Danfoss VLT Metasys Operating guide

Contents
VLT® Metasys
1 Overview
1.1.1 Software Version 2
1.1.2 Introduction 2
1.1.3 About this Manual 2
1.1.4 References 2
2 Instructions
2.1.1 Abbreviations and Definitions 3
2.1.2 Network Connection 3
2.1.3 Hardware Set-up 3
2.1.5 VLT Parameters 4
3 Appendix
3.1.1 Analog Inputs (AI) 18
3.1.2 Binary Inputs (BI) 19
3.1.3 Analog Outputs (AO) 23
3.1.4 Binary Outputs (BO) 24
3.1.5 Internal Floating Point (ADF) 25
2
3
18
3.1.6 Internal Integers (ADI) 27
Index
29
MG.11.G2.02 - VLT® is a registered Danfoss trademark 1
Overview
VLT® Metasys
11
1 Overview
1.1.1 Software Version
VLT HVAC Drive
FC 102 Series
Software version: 3.4x
and VLT AQUA Drive FC 202 Series
Software version: 1.7x
This guide can be used with all VLT HVAC Drive frequency converters with
software version 3.4x and VLT AQUA Drive frequency converters with
software version 1.7x.
The actual software version number can be read from
par. 15-43 Software Version.
1.1.2 Introduction
The frequency converter control board is program selectable for use with the Johnson Controls Metasys N2 protocol. Metasys N2 is a master/slave control network. The physical layer is RS-485 compatible, half duplex 9600 baud shielded twisted pair. The N2 software protocol is designed to be general in nature to accommodate the unique properties each device type may have. Every device connection to the N2 network can be thought of as a small data manager. Data points in the database are classified as analog I/O (floating point), binary I/O or integer data points - floats, integers or bytes. Each data type has its own unique structure defined in the Metasys N2 system Protocol Specification for Vendors.
The information in this manual is intended to provide you with comprehensive information on how to install and set up the frequency converter for communication over a Metasys network.
For specific information on operation of the drive, refer to the
VLT HVAC Drive Operating Instructions, MG.11.Ax.yy or the VLT AQUA Drive Operating Instructions, MG.20.Mx.yy.
1.1.3 About this Manual
This manual is for both instructional and for reference purposes. This manual can also serve as a guideline when you specify and optimize your communication system. It is highly recommended that you read this manual in its entirety before initiating any programming. It is assumed that the user has full knowledge of the capabilities and limitation of the controller node in addition to full knowledge of the frequency converter.
References
1.1.4
In addition to this manual, the following two manuals should be consulted: VLT HVAC Drive Operating Instructions, MG.
11.Ax.yy, VLT AQUA Drive Operating Instructions, MG.20.Mx.yy and Johnson Controls METASYS N2 System Protocol Specification for Vendors, Johnson Controls number 04-3402-22, rev A.
2 MG.11.G2.02 - VLT® is a registered Danfoss trademark
130BA060.11
68 69 68 69 68 69
RS 485
RS 232 USB
+
-
1 2
S801
ON
130BA272.11
Instructions
VLT® Metasys
2 Instructions
2.1.1 Abbreviations and Definitions
ACK Acknowledge
ADF Internal Floating Points ADI Internal Integers AI Analog Inputs AO Analog Outputs BI Binary Inputs BO Binary Outputs COS Change Of State FC Frequency Converter HPFB High Performance Field Bus JCI Johnson Controls Inc. developers of the METASYS N2 protocol N2 METASYS N2 N2
A N2 master is either a PC with JCI software or a dedicated JCI
mast
controller er NAK Not acknowledged NPA N2 Point Address (Each N2 Point Type has a address range
from 0 to 255) NPT N2 Point Type PAR Parameter Number
2.1.3 Hardware Set-up
RS-485 Bus Connection: One or more frequency converters can be connected to a control (or master) using the RS-485 standardized interface. Terminal 68 is connected to the P signal (TX+, RX+), while terminal 69 is connected to the N signal (TX-,RX-). If more than one frequency converter is connected to a master, use parallel connections.
Illustration 2.1: Bus termination switch
2 2
2.1.2 Network Connection
Connect signal wires to terminal 68 (N+) and terminal 69 (N-) on main control board of the drive. If shielded cabling is used, connect one end of the shield to terminal 61. This terminal is connected to ground via an internal RC link. It is highly recommended to use shielded twisted-pair cables to reduce the differential mode interference between the conductors. Danfoss do not take any responsibility for consequences, if unshielded or untwisted cables are used.
Torque Specifications: Control wire: 18 - 24 AWG, shielded, twisted pair
4.5 in.lb. (0.5 Nm) if screw terminal is used
NOTE
The factory setting for the dip switch is OFF.
In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal 61, which is connected to the frame via an RC-link. Bus termination: The RS-485 bus must be terminated by a resistor network at both ends. For this purpose, set switch S801 on the control card to "ON". For more information, see the paragraph: Switches S201, S202 and S801.
MG.11.G2.02 - VLT® is a registered Danfoss trademark 3
Instructions
2.1.4 Error Codes
VLT® Metasys
22
Error Code 00 is issued after power up or after a time out where all overridden points were released, as long as no Identify yourself
command has been issued by the master. Error Code 01 is issued if the command is not supported or not known by the drive. Error Code 02 is issued if the received telegram has a checksum error. Error Code 03 is issued if the N2 telegram receive buffer exceeds 256 characters. Error Code 05 is issued if the received N2 telegram is too long. Error Code 10 is issued the data is out of expected range Error Code 11 is issued when:
1. A point attributes or attribute bit is unused.
2. A point attributes or attribute bit is for JCI use only.
3. An internal data point attribute for current value can not be changed while running
Error Code 12 is issued when:
1. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is tripped.
2. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is trip locked except for BO 5 "reset"
2.1.5 VLT Parameters
The following parameters may need to be manually set for each drive in the Metasys N2 network. Refer to the VLT HVAC Drive Design Guide, MG.11.Bx.yy, or VLT AQUA Drive Design Guide, MG.20.Nx.yy, for the frequency converter for programming.
Parameter list
VLT Parameter Description Default Desired Setting 8-01 Control Side Digital & Ctrl. Word 8-02 Control Source FC Port FC Port 8-03 Control Word Timeout 60 s 1-18000 s 8-30 Protocol FC Metasys N2 8-31 Address 1 1-255 8-32 Baud Rate 9600 Fixed to 9600 8-33 Parity Even, 1stop Fixed to No Parity, 1stop 8-37 Maximum Inter-char Delay 25 s for Metasys N2
4 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.6 General Commands (Acknowledged)
VLT Response Command Subcommand
ACK 0 4 -
ACK 0 5 -
ACK 0 9 - Status update Message -
ACK F - - Identify Device Type -
ACK 0 0 - Synch Time -
ACK, no action 8 0 - Upload -
ACK, no action 8 1 - Upload -
ACK, no action 8 3 - Upload Record -
ACK, no action 8 4 - Upload Complete -
ACK, no action 9 0 - Download -
ACK, no action 9 1 - Download -
ACK, no action 9 3 - Download -
ACK, no action 9 4 - Download Complete -
NAK 0 1 - Read Memory 01
NPA Object
no.
Attribute Message Type Error Code Comments
Poll Message
No Acknowledge
Poll message
With Acknowledge
The slave is to respond with any data
-
-
points, analog or binary I/O that have
been flagged for COS The slave is to respond with any data points, analog or binary I/O that have
been flagged for COS
Slave device must respond with device
manufacturing model number (Par. 6-21),
days in service (Par. 6-00) and device
status
Slave device responds with an identifica-
tion number of 10H to indicate non JCI
device
The internal clock is syncronized by this
command
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Record optional, no support in the
frequency converter
Optional, no support in the frequency
converter
Slave device memory read based on
memory addresses
2 2
NAK 0 8 - Warm Start 01 JCI use only
MG.11.G2.02 - VLT® is a registered Danfoss trademark 5
Instructions
VLT® Metasys
2.1.7 Analog Input Commands (Acknowledged)
22
VLT
Response
ACK 1 - 1 0-23 1 Byte
ACK 1 - 1 0-23 2 Byte
ACK 1 - 1 0-23 3 Float
ACK 1 - 1 0-23 8 Float
ACK 1 - 1 0-23 9 Float
ACK 1 - 1 0-23 10 Float
ACK 1 - 1 0-23 11 Float
ACK 1 - 1 0-23 12 Float
ACK 2 - 1 0-23 1 Byte
ACK 2 - 1 0-23 8 Float
ACK 2 - 1 0-23 9 Float
ACK 2 - 1 0-23 10 Float
ACK 2 - 1 0-23 11 Float
ACK 2 - 1 0-23 12 Float
ACK, no
action
ACK, no
action
ACK, no
action
Command Subcom-
mand
7 2 1 0-23 - Float
7 3 1 0-23 - -
7 7 1 0-23 - -
Region
NPA Object
no.
Attribute
No.
Attribute Message Type Comments
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Override
Analog inputs
Override
Analog Release
Write Analog Input Attrib-
utes
Read Object Configuration attribute
associated with each individual point
1)
Read Object Status attribute
associated with each individual point
2)
Read Analog Input Value attribute associated with each individual point Read Low Alarm attribute associated
with each individual point
Read Low Warning attribute associ-
ated with each individual point
Read High Warning attribute associ-
ated with each individual point
Read High Alarm attribute associated
with each individual point
Read Differential attribute associated
with each individual point
Write to Object Configuration attrib-
ute associated with each individual
point
Write to Low Alarm Limit attribute associated with each individual point Write to Low Warning Limit attribute associated with each individual point Write to High Warning Limitattribute associated with each individual point
Write to High Alarm Limit attribute associated with each individual point Write to Differential attribute associ-
ated with each individual point
Analog inputs are "outputs" from the
frequency converter and should not
be written over by the network
controller
Analog inputs are "outputs" from the
frequency converter and should not
be written over by the network
controller
Optional command for slave devices.
Only used for N2
commissioning purposes
6 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.8 Analog Input Commands (Not Acknowledged)
VLT
Response
Comm and Region NPA Object no. Attribute
No.
Attribute Message Type Error
NAK 1 1 0-23 4 Float Read Analog
Input
NAK 1 1 0-23 5 Float Read Analog
Input
NAK 2 - 0-23 2 Byte Write Analog
Input
NAK 2 - 0-23 3 Float Write Analog
Input
NAK 2 - 0-23 4 Float Write Analog
Input
NAK 2 - 0-23 5 Float Write Analog
Input
NAK 2 - 0-23 6 Float Write Analog
Input
NAK 2 - 0-23 7 Float Write Analog
Input
NAK 2 - 0-23 13 Integer Write Analog
Input
NAK 2 - 0-23 14 Float Write Analog
Input
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
Comments
Code
1 )
Read Linear Ranging Parameter 1
11
attribute associated with each individual point. (JCI use only)
1)
Read Linear Ranging Parameter 2
11
attribute associated with each individual point. (JCI use only)
11
11
11
1)
1)
1)
Object Status writeable
Analog Input Value not writeable
Write to Linear Ranging Parame-
ter 1 attribute associated with
each individual point. (JCI use
1)
Write to Linear Ranging Parame-
11
ter 2 attribute associated with
each individual point. (JCI use
1)
Write to Linear Ranging Parame-
11
ter 3 attribute associated with
each individual point. (JCI use
1)
Write to Linear Ranging Parame-
11
ter 4 attribute associated with
each individual point. (JCI use
1)
11
Write to Filter Weight attribute associated with each individual
point. (JCI use only)
1)
Write to AI Offset attribute associ-
11
ated with each individual point.
(JCI use only)
2 2
only)
only)
only)
only)
MG.11.G2.02 - VLT® is a registered Danfoss trademark 7
Instructions
VLT® Metasys
2.1.9 Analog Output Commands (Acknowledged)
22
VLT
Response
ACK 1 - 3 0-2 1 Byte Read Analog
ACK 1 - 3 0-2 2 Byte Read Analog
ACK 0 9 - - - - Status update
ACK 1 - 3 0-2 3 Float Read Analog
ACK 2 - 3 0-2 1 Byte Write Analog
ACK 7 2 3 0-2 - Float Override Analog
ACK 7 2 3 0-2 - Float Override Analog
ACK 7 3 3 0-2 - - Override Release Set the current value, the value
ACK, no
action
ACK, no
action
Command Sub
command
7 7 3 0-2 - - Write Analog
7 8 3 0-2 - - Read Analog
Region NPA Object no. Attribute
No.
Attribute Message Type Comments
Output Attributes
Output
Output
Message
Output
Output
Output
Output
Output
Read Object Configuration
attribute associated with each
individual point
Read Object Status attribute
associated with each individual
point Slave device must respond with device manufacturing
model number (Par. 6-21), days
in service (Par. 6-00) and
device status
Read Current Value attribute
associated with each individual
point
Write to Object Configuration attribute associated with each
individual point
Write to analog output current
value (frequency setpoint)
Write to analog output current
value (frequency setpoint)
that it was before the 1.
Override Command was issued
Optional command for slave
devices. Only used for N2 Attributes commissioning
purposes. Not to be implemen-
ted at this time
Optional command for no
action slave devices. Only used
for N2 commissioning
purposes. Not to be implemen-
ted at this time
8 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.10 Analog Output Commands (Not Acknowledged)
VLT
Response
0-2 1 3 0-2 4 Float Read Analog
NAK 1 3 0-2 5 Float Read Analog
NAK 2 3 0-2 2 Byte Write Analog
NAK 2 3 0-2 3 Float Write Analog
NAK 2 3 0-2 4 Float Write Analog
NAK 2 3 0-2 5 Float Write Analog
Command Region NPA Object
no.
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
Attribute
No.
Attribute Message Type Error
Output
Output
Output
Output
Output
Output
Comments
Code
11
11
11
11
11
11
1
1
1
1
1
1
Read Low Linear Ranging
Parameter attribute associated
with each individual point. (JCI
use only) Read High Linear Ranging Para­meter attribute associated with
each individual point. (JCI use
Object Status not writeable
Write to Current Value structure
attributes associated with each
individual point. (N2 does not support this, override function
must be used)
Write Debouncing Value in msec
attribute associated with each
individual point.(JCI use only)
Write Accumulator value attrib-
ute associated with each individ-
ual point. (JCI use only)
2 2
only)
MG.11.G2.02 - VLT® is a registered Danfoss trademark 9
Instructions
VLT® Metasys
2.1.11 Binary Input (BI) Commands (Acknowledged)
22
VLT
Response
ACK 1 - 2 0-135 1 Byte Read Binary
ACK 1 - 2 0-135 2 Byte Read Binary
ACK 2 - 2 0-135 1 Byte Write Binary
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
Command Subcom-
mand
7 2 2 0-135 - Byte(0/1) Override Binary
7 3 2 0-135 - - OverrideRe-
7 7 2 0-135 - - Write Binary
7 8 2 0-135 - - Read Binary
Region NPA Object no. Attribute No. Attribute Message Type Comments
Input
Input
Input
Input
lease
Input
Input
Read Object Configuration
attribute associated with
each individual point Read Object Status attribute associated with each individ-
ual point
Write to Object Configuration
attribute associated with
each individual point
Binary inputs are "outputs"
from the frequency converter
and should not be written
over by the network control-
ler. (Status word, Warnings,
and Alarms)
Binary inputs are "outputs"
from the drive and should
not be written over by the
network controller. (Status word, Warnings and Alarms) Optional command for slave
devices. Only Attributes used
for N2 commissioning
purposes. Not to be
implemented at this time
Optional command for Attrib-
utes slave devices. Only used
for N2 commissioning
purposes. Not to be
implemented at this time
2.1.12 Binary Input (BI) Commands (Not Acknowledged)
VLT
Response
NAK 2 2 0-135 2 Byte Write Binary
NAK 2 2 0-135 3 Integer Write Binary
NAK 2 2 0-135 4 Integer32Write Binary
10 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Command Region NPA Object
no.
Attribute No. Attribute Message Type Error
Input
Input
Input
Comments
Code
1
11
11
11
Object Status not writeable
1
Write Debouncing Value in msec
attribute associated with each individual point.(JCI use only)
1
Write Accumulator value attrib-
ute associated with each individ-
ual point (JCI use only)
Instructions
VLT® Metasys
2.1.13 Binary Output Commands (Acknowledged)
VLT
Response
ACK 1 - 4 0-10 1 Byte Read Binary
ACK 1 - 4 0-10 2 Byte Read Binary
ACK 2 - 4 0-10 1 Byte Write Binary
ACK 7 2 4 0-10 - Byte(0/1) Override Binary
ACK 7 2 4 0-10 - Byte(0/1) Override Binary
ACK 7 3 4 0-10 - - Override Release Set the current value, the value that
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
Command Subcom-
mand
1 - 4 0-10 3 Integer Read Binary
1 - 4 0-10 4 Integer Read Binary
1 - 4 0-10 5 Integer Read Binary
2 - 4 0-10 3 Integer Write Binary
2 - 4 0-10 4 Integer Write Binary
2 - 4 0-10 5 Integer Write Binary
7 7 4 0-10 - - Write Binary
7 8 4 0-10 - - Read Binary
Region NPA Object
no.
Attribute
No.
Attribute Message Type Comments
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Read structure attributes associated
with each individual point
Read structure attributes associated
with each individual point
Write to Object Configuration attrib-
ute associated with each
individual point
Write to binary output current state
(VLT control word)
Write to binary output current state
(VLT control word)
it was before the 1. Override
Command was issued
Read Minimum On-time attribute
associated with each
individual point. Return value = 0
Read Minimum Off-time attribute
associated with each
individual point. Return value = 0
Read Maximum Cycles/ Hour attrib-
ute associated with each individual point. Return value = 0 Write Minimum On-time attribute
associated with each individual
point
Write Minimum Off-time attribute
associated with each individual
point
Write Maximum Cycles/ Hour attrib-
ute associated with each
individual point
Optional command for slave
devices. Only Attributes used for N2
commissioning purposes
Optional command for slave
devices. Only Attributes used for N2
commissioning purposes
2 2
MG.11.G2.02 - VLT® is a registered Danfoss trademark 11
Instructions
VLT® Metasys
2.1.14 Binary Output (BO) Commands (Not Acknowledged)
22
VLT
Response
NAK 1 4 0-10 6 Integer Read Binary
NAK 1 4 0-10 7 Integer Read Binary
NAK 2 4 0-10 2 Byte Write Binary
NAK 2 4 0-10 6 Integer Write Binary
NAK 2 4 0-10 7 Integer Write Binary
Command Region NPA Object
no.
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
Attribute No. Attribute Message Type Error Code Comments
1)
Read Interstage on delay attrib-
11
Output
individual point. (JCI use only)
1)
Read Interstage off delay attrib-
11
Output
individual point. (JCI use only)
1)
11
Output
11
Output
11
Output
Object Status not writeable
1)
Write Interstage on delay attrib-
individual point. (JCI use only)
1)
Write Interstage off delay attrib-
individual point. (JCI use only)
ute associated with each
ute associated with each
ute associated with each
ute associated with each
2.1.15 Internal Integers (ADI) Commands (Acknowledged)
VLT
Response
ACK 1 - 6 0-254 1 Integer Read Internal
ACK 1 - 6 0-254 2 Integer Read Internal
ACK 2 - 6 0-254 - Integer Write Internal
ACK 7 2 6 0-254 - Integer Override Internal
ACK 7 3 6 0-254 - - Override Release Set the current value, the
Command Subcom-
mand
Region NPA Object no. Attribute No. Attribute Message Type Comments
Read Object Status associ-
Parameter of
object type
integer (16 bit)
Parameter of
object type
integer (16bit)
Parameter of
object type
integer (16bit)
Parameter of
object type
Integer (16 bit)
ated with each individual
point
Read Current Value attrib-
ute associated with each
individual point
Write to Current Value
attribute associated with
each individual point
Write to internal parame-
ter current value (set-up
parameters for VLT)
value that it was before
the 1. Override Command
was issued
12 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.16 Internal Floating Point Commands (Acknowledged)
VLT
Response
ACK 1 - 5 0-101 1 Byte Read Internal
ACK 1 - 5 0-101 2 Float Read Internal
ACK 2 - 5 0-101 - Float Write Internal
ACK 2 - 5 0-101 - Float Write Internal
ACK 7 2 5 0-101 - Float Override Internal
ACK 7 3 5 0-101 - - Override Release Set the current value, the
Command Subcom-
mand
Region NPA Object no. Attribute No. Attribute Message Type Comments
Read Object Status
Parameter of
object type float
Parameter of
object type float
Parameter of
object type float
Parameter of
object type float
Parameter of
object type float
associated with each
individual point
Read Current Value
attribute associated with
each individual point
Write to Current Value
attribute associated with
each individual point
Write to Current Value
attribute associated with
each individual point
Write to internal parame-
ter current value (set-up
parameters for VLT)
value that it was before
the 1. Override
Command was issued
2 2
MG.11.G2.02 - VLT® is a registered Danfoss trademark 13
Instructions
VLT® Metasys
2.2.1 Start-up of the Frequency Converter
22
drive or remote. Use the Extended Menu key to access the 8-** group parameters (serial communication). The settings shown below are typical. Some settings may be changed to meet the application requirements. The settings below will serve as a good starting reference. Refer to the operating instruction manual for instructions on changing parameters and program­ming the drive.
Examples of typical settings. Program the following:
Parameter: Setting:
Use the frequency converter keypad mounted either on the
Par. 8-30 Protocol Par. 8-31 Address Par. 8-32 Baud Rate
Par. 8-50 Coasting Select Par. 8-52 DC Brake Select Par. 8-53 Start Select Par. 8-54 Reversing Select Par. 8-55 Set-up Select Par. 8-56 Preset Reference Select Par. 8-94 Bus Feedback 1 Par. 8-95 Bus Feedback 2
[3] Metasys N2 1 (Default) [2] 9600 Baud (fixed at 9600 for N2 protocol) [3] Logic OR [3] Logic OR [3] Logic OR [0] Digital input [3] Logic OR [3] Logic OR 0 0
Telegram code: >XX72040401YY <CR>
Issue a frequency reference through the master, to the device:
Example 3:
Over-ride analog output, speed (50%) change command: Device address XX Char1 command 7 Char1 subcommand 2 Char2 region 03 Char2 object number (NPA) 00 Char8 override value * 4E 00 00 00 override value = 50%
Checksum YY
Setting:
speed (IEEE floating point, format)
Telegram code: >XX7203004E000000<CR>
To calculate override value for speed: refer to Scaling of Bus Reference and Bus Feedback. Issue an override release command through the master to the device:
NOTE
Send an F command to begin communications between the master and the drive
Example 1:
F command Device address XX Char1 command F Checksum YY
Telegram code: >XXFYY <CR>
Issue a run command through the master, to the device:
Example 2:
start, BO override command: Setting:
Bus Device address XX Char1 command 7 Char1 subcommand 2 Char2 region 04 Char2 object number (NPA) 04 (Start) Char2 override value 01 (Active) Checksum YY
Setting:
Example 4:
Bus stop, BO over-ride release command: Device address XX Char1 command 7 Char1 subcommand 2 Char2 region 04 Char2 object number (NPA) 04 (Start) Char8 override value * 00 (Not active) Checksum Y
Setting:
Telegram code: >XX72040400YY <CR>
If the preceding commands were issued, the drive should have accelerated to 50% after the speed reference was issued. After the override release, the drive should have stopped.
14 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.2.2 Scaling of Bus Reference and Feedback
Reference/ feedback 20% 20 * 16384/100 3276.8 454C CCCD 50% 50 * 16384/100 8192 4600 0000
100%
200%
-100%
-200%
Table 2.1: Reference/feedback values
Scaling Float IEEX hex
100 *
16384/100
200 *
16384/100
-100 *
16384/100
-200 *
16384/100
16384 4680 0000
32767 46FF FE00
-16384 C680 0000
-32768 C700 0000
The reference/feedback value is the percentage of the range of parameter 3-02 and 3-03. Values within the ranges 100% to 200% and -200% to -100% applies only to the reference. The Float representation of the value 200% must be limited to maximum 32767 and minimum -32768.
Status Update Request
2.2.3
A Status Update Request will cause the drive to report its current operating status. The status codes, descriptions and associated alarms are shown in the chart below.
The Device Status Code consists of two parts. The Least Signif­icant Byte, (LSB) of the hex number is the Alarm Number. The Most Significant Byte (MSB) indicates if the alarm is a normal trip (01) that can be reset automatically or manually, or if the alarm is a trip lock (02) requiring cycling power to the drive.
Status codes with associated alarms and descriptions
Device Status Code1 0x0000 - Device OK 0x0102 2 Live zero error 0x0204 4 Phase fault (Trip lock) 0x0107 7 Over voltage 0x0108 8 Under voltage 0x0109 9 Inverter overloaded 0x010A 10 Motor overloaded 0x010B 11 Motor thermistor 0x010C 12 Current limit 0x020D 13 Over current (Trip lock) 0x020E 14 Earth fault (Trip lock) 0x020F 15 Switch mode fault (Trip lock) 0x0210 16 Short circuit (Trip lock) 0x0111 17 Standard bus time out 0x0112 18 HPFB time out 0x0116 22 Auto optimization not OK 0x021D 29 Heat sink temperature to high (Trip
0x011E 30 Motor phase U missing 0x011F 31 Motor phase V missing 0x0120 32 Motor phase W missing 0x0122 34 Profibus communication error 0x0225 37 Inverter fault (Trip lock) 0x013C 60 Safety interlock 0x0263 99 Unknown fault (Trip lock)
Alarm
No.
Description
lock)
Read/write notes A write command to an ADF (Internal Floating Point) or BD (Internal Byte) point type will be stored in the drive's EEPROM.
2 2
NOTE
If write command is issued to an overridden point, the new value will not be stored in the drive's EEPROM.
MG.11.G2.02 - VLT® is a registered Danfoss trademark 15
Instructions
VLT® Metasys
2.2.4 Override/Override Release Commands
Handling of Poll Message Commands
2.2.6 and Time Out, 8-04 (Setting [20], N2 Override release)
22
The way the overridden points are released is very important to the way the drive will behave during the override release time out or for release commands issued by the N2 master. This is due to the fact that the active setup can be changed to a different setup. If one would release the active setup before the values that have been overridden in that setup, the backup values would then be restored to the wrong setup, leaving the overridden values in the old setup unchanged.
The release after override time out: During an override release time-out, all points which are overridden, will be released in the order, which they are specified in Appendix POINTMAP:
1. Release Analog Outputs from point address (NPA) 0 to 255.
2. Release Binary Outputs from point address (NPA) 0 to 255.
3. Release Internal Floating Points from point address (NPA) 0 to 255.
4. Release Internal Integer Points from point address (NPA) 0 to 255.
5. Release Internal Byte points from point address (NPA) 0 to 255.
The Identity Command will cause the drive to report all AI, AO, BI and BO points, which are available when the next Poll (0/4) is received. The drive also supports COS for AI and BI point types. The drive is limited to responding with up to 200 ASCII characters, so multiple messages may need to be sent before all available points have been reported.
Upon receiving the Poll (0/4), the frequency converter will begin exporting the requested information. The frequency converter will continue to export new information upon receiving the 0/5 Poll until it has sent all requested informa­tion. Then it will respond to a new 0/5 Poll with an ACK response to indicate all information has been transmitted and complete the Poll sequence receiving a 0/4 Poll before sending the ACK response will cause the frequency converter to re-transmit its latest response.
The drawing below illustrates the AI COS handling.
Change of State (COS)/POLLING
2.2.5
A change of state occurs when a new command has been issued for the drive. This command can be issued through the bus or through a drive related status change or command. The master can issue a series of poll commands to the network devices to get an update on any status changes from the time of the last polling. When polling a frequency converter for the first time after a network has been powered up after an F command has been issued, a 0/4 poll command must be issued.
16 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
For AI: Alarm Enable or Warning Enable must be set in the Object Configuration Attribute (Attribute 1). Low/High Alarm limits (Attribute 8, 11) or Low/High Warning limits (Attribute 9, 10) must be programmed. Differential Value (Attribute 12) must also be programmed.
For BI: Alarm Enable must be set in the Object Configuration Attrib­ute (Attribute 1).
Normal state must be programmed in the Object Configura­tion Attribute (Attribute 1)
Att XX = Attribute number, HA = High alarm, LA = Low alarm, HW = High Warning, LW = Low Warning
The AI COS alarms will only be cleared when the point value goes below the high alarm/warning or above the low alarm/ warning limit by more than the programmed differential value (Attribute 12). The BI COS will set the Alarm (Object Status bit 4) if COS enabled (Object Configuration Bit 0) is set, Alarm Enabled (Object configuration bit 3) is set, and Current State (Object Status bit 6) is different from Normal State (Object Configura­tion bit 1).
VLT® Metasys
2 2
MG.11.G2.02 - VLT® is a registered Danfoss trademark 17
Appendix
3 Appendix
3.1.1 Analog Inputs (AI)
VLT® Metasys
3
NPA Unit Description Range FC Par. Number
0 % Reference [%] - 16-02 1 - Reference [Unit] - 16-01 2 - Feedback - 16-52 3 Hz Frequency - 16-13 4 - User defined readout - 16-09 5 A Current - 16-14 6 kW Power - 16-10 7 hp Power - 16-11 8 V Output Voltage - 16-12
9 V DC Voltage - 16-30 10 % Motor Thermal Protection - 16-18 11 % Inverter Thermal Protection - 16-35 12 V Terminal 53 analog - 16-62 13 V Terminal 54 analog - 16-64 16 % External reference - 16-50 17 C Heat sink temperature - 16-34 18 Hour Operating hours - 15-00 19 Hour Running hours - 15-01 20 kWh kWh counter - 15-02 21 - Power-ups - 15-03 22 - Over temps - 15-04 23 - Over voltages - 15-05 24 - Start Ups - 15-08 25 - Torque [%] - 16-22 26 - Speed [rpm] - 16-17 27 - Analog Input, GPIO X30/11 - 16-75 28 - Analog Input, GPIO X30/12 - 16-76 29 - Analog Input, IO option X42/1 -20.000 to +20.000 18-20 30 - Analog Input, IO optionX42/3 -20.000 to +20.000 18-21 31 - Analog Input, IO optionX42/5 -20.000 to +20.000 18-22 32 - Analog Out X42/7 - 18-33 33 - Analog Out X42/9 - 18-34 34 - Analog Out X42/11 - 18-35 40 - ECB: Bypass Running Hours 45 - Feedback 1 [Unit] - 16-54 46 - Feedback 2 [Unit] - 16-55 47 - Feedback 3 [Unit] - 16-56 48 - Ext. 1 Feedback [Unit] - 21-18 49 - Ext. 2 Feedback [Unit] - 21-38
0-232/10
31-11
The default values are shown in bold on the following pages. Any point not listed on the following pages is reserved for future use.
Some Metasys software uses an object number range from 0 to 255, other Metasys software uses the range 1 to 254. The latter software will interpret object number 0 as 1, and 1 as 2, etc. To access the proper point with this Metasys software, add 1 to the NPA number in the tables.
18 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Appendix
3.1.2 Binary Inputs (BI)
NPA Unit Description Range FC Par. Number
0 15 Timers Status 0=OK, 1=Limit 1 14 Current Status 0=OK, 1=Limit 2 13 Voltage Status 0=OK, 1=Limit 3 12 Inverter Status 0=OK, 1 =Stall, Auto-start 4 11 Running Status 0=Not Running, 1=Running 5 10 Frequency Status 0=Out of Range, 1=In Range 6 9 Control Status 0=Local, 1= Bus 7 8 Reference Status 0=Not on Ref., 1=On Ref. 8 7 Warning Status 0=No Warning , 1= Warning
9 3 Tripped Status 0=No Trip , 1=Tripped 10 2 Drive Enabled Status 0=Not Enabled , 1=Enabled 11 1 Drive Ready Status 0=Not Ready, 1=Ready 12 0 Drive Controller Status 0=Not Ready, 1=Ready 16 31 Reserved 17 30 Reserved 18 29 Unused 19 28 Unused 20 27 Voltage Limit 0=OK, 1=Warning 21 26 Low Temperature 0=OK, 1=Warning 22 25 Current Limit 0=OK, 1=Warning 23 24 Mains Failure 0=OK, 1=Warning 24 23 24V Supply Low 0=OK, 1=Warning 25 22 Fieldbus Fault 0=OK, 1=Warning 26 21 Speed Limit 0=OK, 1=Warning 27 20 Brake IGBT 0=OK, 1=Warning 28 19 Brake Resistor 0=OK , 1=Warning 29 18 Brake Overload 0=OK, 1=Warning 30 17 10V low 0=OK, 1=Warning 31 16 Live Zero Error 0=OK, 1=Warning 32 15 No Motor 0=OK, 1=Warning 33 14 Mains Phase Loss 0=OK, 1=Warning 34 13 DC Voltage High 0=OK, 1=Warning 35 12 DC Voltage Low 0=OK, 1=Warning 36 11 DC Overvoltage 0=OK, 1=Warning 37 10 DC Undervoltage 0=OK, 1=Warning 38 9 Inverter Overload 0=OK, 1=Warning 39 8 Motor ETR Overload 0=OK, 1=Warning
40 7
41 6 Torque Limit 0=OK, 1=Warning 42 5 Over Current 0=OK, 1=Warning 43 4 Ctrl. Word Timeout 0=OK, 1=Warning 44 3 Ctrl. Card Temp. 0=OK, 1=Warning 45 2 Earth Fault 0=OK, 1=Warning 46 1 Pwr. Card Temp 0=OK,1=Warning 47 0 Brake Check 0=OK1=Warning
VLT® Metasys
Motor Thermal
Overload
0=OK, 1=Warning
Par. 16-03 Status Word
Par. 16-92 Warning Word
3
3
MG.11.G2.02 - VLT® is a registered Danfoss trademark 19
3
Appendix
Binary Inputs (BI), continued..
NPA Unit Description Range FC Par. Number
48 31 Reserved 49 30 Reserved 50 29 Drive Initialized 0=OK, 1=Alarm 51 28 Option Change 0=OK, 1=Alarm 52 27 Brake IGBT 0=OK, 1=Alarm 53 26 Brake Resistor 0=OK, 1=Alarm 54 25 1.8V Supply Low 0=OK, 1=Alarm 55 24 Mains Failure 0=OK, 1=Alarm 56 23 24V Supply Low 0=OK, 1=Alarm 57 22 Fieldbus Fault 0=OK, 1=Alarm 58 21 W Phase Loss 0=OK, 1=Alarm 59 20 V Phase Loss 0=OK, 1=Alarm 60 19 U Phase Loss 0=OK, 1=Alarm 61 18 Brake Overload 0=OK, 1=Alarm 62 17 Internal Fault 0=OK, 1=Alarm 63 16 Live Zero Error 0=OK, 1=Alarm 64 15 AMA not ok 0=OK, 1=Alarm 65 14 Mains Phase Loss 0=OK, 1=Alarm 66 13 Inrush Fault 0=OK, 1=Alarm 67 12 Short Circuit 0=OK, 1=Alarm 68 11 DC Overvoltage 0=OK, 1=Alarm 69 10 DC Undervoltage 0=OK, 1=Alarm 70 9 Inverter Overload 0=OK, 1=Alarm 71 8 Motor ETR Overload 0=Trip, 1=Trip lock 72 7 Motor Thermal Overload 0=OK, 1=Alarm 73 6 Torque Limit 0=OK,1=Alarm 74 5 Over Current 0=OK,1=Alarm 75 4 Ctrl. Word Timeout 0=OK,1=Alarm 76 3 Ctrl. Card Temp 0=OK,1=Alarm 77 2 Earth Fault 0=OK,1=Alarm 78 1 Pwr. Card Temp 0=OK,1=Alarm 79 0 Brake check 0=OK,1=Alarm 80 31 0=FALSE, 1=TRUE 81 30 0=FALSE, 1=TRUE 82 29 0=FALSE, 1=TRUE 83 28 0=FALSE, 1=TRUE 84 27 0=FALSE, 1=TRUE 85 26 0=FALSE, 1=TRUE 86 25 0=FALSE, 1=TRUE 87 24 0=FALSE, 1=TRUE 88 23 0=FALSE, 1=TRUE 89 22 0=FALSE, 1=TRUE 90 21 0=FALSE, 1=TRUE 91 20 0=FALSE, 1=TRUE 92 19 0=FALSE, 1=TRUE 93 18 0=FALSE, 1=TRUE 94 17 0=FALSE, 1=TRUE 95 16 0=FALSE , 1=TRUE 96 15 OVC Active 0=FALSE , 1=TRUE 97 14 Out of Speed Reange 0=Auto mode, 1=Hand mode
VLT® Metasys
Par. 16-90 Alarm Word
Par. 16-94 Ext. Status Word
20 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Appendix
Binary Inputs (BI), continued..
NPA Unit Description Selection FC Par. Number
98 13 Braking 0=FALSE, 1=TRUE
99 12 Braking Max 0=Remote ref., 1=Local ref. 100 11 Brake Check Ok 0=FALSE, 1=TRUE 101 10 Output Frequency Low 0=FALSE, 1=TRUE 102 9 Output Frequency High 0=FALSE, 1=TRUE 103 8 Output Current Low 0=FALSE, 1=TRUE 104 7 Output Current High 0=FALSE, 1=TRUE 105 6 Feedback Low 0=FALSE, 1=TRUE 106 5 Feedback High 0=FALSE, 1=TRUE 107 4 Catch Up 0=FALSE, 1=TRUE 108 3 Slow Down 0=FALSE, 1=TRUE 109 2 Start CW/CCW 0=FALSE, 1=TRUE 110 1 AMA Running 0=FALSE, 1=TRUE 111 0 Ramping 0=FALSE, 1=TRUE 112 9 Ramp 0=RAMP 1, 1=RAMP 2 113 15 Reverse 0=No function, 1=reverse 114 14 Setup MSB 0=FALSE, 1=TRUE 115 13 Setup LSB 0=FALSE, 1=TRUE 116 12 Relay02 0=Relay04 off, 1=Relay04 on 117 11 Relay01 0=Relay01 off, 1=Relay01 on 118 10 Res., always 0 (data valid) 0=FALSE 119 8 Jog 0=No Function, 1=Jog 120 7 Reset 0=No Function, 1=Reset 121 6 Start 0=start, 1=stop 122 5 Freeze Output 0=Freeze output, 1=Ramping 123 4 Q-stop 0=Q-stop, 1=Ramping 124 3 Coast 0=Coasting, 1=no Coast 125 2 DC Brake 0=DC Brake, 1=Ramp stop 126 1 Preset ref. MSB 0=FALSE, 1=TRUE 127 0 Preset ref. LSB 0=FALSE, 1=TRUE 128 0 Terminal 33 0=FALSE, 1=TRUE 129 1 Terminal 32 0=FALSE, 1=TRUE 130 2 Terminal 29 0=FALSE, 1=TRUE 131 3 Terminal 27 0=FALSE, 1=TRUE 132 4 Terminal 19 0=FALSE, 1=TRUE 133 5 Terminal 18 0=FALSE, 1=TRUE 134 6 GPIO Term X30/2 0=FALSE, 1=TRUE 135 7 GPIO Term X30/3 0=FALSE, 1=TRUE 136 8 GPIO Terminal X30/4 0=FALSE, 1=TRUE
VLT® Metasys
Par. 16-94 Ext. Status Word
Par. 16-00 Control Word
Par. 16-60 Digital Input
3
3
MG.11.G2.02 - VLT® is a registered Danfoss trademark 21
3
Appendix
Binary Inputs (BI), continued..
NPA Unit Description
150 10
151 9 ECB External Interlock 0=FALSE, 1=TRUE 152 8 ECB M3 Contactor Fault 0=FALSE, 1=TRUE 153 7 ECB M2 Contactor Fault 0=FALSE, 1=TRUE 154 6 ECB Overload Trip 0=FALSE, 1=TRUE
155 5
156 4 ECB Reserved 0=FALSE, 1=TRUE 157 3 ECB Bypass Mode 0=FALSE, 1=TRUE
158 2
159 1 ECB Drive Mode 0=FALSE, 1=TRUE 160 0 ECB Test Mode 0=FALSE, 1=TRUE 187 31 - 0=FALSE, 1=TRUE 188 30 - 0=FALSE, 1=TRUE 189 29 - 0=FALSE, 1=TRUE 190 28 - 0=FALSE, 1=TRUE 191 27 - 0=FALSE, 1=TRUE 192 26 - 0=FALSE, 1=TRUE 193 25 Fire Mode 0=FALSE, 1=TRUE 194 24 Drive Bypass 0=FALSE, 1=TRUE 195 23 Running 0=FALSE, 1=TRUE 196 22 Sleep Boost 0=FALSE, 1=TRUE 197 21 Sleep 0=FALSE, 1=TRUE 198 20 Start Delay 0=FALSE, 1=TRUE 199 19 Start Applied 0=FALSE, 1=TRUE 200 18 Start 0=FALSE, 1=TRUE 201 17 Start Request 0=FALSE, 1=TRUE 202 16 Jog 0=FALSE, 1=TRUE 203 15 Jog Request 0=FALSE, 1=TRUE 204 14 Freeze Output 0=FALSE, 1=TRUE 205 13 Freeze Output Request 0=FALSE, 1=TRUE 206 12 Standby 0=FALSE, 1=TRUE 207 11 Stop 0=FALSE, 1=TRUE 208 10 DC Brake 0=FALSE, 1=TRUE 209 9 Quick Stop 0=FALSE, 1=TRUE 210 8 Drive Ready 0=FALSE, 1=TRUE 211 7 Control Ready 0=FALSE, 1=TRUE 212 6 Start Prevented 0=FALSE, 1=TRUE 213 5 Relay 123 Active 0=FALSE, 1=TRUE 214 4 Profibus OFF3 Active 0=FALSE, 1=TRUE 215 3 Profibus OFF2 Active 0=FALSE, 1=TRUE 216 2 Profibus OFF1 Active 0=FALSE, 1=TRUE 217 1 Auto/Hand 0=AUTO, 1=TRUE 218 0 OFF 0=AUTO, 1=TRUE
VLT® Metasys
ECB Manual Bypass
ECB Motor Running from
Bypass/Drive
ECB Automatic Bypass
Override
Mode
Selection
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
1)
FC Par. Number
Par. 31-10 Bypass Status
Word
Par. 16-95 Ext. Status Word
2
1)
The values in bold are the default values
22 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Appendix
3.1.3 Analog Outputs (AO)
NPA Unit Description Range FC Par. Number
0 %
1 Bus Feedback 1 8-94 2 Bus Feedback 2 8-95 3 Bus Feedback 3 8-96 4 Analog Output 42 6-53 5 Pulse Output 27 5-93 6 Pulse Output 29 5-95
7
8
9
10
VLT® Metasys
Bus reference
Analog Output, GPIOTer-
minal X30/8
Analog Output, IO Option
Analog Output, IO Option
Analog Output, IO Option
X42/7
X42/9
X42/11
1
-200 to 200 Proportionally mapped into the range
-32768 to 32767
Shared Variable
6-63
26-53
26-63
26-73
3
3
MG.11.G2.02 - VLT® is a registered Danfoss trademark 23
Appendix
3.1.4 Binary Outputs (BO)
VLT® Metasys
3
NPA Unit Description
0 2 DC Brake Inverse 0=Active, 1=Not Active 1 3 Coast Inverse 0=Active, 1=Not Active 2 4 Stop Inverse 0=Active, 1=Not Active 3 5 Freeze Output Inverse 0=Active, 1=Not Active 4 6 Start 0=Not active, 1=Active 5 7 Stop 0=Not active, 1=Active 6 8 Jog 0=Not active, 1=Active 8 11 Relay01 0=Not active, 1=Active
9 12 Relay02 0=Not active, 1=Active 10 15 Reversing 0=Not active, 1=Active 11 13 Setup LSB 0=Not active, 1=Active 12 14 Setup MSB 0=Not active, 1=Active 13 0 Preset ref. LSB 0=Not active, 1=Active 14 1 Preset ref. MSB 0=Not active, 1=Active 20 0 Output Terminal 27 0=Not active, 1=Active 21 1 Output Terminal 29 0=Not active, 1=Active 22 2 Output Terminal X30/6 0=Not active, 1=Active 23 3 Output Terminal X30/7 0=Not active, 1=Active 24 4 CC Relay 1 0=Not active, 1=Active 25 5 CC Relay 2 0=Not active, 1=Active 26 6 Option B Relay 1 0=Not active, 1=Active 27 7 Option B Relay 2 0=Not active, 1=Active 28 8 Option B Relay 3 0=Not active, 1=Active 29 9 Reserved 0=Not active, 1=Active 30 10 Reserved 0=Not active, 1=Active 31 11 Reserved 0=Not active, 1=Active 32 12 Reserved 0=Not active, 1=Active 33 13 Reserved 0=Not active, 1=Active 34 14 Reserved 0=Not active, 1=Active 35 15 Reserved 0=Not active, 1=Active 36 16 Option C Relay 1 0=Not active, 1=Active 37 17 Option C Relay 2 0=Not active, 1=Active 38 18 Option C Relay 3 0=Not active, 1=Active 39 19 Option C Relay 4 0=Not active, 1=Active 40 20 Option C Relay 5 0=Not active, 1=Active 41 21 Option C Relay 6 0=Not active, 1=Active 42 22 Option C Relay 7 0=Not active, 1=Active 43 23 Option C Relay 8 0=Not active, 1=Active 44 24 Reserved 0=Not active, 1=Active 45 25 Reserved 0=Not active, 1=Active 46 26 Reserved 0=Not active, 1=Active 47 27 Reserved 0=Not active, 1=Active 48 28 Reserved 0=Not active, 1=Active 49 29 Reserved 0=Not active, 1=Active 50 30 Reserved 0=Not active, 1=Active 52 ECB Activate 31-19 60 No Flow Detection 0=Not active, 1=Active 22-21
61
Enable Interval between starts
0=Disable, 1=Enable 22-75
Range
1)
FC Par. Number
Par. 16-00 Control Word
Par. 5-90 Digital & Relay Bus
Control
1)
The values in BOLD are the default values.
24 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Appendix
VLT® Metasys
3.1.5 Internal Floating Point (ADF)
NPA Unit Description Range FC Par. Number
0 - Max value of custom readout 0-32
1 - Min value of custom readout 0-31 13 A 14 RPM Motor nom. Speed 1-25 16 % Resonance damping 1-64 18 Sec Start delay 1-71 19 % Preheat DC-current 2-00 20 % DC brake current 2-01 21 Sec DC braking time 2-02 22 Hz DC brake cut-in frequency 2-03 29 - Max output Frequency 4-19 34 Sec Ramp Up Time 3-41 35 Sec Ramp Down Time 3-42 36 Hz Jog Frequency 3-11 37 % Digital Reference 1 3-10:0 38 % Digital Reference 2 3-10:1 39 % Digital Reference 3 3-10:2 40 % Digital Reference 4 3-10:3 41 A Current Limit 4-18 42 Hz Frequency 1. Bypass start 4-61:0 43 Hz Frequency 1. Bypass stop 4-63:0 44 Hz Frequency 2. Bypass start 4-61:1 45 Hz Frequency 2. Bypass stop 4-63:1 46 Hz Frequency 3. Bypass start 4-61:2 47 A Frequency 3. Bypass stop 4-63:2 48 A Frequency 4. Bypass start 4-61:3 49 Hz Frequency 4. Bypass stop 4-63:3 50 A 51 A 52 Hz 53 Hz 54 Unit 55 Unit 56 Unit 57 Unit 60 V Terminal 53 min scale V 6-10 61 V Terminal 53 max scale V 6-11 62 V Terminal 53 min scale mA 6-12 63 V Terminal 53 max scale mA 6-13 64 A Terminal 54 min. scale V 6-20 65 V Terminal 54 max. scale V 6-21 66 V Terminal 54 min. scale mA 6-22 67 A Terminal 54 max. scale mA 6-23 68 Hz Terminal 42 output puls scale 5-62 69 Hz Terminal 45 output puls scale 5-65 70 mSec CC Relay 1 ON Delay 5-41:0 71 mSec CC Relay 1 ON Delay 5-42:0 72 mSec CC Relay 1 ON Delay 5-41:1 73 Sec CC Relay 1 ON Delay 5-42:1
Motor Current(I
Warning Current Low(I
Warning Current High (I
Warning Freq. Low(F Warning Freq. High(F Warning Low Ref.(Ref
Warning High Ref.(Ref
Warning Low FB.(FB
Warning High FB.(FB
M.N
)
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
)
)
)
) )
)
)
)
1-24
4-50 4-51 4-52 4-53 4-54 4-55 4-56 4-57
3
3
MG.11.G2.02 - VLT® is a registered Danfoss trademark 25
3
Appendix
VLT® Metasys
Internal Floating Point (ADF), continued..
NPA Unit Description Range FC Par. Number
80 Sec No Flow Timer 0-600 22-24 81 Sec Dry Pump Timer 0-600 22-27 82 Sec Minimum Run Time 0-600 22-40 83 Hz Minimum Sleep Time 0-600 22-41 84 % Boost setpoint -100% - +100% 22-45 85 Hz Wake-up Speed Par. 4-12 to 4-14 22-43 86 Sec Max Boost Time 0-600 22-46 87 kHz Switch Frequency 14-01 88 Unit Set point 1 20-21 89 Unit Set point 2 20-22 90 Hz PID Start Frequency 20-83 91 - PID Proportional Gain 20-93 92 Sec PID Integration Time 20-94 93 Sec PID Differentiation Time 20-95 94 - PID D-gain Limit 20-96
95 Unit Set Point 3 20-23 100 - Control Timeout Function 8-04 101 - Control Timeout Time 8-03 110 Sec Option B Relay 1 ON Delay 0.01 to 600.00 5-41:6 111 Sec Option B Relay 1 OFF Delay 0.01 to 600.00 5-42:6 112 Sec Option B Relay 2 ON Delay 0.01 to 600.00 5-41:7 113 Sec Option B Relay 2 OFF Delay 0.01 to 600.00 5-42:7 114 Sec Option B Relay 3 ON Delay 0.01 to 600.00 5-41:8 115 Sec Option B Relay 3 OFF Delay 0.01 to 600.00 120 V Analogue Input, GPIO option X30/11, Low Voltage 6-30 121 V Analogue Input, GPIO option X30/11, High Voltage 6-31 122 V Analogue Input, GPIO option X30/12 Low Voltage 6-40 123 V Analogue Input, GPIO option X30/12, High Voltage 6-41 124 V Analogue Input, IO X42/1, Low Voltage 0.07 to 10.00 26-10 125 V Analogue Input, IO option X42/1, High Voltage 0.07 to 10.00 26-11 126 V Analogue Input, IO option X42/3, Low Voltage 0.07 to 10.00 26-20 127 V Analogue Input, IO option, X42/3, High Voltage 0.07 to 10.00 26-21 128 V Analogue Input, IO option X42/5, Low Voltage 0.07 to 10.00 26-30 129 V Analogue Input, IO option X42/5, High Voltage 0.07 to 10.00 26-31 130 % Analogue Output 42 Timeout Preset 6-54 131 % Analogue Output, GPIO option X30/8, Timeout Preset 6-64 132 % Analogue Output, IO option X42/7, Timeout Preset 0.00 to 100.00 26-54 133 % Analogue Output, IO option X42/9, Timeout Preset 0.00 to 100.00 26-64 134 % Analogue Output, IO option X42/11, Timeout Preset 0.00 to 100.00 26-74 140 Ext. 1 Setpoint 21-15 141 Ext. 1 Proportinal Gain 21-21 142 Ext. 1 Integral Gain 21-22 143 Ext. 1 Differentation Time 21-23 144 Ext. 2 Setpoint 21-35 145 Ext. 2 Proportinal Gain 21-41 146 Ext. 2 Integral Time 21-42 147 Ext. 2 Differentation Time 21-43
26 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Appendix
VLT® Metasys
3.1.6 Internal Integers (ADI)
NPA Unit Description Range FC Par. Number
0 - Language Selection 0-01 1 - Setup Copy Function 0-51 2 - Custom Readout Unit 0-30 3 - Large Readout 0-23 4 - Small Readout 1 0-20 5 - Small Readout 2 0-21 6 - Small Readout 3 0-22 7 - Unit of Local Reference 0-05 8 - Hand Start Button 0-40
9 - Off/Stop Button 0-41 10 - Auto Start Button 0-42 11 - Reset Button 0-43 13 - Operating State at Power Up 0-04 21 - Torque Characteristics 1-03 23 - Motor Preheat 2-00 24 - Motor Thermal Protection 1-90 31 - Reference Site 3-13 32 - Over Volt Control 2-17 33 - Reference Function 3-04 40 - Digital Input 18 5-10 41 - Digital Input 19 5-11 42 - Digital Input 27 5-12 43 - Digital Input 29 5-13 44 - Digital Input 32 5-14 45 - Digital Input 33 5-15 51 Sec Live Zero Time Out 6-00 52 - Live Zero Function 6-01 53 - Signal Output 42 6-50 55 - CC Relay 1 Function 0 to 255 5-40:0 56 - CC Relay 2 Function 0 to 255 5-40:1 57 - Option B Relay 1 Function 0 to 255 5-40:6 58 - Option B Relay 2 Function 0 to 255 5-40:7 59 - Option B Relay 3 Function 0 to 255 5-40:8 60 - Reset Function 14-20 61 - Flying Start 1-73 62 - Noise Reduction Method 14-04 63 - Broken Belt Function 22-60
3
3
MG.11.G2.02 - VLT® is a registered Danfoss trademark 27
3
Appendix
VLT® Metasys
Internal Integers (ADI), continued..
NPA Unit Description Range FC Par. Number
64 Sec Trip Delay on Overload 14-25 68 - PID Normal/Inverse 20-81 69 - PID Anti Windup 20-91 70 - Feedback 1 Conversion 20-01 71 - Feedback 1 Source Unit 20-02 72 - Feedback 2 Conversion 20-04 73 - Feedback 2 Source Unit 20-05 75 - Two Feedback Calculation 20-20 80 - Coasting 8-50 81 - DC Brake 8-52 82 - Start 8-53 83 - Reversing 8-54 84 - Selection of Setup 8-55 85 - Selection of Speed 8-56 90 - Reset kWh Counter 15-06 91 - Reset Running Hours Counter 15-07 92 - Operation Mode 14-22
101 -
102 -
103 -
104 -
105 -
106 -
107 -
110 - ECB Bypass Mode 0 - 4 31-00 111 - ECB Bypass Start Timer Delay 0 - 60 31-01 112 - ECB Bypass Trip Bypass Delay 0 - 300 31-02 120 - Dry Pump Function 0 - 2 22-26 121 - Broken Belt Action 0 - 2 22-60 122 % Broken Belt Torque 0 - 100% 22-61 123 sec Broken Belt Timer 0 - 600 22-62 124 sec Interval Between Starts Par. 22-76 - 36-00 22-76 125 sec Minimum Run Time Par. 22-77 - 36-00 22-77 254 - Active Setup 0-10
Analogue Input, IO option X42/1
Mode
Analogue Input, IO option X42/3
Mode
Analogue Input, IO option X42/5
Mode
Analogue Input, GPIO option X30/8
Mode
Analogue Input, IO option X42/7
mode
Analogue Input, IO option X42/9
Mode
Analogue Input, IO option X42/11
Mode
0 - 3 26-00
0 - 3 26-01
0 - 3 26-02
0 -145 26-50
0 -145 26-60
0 -145 26-70
6-60
28 MG.11.G2.02 - VLT® is a registered Danfoss trademark
Index
VLT® Metasys
Index
A
Abbreviations And Definitions 3 Analog Input Commands (acknowledged) 6 Analog Input Commands (not Acknowledged) 7 Analog Inputs (ai) 18 Analog Output Commands (acknowledged) 8 Analog Output Commands (not Acknowledged) 9 Analog Outputs (ao) 23
B
Binary Input (bi) Commands (acknowledged) 10 Binary Input (bi) Commands (not Acknowledged) 10 Binary Inputs (bi) 19 Binary Output (bo) Commands (not Acknowledged) 12 Binary Output Commands (acknowledged) 11 Binary Outputs (bo) 24
C
Change Of State (cos)/polling
V
VLT Parameters 4
16
E
Error Codes
G
General Commands (acknowledged)
H
Handling Of Poll Message Commands Hardware Set-up 3
I
Internal Floating Point (adf) Internal Floating Point Commands (acknowledged) 13 Internal Integers (adi) 27 Internal Integers (adi) Commands (acknowledged) 12
N
Network Connection
O
Override/override Release Commands And Time Out
R
Reference/feedback Values References 2
4
5
16
25
3
16
15
S
Scaling Of Bus Reference And Feedback Software Version 2 Start-up Of The Frequency Converter 14 Status Update Request 15
T
Typical Settings
MG.11.G2.02 - VLT® is a registered Danfoss trademark 29
15
14
Loading...