1 delayed contact (terminals 15-16-18) and
1 instantaneous contact (terminals 25-26-28)
E11 ON delay
R11 OFF delay with control contact
Es11 ON delay with control contact
Wu11 Single shot leading edge voltage controlled
Ws11 Single shot leading edge with control contact
Wa11 Single shot trailing edge with control contact
Bi11 Flasher pulse first
Bp11 Flasher pause first
2 delayed contacts
E20 ON delay
R20 OFF delay with control contact
Es20 ON delay with control contact
Wu20 Single shot leading edge voltage controlled
Ws20 Single shot leading edge with control contact
Wa20 Single shot trailing edge with control contact
Bi20 Flasher pulse first
Bp20 Flasher pause first
Supply voltage:
12 to 400V AC terminals A1-A2 (galvanically separated)
selectable via power modules TR2
Tolerance: according to specification of power module
Rated frequency: according to specification of power module
Rated consumption: 2VA (1.5W)
Duration of operation: 100%
Reset time: 100ms
Residual ripple for DC: Drop-out voltage: >30% of the supply voltage
Overvoltage category: III (according to IEC 60664-1)
Rated surge voltage: 4kV
6. Output circuit
2 potential free change-over contacts
Rated voltage: 250V AC
Fusing: 5A fast acting
Mechanical life: 20 x 106 operations
Electrical Life: 2 x 105 operations
at 1000VA resistive load
Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category: III (according to IEC 60664-1)
Rated surge voltage: 4kV
7. Control contact
Activation: bridge Y1-Y2
Potential free: yes, basic isolation against input
and output circuit
Loadable: no
Control voltage: max. 5V
Short circuit current: max. 1mA
Line length: max. 10m
Control pulse length: min. 50ms
3. Indicators
Green LED ON: indication of supply voltage
Green LED flashes: indication of time period
Yellow LED ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: any. Shockproof terminal connection according to
VBG 4 (PZ1 required), IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
www.tele-online.com
8. Remote potentiometer (not included)
The internal potentiometer is de-activated when a remote potentio-meter
is connected !!!
Connections:1MΩpotentiometer(typeRONDOR2),
terminals Z1-Y2
Line type: twisted pair
Control voltage: max. 5V
Relative humidity: 15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree: 3 (according to IEC 664-1)
Vibration resistance: 10 to 55Hz 0.35mm (according to IEC 68-2-6)
Shock resistance: 15g 11ms (according to IEC 68-2-27)
Functions
The internal potentiometer is de-activated when a remote-potentio-meter
is connected ! The function has to be set before connecting the relay to
the supply voltage.
ON delay (E11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired (green LED illuminated) the
delayed contact switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the expiry of the interval t, the interval
already expired is erased and is restarted when the supply voltage is
next applied.
OFF delay with control contact (R11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, both
contacts switch into on-position (yellow LED illuminated). If the control
contact is opened, the instantaneous contact switches into off-position
and the set interval t begins (green LED flashes). After the interval t
has expired (green LED illuminated) the delayed contact switches into
off-position (yellow LED not illuminated). If the control contact is closed
again before the interval t has expired, the interval already expired is
erased and is restarted with the next cycle.
ON delay with control contact (Es11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the
instantaneous contact switches into on-position and the set interval t
begins (green LED flashes). After the interval t has expired (green LED
illuminated) the delayed contact switches into on-position (yellow LED
illuminated). This status remains until the control contact is opened
again.
If the control contact is opened before the interval t has expired, the
interval already expired is erased and is restarted with the next cycle.
Single shot leading edge voltage controlled (Wu11)
When the supply voltage U is applied, both contacts switch into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated) the
delayed contact switches into off-position (yellow LED not illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the interval t has expired, the both contacts
switch into off-position. The interval already expired is erased and is
restarted when the supply voltage is next applied.
Single shot leading edge with control contact (Ws11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, both
contacts switch into on-position (yellow LED illuminated) and the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the delayed contact switches into off-position
(yellow LED not illuminated). The instantaneous contact remains in
on-position, until the control contact is opened again. During the interval,
the control contact (and the instantaneous contact) can be operated any
number of times. A further cycle can only be started when the cycle run
has been completed.
www.tele-online.com
Page 3
G2ZMF11
U
LED U
R
15-16-18
R
25-26-28
t
<t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t
Y1-Y2
<t
U
LED U
R
15-16-18
R
25-26-28
t
<t
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
ttttt
U
LED U
R
15-16-18
R
25-26-28
tttt
U
LED U
R
15-16-18
R
25-26-28
t
<t
Functions
Single shot trailing edge with control contact (Wa11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed the
instantaneous contact switches into on-position. When the control
contact is opened, the instantaneous contact switches into off-position,
the delayed contact switches into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval t
has expired (green LED illuminated), the delayed contact switches into
off-position (yellow LED not illuminated). During the interval, the control
contact (and the instantaneous contact) can be operated any number of
times. A further cycle can only be started when the cycle run has been
completed.
Flasher pulse first (Bi11)
When the supply voltage U is applied, the instantaneous contact and
the delayed contact switch into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval t has
expired, the delayed contact switches into off-position (yellow LED not
illuminated) and the set interval t begins again. The delayed contact is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
OFF delay with control contact (R20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the output
relay R switches into on-position (yellow LED illuminated). If the control
contact is opened, the set interval t begins (green LED flashes). After the
interval t has expired (green LED illuminated) the output relay switches
into off-position (yellow LED not illuminated). If the control contact
is closed again before the interval t has expired, the interval already
expired is erased and is restarted with the next cycle.
ON delay with control contact (Es20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the output relay R switches into on-position
(yellow LED illuminated). This status remains until the control contact is
opened again. If the control contact is opened before the interval t has
expired, the interval already expired is erased and is restarted with the
next cycle.
Flasher pause first (Bp11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired, the delayed contact switches
into on-position (yellow LED illuminated) and the set interval t begins
again. After the interval t has expired, the delayed contact switches
into off-position (yellow LED not illuminated). The delayed contact is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
ON delay (E20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay R switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the expiry of the interval t, the interval
already expired is erased and is restarted when the supply voltage is
next applied.
Single shot leading edge voltage controlled (Wu20)
When the supply voltage U is applied, the output relay R switches into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay switches into off-position (yellow LED not illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the interval t has expired, the output relay
switches into off-position. The interval already expired is erased and is
restarted when the supply voltage is next applied.
Single shot leading edge with control contact (Ws20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the output
relay R switches into on-position (yellow LED illuminated) and the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the output relay switches into off-position
(yellow LED not illuminated). During the interval, the control contact can
be operated any number of times. A further cycle can only be started
when the cycle run has been completed.
www.tele-online.com
Page 4
G2ZMF11
15
16 182526 28
A1A2Y1
Y2Z1
15
16 18
25 26 28
R2
1
2
3
S
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
ttttt
U
LED U
R
15-16-18
R
25-26-28
ttttt
Functions
Single shot trailing edge with control contact (Wa20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). Closing the control contact Y1-Y2 has no influence on
the condition of the output relay R. When the control contact is opened,
the output relay switches into on-position (yellow LED illuminated) and
the set interval t begins (green LED flashes). After the interval t has
expired (green LED illuminated), the output relay switches into offposition (yellow LED not illuminated). During the interval, the control
contact can be operated any number of times. A further cycle can only
be started when the cycle run has been completed.
Flasher pulse first (Bi20)
When the supply voltage U is applied, the output relay R switches into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired, the output relay switches
into off-position (yellow LED not illuminated) and the set interval t begins
again. The output relay is triggered at a ratio of 1:1 until the supply
voltage is interrupted.
Dimensions
Connections
Flasher pause first (Bp20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
again. After the interval t has expired, the output relay switches into offposition (yellow LED not illuminated). The output relay is triggered at a
ratio of 1:1 until the supply voltage is interrupted.
RELEASE 2009/07
Subject to alterations and errors
www.tele-online.com