Control based on heat output
Jumper 2 Input signal (V)Heat output (%)Description
(1)
0–2.0
2.0–2.2
2.0–10
(1)
(1)
%
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
0–20Boiler off
20–22Hysteresis
20–100Required output
The 0–10 V signal controls the boiler output. This control modulates on the
basis of the heat output. The minimum output is linked to the boiler's
modulation depth. The output varies between the minimum and maximum
value on the basis of the value defined by the controller.
Connecting the hydraulic pressure sensor (Wps)
Fig.45Wps connection
The hydraulic pressure sensor registers the water pressure and can shut
the boiler down when the minimum water pressure is reached. To activate
this blocking option, a minimum pressure must be set.
See
Manual for the control panel.
Page 46
AD-0000554-01
Tout
Tout
AD-3000038-01
01020
-20
-10
10
30
70
50
90
F
1
3
4
2
AD-0000555-01
Gps
Gps
6 Installation
467600532 - v.11 - 13122018
Fig.46Connecting an outside sensor
1. Connect the water pressure sensor to the Wps terminals of the
terminal strip.
0 = Earth or neutral of the power supply
S = Signal or output from the sensor
+ = Supply voltage
Connecting an outside sensor
DIEMATIC iSystem: The outside sensor must be connected to the S.EXT
input.
IniControl: An outside sensor can be connected to the Tout terminals of
the connector. In the event of an on/off thermostat, the boiler will regulate
the temperature using the set point of the internal heating curve (
1. Connect the two-wire cable to the Tout terminals of the connector.
Important
An OpenTherm controller can also use this outside sensor. In that
case, the desired internal heating curve must be set on the
controller.
F).
Fig.47Heating curve
Fig.48Gps connection
1 Flow temperature setting (T
set
)
2 Heating curve set point (minimum outside temperature)
3 Heating curve set point (flow temperature)
4 Heating curve set point (maximum outside temperature)
F Heating curve
If an outside temperature sensor is connected, it is possible to adapt the
internal heating curve. Various parameter settings can be used to change
the internal heating curve.
See
Manual for the control panel.
Connecting the minimum gas pressure switch (Gps)
The minimum gas pressure switch blocks the boiler if the gas inlet
pressure drops too low. Check the setting for the Gps minimum gas
pressure switch (see table below).
Tab.34Setting the minimum gas pressure switch
C 330 ECOMinimum value (mbar)
28014
35013
43010
50010
57010
65010
1. Connect the minimum gas pressure switch to the Gps terminals of the
connector
2. Set the presence of the gas pressure switch using a parameter
setting.
See
Manual for the control panel.
Page 47
Fig.49VPS connection
AD-0000556-01
VPS
VPS
7600532 - v.11 - 1312201847
6 Installation
Connecting the gas leakage control (VPS)
The gas leakage control checks and controls the safety valves on the gas
valve unit. The test takes place before the boiler starts up. In the event of
a leak in the gas valve unit, the boiler will lock out. The pressure switch
must be set at 50% of the supply pressure (see table below).
Tab.35Setting the gas pressure switch
C 330 ECOGas inlet pressure
(max.)
(mbar)
2803015
3503015
43010040
50010040
57010040
6503015
1. Connect the gas leakage control to the VPS terminals of the terminal
strip.
2. Set the presence of the gas leakage control using a parameter setting.
Vps setting (max.)
(mbar)
See
Manual for the control panel.
6.6
Filling the installation
6.6.1
Water treatment
In many cases, the boiler and central heating system can be filled with
normal tap water and water treatment will not be necessary.
Warning
Do not add chemical products to the central heating water without
first consulting a water treatment professional. For example:
antifreeze agent, water softeners, pH-increasing or -lowering
agents, chemical additives and/or inhibitors. Such agents can
cause faults in the boiler and damage to the heat exchanger.
For optimum functioning of the boiler, the water in the installation must
comply with following characteristics:
Tab.36Total installed heat output (kW)
≤ 7070-200200-550> 550
Degree of acidity (untreated water)pH7-97-97-97-9
Degree of acidity (treated water)pH7-8.57-8.57-8.57-8.5
Conductivity at 25°CμS/cm≤ 800≤ 800≤ 800≤ 800
Chloridesmg/l≤ 150≤ 150≤ 150≤ 150
Other componentsmg/l< 1< 1< 1< 1
Total hardness of the water
(1)
°f1-351-201-151-5
°dH0.5-20.00.5-11.20.5-8.40.5-2.8
mmol/l0.1-3.50.1-2.00.1-1.50.1-0.5
(1) For installations that are heated at constant high temperatures with a total installed heat output up to 200 kW, maximum total water
hardness of 8.4°dH (1.5 mmol/l, 15°f) applies and for above 200 kW a maximum total water hardness of 2.8°dH (0.5 mmol/l, 5°f) applies
Page 48
AD-0000500-01
1
2
AD-0000512-01
6 Installation
487600532 - v.11 - 13122018
Important
If water treatment is necessary, De Dietrich recommends the
following manufacturers:
Cillit
Climalife
Fernox
Permo
Sentinel
6.6.2 Filling the siphon
Fig.50Filling the siphon
1. Fill the siphon with water up to the mark using the condensate
collector.
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
Warning
Put the sealing cap back on the condensate collector.
6.6.3 Filling the installation
Fig.51Filling the installation
1. Disconnect the boiler from the power supply.
2. Fill the central heating system with clean tap water.
Important
The recommended water pressure is between 1.5 bar and 2 bar.
3. Check the water-side connections for tightness.
4. Power up the boiler.
Important
DIEMATIC iSystem: If the water pressure is below 0.8 bar, the
symbol will flash (only if a hydraulic pressure sensor is
connected). If the water pressure is too low, top up the central
heating system.
IniControl: Check the water pressure that is shown on the
display (only if a hydraulic pressure sensor is connected). If the
water pressure is lower than 0.8 bar, top up the central heating
system.
A filling and drain valve (½") is fitted on the front section as
standard.
Page 49
7 Commissioning
C
AD-0000518-01
7600532 - v.11 - 1312201849
7.1 Checklist before commissioning
7 Commissioning
Warning
Do not put the boiler into operation if the type of gas supplied does
not conform to the approved gas types.
1. Check that the gas type supplied matches the data shown on the
boiler's data plate.
2. Check the gas circuit.
3. Check the hydraulic circuit.
4. Check the water pressure in the central heating system.
5. Check the electrical connections of the thermostat and the other
external connections.
6. Check the other connections.
7. Test the boiler at full load. Check the setting of the gas/air ratio and
correct it, if necessary.
8. Test the boiler at part load. Check the setting of the gas/air ratio and
correct it, if necessary.
9. Final activities.
Fig.52Gas inlet pressure measuring point
7.1.1
1. Open the main gas tap.
2. Open the boiler gas tap.
3. Remove the casings on the inspection side.
4. Check the gas inlet pressure at measuring point C on the gas pipe.
5. Check the tightness of the gas pipe, including the gas taps.
6. Vent the gas supply pipe by unscrewing measuring point C.
7. Tighten the measuring point again when the pipe has been fully
7.1.2
1. Check the water pressure in the central heating system.
2. Check the siphon; it should be fully filled with clean water.
3. Check the water-side connections for tightness.
Gas circuit
Warning
Ensure that the boiler is disconnected from the power supply.
Warning
The pressure must be the same as the one shown on the data
plate.
vented.
Hydraulic circuit
If necessary, top up the central heating system.
7.1.3 Connections for the air and flue gas pipes
1. Check the flue gas outlet and air supply connections for tightness.
7.1.4 Electrical connections
1. Check the electrical connections.
Page 50
AD-0000532-01
21
AD-4000059-01
7 Commissioning
507600532 - v.11 - 13122018
7.2 Commissioning procedure
Warning
Initial commissioning must be done by a qualified professional.
If adapting to another type of gas the boiler must be adjusted
before switching it on.
See
Adaptation to a different gas type, page 0
1. Open the main gas tap.
2. Open the boiler gas tap.
3. Switch the power on with the boiler's on/off switch.
4. Set the components (thermostats, control) so that heat is demanded.
The start-up program will start and cannot be interrupted. During the
start-up cycle, all segments of the display are shown briefly.
Error during start-up procedure:
In the event of a fault, a message with the corresponding code is
displayed.
The meaning of the error codes can be found in the error table.
See
Manual for the control panel.
7.3 Gas settings
Fig.53
Fig.54Setting to full load
Flue gas measuring point
7.3.1 Checking/setting the combustion
Important
Checking and/or setting the boiler C 630 ECO: the properties
described and the instructions apply to each boiler module. Make
sure that the other boiler module is out of operation during this
check and/or setting.
1. Unscrew the cap from the flue gas measuring point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
Warning
During measurement, seal the opening around the sensor fully.
Important
The flue gas analyser must have a minimum accuracy of ±0.25%
O2.
3. Measure the percentage of O2 in the flue gases. Take measurements
at full load and at part load.
Performing the full load test (IniControl)
1. Press the two keys at the same time.
The symbol appears on the display. The boiler is now set to full
load.
Page 51
Performing the full load test (DIEMATIC iSystem)
MW-C002271-02
STD
(
'
t
p
b
AUTO
x
c
r
j
M
g
m
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
g
m
r
j
M
GENE :
BOILER TEMP.
CURRENT
WIND SPEED
PMAX
68°C
10µA
5600 tr/min
a
C002347-F-04
AUTO => PMAX
7600532 - v.11 - 1312201851
7 Commissioning
Fig.55
Fig.56
1. From the start page, press the key.
The EMISSION MESURMENTS menu appears on the display.
2. Turn the rotary button until PMAX is displayed.
3. Confirm the selection.
The boiler is now set to full load.
Checking/setting values for O2 at full load
1. Measure the percentage of O2 in the flue gases.
2. Compare the measured value with the checking values in the table.
Tab.37Checking/setting values O2 at full load for G20 (H gas)
Values at full load for G20 (H gas)
C 330 ECO
C 630 ECO
(1) Nominal value
O2 (%)
4.3 - 4.8
4.3 - 4.8
(1)
(1)
(1)
Caution
The O2 values at full load must be lower than the O2 values at low
load.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
Page 52
AD-0000492-01
O
A
A
3
AD-4000060-01
MW-C002271-02
STD
(
'
t
p
b
AUTO
x
c
r
j
M
g
m
7 Commissioning
527600532 - v.11 - 13122018
Fig.57
Adjusting screw A
4. Using the adjusting screw A, set the percentage of O2 for the gas type
being used to the nominal value. This should always be inside the
highest and lowest setting limit. The direction in which the adjusting
screw must be turned to increase or decrease the gas flow is
indicated on the gas valve unit.
Important
The 5- to 9-section boilers are supplied with a different gas valve
unit from the 10-section boiler. See drawing for the position of
adjusting screw A for full load.
5. Check the flame through the inspection window.
Important
The flame must not blow off.
Fig.58Setting to low load
Fig.59
Performing the low load test (IniControl)
1. Press the key several times until appears on the display.
The boiler is now set to low load.
Performing the low load test (DIEMATIC iSystem)
1. From the start page, press the key.
The EMISSION MESURMENTS menu appears on the display.
2. Turn the rotary button until PMIN is displayed.
Page 53
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
g
m
r
j
M
GENE :
BOILER TEMP.
CURRENT
WIND SPEED
PMIN
68°C
10µA
1850 tr/min
a
C002348-F-04
AUTO => PMIN
AD-0000493-01
B
3
B
2.5
7 Commissioning
7600532 - v.11 - 1312201853
Fig.60
3. Confirm the selection.
The boiler is now set to low load.
Checking/setting values for O2 at low load
1. Measure the percentage of O2 in the flue gases.
2. Compare the measured value with the checking values in the table.
Tab.38Checking and setting values for O2 at low load for G20 (H
gas)
Values at low load for G20 (H gas)
C 330 ECO
C 630 ECO
(1) Nominal value
O2 (%)
(1)
4.8
- 5.4
(1)
4.8
- 5.4
(1)
Fig.61Adjusting screw B
Caution
The O2 values at low load must be higher than the O2 values at
full load.
3. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
4. Using the adjusting screw B, set the percentage of O2 for the gas type
being used to the nominal value. This should always be inside the
highest and lowest setting limit. The direction in which the adjusting
screw must be turned to increase or decrease the gas flow is
indicated on the gas valve unit.
Important
The 5- to 9-section boilers are supplied with a different gas valve
unit from the 10-section boiler. See drawing for the position of
adjusting screw B for full load.
5. Check the flame through the inspection window.
Important
The flame must not blow off.
6. Repeat the full load test and the low load test as often as necessary
until the correct values are obtained.
7. Set the boiler back to the normal operating status.
Page 54
AD-3001124-01
Adjusted for / Réglée pour /
Ingesteld op / Eingestellt auf
/ Regolato per / Ajustado
para / Ρυθμισμένο για /
Nastawiony na / настроен
для / Reglat pentru /
настроен за / ayarlanmıştır /
Nastavljen za / beállítva/
Nastaveno pro / Asetettu
kaasulle / Justert for/
indstillet til/ ضبط ل :
2. Screw the cap on to the flue gas measuring point.
3. Seal the gas valve unit.
4. If installed: check the setting of the Gps minimum gas pressure switch.
The pressure switch must be set at 10 mbar.
5. If installed: check the setting of the minimum gas pressure switch for
Vps gas leakage control. The pressure switch must be set at 50% of
the supply pressure (maximum 40 bar).
6. Reattach the casing to the inspection side.
7. Briefly press the key to return the boiler to the normal operating
status.
8. Heat the CH system up to approximately 70 °C.
9. Switch the boiler off.
10. Vent the central heating system after approx. 10 minutes.
11. Turn on the boiler.
12. Check the water pressure. If necessary, top up the central heating
system.
13. Fill in the following data on the sticker included, and attach it next to
the data plate on the appliance.
The gas type;
The gas supply pressure;
If set to overpressure application, fill in the type;
The parameters modified for the changes mentioned above.
14. Inform the user of the maintenance to be performed.
Fig.63Position of the documentation folder
15. Hand over all manuals to the user. A documentation folder can be
found in the frame of the boiler. Use it to store all boiler manuals
together with other documents relating to the installation
16. Confirm the commissioning with a signature and a company stamp.
The boiler is now ready for operation.
For more information, see
Connecting the gas leakage control (VPS), page 47
Page 55
8 Operation
7600532 - v.11 - 1312201855
8.1 Use of the control panel
8 Operation
Important
For operation of the C 630 ECO boiler: each module has its own
control panel
See
For more detailed information: Manual for the control panel
This includes information about changing and reading parameters, the
meaning of error codes and deleting the error memory.
8.2
Start-up
8.3 Shutdown
Start the boiler up as follows:
1. Open the boiler gas valve.
2. Switch the power on with the boiler's on/off switch.
3. The start-up program will start and cannot be interrupted. During the
start-up cycle, all segments of the display are shown briefly.
4. IniControl: Check the water pressure that is shown on the display
(only if a hydraulic pressure sensor is connected). If the water
pressure is lower than 0.8 bar, top up the central heating system.
5. DIEMATIC iSystem: If the water pressure is below 0.8 bar, the
symbol will flash (only if a hydraulic pressure sensor is connected). If
the water pressure is too low, top up the central heating system.
DIEMATIC iSystem: Do not disconnect the boiler from the power supply. If
the central heating system is not used for a long period, we recommend
activating the HOLIDAYS mode.
See
Manual for the control panel.
IniControl: If the central heating is not due to be used for a long period of
time, it is recommended that the boiler be disconnected from the power
supply.
1. Turn the on/off switch to the off position.
2. Switch off the boiler's electrical connection.
3. Shut off the gas supply.
4. Keep the area frost-free.
Caution
In the event of low temperatures, we recommend that the
installation continues to operate at a lower temperature. This will
prevent freezing.
8.4
Frost protection
IniControl: Set the temperature control low, for example to 10 °C.
IniControl: If there is no heat demand, the boiler will only switch on to
protect itself against frost.
If the temperature of the central heating water in the boiler drops too low,
the built-in boiler protection system is activated. This system works as
follows:
If the water temperature is lower than 7 °C, the heating pump switches
on.
If the water temperature is lower than 4 °C, the boiler switches on.
Page 56
8 Operation
567600532 - v.11 - 13122018
If the water temperature is higher than 10℃, the boiler shuts down and
the circulation pump continues to run for a short time.
To prevent the system and radiators freezing in frost-sensitive areas (e.g.
a garage), a frost thermostat or outside sensor can be connected to the
boiler.
Caution
The frost protection does not work if the boiler is out of
operation.
IniControl: The boiler protection only protects the boiler, not the
system.
DIEMATIC iSystem: The boiler protection only protects the
boiler, not the system. To protect the installation, set the
appliance to HOLIDAYS mode.
DIEMATIC iSystem: The HOLIDAYS mode protects:
The installation if the outside temperature drops below 3 °C (default
setting).
The room temperature if a remote control is connected and the room
temperature is lower than 6 °C (default setting).
The domestic hot water boiler if the boiler temperature is lower than 4 °C
(the water is heated to 10 °C).
To configure the HOLIDAYS mode:
See
Manual for the control panel.
Page 57
9 Settings
7600532 - v.11 - 1312201857
9.1 Changing the parameters
9 Settings
The boiler’s control unit is set for the most common central heating
systems. These settings will ensure that virtually every central heating
system operates effectively. The user or the installer can optimise the
parameters as required.
See
Manual for the control panel.
Caution
Changing the factory settings may adversely affect the operation
of the boiler.
9.2
Displaying the measured values
The control unit continually registers various values from the boiler and the
connected sensors. These values can be read on the control panel of the
boiler.
See
Manual for the control panel.
Page 58
10 Maintenance
587600532 - v.11 - 13122018
10 Maintenance
10.1 General
The cast aluminium/silicon heat exchanger forms the heart of the boiler.
When combined with the special geometric shape, the flue gas pollution
remains limited. Nevertheless, we recommend cleaning the flue gas side
of the heat exchanger thoroughly during the annual inspection and
service.
Boilers must be inspected at least once a year or every 3000 operating
hours.
Caution
Maintenance operations must be completed by a qualified
installer.
During inspection or maintenance work, always replace all
gaskets of the disassembled parts.
Replace defective or worn parts with original spare parts.
Important
Adjust the frequency of inspection and service to the conditions of
use. This applies especially to boilers in constant use (for specific
processes).
Important
For work on the C 630 ECO boiler: The features and instructions
described apply to each boiler module.
10.2 Standard inspection and maintenance operations
Warning
Always wear safety goggles and a dust mask during cleaning work
(involving compressed air).
For a service, always perform the following standard inspection and
maintenance operations.
Caution
Check whether all gaskets have been positioned properly
(absolutely flat in the appropriate groove means they are gas
tight).
During the inspection and maintenance operations, water
(drops, splashes) must never come into contact with the
electrical parts.
10.2.1 Preparation
Preparation prior to commencing inspection and maintenance activities:
1. First heat the boiler on high for about 5 minutes (return temperature
65ºC) to dry the heat exchanger on the flue gas side.
10.2.2 Checking the water pressure
1. IniControl: Check the water pressure that is shown on the display
(only if a hydraulic pressure sensor is connected).
2. DIEMATIC iSystem: If the water pressure is below 0.8 bar, the
symbol will flash (only if a hydraulic pressure sensor is connected).
3. If necessary, top up the central heating system.
For more information, see
Filling the installation, page 48
Page 59
AD-0000534-01
1
2
AD-0000513-01
2
3
2
P
P1
10 Maintenance
7600532 - v.11 - 1312201859
10.2.3 Checking the ionisation current
1. Check the ionisation current at full load and at low load.
The value is stable after 1 minute.
2. Clean or replace the ionisation and ignition electrode if the value is
lower than 3 µA.
10.2.4 Checking the water quality
Fig.64
Fig.65Gas valve unit measuring points
Filling/drain valve
1. Fill a clean bottle with some water from the system/boiler from the
filling/drain valve.
2. Check the quality of this water sample or have it checked.
Warning
More information regarding water quality requirements is available
in our Water quality instructions. This manual forms part of the set
of documents supplied with the boiler. Always adhere to the
instructions in the aforementioned document.
10.2.5
1. Check the flue gas outlet and air supply connections for condition and
Checking the flue gas outlet/air supply connections
tightness.
10.2.6 Checking the gas filter
The gas valve unit on the boiler is fitted with a gas filter as standard.
Check this for soiling.
1. Set the boiler to full load.
2. Measure the gas inlet pressure via the measuring point P1 on the gas
pipe.
This gas inlet pressure should be at least 17 mbar.
3. Check the gas inlet pressure at measuring point 2 on the gas valve
unit.
4. Compare the measured values with the checking values in the table.
Tab.39Minimum gas inlet pressure values at gas valve unit
measuring point 2
C 330 ECOMinimum value (mbar)
28014
35013
43010
50010
57010
65010
5. If the measured value is lower than the control value, clean or replace
the gas filter.
10.2.7 Checking the combustion
Combustion is checked by measuring the O2percentage in the flue gas
outlet duct.
Page 60
AD-0000535-01
1
2
3
AD-0000533-01
1
2
AD-0000536-01
1
2
10 Maintenance
607600532 - v.11 - 13122018
For more information, see
Checking/setting the combustion, page 50
Fig.66Air supply hose
Fig.67Dirt trap
10.2.8
Check the air supply hose
1. Disconnect the hose on the air box side by loosening the bayonet
fitting.
2. Check the hose for damage and pollution.
3. Remove the pollution from the hose with a cloth or soft brush.
4. Replace the hose if it is faulty and/or leaking.
10.2.9 Checking the dirt trap
Important
With room-sealed operation, disconnect the air supply pipe
above the boiler to access the dirt trap.
In room ventilated operation with an air supply filter, remove the
filter to access the dirt trap.
1. Check the dirt trap on the air supply side for soiling.
2. First remove coarse soiling and clean the trap with a vacuum cleaner
or a cloth.
Fig.68Air box
10.2.10
Checking the air box
1. Check the air box for soiling.
2. Clean the dirty air box using a vacuum cleaner. Do this from the
connection opening for the air supply hose.
Important
If the air box is dirty, the following components must also be
dismantled and blown clean:
Non-return valve
Venturi
Fan
Page 61
AD-0000539-01
SLOW
(+)
7
3
5
1
P
1
(+)
2
4
P
2
(-)
X mbar
6
........ mb
ar
8
5.5 mbar....6,5
10 Maintenance
7600532 - v.11 - 1312201861
10.2.11 Checking the PS air pressure differential switch
Checking the air pressure differential switch + side
Fig.69
+ side of the air pressure differential
switch
1. Switch off the boiler.
2. Disconnect the silicon hose on the + side (P1) of the air pressure
differential switch.
3. Take a large plastic syringe and connect a T piece with a hose
connected to the mouth.
4. Connect the + side of the air pressure differential switch to one end of
the T piece with a hose.
5. On the other end of the T piece, connect the + side of a pressure
gauge.
6. Turn on the boiler
7. Push the syringe in very slowly until the boiler goes into failure mode.
Code /.
8. Make a note of the pressure indicated by the pressure gauge at that
point.
A switch pressure of between 5.5 and 6.5 mbar is fine. A lower or
higher switch pressure indicates a problem with the air pressure
differential switch.
Page 62
AD-0000540-01
SLOW
4
P
1
(+)
1
2
3
P
2
(-)
X mbar
........ mb
ar
5
-5.5 mbar....-6,5
(+)
10 Maintenance
627600532 - v.11 - 13122018
Checking the air pressure differential switch – side
Fig.70
– side of the air pressure differential
switch
1. Attach silicon hose on the + side (P1) of the air pressure differential
switch.
2. Disconnect the silicon hose on the - side (P2) of the air pressure
differential switch.
3. Connect the - side of the air pressure differential switch to one end of
the T piece with a hose.
4. Pull out the syringe until the boiler goes into failure mode.
Code /.
5. Make a note of the pressure indicated by the pressure gauge at that
point.
A switch pressure of between - 5.5 and - 6.5 mbar is fine. A lower or
higher switch pressure indicates a problem with the air pressure
differential switch.
6. Remove any soiling from all connection points for hoses and the air
pressure differential switch.
7. Check the condition and tightness of the hoses of the air pressure
differential switch.
Replace the hoses if necessary.
Page 63
10.2.12 Checking the VPS gas leakage control
AD-0000541-01
10
5/6/7/8/9
3
5
7
2
P
P1
3
4
2
9
SLOW
(+)
8
X mbar
30 sec
≥ 0.5 x
≤ 0.5 x
1
3
6
7600532 - v.11 - 1312201863
Checking the VPS for leaks
10 Maintenance
Fig.71
Checking the VPS for leaks
1. Switch off the boiler.
2. Close the boiler gas tap.
3. Remove the pressure from the gas pipe by unscrewing the screw in
measuring point P1.
4. As soon as the gas pipe is pressure-free, re-tighten the screw.
5. Open the screw at measuring point 3 on the gas valve unit (on the
other side of the VPS pressure switch).
6. Take a large plastic syringe and connect a T piece with a hose
connected to the mouth.
7. Connect one end of the T piece to measuring point 3 of the gas valve
unit.
8. Connect the other end of the T piece to a pressure gauge.
9. Push the syringe in very slowly until the pressure gauge indicates the
minimum inlet gas pressure value.
10. Check the measured pressure for about 30 seconds. If pressure
decreases by more than half, this indicates a gas leak.
11. Replace the gas valve unit or the VPS if necessary.
Page 64
AD-0000542-01
3
2
1
10
5/6/7/8/9
SLOW
(+)
X mbar
........ mb
ar
6
VPS
GPS
VPS GPS
33
5/67/8/910
3
2
4
GPS
VPS
0 Ohm
55
10 sec
10 sec
3
2
2
3
313
2
10 Maintenance
647600532 - v.11 - 13122018
Checking the VPS switch value
Fig.72
Checking the VPS switch value
1. Remove the pressure from the gas valve unit; first remove the hose
that is attached to measuring point 3 of the gas valve unit (on the
other side of the VPS pressure switch).
2. Wait approximately 10 seconds and reconnect the disconnected hose
to measuring point *3 of the gas valve unit.
3. Remove the connecting plug from the VPS gas leakage control.
4. Connect an ohmmeter to terminals 2 and 3 of the VPS.
5. Push the syringe in very slowly until the ohmmeter indicates 0 Ohm.
6. Make a note of the pressure indicated by the pressure gauge at that
point. If the measured pressure differs by more than 2 mbar from the
VPS set-up value, set the pressure switch to the correct value or
replace it.
Page 65
AD-0000543-01
P1
6
3
2
P
3
2
(+)
X mbar
........ mb
ar
7
≤ 10.0
1
10
5/6/7/8/9
22
2
4
10 Maintenance
7600532 - v.11 - 1312201865
10.2.13 Checking the Gps minimum gas pressure switch
Fig.73
Checking the Gps
1. Switch off the boiler.
2. Open the screw in measuring point 2 of the gas valve unit.
3. Connect a pressure gauge to measuring point 2 of the gas valve unit.
4. Turn on the boiler.
5. Set the boiler to low load.
6. Close the boiler gas valve very slowly until the boiler goes into
blocking mode.
Code B 15 BL.GAS PRESS/; .
7. Make a note of the pressure indicated by the pressure gauge at that
point. Compare the measured values with the checking values in the
table. If the measured pressure is lower, set the gas pressure switch
to the correct value or replace it.
Tab.40Minimum gas pressure switch value
C 330 ECOMinimum value (mbar)
28014
35013
43010
50010
57010
65010
10.3 Specific maintenance work
Perform the specific maintenance work if this proves to be necessary
following the standard inspection and maintenance work. To conduct the
specific maintenance work:
Page 66
AD-0000505-02
2
1
3
6
7
5
4
10 Maintenance
667600532 - v.11 - 13122018
10.3.1 General
Danger
Disconnect the boiler's electricity supply.
Shut off the gas supply.
Caution
During inspection or maintenance work, always replace all
gaskets of the disassembled parts.
10.3.2 Clean the fan and venturi
Fig.74Clean the fan and venturi
1. Remove the electrical connections from the fan. Push the safety slides
on both sides of the power plug right to the back (using a small
screwdriver, for example).
2. Unscrew the bolts from the extension piece under the fan.
Support the gas valve unit, using a block of wood, for example.
3. Disconnect the air supply hose from the venturi.
4. Unscrew the nuts on the fan output.
5. Disconnect the fan from the adaptor.
6. Clean the fan with a soft plastic brush.
7. Clean the venturi with a soft plastic brush.
8. Reassemble the unit in reverse order.
Important
Reconnect the fan's electrical connection.
Page 67
10.3.3 Cleaning and inspecting the non-return valve
AD-0000504-01
4
5
1
2
3
6
AD-0000501-01
1
1
2
3
4
7600532 - v.11 - 1312201867
10 Maintenance
Fig.75Checking the non-return valve
1. Remove the electrical connections from the fan. Push the safety slides
on both sides of the power plug right to the back (using a small
screwdriver, for example).
2. Unscrew the bolts from the extension piece under the fan.
Support the gas valve unit, using a block of wood, for example.
3. Unscrew the nuts on the fan output.
4. Disconnect the fan adaptor.
5. Inspect the non-return valve and replace it if faulty or seriously
damaged.
6. If the non-return valve does not need to be replaced, clean it with a
soft plastic brush or compressed air.
7. Reassemble the unit in reverse order.
Caution
Reconnect the fan's electrical connection.
Fig.76Replacing the ionisation/ignition
electrode
10.3.4 Replacing the ionisation/ignition electrode
The ionisation/ignition electrode must be replaced if:
The ionisation current is < 3 µA.
The electrode is damaged or worn.
The specific maintenance activities are carried out.
1. Unscrew the 2 screws on the middle top casing.
2. Remove the middle top casing.
3. Remove the plug of the electrode from the ignition transformer.
Important
The ignition cable is fixed to the electrode and therefore may not
be removed.
4. Unscrew the 2 screws on the electrode and pull these forwards.
Caution
Do not fit the new electrode until the burner has been cleaned and
refitted. This will prevent damage occurring.
5. Remove the entire component.
6. Fit the new ionisation/ignition electrode.
7. Reassemble the unit in reverse order.
For more information, see
Cleaning the burner, page 69
Page 68
AD-0000524-01
4mm
3mm
1a
4x
2
2
1a 2x
1b
1c
1b
1c
5
4
3
4
3
10 Maintenance
687600532 - v.11 - 13122018
10.3.5 Clean the gas filter
Fig.77Clean the gas filter
Important
The 5- to 9-section boilers are supplied with a different gas valve
unit from the 10-section boiler.
1. Remove the gas filter.
2. Carry out a visual check.
3. Clean the gas filter without the use of liquids (shake it or carefully blow
it clean).
4. Replace the gas filter if necessary.
5. Reassemble the unit in reverse order.
Caution
In this gas valve unit, the gas filter holder has a positioning ridge.
Position this at the top left during assembly.
Page 69
10.3.6 Cleaning the burner
AD-0000499-02
1
2
2-5 bar
min. 1cm
3
4
5
6
1
2
AD-0000538-01
7600532 - v.11 - 1312201869
10 Maintenance
Fig.78
Cleaning the burner
1. Unscrew the bolts from the adaptor and remove the adaptor.
2. Lift the burner out of the heat exchanger.
3. Check the burner and, if necessary, clean without touching it (e.g. with
compressed air between 2 and 5 bars: maintain a minimum distance
of 1 cm from the surface of the burner).
Caution
Never clean the burner's surface with a brush or similar item.
4. Carefully hoover the dirt from the inside of the burner.
5. Inspect the burner end cap.
6. Replace the burner or the burner end cap if faulty or seriously
damaged.
Caution
Do not refit the burner until the burner area, heat exchanger,
condensate collector and siphon have been cleaned.
Fig.79Cleaning the burner area
10.3.7 Cleaning the burner area
1. Visually inspect the burner area.
2. Remove any visible soiling with a vacuum cleaner.
Page 70
AD-3001122-01
7
2
7
3
4
5
5
6
6
8
1
10 Maintenance
707600532 - v.11 - 13122018
10.3.8 Cleaning the heat exchanger
Fig.80
Clean the heat exchanger
1. Remove the insulation set from the heat exchanger (locally).
2. Unscrew the nuts from the inspection hatch on the heat exchanger.
3. Take the inspection trap off the heat exchanger and remove the
insulation cloth.
The insulation cloth may stick to the heat exchanger. Avoid
damaging or tearing the insulation cloth. Remove the silicon
insulation cord.
4. Inspect the insulation cloth and replace if it is faulty or seriously
damaged.
5. Clean the areas between the pins of the heat exchanger using the
special cleaning tool or cleaning knife (accessory). Always work from
the bottom to the top. Move the cleaning knife between the pins
horizontally and diagonally.
Important
A range of cleaning knives are available for the various boilers.
Always use the cleaning knife specially designed for this boiler.
This knife is 560 mm long.
6. Use compressed air to blow the cleaned parts through in turn. Do this
from the service side and from the burner area.
7. Fit the inspection trap with the silicon cord and the insulation cloth.
8. Use clean water to thoroughly rinse the heat exchanger from the
burner area.
10.3.9 Clean the condensate collector
Page 71
AD-0000531-01
1
2
1
min.
5 min.
AD-0000490-01
4
1
2
3
4
10 Maintenance
7600532 - v.11 - 1312201871
Fig.81Clean the condensate collector
1. Loosen both the sealing caps on the condensate collector (in front of
and behind the flue gas extraction connection).
2. Thoroughly clean the condensate collector with water. Rinse each
side of the condensate collector for at least 5 minutes with the largest
possible water flow.
3. Refit both sealing caps on the condensate collector.
10.3.10 Clean the siphon
Fig.82Cleaning the siphon
1. Remove the siphon.
2. Clean the siphon with water.
3. Put the siphon back in place.
4. Fill the siphon with water up to the mark via the condensate collector.
Danger
The siphon must always be sufficiently filled with water. This
prevents flue gases from entering the room.
Page 72
AD-0000537-01
1
2
3
3
3
3
4
10 Maintenance
727600532 - v.11 - 13122018
10.3.11 Remounting the burner
Fig.83
Remounting the burner
1. Fit the burner.
Important
The burner has 2 holes at the front. Position these on the 2
support pins at the burner opening.
2. Fit the new ionisation/ignition electrode.
3. Fit the venturi and the fan.
Caution
Reconnect the fan's electrical connection.
4. Fit the air supply hose.
10.3.12 Reassembling the boiler
1. Fit all removed parts in the reverse order.
Caution
During inspection and maintenance operations, always replace all
gaskets on the parts removed.
2. Carefully open the water tap.
3. Fill the installation with water.
4. Vent the installation.
5. Top up with more water if necessary.
6. Check the tightness of the gas and water connections.
7. Put the boiler back into operation.
10.3.13
Putting the boiler back into operation
1. Open the main gas tap
2. Check the gas circuit.
3. Check the water pressure.
4. Check that there are no leaks on the hydraulic connections.
5. Check the flue gas outlet and the air supply.
6. Check the electricity supply.
7. Check the electrical connections.
8. Switch the power on with the boiler's on/off switch.
9. Check the gas inlet pressure at the measuring point P2 on the gas
valve unit.
Page 73
10 Maintenance
7600532 - v.11 - 1312201873
10. Check the ionisation current.
11. Check the combustion.
12. Check that gas connections between the gas valve unit and the
venturi are sealed.
13. Vent the air from the CH system.
Page 74
11 Troubleshooting
747600532 - v.11 - 13122018
11 Troubleshooting
11.1 Error codes
Important
Operating the C 630 ECO boiler: the properties described and the
instructions apply to each boiler module.
When a failure is signalled, the boiler stops or becomes locked. In the
event of an error, a corresponding code is displayed. The meaning of the
error codes can be found in the error table.
See
Manual for the control panel.
Important
The error code is needed to find the cause of the error quickly and
correctly and for any support from De Dietrich.
Page 75
12 Disposal
7600532 - v.11 - 1312201875
12.1 Removal/recycling
12 Disposal
Important
Removal and disposal of the boiler must be carried out by a
qualified person in accordance with local and national regulations.
To remove the boiler, proceed as follows:
1. Switch off the boiler's electrical connection.
2. Shut off the gas supply.
3. Shut off the water supply.
4. Drain the system.
5. Remove the siphon.
6. Remove the air supply/flue gas outlet pipes.
7. Disconnect all pipes on the boiler.
8. Remove the boiler.
Page 76
13 Spare parts
767600532 - v.11 - 13122018
13 Spare parts
13.1 General
Only replace defective or worn boiler parts with original parts or
recommended parts.
Important
When ordering a part, you must state the part number that
appears in the list beside the position number of the required part.
50057600368 Clamping ring + gasket seal Ø 250 mmxxxxxx
50067600369 Clamping ring + gasket seal Ø 350 mmxxxxxx
Page 89
14 Appendix
7600532 - v.11 - 1312201889
14 Appendix
14.1 ErP information
14.1.1 Product fiche
Tab.46Product fiche
De Dietrich - C 330 ECO280350430500570650
Seasonal space heating energy efficiency
class
Rated heat output
Seasonal space heating energy efficiency%------
Annual energy consumptionGJ------
Sound power level LWA indoorsdB727272---
(Prated or Psup)
kW261327395---
------
See
For specific precautions in relation to assembly, installation and
maintenance: Safety, page 5
14.2 EC declaration of conformity
The unit complies with the standard type described in the EC declaration
of conformity. It has been manufactured and commissioned in accordance
with European directives.
The original declaration of conformity is available from the manufacturer.
All technical and technological information contained in these technical instructions, as well as any drawings and technical
descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.