MG.11.G2.02 - VLT® is a registered Danfoss trademark 1
Overview
VLT® Metasys
11
1 Overview
1.1.1 Software Version
VLT HVAC Drive
FC 102 Series
Software version: 3.4x
and VLT AQUA Drive FC 202 Series
Software version: 1.7x
This guide can be used with all VLT HVAC Drive frequency converters with
software version 3.4x and VLT AQUA Drive frequency converters with
software version 1.7x.
The actual software version number can be read from
par. 15-43 Software Version.
1.1.2 Introduction
The frequency converter control board is program selectable
for use with the Johnson Controls Metasys N2 protocol.
Metasys N2 is a master/slave control network. The physical
layer is RS-485 compatible, half duplex 9600 baud shielded
twisted pair. The N2 software protocol is designed to be
general in nature to accommodate the unique properties each
device type may have. Every device connection to the N2
network can be thought of as a small data manager. Data
points in the database are classified as analog I/O (floating
point), binary I/O or integer data points - floats, integers or
bytes. Each data type has its own unique structure defined in
the Metasys N2 system Protocol Specification for Vendors.
The information in this manual is intended to provide you with
comprehensive information on how to install and set up the
frequency converter for communication over a Metasys
network.
For specific information on operation of the drive, refer to the
VLT HVAC Drive Operating Instructions, MG.11.Ax.yy or the VLT
AQUA Drive Operating Instructions, MG.20.Mx.yy.
1.1.3 About this Manual
This manual is for both instructional and for reference
purposes. This manual can also serve as a guideline when you
specify and optimize your communication system.
It is highly recommended that you read this manual in its
entirety before initiating any programming. It is assumed that
the user has full knowledge of the capabilities and limitation
of the controller node in addition to full knowledge of the
frequency converter.
References
1.1.4
In addition to this manual, the following two manuals should
be consulted: VLT HVAC Drive Operating Instructions, MG.
11.Ax.yy, VLT AQUA Drive Operating Instructions, MG.20.Mx.yy
and Johnson Controls METASYS N2 System Protocol Specification
for Vendors, Johnson Controls number 04-3402-22, rev A.
2MG.11.G2.02 - VLT® is a registered Danfoss trademark
130BA060.11
68 6968 6968 69
RS 485
RS 232
USB
+
-
12
S801
ON
130BA272.11
Instructions
VLT® Metasys
2 Instructions
2.1.1 Abbreviations and Definitions
ACK Acknowledge
ADF Internal Floating Points
ADIInternal Integers
AIAnalog Inputs
AOAnalog Outputs
BIBinary Inputs
BOBinary Outputs
COS Change Of State
FCFrequency Converter
HPFB High Performance Field Bus
JCIJohnson Controls Inc. developers of the METASYS N2 protocol
N2METASYS N2
N2
A N2 master is either a PC with JCI software or a dedicated JCI
mast
controller
er
NAK Not acknowledged
NPA N2 Point Address (Each N2 Point Type has a address range
from 0 to 255)
NPT N2 Point Type
PAR Parameter Number
2.1.3 Hardware Set-up
RS-485 Bus Connection:
One or more frequency converters can be connected to a
control (or master) using the RS-485 standardized interface.
Terminal 68 is connected to the P signal (TX+, RX+), while
terminal 69 is connected to the N signal (TX-,RX-). If more than
one frequency converter is connected to a master, use parallel
connections.
Illustration 2.1: Bus termination switch
22
2.1.2 Network Connection
Connect signal wires to terminal 68 (N+) and terminal 69 (N-)
on main control board of the drive. If shielded cabling is used,
connect one end of the shield to terminal 61. This terminal is
connected to ground via an internal RC link. It is highly
recommended to use shielded twisted-pair cables to reduce
the differential mode interference between the conductors.
Danfoss do not take any responsibility for consequences, if
unshielded or untwisted cables are used.
Torque Specifications:
Control wire:18 - 24 AWG, shielded, twisted pair
4.5 in.lb. (0.5 Nm) if screw terminal is used
NOTE
The factory setting for the dip switch is OFF.
In order to avoid potential equalizing currents in the screen,
earth the cable screen via terminal 61, which is connected to
the frame via an RC-link.
Bus termination: The RS-485 bus must be terminated by a
resistor network at both ends. For this purpose, set switch
S801 on the control card to "ON". For more information, see
the paragraph: Switches S201, S202 and S801.
MG.11.G2.02 - VLT® is a registered Danfoss trademark 3
Instructions
2.1.4 Error Codes
VLT® Metasys
22
Error Code 00is issued after power up or after a time out where all overridden points were released, as long as no Identify yourself
command has been issued by the master.
Error Code 01is issued if the command is not supported or not known by the drive.
Error Code 02is issued if the received telegram has a checksum error.
Error Code 03is issued if the N2 telegram receive buffer exceeds 256 characters.
Error Code 05is issued if the received N2 telegram is too long.
Error Code 10is issued the data is out of expected range
Error Code 11is issued when:
1. A point attributes or attribute bit is unused.
2. A point attributes or attribute bit is for JCI use only.
3. An internal data point attribute for current value can not be changed while running
Error Code 12is issued when:
1. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is tripped.
2. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is trip locked except for BO 5
"reset"
2.1.5 VLT Parameters
The following parameters may need to be manually set for each drive in the Metasys N2 network. Refer to the VLT HVAC DriveDesign Guide, MG.11.Bx.yy, or VLT AQUA Drive Design Guide, MG.20.Nx.yy, for the frequency converter for programming.
Parameter list
VLT ParameterDescriptionDefaultDesired Setting
8-01Control SideDigital & Ctrl. Word
8-02Control SourceFC PortFC Port
8-03Control Word Timeout60 s1-18000 s
8-30ProtocolFCMetasys N2
8-31Address11-255
8-32Baud Rate9600Fixed to 9600
8-33ParityEven, 1stopFixed to No Parity, 1stop
8-37Maximum Inter-char Delay25 s for Metasys N2
4MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.6 General Commands (Acknowledged)
VLT Response Command Subcommand
ACK04-
ACK05-
ACK09-Status update Message-
ACKF--Identify Device Type-
ACK00-Synch Time-
ACK, no action80-Upload-
ACK, no action81-Upload-
ACK, no action83-Upload Record-
ACK, no action84-Upload Complete-
ACK, no action90-Download-
ACK, no action91-Download-
ACK, no action93-Download-
ACK, no action94-Download Complete-
NAK01-Read Memory01
NPA Object
no.
Attribute Message Type Error CodeComments
Poll Message
No Acknowledge
Poll message
With Acknowledge
The slave is to respond with any data
-
-
points, analog or binary I/O that have
been flagged for COS
The slave is to respond with any data
points, analog or binary I/O that have
been flagged for COS
Slave device must respond with device
manufacturing model number (Par. 6-21),
days in service (Par. 6-00) and device
status
Slave device responds with an identifica-
tion number of 10H to indicate non JCI
device
The internal clock is syncronized by this
command
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Optional, no support in the frequency
converter
Record optional, no support in the
frequency converter
Optional, no support in the frequency
converter
Slave device memory read based on
memory addresses
22
NAK08-Warm Start01JCI use only
MG.11.G2.02 - VLT® is a registered Danfoss trademark 5
Instructions
VLT® Metasys
2.1.7 Analog Input Commands (Acknowledged)
22
VLT
Response
ACK1-10-231Byte
ACK1-10-232Byte
ACK1-10-233Float
ACK1-10-238Float
ACK1-10-239Float
ACK1-10-2310Float
ACK1-10-2311Float
ACK1-10-2312Float
ACK2-10-231Byte
ACK2-10-238Float
ACK2-10-239Float
ACK2-10-2310Float
ACK2-10-2311Float
ACK2-10-2312Float
ACK, no
action
ACK, no
action
ACK, no
action
Command Subcom-
mand
7210-23-Float
7310-23--
7710-23--
Region
NPA Object
no.
Attribute
No.
Attribute Message TypeComments
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Read Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Write Analog
Input
Override
Analog inputs
Override
Analog Release
Write Analog
Input Attrib-
utes
Read Object Configuration attribute
associated with each individual point
1)
Read Object Status attribute
associated with each individual point
2)
Read Analog Input Value attribute
associated with each individual point
Read Low Alarm attribute associated
with each individual point
Read Low Warning attribute associ-
ated with each individual point
Read High Warning attribute associ-
ated with each individual point
Read High Alarm attribute associated
with each individual point
Read Differential attribute associated
with each individual point
Write to Object Configuration attrib-
ute associated with each individual
point
Write to Low Alarm Limit attribute
associated with each individual point
Write to Low Warning Limit attribute
associated with each individual point
Write to High Warning Limitattribute
associated with each individual point
Write to High Alarm Limit attribute
associated with each individual point
Write to Differential attribute associ-
ated with each individual point
Analog inputs are "outputs" from the
frequency converter and should not
be written over by the network
controller
Analog inputs are "outputs" from the
frequency converter and should not
be written over by the network
controller
Optional command for slave devices.
Only used for N2
commissioning purposes
6MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.8 Analog Input Commands (Not Acknowledged)
VLT
Response
Comm and Region NPA Object no.Attribute
No.
Attribute Message TypeError
NAK110-234FloatRead Analog
Input
NAK110-235FloatRead Analog
Input
NAK2-0-232ByteWrite Analog
Input
NAK2-0-233FloatWrite Analog
Input
NAK2-0-234FloatWrite Analog
Input
NAK2-0-235FloatWrite Analog
Input
NAK2-0-236FloatWrite Analog
Input
NAK2-0-237FloatWrite Analog
Input
NAK2-0-2313IntegerWrite Analog
Input
NAK2-0-2314FloatWrite Analog
Input
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
Comments
Code
1 )
Read Linear Ranging Parameter 1
11
attribute associated with each
individual point. (JCI use only)
1)
Read Linear Ranging Parameter 2
11
attribute associated with each
individual point. (JCI use only)
11
11
11
1)
1)
1)
Object Status writeable
Analog Input Value not writeable
Write to Linear Ranging Parame-
ter 1 attribute associated with
each individual point. (JCI use
1)
Write to Linear Ranging Parame-
11
ter 2 attribute associated with
each individual point. (JCI use
1)
Write to Linear Ranging Parame-
11
ter 3 attribute associated with
each individual point. (JCI use
1)
Write to Linear Ranging Parame-
11
ter 4 attribute associated with
each individual point. (JCI use
1)
11
Write to Filter Weight attribute
associated with each individual
point. (JCI use only)
1)
Write to AI Offset attribute associ-
11
ated with each individual point.
(JCI use only)
22
only)
only)
only)
only)
MG.11.G2.02 - VLT® is a registered Danfoss trademark 7
Instructions
VLT® Metasys
2.1.9 Analog Output Commands (Acknowledged)
22
VLT
Response
ACK1-30-21ByteRead Analog
ACK1-30-22ByteRead Analog
ACK09----Status update
ACK1-30-23FloatRead Analog
ACK2-30-21ByteWrite Analog
ACK7230-2-FloatOverride Analog
ACK7230-2-FloatOverride Analog
ACK7330-2--Override Release Set the current value, the value
ACK, no
action
ACK, no
action
CommandSub
command
7730-2--Write Analog
7830-2--Read Analog
Region NPA Object no.Attribute
No.
Attribute Message TypeComments
Output Attributes
Output
Output
Message
Output
Output
Output
Output
Output
Read Object Configuration
attribute associated with each
individual point
Read Object Status attribute
associated with each individual
point
Slave device must respond
with device manufacturing
model number (Par. 6-21), days
in service (Par. 6-00) and
device status
Read Current Value attribute
associated with each individual
point
Write to Object Configuration
attribute associated with each
individual point
Write to analog output current
value (frequency setpoint)
Write to analog output current
value (frequency setpoint)
that it was before the 1.
Override Command was issued
Optional command for slave
devices. Only used for N2
Attributes commissioning
purposes. Not to be implemen-
ted at this time
Optional command for no
action slave devices. Only used
for N2 commissioning
purposes. Not to be implemen-
ted at this time
8MG.11.G2.02 - VLT® is a registered Danfoss trademark
Instructions
VLT® Metasys
2.1.10 Analog Output Commands (Not Acknowledged)
VLT
Response
0-2130-24FloatRead Analog
NAK130-25FloatRead Analog
NAK230-22ByteWrite Analog
NAK230-23FloatWrite Analog
NAK230-24FloatWrite Analog
NAK230-25FloatWrite Analog
Command RegionNPA Object
no.
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
Attribute
No.
Attribute Message TypeError
Output
Output
Output
Output
Output
Output
Comments
Code
11
11
11
11
11
11
1
1
1
1
1
1
Read Low Linear Ranging
Parameter attribute associated
with each individual point. (JCI
use only)
Read High Linear Ranging Parameter attribute associated with
each individual point. (JCI use
Object Status not writeable
Write to Current Value structure
attributes associated with each
individual point. (N2 does not
support this, override function
must be used)
Write Debouncing Value in msec
attribute associated with each
individual point.(JCI use only)
Write Accumulator value attrib-
ute associated with each individ-
ual point. (JCI use only)
22
only)
MG.11.G2.02 - VLT® is a registered Danfoss trademark 9
Loading...
+ 20 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.