1. Do not use naked flames, do not smoke and
do not operate electrical contacts or switches
(doorbell, lighting, motor, lift etc).
2. Shut off the gas supply.
3. Open the windows.
4. Trace possible leaks and seal them off
immediately.
5. If the leak is upstream of the gas meter, notify
the gas company.
Danger
If you smell flue gases:
1.2
1. Switch the boiler off.
2. Open the windows.
3. Trace possible leaks and seal them off
immediately.
Caution
After maintenance or repair work, check the
entire heating installation to ensure that there are
no leaks.
Recommendations
Warning
Installation and maintenance of the boiler must be
carried out by a qualified installer in accordance
with local and national regulations.
Warning
If the mains lead is damaged, it must be replaced
by the original manufacturer, the manufacturer's
dealer or another suitably skilled person to
prevent hazardous situations from arising.
Warning
Always disconnect the mains supply and close
the main gas tap when working on the boiler.
Warning
Check the entire system for leaks after
maintenance and servicing work.
1 Safety
6AMC7686707 - v.01 - 06092018
Caution
Make sure the boiler can be reached at all
times.
The boiler must be installed in a frost-free area.
If the power cord is permanently connected, you
must always install a main bipolar switch with
an opening gap of at least 3 mm (EN 60335-1).
Drain the boiler and central heating system if
you are not going to use your home for a long
time and there is a chance of frost.
The frost protection does not work if the boiler is
out of operation.
The boiler protection only protects the boiler,
not the system.
Check the water pressure in the system
regularly. If the water pressure is lower than 0.8
bar, the system must be topped up
(recommended water pressure between 1.5 and
2 bar).
1.3
Important
Keep this document near to the boiler.
Important
Only remove the casing for maintenance and
repair operations. Refit all panels when
maintenance work and servicing are complete.
Important
Instruction and warning labels must never be
removed or covered and must be clearly legible
throughout the entire service life of the boiler.
Damaged or illegible instructions and warning
stickers must be replaced immediately.
Important
Modifications to the boiler require the written
approval of De Dietrich.
Liabilities
1.3.1 Manufacturer's liability
Our products are manufactured in compliance with the
requirements of the various Directives applicable. They
are therefore delivered with the marking and any
documents necessary. In the interests of the quality of
our products, we strive constantly to improve them. We
therefore reserve the right to modify the specifications
given in this document.
1 Safety
7686707 - v.01 - 06092018AMC7
Our liability as manufacturer may not be invoked in the
following cases:
Failure to abide by the instructions on installing and
maintaining the appliance.
Failure to abide by the instructions on using the
appliance.
Faulty or insufficient maintenance of the appliance.
1.3.2 Installer's liability
The installer is responsible for the installation and initial
commissioning of the appliance. The installer must
observe the following instructions:
Read and follow the instructions given in the manuals
provided with the appliance.
Install the appliance in compliance with prevailing
legislation and standards.
Carry out initial commissioning and any checks
necessary.
Explain the installation to the user.
If maintenance is necessary, warn the user of the
obligation to check the appliance and keep it in good
working order.
Give all the instruction manuals to the user.
1.3.3 User's liability
To guarantee optimum operation of the system, you
must abide by the following instructions:
Read and follow the instructions given in the manuals
provided with the appliance.
Call on a qualified professional to carry out installation
and initial commissioning.
Get your installer to explain your installation to you.
Have the required inspections and maintenance
carried out by a qualified installer.
Keep the instruction manuals in good condition close
to the appliance.
2 About this manual
8AMC7686707 - v.01 - 06092018
2 About this manual
2.1 General
This manual is intended for the installer of a AMC boiler.
Important
The manual is also available on our internet site.
2.2
2.3
Additional documentation
The following documentation is available in addition to this manual:
User manual
Symbols used
2.3.1 Symbols used in the manual
This manual uses various symbols to draw attention to special instructions.
We do this to improve user safety, to prevent problems and to guarantee
correct operation.
Danger
Risk of dangerous situations that may result in serious personal
injury.
Warning
Risk of dangerous situations that may result in minor personal
injury.
Caution
Risk of material damage.
Important
Please note: important information.
See
Reference to other manuals or pages in this manual.
3 Technical specifications
7686707 - v.01 - 06092018AMC9
3 Technical specifications
3.1 Homologations
3.1.1 Certifications
Tab.1Certifications
CE identification numberPIN 0063CR3604
Class NOx
(1)
Type of connectionB23, B
(1) EN 15502–1
3.1.2 Unit categories
Tab.2Unit categories
CountryCategoryGas typeConnection pressure (mbar)
IrelandII
2H3B/P
G20 (H gas)
G30/G31 (butane/propane)
6
C
13(X)
C
(10)3(X)
23P
, C
33(X)
, C
20
30
, B
(12)3(X)
33
, C
43P
, C
53(X)
, C
63(X)
, C
93(X)
,
3.1.3 Directives
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines
specified in this manual.
3.1.4 Factory test
Before leaving the factory, each boiler is optimally set and tested for:
Electrical safety.
Adjustment of (O2).
Domestic hot water function (For combi-boilers only).
Water tightness.
Gas tightness.
Parameter setting.
3.2
Tab.3General
AMC 152525/28 MI35
Nominal output (Pn) for central heat
ing operation (80 °C/60 °C)
Nominal output (Pn) for central heat
ing operation (50/30 °C)
Nominal output (Pn) for DHW opera
tion
Nominal input (Qnh) central heating
operation (Hi)
Nominal input (Qnh) for central heat
ing operation (Hi) Propane
Technical data
min-max
(1)
min–max
(1)
min–max
(1)
min–max
(1)
kW3.0 - 14.9
14.9
kW3.4 - 15.8
15.8
kW-
-
kW3.1 - 15.0
15.0
5.0 - 24.8
24.8
5.6 - 25.5
25.5
-
-
5.2 - 25.0
25.0
5.0 - 24.8
19.9
5.6 - 25.5
20.5
5.0 - 27.8
27.8
5.2 - 25.0
20.1
7.0 - 34.5
7.9 - 35.6
7.3 - 34.8
min-max5.2 - 15.05.9 - 25.05.9 - 25.07.3 - 34.8
34.5
35.6
-
-
34.8
3 Technical specifications
10AMC7686707 - v.01 - 06092018
AMC 152525/28 MI35
Nominal input (Qnh) central heating
operation (Hs)
Nominal input (Qnh) for central heat
ing operation (Hs) Propane
Nominal input (Qnw) for DHW opera
tion (Hi)
Nominal input (Qnw) for DHW opera
tion (Hi) Propane
Nominal input (Qnw) for DHW opera
tion (Hs)
Nominal input (Qnw) for DHW opera
tion (Hs) Propane
Full load central heating efficiency
min–max
(1)
min-max
(1)
min–max
(1)
min–maxkW-
min–max
(1)
min–maxkW-
kW3.4 - 16.7
16.7
5.8 - 27.8
27.8
5.8 - 27.8
22.3
8.1 - 38.7
5.8 - 16.76.5 - 27.86.5 - 27.88.1 - 38.7
kW-
-
-
kW-
-
-
-
-
-
5.2 - 28.0
28.0
5.9 - 28.0-
-
-
-
-
5.8 - 31.1
31.1
6.5 - 31.1-
-
%99.399.299.299.1
(Hi) (80/60 °C) (92/42/EEC)
Full load central heating efficiency
%105.3102.0102.0102.2
(Hi) (50°C/30°C) (EN15502)
Part load central heating efficiency
%94.996.196.196.3
(Hi) (return temperature 60°C)
Part load central heating efficiency
%110.2110.1110.1110.6
(Hi) (92/42/EEC) (return temperature
30°C)
Full load central heating efficiency
%89.489.389.389.2
(Hs) (80/60°C) (92/42/EEC)
Full load central heating efficiency
%94.891.991.992.0
(Hs) (50°C/30°C) (EN15502)
Part load central heating efficiency
%85.586.586.586.7
(Hs) (return temperature 60°C)
Part load central heating efficiency
%99.299.199.199.6
(Hs) (92/42/EEC) (return temperature
30°C)
(1) Minimum amount of water that comes out of the tap to make the boiler start.
Tab.7Electrical data
AMC 152525/28 MI35
Supply voltageV~230230230230
Power consumption – full loadmax
(1)
W67
67
77
77
84
68
54
121
93
93
Power consumption – part loadmaxW27262627
Power consumption – standbymaxW4444
Electrical protection index
(2)
Fuses
(1) Factory setting.
(2) Splashproof; under certain conditions, the boiler may be installed in damp areas, such as bathrooms.
(3) The fuse is located on the CU-GH08 control unit
IPIPX5DIPX5DIPX5DIPX5D
(3)
CU-GH
A2.52.52.52.5
Tab.8Other data
AMC 152525/28 MI35
Minimum mounting weight
(1)
kg36363831
Total weight (empty)kg38384033
Average acoustic level at a distance
of one metre from the boiler (LPA)
Central
heating op
dB(A)37
43
-
-
40
44
eration
DHW oper
ation
(1) Without front panel.
Tab.9Technical parameters
AMC 152525/28 MI35
Condensing boilerYesYesYesYes
Low-temperature boiler
(1)
NoNoNoNo
B1 boilerNoNoNoNo
Cogeneration space heaterNoNoNoNo
Combination heaterNoNoYesNo
Rated heat output
Prated
kW15252535
31
33
45
-
3 Technical specifications
12AMC7686707 - v.01 - 06092018
AMC 152525/28 MI35
Useful heat output at nominal heat
P
4
kW14.924.824.834.5
output and high temperature oper
(2)
ation
Useful heat output at 30% of rated
P
1
kW5.08.38.311.6
heat output and low temperature
(1)
regime
Seasonal space heating energy effi
ƞ
s
%94949495
ciency
Useful efficiency at rated heat out
put and high temperature regime
Useful efficiency at 30% of rated
ƞ
4
(2)
ƞ
1
%89.589.489.489.3
%99.399.299.299.6
heat output and low temperature
(1)
regime
Auxiliary electricity consumption
Full load
Part load
Standby mode
elmax
elmin
P
SB
kW0.0270.0370.0370.050
kW0.0180.0170.0170.018
kW0.0040.0040.0040.004
Other items
Standby heat loss
Ignition burner power consumption
Annual energy consumption
Sound power level, indoors
Emissions of nitrogen oxidesNO
P
stby
P
ign
Q
HE
L
WA
X
kW0.0780.0780.0780.054
kW----
GJ467676105
dB(A)45515153
mg/kWh27252541
Domestic hot water parameters
Declared load profile--A-
Daily electricity consumption
Annual electricity consumption
Water heating energy efficiency
Daily fuel consumption
Annual fuel consumption
(1) Low temperature means 30°C for condensing boilers, 37°C for low temperature boilers and 50°C (at heater inlet) for other heating appli
ances.
(2) High temperature operation means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
Q
elec
AEC
ƞ
wh
Q
fuel
AFC
kWh--0.169-
kWh--37-
%--82.4-
kWh--22.045-
GJ--17-
See
See the back of this manual for contact information.
3.3 Dimensions and connections
AD-0001436-02
67
195
265
132
199
266
331
690
450
450
225
140
140
150
255
7686707 - v.01 - 06092018AMC13
Fig.1Dimensions
3 Technical specifications
Tab.10Connections
AMC 152525/28 MI35
Connecting the flue gas outletØ 60 mmØ 60 mmØ 60 mmØ 60 mm
Connecting the air supplyØ 100 mmØ 100 mmØ 100 mmØ 100 mm
Power supply (P)
On/off switch (S)
Automatic refill device
4
5
6
Control unit (CU-GH08)
Display (DIS)
Spare CAN-Bus connection
1
2
3
3 Technical specifications
7686707 - v.01 - 06092018AMC15
7
Service connection
8
Fan supply
9
CB-03 PCB
10
Ignition transformer (IT)
11
Ionisation/ignition electrode (E)
12
Gas combination block (GB)
13
Three-way valve (3WV)
14
Circulation pump (CH)
15
Flow sensor (FTS)
16
Return sensor (TR)
17
Tap water temperature sensor (TDHW)
18
Fan control (PWM)
19
20
21
22
BK
BL
BR
GN/YW
GY
RD
WH
Flow sensor (FS)
Pressure sensor (PS)
PWM pump
Storage information (CSU)
Black
Blue
Brown
Green/Yellow
Grey
Red
White
4 Description of the product
16AMC7686707 - v.01 - 06092018
4 Description of the product
The AMC boiler is delivered with a combination of the control panel,
control unit and extension PCB. The contents of this manual are based on
the following software and navigation information:
Tab.11Software and navigation information
Name visible in displaySoftware version
Boiler AMC CU-GH081.4
Control panel Diematic EvolutionMK31.29
PCB SCB-10SCB-100.5
4.1
General description
4.2 Operating principle
The AMC boiler is a wall-mounted gas boiler with the following
characteristics:
High-efficiency heating
Low polluting emissions
Automatic refill device
High-quality electronic control panel
Easier installation and connection thanks to the mounting frame
delivered with the appliance.
The following boiler types are available:
TypeMode
AMC 15
AMC 25
AMC 35
AMC 25/28 MIHeating and production of domestic hot water.
4.2.1
The boiler has an automatic refill device located under the boiler.
The automatic refill device will refill the central heating system whenever
the water pressure is lower than the set minimum. Refilling can be
automatic or semi-automatic. On the semi-automatic setting, refilling will
only start after confirmation by the user. The automatic refill device can
also be used to fill an empty system.
If refilling takes too long or occurs too often (e.g. because the system
leaks), a warning code will appear on the display and refilling will stop.
Automatic refill device
Heating only (option of producing domestic hot
water using a separate hot water appliance).
4.2.2
The energy-efficient, modulating circulation pump is controlled by the
control unit based on ΔT. The graphs show the total dynamic head at
various outputs.
Circulation pump
Important
The benchmark for the efficient circulation pumps is EEI ≤ 0.20.
Fig.3AMC 15 - 25 - 25/28 MI
AD-3000862-02
Q
1600140012001000600800400200
0
0
100
200
300
400
500
600
H
700
355
25 kW
1080
494
20 kW
860
585
15 kW
650
640
10 kW
430
AD-3000863-02
Q
1600140012001000600800400200
0
0
100
200
300
400
500
600
H
700
231
35 kW
1500
387
30 kW
1290
508
25 kW
1080
594
20 kW
860
7686707 - v.01 - 06092018AMC17
4 Description of the product
H
Total dynamic head CH (mbar)
Fig.4AMC 35
H
Total dynamic head CH (mbar)
Q
Water flow rate (l/h)
Q
Water flow rate (l/h)
4.2.3 Water flow
The modulating control of the boiler limits the maximum temperature
difference between the flow and return and the maximum rise velocity of
the flow temperature. In addition, a heat exchanger temperature sensor is
mounted to monitor the minimum water flow. As a result, the boiler is
virtually unaffected by low water flow.
AD-0000428-01
1
8
7
6
2345
AD-3000830-01
1
7
6
2345
4 Description of the product
18AMC7686707 - v.01 - 06092018
4.2.4 Skeleton diagram
Fig.5AMC 15 - 25
Fig.6AMC 35
1
Heat exchanger (CH)
2
Heating circuit flow (primary circuit)
3
Heating circuit flow (secondary circuit)
4
Heating return (secondary circuit)
5
Heating return (primary circuit)
6
Three-way valve
7
Circulation pump (CH)
8
Expansion vessel
1
Heat exchanger (CH)
2
Heating circuit flow (primary circuit)
3
Heating circuit flow (secondary circuit)
4
Heating return (secondary circuit)
5
Heating return (primary circuit)
6
Three-way valve
7
Circulation pump (CH)
AD-0000419-01
1
2
3
10
9
8
4567
AD-0001371-02
2
16
15
14
17
18
19
20
21
22
3
4
5
6
7
8
9
10
11
12
13
123
4 Description of the product
7686707 - v.01 - 06092018AMC19
Fig.7AMC 25/28 MI
4.3
Main components
Fig.8AMC 15 - 25
1
Heat exchanger (CH)
2
Hydroblock
3
Plate heat exchanger (DHW)
4
Central heating circuit flow
5
Domestic hot water outlet
6
Domestic cold water inlet
7
Central heating circuit return
8
Three-way valve
9
Circulation pump (CH)
10
Expansion vessel
1
Flue gas outlet
2
Casing/air box
3
Flue gas measuring point
4
Mixing tube
5
Hydraulic flow pipe
6
Air intake silencer
7
Combined gas valve unit
8
Automatic air vent hose
9
Hydroblock, flow side
10
Housing for PCBs
11
Safety valve hose
12
Siphon
13
Instrument box
14
Circulation pump
15
Hydroblock, return side
16
Return pipe
17
Three-way valve
18
Condensate collector
19
Fan
20
Heat exchanger (CH)
21
Expansion vessel
22
Ionisation/ignition electrode
23
Air supply
AD-0001372-02
2
15
16
17
14
18
19
20
21
3
4
5
6
7
8
9
13
1
22
10
11
12
AD-0001373-03
2
17
16
15
14
18
19
20
21
22
23
3
4
5
6
8
7
9
10
11
12
13
124
4 Description of the product
20AMC7686707 - v.01 - 06092018
Fig.9
AMC 35
Fig.10AMC 25/28 MI
4.4
4.5
Control panel
Standard delivery
1
Flue gas outlet
2
Casing/air box
3
Flue gas measuring point
4
Mixing tube
5
Hydraulic flow pipe
6
Air intake silencer
7
Combined gas valve unit
8
Automatic air vent hose
9
Hydroblock, flow side
10
Housing for PCBs
11
Safety valve hose
12
Siphon
13
Instrument box
14
Circulation pump
15
Hydroblock, return side
16
Return pipe
17
Three-way valve
18
Condensate collector
19
Fan
20
Heat exchanger (CH)
21
Ionisation/ignition electrode
22
Air supply
1
Flue gas outlet
2
Casing/air box
3
Flue gas measuring point
4
Mixing tube
5
Hydraulic flow pipe
6
Air intake silencer
7
Combined gas valve unit
8
Automatic air vent hose
9
Hydroblock, flow side
10
Housing for PCBs
11
Safety valve hose
12
Siphon
13
Instrument box
14
Circulation pump
15
Hydroblock, return side
16
Return pipe
17
Plate heat exchanger (DHW)
18
Three-way valve
19
Condensate collector
20
Fan
21
Heat exchanger (CH)
22
Expansion vessel
23
Ionisation/ignition electrode
24
Air supply
The AMC boiler is supplied with a Diematic Evolution control panel.
For more information, see
Control panel description, page 77
The delivery includes:
The boiler, fitted with a three-core cable
Mounting frame with automatic refill device
Connection kit including cable glands and clamping rings
4 Description of the product
7686707 - v.01 - 06092018AMC21
Condensate drain hose for siphon and safety valve
Condensates collector
Seal plates for sealing off the lines for the secondary heating circuit if it
is not being used
Documentation
Mounting template
Sticker: This central heating unit is set for ...
This manual only deals with the standard scope of supply. For the
installation or mounting of any accessories supplied with the boiler, please
refer to the mounting instructions delivered with the accessories in
question.
AD-0001197-01
AD-0001376-02
450
min.10
0
0
4
5
0
min.
250
m
i
n.
2
5
0
690
5 Before installation
22AMC7686707 - v.01 - 06092018
5 Before installation
5.1 Installation regulations
Warning
The boiler must be installed by a qualified installer in accordance
with local and national regulations.
5.2
Choice of the location
Fig.11Position of data plate
Fig.12Installation area
5.2.1 Data plate
The data plate on top of the boiler states the boiler serial number and
important boiler specifications such as the model and gas category. The
configuration numbers CN1 and CN2 codes are also stated on the data
plate.
5.2.2 Location of the boiler
Use the guidelines and the required installation space as a basis for
determining the correct place to install the boiler.
When determining the correct installation area, take account of the
permitted position of the flue gas outlet and/or air supply outlet.
Ensure that there is sufficient space around the boiler for good access
and ease of maintenance.
Mount the boiler onto a flat surface.
Danger
It is forbidden to store, even temporarily, combustible products
and substances in the boiler or near the boiler.
Warning
Fix the appliance to a solid wall capable of bearing the weight of
the boiler when full of water and fully equipped.
Do not place the appliance above a heat source or a cooking
appliance.
Do not locate the boiler in direct or indirect sunlight.
Caution
The boiler must be installed in a frost-free area.
An earthed electrical connection must be available close to the
boiler.
A connection to the drain must be present for the condensate
drain close to the boiler.
5.2.3 Ventilation
AD-0001377-02
min. 550
min.550
min. 250
50 (2)
min. 250
100
min. (1)
7686707 - v.01 - 06092018AMC23
5 Before installation
Fig.13
Space for ventilation
(1)
Distance between the front of the boiler and the internal wall of the
casing.
(2)
Space on either side of the boiler.
If the boiler is installed in a closed casing, observe the minimum
dimensions indicated. Also allow for openings to prevent the following
hazards:
Accumulation of gas
Heating of the casing
Minimum cross section of the openings: S1 + S2 = 150 cm
2
AD-0001379-02
76499
02
-01
50
57
41
13
152,5
154,5
216
216
2
20
220
2
6,5
120
432
450
6
76
7
6
7
6565
63
50
1
95
690
42
487
715
3
6
100
59
10
(1x)
10
(1x)
1
0
(1x)
104,5
1
04,5
5
1
0
(1
x
)
1
0
(1x)
1
2
3
4
5
6 Installation
24AMC7686707 - v.01 - 06092018
6 Installation
6.1 General
Warning
The boiler must be installed by a qualified installer in accordance
with local and national regulations.
6.2
Preparation
Fig.14Installing the mounting frame
6.2.1 Installing the mounting frame
The boiler is supplied with a mounting template.
Proceed as follows to hang the mounting frame:
1. Attach the mounting template of the boiler to the wall using adhesive
tape.
Warning
Use a level on the mounting frame to check whether the
mounting template is perfectly horizontal.
Protect the boiler against building dust and cover the flue gas
outlet and air supply connection points. Only remove this cover
to assemble the relevant connections.
2. Drill 3 holes of Ø 10 mm.
Important
The extra holes are intended for use in the event that one of the
two fastening holes is not suitable for correct fastening of the plug.
3. Fit the Ø 10 mm plugs.
4. Attach the mounting frame to the wall with the Ø 8 mm screws
supplied
5. Remove the level from the mounting frame.
6.2.2 Positioning the boiler
AD-0001380-02
AD-0001381-02
AD-3001203-01
7686707 - v.01 - 06092018AMC25
6 Installation
Fig.15Removing boiler protection
Fig.16Fitting gaskets
1. Remove the black protective strip on the underside of the boiler.
2. Remove the dust caps from all of the hydraulic inlets and outlets on
the boiler.
Caution
The valve of the filling loop must be closed.
3. Fit a fibre gasket to each joint on the valve plate.
Fig.17Fitting the boiler
4. Position the boiler above the mounting frame. Gently lower the boiler.
5. Tighten the valve nuts on the boiler.
AD-0001383-03
1
2
AD-0001384-03
2
1
6 Installation
26AMC7686707 - v.01 - 06092018
6.3 Hydraulic connections
6.3.1 Rinsing the system
Installation must be carried out in accordance with the prevailing
regulations, codes of practice and the recommendations in this manual.
Before a new boiler can be connected to an existing or new system, the
entire system must be thoroughly cleaned and flushed. This step is
absolutely crucial. The flushing helps to remove residue from the
installation process (weld slag, fixing products etc.) and accumulations of
dirt (silt, mud etc.)
Important
Flush the system with a volume of water equivalent to at least
three times the volume of the system. Flush the DHW pipes with a
volume of water equivalent to at least 20 times the volume of the
pipes.
Fig.18Connecting the heating circuit
6.3.2
Water flow
The boiler's modulating control system limits the maximum difference in
temperature between the heating flow and return, and the maximum
speed at which the flow temperature increases. In this way, the boiler does
not require a minimum water flow rate.
Important
In the case of a combi boiler in an installation in which the flow
can be fully disconnected from the return (e.g. by using
thermostatic valves), a bypass pipe should be fitted or the
expansion vessel placed on the central heating flow pipe.
6.3.3
Connection of the heating circuit
1. Fit the inlet pipe for CH water to the CH return connection .
2. Fit the outlet pipe for CH water to the CH flow connection .
Caution
Carry out any welding work required at a safe distance from the
boiler or before the boiler is fitted.
If using synthetic pipes, follow the manufacturer's (connection)
instructions.
6.3.4 Connection of the water circuit for domestic use
Fig.19Connecting water circuit for
domestic use
1. Connect the cold water inlet pipe to the domestic cold water
connection .
2. Connect the domestic hot water outlet pipe to the domestic hot water
connection
Caution
AD-0001385-04
4
3
2
1
AD-0001207-03
1
2
7686707 - v.01 - 06092018AMC27
If using synthetic pipes, follow the manufacturer's (connection)
instructions.
Carry out any welding work required at a safe distance from the
boiler or before the boiler is fitted.
6.3.5 Connecting the secondary heating circuit
6 Installation
Fig.20Connecting the secondary heating
circuit
Fig.21Disconnecting the secondary
heating circuit
1. Fit the pipe supplied with the mounting frame to the domestic cold
water connection of the automatic (re)fill device.
2. Connect the domestic cold water inlet to this pipe.
3. Fit the inlet pipe for CH water to the CH return connection .
4. Fit the outlet pipe for CH water to the CH flow connection .
Caution
Carry out any welding work required at a safe distance from the
boiler or before the boiler is fitted.
If using synthetic pipes, follow the manufacturer's (connection)
instructions.
6.3.6
Disconnecting the secondary heating circuit
These connections must be closed off if the secondary heating circuit is
not connected (solo use of the boiler). To do this, proceed as follows:
Important
The blanking plates needed are supplied with the boiler.
1. Remove the secondary heating circuit valves from the mounting
frame.
2. Place a blanking plate in the fitting (G½") and install this on the CH
return connection .
3. Place a blanking plate in the fitting (G½") and install this on the CH
flow connection .
6.3.7 Connecting the expansion vessel
The boiler is fitted as standard with an 12 litre expansion vessel.
If the water volume is greater than 150 litres or the static height of the
system exceeds 5 metres, an additional expansion vessel must be fitted.
Refer to the table below to determine the expansion vessel required for
the system.
Validity terms of the table:
3-bar safety valve
Average water temperature: 70°C
Flow temperature: 80°C
Return temperature: 60°C
The filling pressure in the system is lower than or equal to the inflation
pressure in the expansion vessel.
AD-3001204-01
1
2
4
4
3
3
AD-0001387-03
1
6 Installation
28AMC7686707 - v.01 - 06092018
Tab.12Volume of the expansion vessel (litres)
Initial pressurinstae of the ex
pansion vessel
Volume of the system (litres)
100125150175200250300> 300
0.5 bar4.86.07.28.49.612.014.4Volume of the system x 0.048
1 bar8.010.0
(1
14.016.020.024.0Volume of the system x 0.080
12.0
)
1.5 bar13.316.620.023.326.633.339.9Volume of the system x 0.133
(1) Standard configuration.
6.3.8 Connecting the condensate drain pipe
Fig.22Connecting the condensate
discharge pipe
6.4 Gas connection
1. Fit a plastic drain pipe of Ø 32 mm or larger, terminating in the drain.
Important
Fit a watertrap or siphon in the drain pipe.
2. Insert the condensate collector into the drain pipe.
3. Attach the boiler siphon and safety valve drain hose to the condensate
discharge pipe connection and the safety valve .
4. Slide the hose into the drain pipe.
Caution
Never seal the condensate drain.
The drain pipe must slope down at least 30 mm per metre, the
maximum horizontal length is 5 metres.
Condensed water must not be discharged into a gutter.
For more information, see
Filling the siphon, page 66
Warning
Before starting work on the gas pipes, turn off the main gas tap.
Before installing, check that the gas meter has sufficient
capacity. Take into account the consumption of all appliances.
Notify the local energy company if the gas meter has insufficient
capacity.
Fig.23Connecting the gas pipe
1. Fit the gas supply pipe to the gas connection .
2. Fit the gas pipe to the gas tap.
Caution
Always perform welding work at a sufficient distance from the
boiler.
Remove dirt and dust from the gas pipe.
Important
We recommend installing a gas filter to prevent clogging of the
gas valve unit.
6.5 Air supply/flue gas outlet connections
AD-3000924-01
AD-3000925-01
AD-3000926-01
AD-3000927-01
7686707 - v.01 - 06092018AMC29
Tab.13Types of flue gas connections
TypePrincipleDescription
B
23
B
23P
Room-ventilated version
Without down-draught diverter.
Flue gas discharge via the roof.
Air from the installation area.
6.5.1 Classification
Important
The installer is responsible ensuring that the right type of flue
gas outlet system is used and that the diameter and length are
correct.
Always use connection materials and roof terminal supplied by
the same manufacturer. Consult the manufacturer for
compatibility details.
Without down-draught diverter.
Joint flue gas discharge via the roof, with guar
anteed natural draft. (at all times underpressure
in the joint discharge duct)
Flue gas discharge rinsed with air, air from the
installation area (special construction).
Room-sealed version
Discharge in the outside wall.
Inlet opening for the air supply is in the same
pressure zone as the discharge (e.g. a com
bined outside wall feed-through).
Parallel not permitted
Room-sealed version
Flue gas discharge via the roof.
Inlet opening for the air supply is in the same
pressure zone as the discharge (e.g. a concen
tric roof feed-through).
Combined air supply and flue gas outlet system
(CLV) with overpressure.
Concentric (preferably).
Parallel (if concentric is not possible).
Minimum permitted pressure difference between
the air supply and the flue gas outlet is -200 Pa
(including -100 Pa wind pressure).
The channel must be designed for a nominal
flue gas temperature of 25°C
Place a condensation drain, equipped with a si
phon, at the bottom of the channel.
Maximum permissible recirculation of 10%.
The common outlet should be appropriate for a
pressure of at least 200 Pa.
The roof feed-through must be designed for this
configuration and must cause a draught in the
channel.
A draught diverter is not permitted.
Important
The fan speed must be adapted for
this configuration.
Contact us for more information.
C
53(X)
Connection in different pressure zones
Closed unit.
Separate air supply duct.
Separate flue gas discharge duct.
Discharging into various pressure areas.
The air supply and the flue gas outlet must not
be placed on opposite walls.
Air supply and flue gas discharge duct in shaft
or ducted:
Concentric.
Air supply from existing duct.
Flue gas discharge via the roof.
Inlet opening for the air supply is in the same
pressure zone as the discharge.
When selecting the material,
please note the following:
Condensed water must flow
back to the appliance
The material must be resist
ant to the flue gas tempera
ture of this appliance.
Maximum permissible recir
culation of 10%.
The air supply and the flue
gas outlet must not be placed
on opposite walls.
Minimum permitted pressure
difference between the air
supply and the flue gas outlet
is -200 Pa (including -100 Pa
wind pressure).