Datasheet G2ZMF11 Specification

Page 1
Timers - Multifunction16 functions
GAMMA series
16 functions
16 time ranges
Connection of remote potentiometer possible
Supply voltage selectable via power modules
Width 22.5mm
Industrial design
Technical data
G2ZMF11
1. Functions
1 delayed contact (terminals 15-16-18) and 1 instantaneous contact (terminals 25-26-28) E11 ON delay R11 OFF delay with control contact Es11 ON delay with control contact Wu11 Single shot leading edge voltage controlled Ws11 Single shot leading edge with control contact Wa11 Single shot trailing edge with control contact Bi11 Flasher pulse first Bp11 Flasher pause first
2 delayed contacts E20 ON delay R20 OFF delay with control contact Es20 ON delay with control contact Wu20 Single shot leading edge voltage controlled Ws20 Single shot leading edge with control contact Wa20 Single shot trailing edge with control contact Bi20 Flasher pulse first Bp20 Flasher pause first
2. Time ranges
Time range Adjustment range 1s 50ms 1s 3s 150ms 3s 10s 500ms 10s 30s 1500ms 30s 1min 3s 1min 3min 9s 3min 10min 30s 10min 30min 90s 30min 1h 3min 1h 3h 9min 3h 10h 30min 10h 30h 90min 30h 1d 72min 1d 3d 216min 3d 10d 12h 10d 30d 36h 30d
5. Input circuit
Supply voltage: 12 to 400V AC terminals A1-A2 (galvanically separated) selectable via power modules TR2 Tolerance: according to specification of power module Rated frequency: according to specification of power module Rated consumption: 2VA (1.5W) Duration of operation: 100% Reset time: 100ms Residual ripple for DC: ­Drop-out voltage: >30% of the supply voltage Overvoltage category: III (according to IEC 60664-1) Rated surge voltage: 4kV
6. Output circuit
2 potential free change-over contacts Rated voltage: 250V AC
Switching capacity (distance <5mm): 750VA (3A / 250V AC) Switching capacity (distance >5mm): 1250VA (5A / 250V AC)
Fusing: 5A fast acting Mechanical life: 20 x 106 operations Electrical Life: 2 x 105 operations at 1000VA resistive load Switching frequency: max. 60/min at 100VA resistive load max. 6/min at 1000VA resistive load (according to IEC 947-5-1) Overvoltage category: III (according to IEC 60664-1) Rated surge voltage: 4kV
7. Control contact
Activation: bridge Y1-Y2 Potential free: yes, basic isolation against input and output circuit Loadable: no Control voltage: max. 5V Short circuit current: max. 1mA Line length: max. 10m Control pulse length: min. 50ms
3. Indicators
Green LED ON: indication of supply voltage Green LED flashes: indication of time period Yellow LED ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40 Mounted on DIN-Rail TS 35 according to EN 50022 Mounting position: any. Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 Tightening torque: max. 1Nm Terminal capacity: 1 x 0.5 to 2.5mm² with/without multicore cable end 1 x 4mm² without multicore cable end 2 x 0.5 to 1.5mm² with/without multicore cable end 2 x 2.5mm² flexible without multicore cable end
www.tele-online.com
8. Remote potentiometer (not included)
The internal potentiometer is de-activated when a remote potentio-meter is connected !!!
Connections: 1MΩpotentiometer(typeRONDOR2),
terminals Z1-Y2 Line type: twisted pair Control voltage: max. 5V
Shortcircuitcurrent:  max.5μA
Line length: max. 5m
Page 2
G2ZMF11
U
LED U
R
15-16-18
R
25-26-28
t
Y1-Y2
<t
U
LED U
R
15-16-18
R
25-26-28
t
<t
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t
<t
U
LED U
R
15-16-18
R
25-26-28
t
Y1-Y2
<t
Technical data
9. Accuracy
Base accuracy: ±1% (of maximum scale value)
using1MΩremotepotentiometer
Frequency response: -
Adjustmentaccuracy: ≤5%(ofmaximumscalevalue)  using1MΩremotepotentiometer
Repetition accuracy: <0.5% or ±5ms
Voltageinuence:  ­Temperatureinuence: ≤0.01%/°C
10. Ambient conditions
Ambienttemperature: -25to+55°C(accordingtoIEC68-1)  -25to+40°C(accordingtoUL508) Storagetemperature: -25to+70°C Transporttemperature: -25to+70°C
Relative humidity: 15% to 85% (according to IEC 721-3-3 class 3K3) Pollution degree: 3 (according to IEC 664-1) Vibration resistance: 10 to 55Hz 0.35mm (according to IEC 68-2-6) Shock resistance: 15g 11ms (according to IEC 68-2-27)
Functions
The internal potentiometer is de-activated when a remote-potentio-meter is connected ! The function has to be set before connecting the relay to the supply voltage.
ON delay (E11)
When the supply voltage U is applied, the instantaneous contact switches into on-position and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into on-position (yellow LED illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the interval t, the interval already expired is erased and is restarted when the supply voltage is next applied.
OFF delay with control contact (R11)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, both contacts switch into on-position (yellow LED illuminated). If the control contact is opened, the instantaneous contact switches into off-position and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into off-position (yellow LED not illuminated). If the control contact is closed again before the interval t has expired, the interval already expired is erased and is restarted with the next cycle.
ON delay with control contact (Es11)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, the instantaneous contact switches into on-position and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into on-position (yellow LED illuminated). This status remains until the control contact is opened again. If the control contact is opened before the interval t has expired, the interval already expired is erased and is restarted with the next cycle.
Single shot leading edge voltage controlled (Wu11)
When the supply voltage U is applied, both contacts switch into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into off-position (yellow LED not illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the interval t has expired, the both contacts switch into off-position. The interval already expired is erased and is restarted when the supply voltage is next applied.
Single shot leading edge with control contact (Ws11)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, both contacts switch into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into off-position (yellow LED not illuminated). The instantaneous contact remains in on-position, until the control contact is opened again. During the interval, the control contact (and the instantaneous contact) can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
www.tele-online.com
Page 3
G2ZMF11
U
LED U
R
15-16-18
R
25-26-28
t
<t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t
Y1-Y2
<t
U
LED U
R
15-16-18
R
25-26-28
t
<t
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t t t t t
U
LED U
R
15-16-18
R
25-26-28
t t t t
U
LED U
R
15-16-18
R
25-26-28
t
<t
Functions
Single shot trailing edge with control contact (Wa11)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed the instantaneous contact switches into on-position. When the control contact is opened, the instantaneous contact switches into off-position, the delayed contact switches into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated), the delayed contact switches into off-position (yellow LED not illuminated). During the interval, the control contact (and the instantaneous contact) can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
Flasher pulse first (Bi11)
When the supply voltage U is applied, the instantaneous contact and the delayed contact switch into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired, the delayed contact switches into off-position (yellow LED not illuminated) and the set interval t begins again. The delayed contact is triggered at a ratio of 1:1 until the supply voltage is interrupted.
OFF delay with control contact (R20)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, the output relay R switches into on-position (yellow LED illuminated). If the control contact is opened, the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the output relay switches into off-position (yellow LED not illuminated). If the control contact is closed again before the interval t has expired, the interval already expired is erased and is restarted with the next cycle.
ON delay with control contact (Es20)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the control contact is opened again. If the control contact is opened before the interval t has expired, the interval already expired is erased and is restarted with the next cycle.
Flasher pause first (Bp11)
When the supply voltage U is applied, the instantaneous contact switches into on-position and the set interval t begins (green LED flashes). After the interval t has expired, the delayed contact switches into on-position (yellow LED illuminated) and the set interval t begins again. After the interval t has expired, the delayed contact switches into off-position (yellow LED not illuminated). The delayed contact is triggered at a ratio of 1:1 until the supply voltage is interrupted.
ON delay (E20)
When the supply voltage U is applied, the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the interval t, the interval already expired is erased and is restarted when the supply voltage is next applied.
Single shot leading edge voltage controlled (Wu20)
When the supply voltage U is applied, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the output relay switches into off-position (yellow LED not illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the interval t has expired, the output relay switches into off-position. The interval already expired is erased and is restarted when the supply voltage is next applied.
Single shot leading edge with control contact (Ws20)
The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the output relay switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
www.tele-online.com
Page 4
G2ZMF11
15
16 182526 28
A1A2Y1
Y2Z1
15
16 18
25 26 28
R2
1
2
3
S
U
LED U
R
15-16-18
R
25-26-28
t
t
Y1-Y2
U
LED U
R
15-16-18
R
25-26-28
t t t t t
U
LED U
R
15-16-18
R
25-26-28
t t t t t
Functions
Single shot trailing edge with control contact (Wa20)
The supply voltage U must be constantly applied to the device (green LED illuminated). Closing the control contact Y1-Y2 has no influence on the condition of the output relay R. When the control contact is opened, the output relay switches into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated), the output relay switches into off­position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
Flasher pulse first (Bi20)
When the supply voltage U is applied, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins (green LED flashes). After the interval t has expired, the output relay switches into off-position (yellow LED not illuminated) and the set interval t begins again. The output relay is triggered at a ratio of 1:1 until the supply voltage is interrupted.
Dimensions
Connections
Flasher pause first (Bp20)
When the supply voltage U is applied, the set interval t begins (green LED flashes). After the interval t has expired, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins again. After the interval t has expired, the output relay switches into off­position (yellow LED not illuminated). The output relay is triggered at a ratio of 1:1 until the supply voltage is interrupted.
RELEASE 2009/07
Subject to alterations and errors