Retain this documentation for instruction and for future
reference.
These Operating Instructions explain the function and
operation and provide installation and wiring guidelines
for the safety option.
Also refer to the following documents from the motion
control range:
MCT 10 Set-up Software Operating Instructions
•
describe the configuration of the safety option.
VLT® AutomationDrive FC 301/FC 302 Operating
•
Instructions describe the frequency converter.
The online help for the MCT 10 Set-up Software
•
describes how to set the parameters for the
frequency converter and the safety option.
Be conversant with the information in these documents to
fully understand this manual.
Chapter 2 Legal Information and Safety
Provides information on the most important product
features.
Chapter 4 Installation
Explains how to install and wire the product.
Chapter 5 Commissioning
Describes how to commission the product.
Chapter 6 General Parameter Set-up
Describes the basic parameters for setting.
Chapter 7 Service and Repair
Describes how to replace a defective safety option and
how to update, service and modify its firmware.
Chapter 8 Warnings and Alarms
Contains a table overview of the warnings and alarms.
Troubleshooting tips are also part of the overview.
Chapter 9 Technical Specifications
Specifies the technical details of the safety option.
The manuals listed below contain important information
about safety systems that must be used to mount and set
up the speed monitoring safety functions of the safety
option module.
VLT® is a registered trademark.
1.2
Overview of Documentation
Chapter 1 Introduction
Explains the contents, structure and specific order of this
manual.
According to the Machinery Directive regulation, it is
hereby stated that the original language of these
Operating Instructions is English UK.
2.1.1 Copyright and Revisions
This publication contains information proprietary to
Danfoss and is protected by Copyright laws of Denmark,
international treaties and most other countries. All
trademarks in this publication are property of the
respective companies. Danfoss and the Danfoss logotype
are trademarks of Danfoss A/S. All rights reserved.
Although Danfoss has tested and reviewed the correctness,
completeness and documentation of this publication,
Danfoss makes no warranty or representation, neither
express or implied, with respect to this publication,
including but not limited to its quality, correctness,
completeness, performance, or fitness for a particular
purpose.
Danfoss reserves the right to revise, update and change
this publication at any time without prior notice or specific
obligation to inform former or present users of such
revisions or changes.
Warranty and Liability
2.1.2
All claims to warranty and liability are rendered invalid if
2.2.1 Safety Precautions
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when
connected to AC mains input power. Installation, start
up, and maintenance should be performed by qualified
personnel only. Failure to perform installation, start up,
and maintenance by qualified personnel could result in
death or serious injury.
WARNING
UNINTENDED START!
When the frequency converter is connected to AC mains,
the motor may start at any time. The frequency
converter, motor, and any driven equipment must be in
operational readiness. Failure to be in operational
readiness when the frequency converter is connected to
AC mains could result in death, serious injury,
equipment, or property damage.
CAUTION
This option is suitable for performing mechanical work
on the frequency converter system or affected area of a
machine only. It does NOT provide electrical safety. This
option should NOT be used as a control for starting
and/or stopping the frequency converter. See the
requirements for those applications in ISO 12100.
the product was used contrary to the purpose for
•
which it is intended.
damage can be attributed to not having followed
•
the guidelines in the manual.
operating personnel are not suitably qualified.
•
any type of modification has been made (e.g.
•
exchanging components on the PCB boards,
soldering work etc.).
The safety option is intended to be part of the safetyrelated control system of a machine. Before installation,
a risk assessment shall be performed to determine
whether the specifications of this safety option are
suitable for all foreseeable operational and environmental characteristics for the system in which it will be
installed.
The system user is responsible for
the set-up, safety rating and validation of any
•
sensors or actuators connected to the system.
completing a system-level risk assessment and
•
reassessing the system any time a change is
made.
Legal Information and Safet...
Operating Instructions
providing supposition (as needed for the
•
application) that the system fulfills desired safety
rating.
project management and proof testing.
•
programming the application software and the
•
safety option configurations in accordance with
the information in this manual.
access to the control system.
•
analysing all configuration settings and selecting
•
the proper setting to achieve the required safety
rating.
Safety Regulations
2.2.3
Check that the mains supply has been discon-
•
nected and that the necessary time has elapsed
before removing motor and mains supply plugs
and before commencing any repair work.
The [Off] key on the LCP does not disconnect
•
mains supply and must never be used as a safety
switch.
Ensure the following in accordance with national
•
and local regulations:
The equipment must be properly
-
earthed
The user must be protected against
-
supply voltage
The motor must be protected against
-
overload
The earth leakage current exceeds 3.5 mA.
•
Protection against motor overload is not included
•
in the factory setting. If this function is desired,
set 1-90 Motor Thermal Protection to data value [4]ETR trip 1 or data value [3] ETR warning 1.
Do not remove the plugs for the motor and
•
mains supply while the frequency converter is
connected to mains.
NOTICE
The frequency converter has more voltage sources than
L1, L2 and L3, when load sharing (linking of DC
intermediate circuit) or external 24 V DC are installed.
engineers and are suitably experienced to
operate devices, systems, plant and machinery in
accordance with the general standards and
guidelines for safety technology.
are familiar with the basic regulations concerning
•
health and safety/accident prevention
have read and understood the safety guidelines
•
given in this description and also the instructions
given in the VLT® AutomationDrive FC 301/FC 302
Operating Instructions.
have a good knowledge of the generic and
•
specialist standards applicable to the specific
application.
Users of PDS(SR)s are responsible for
hazard and risk analysis of the application.
•
identifying safety functions required and
•
allocating SIL or PLr to each of the functions.
other subsystems and the validity of signals and
•
commands from them.
designing appropriate safety-related control
•
systems (hardware, software, parameterisation,
etc.).
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.
NOTICE
Indicates important information, including situations that
may result in damage to equipment or property.
Approvals
22
2.2.4 Qualified Personnel
The products may only be assembled, installed,
programmed, commissioned, maintained and decommissioned by persons with proven skills. Persons with proven
skills
are qualified electrical engineers, or persons who
with hard guarding, access doors, and safety gates with
solenoid-lock or -unlock safety switches. When the speed
33
of the monitored device drops below the set switch point
(where its speed is no longer considered dangerous), the
safety option sets S37 output low. This allows the operator
to open the safety gate. In speed monitor applications, the
safety output S37 is high for operation (when the motor
speed of the monitored device is below the set switch
point). When the speed exceeds the set value, indicating a
too-high (dangerous) speed, the safety output is low.
The frequency converter
removes the power to the motor,
•
switches the motor to torque-free, if Safe Torque
•
Off is activated
The safety control system
activates the safety functions via inputs on the
•
safety option
evaluates signals from safety devices, such as
•
Illustration 3.1 FC 302 with Safety Option and Fieldbus Option
The safty option performs safety functions in accordance
with EN IEC 61800-5-2. It monitors safe motion sequences
on frequency converters, which are safely brought to a
stop and shut down in the event of an error.
The safety option
activates safety functions
•
monitors safe motion sequences
•
signals the status of safety functions to the safety
•
control system via possible connected Profibus
fieldbus
activates the selected failure reaction Safe Torque
•
Off or Safe Stop 1, in the event of an error
There are 2 variants of the safety option, one with HTL
encoder interface (MCB 151) and one with TTL encoder
interface (MCB 150).
The safety option is constructed as a standard option for
the VLT® AutomationDrive FC 302 and is automatically
detected after mounting.
The safety option can be used to monitor the stopping,
starting or speed of a rotating or laterally moving device.
As speed monitor, the option is often used in combination
If external forces act on the motor (vertical axis) and an
unwanted movement, for example caused by gravity,
could cause a hazard, add measures for fall protection
before operating the motor.
Triggering the Safe Torque Off safety function means that
the delay time for motors with holding brake is not
effective. The motor cannot generate holding torque to
bridge the time to application of the holding brake. Check
whether additional measures have to be taken; for
example, this may cause the load of vertical axes to lower.
processes the safety option status function
•
provides safe connection between safety option
•
and safety control system
provides fault detection at activation of safety
•
functions (shorts across contacts, short circuit) on
signal between the safety control system and
safety option
Behaviour of Holding Brake
CAUTION
E-STOP push buttons
-
Non Contact Magnetic switch
-
Interlocking switch
-
Light curtain devices
-
130BC962.10
Detect
Sensor
E.g. lightcurtain
ProcessSwitch
Logic
E.g. MCB 15x
Actuator
E.g. FC 302
Functions and System Overvi...Operating Instructions
3.1.2 Safety Certification
The safety option is certified for use in safety applications up to and including SIL 2 according to EN IEC 61508 and EN IEC
62061, Performance Level PL d and Category 3 according to EN ISO 13849-1. Safety requirements are based on the
standards valid at the time of certification. The IFA (Institute for Occupational Safety & Health) has approved the safety
option for use in safety-related applications where the de-energised state is considered to be the safe state. All of the
examples related to I/O included in this manual are based on achieving de-energisation as the safe state.
3.1.3 Implementation in Control Systems
In many cases design measures are not sufficient and protective devices are needed to minimise risk. In this context, safety
functions executed by SRP/CS (safety related parts of control systems) are defined. SRP/CS includes the entire safety chain
with sensor (detect), logic (process) and actuator (switch).
Safety functions are defined on the basis of both the application and the hazard. They are often specified in a Type C
standard (a product standard) which provides precise specifications for special machines. If a C standard is not available, the
machine designer defines the safety functions. Typical safety functions are described in more detail in EN ISO 13849-1,
section 5, Specification of Safety Functions. The safety functions for frequency converter systems are described in IEC
61800-5-2.
The standards require a specification of functional
requirements. The specification must contain details about
each safety function that should be executed. Also define
the
necessary interfaces with other control functions
•
required error responses
•
performance level required PLr or achievable SIL
•
level
3.2.1.1
Performance Level (PL) and Safety
Integrity Level (SIL)
For safety-related control systems, Performance Level (PL),
according to EN ISO 13849-1, and SIL levels, according to
EN IEC 61508 and EN IEC 62061, include a rating of the
system's ability to perform its safety functions.
All of the safety-related components of the control system
must be included in both a risk assessment and the
determination of the achieved levels. Refer to EN ISO
13849-1, EN IEC 61508 or EN IEC 62061 standards for
complete information on requirements for PL and SIL
determination.
3.2.2 Validation of Performance Level
Check whether the required Performance Level “PLr”,
determined in the risk assessment, is achieved by the
selected system for each safety function used.
Check the calculation using the SISTEMA SW Tool of IFA
(Institute for Occupational Safety & Health). Danfoss
provides a component library which can be used for the
calculation. Danfoss offers corresponding services to
support the system check by calculation. Library can be
downloaded from www.dguv.de/ifa/en/pra/softwa/sistema.
If using another validation method for the performance
level, use the characteristic safety values specified.
The safety functions are activated using the dual-
•
pole safe inputs on the safety option.
These inputs operate in accordance with the fail-
•
33
safe principle (on switching off). The safety
control system activates the safety functions via a
1/0 transition.
Deactivate the safety functions before applying
•
any changes to them.
3.2.4 Simultaneous Activation of Safety
Functions
All safety functions can be active at the same time.
However, Safe Torque Off has priority over all other safety
functions. Functions already started (e.g. Safe Stop 1 or
Safely Limited Speed) are canceled and the frequency
converter coasts.
Safe Torque Off has the highest priority. If the
•
Safe Torque Off function is triggered, a Safe
Torque Off is managed no matter what other
If 2 Safe Stop 1 functions are active at the same time, the
function with the steepest ramp has higher priority than
the function with less steep ramp.
If 2 Safely Limited Speed functions are active at the same
time, the function with the lowest speed limit has higher
priority than the function with higher speed limit.
If 2 equal safety functions have to be configured, they
must be parameterised as SS1-a and SS1-b or SLS-a and
SLS-b.
functions are active.
Safe Stop 1 has medium priority to the other safe
•
functions.
Safely Limited Speed has the lowest priority.
B Ramp stop function 2
C Actual ramp stop function
Illustration 3.3 2 Safe Stop 1 Safety Functions Active
Illustration 3.3 shows the result of activating first a Safe
Stop 1 function with a given ramp and afterwards
Functions and System Overvi...
Operating Instructions
activating a second Safe Stop 1 function with a steeper
ramp. The lower graph shows the actual ramp function.
3.2.5 Functional Proof Tests
The functional safety standards require that functional
proof tests are performed on the equipment used in the
system. Proof tests are performed at user-defined intervals
and are dependent on PFD and PFH values.
3.2.6 PFD and PFH Definitions
Safety-related systems can be classified as operating in
either a Low Demand mode, or in a High Demand/
Continuous mode.
Low demand mode
The frequency of demands for operation made on a safetyrelated system is no greater than once per year.
High Demand/Continuous mode
The frequency of demands for operation made on a safetyrelated system is greater than once per year.
The SIL value for a low demand safety-related system is
directly related to order-of-magnitude ranges of its average
probability of failure on demand (PFD). The SIL value for a
High Demand/continuous mode safety-related system is
directly related to the probability of a dangerous failure
per hour (PFH).
Intended Use of the Safety Option
3.2.7
CAUTION
RISK OF PERSONAL INJURY AND EQUIPMENT
DAMAGE!
To avoid personal injury and equipment damage, only
use the safety option for its intended purpose.
The following is considered as improper use
any component, technical or electrical modifi-
•
cation to the frequency converter
use of the frequency converter outside the
•
allowed electrical and environmental conditions
specified in chapter 9 Technical Specifications
and in the VLT® AutomationDrive FC 301/FC 302
Operating Instructions.
The safety option is designed for use in safety-related
applications. It meets the requirements for safety functions
in accordance with IEC 61800-5-2, regarding safe motion
monitoring.
3.2.8
MCT 10 Set-up Software with Safe
Plug-in
Use MCT 10 Set-up Software to configure the safety
functions supported in safety option.
Configuration of the safety functions is required
•
for safe motion sequences. In the event of an
error or fault, these functions shut down the
frequency converter's power element in a safe
and controlled way.
Setting of limit values, braking ramps for the
•
safety functions, monitoring of motion sequences.
The software
runs in full with a license key. All functions are
•
available from MCT 10 Set-up Software version
3.18.
supports the configuration of applications with
•
up to max. 256 safety options per project
has a simple language setting for the user
•
interface.
A PDF file and a commissioning report can be generated
for documentation of the project and all its settings.
3.3
Unit Features
The safety option has the following features
2 Dual-pole, digital inputs to activate the safety
•
functions in accordance with EN IEC 61800-5-2
Safe Torque Off (STO)
-
Safe Stop 1 (SS1)
-
Safely Limited Speed (SLS)
-
Reset function
•
Digital input 2 can be used for resetting
-
the safety option after an error or after
deactivation of a safety function.
Status indicators
•
Safe input status (LED 1 and LED 2)
-
Safe output status (LED 4)
-
LED 3 reserved for future use (always in
-
off state)
By Fault or warning the LEDs indicate a
Refer to EN IEC 61800-5-2:2007 (4.2.2.2) for a definition of
Safe Torque Off (STO).
A Category 1 stop triggers a controlled stop. The safety
option monitors the controlled stop. If a power outage or
an error occurs, a controlled stop is impossible. Trigger the
33
safety function Safe Torque Off after the stop to shut off
the motor torque.
Refer to EN IEC 61800-5-2:2007 (4.2.2.3) for a definition of
Safe Stop 1 (SS1).
An evaluation of the machine-related risks determines
Illustration 3.4 MCB 150
which of the 2 stopping methods to use.
NOTICE
When designing the machine application, consider
timing and distance for a coast to stop (Stop Category 0
or Safe Torque Off). For more information regarding stop
categories, refer to EN IEC 60204-1.
3.5.1 Operation and Requirements
3.5 Categories of Safe Stop
International standard EN/ISO 13850 specifies the
functional requirements and design principles of
emergency stop devices.
It applies to all machines, whatever type of energy is used
to control this function.
The standard allows 2 types of stop
During a category 0 stop, the motor coasts down in an
uncontrolled way. If access to the machine coasting down
involves a hazard (results of the hazard and risk analysis),
take protective measures to avoid the hazard.
Illustration 3.5 MCB 151
Category 0 stop: Stopping by immediately
•
cutting-off power or mechanical disconnection
between the dangerous components
Category 1 stop: Controlled stopping with power
•
maintained to the actuator to achieve stopping
(braking for example), then cut-off of power
when zero speed is reached.
The safety option is redundant and self-checking. It
requires digital input signals from an input sensor (e.g.,
PNP proximity switch) or higher resolution TTL or HTL
encoders to monitor for either safe stop or speed
conditions.
Safety Functions
3.5.2
Safety functions maintain a safe condition or prevent
hazardous conditions from arising. The safety functions for
frequency converters are defined in EN IEC 61800-5-2.
The safety option implements the following safety
functions
Safe Torque Off (STO)
•
No power is being fed to the motor
-
which can generate a rotation. Stop
category 0 to EN IEC 60204-1
Safe stop 1 (SS1)
•
Motor decelerates. Monitoring of
-
deceleration ramp and Safe Torque Off
following zero speed, or Safe Torque Off
at the end of a deceleration time. Stop
category 1 to EN IEC 60204-1
The safety function Safe Torque Off disconnects power to
the motor. It is implemented via the frequency converter's
shutdown path and the safety option’s safe outputs.
Features of the safety function
The motor becomes torque-free and no longer
•
generates any hazardous movements
To prevent the frequency converter from running
•
down in an uncontrolled manner. In normal
operation, activate the safety function Safe
Torque Off via the safety function Safe Stop 1
Safe Torque Off is only activated directly when
•
There is an internal error on the safety
-
option
The Safe Stop 1 delay time is set to 0
-
One of the inputs DI1 or DI2 has been
-
selected as Safe Torque Off function
The safety function Safe Torque Off corresponds
•
to a category 0 stop (uncontrolled stop) in
accordance with EN IEC 60204-1.
Prerequisites for normal operation
Input DI1 or DI2: "1" Signal (+24 V DC)
•
S37 output: "1" Signal (+24 V DC).
•
Safety function is activated
By an error after limit values have been exceeded
•
for Safe Stop 1 and Safely Limited Speed
By an internal error on the safety option or
•
frequency converter, if the frequency converter
can no longer be controlled
By executing the safety function Safe Stop 1 (1/0
•
transition). In this case the frequency converter is
monitored before it is switched to torque-free.
By download of parameterisation via MCT 10 Safe
•
Plug-in if the current frequency converter is
running.
By executing the safety function Safe Torque Off
•
(1/0 transition). This function ensures that no
torque-generating energy can continue to affect a
motor and prevents unintentional start-ups.
WARNING
If any external forces influence the motor axis (e.g.
suspended loads), additional measures (e.g. a safety
holding brake) are required to eliminate hazards.
The Safe Torque Off (STO) may be used where power
removal is required to prevent an unintended start. The
function disables the control voltage of the frequency
converter output stage. Thus, it prevents the frequency
converter from generating the voltage required to rotate
the motor (see Illustration 3.6). The function allows for
performing maintenance work on non-electrical parts of
the machinery without switching off the power supply to
the frequency converter.
AActual frequency
1Activation of Safe Torque Off
2Motor standstill
Illustration 3.6 Safe Torque Off
Safe Stop 1 - SS1
3.5.4
The safety function Safe Stop 1 monitors the deceleration
to zero speed in a controlled manner and activates Safe
Torque Off after detection of stop. The Safe Stop 1 can
either be configured as SS1 Delay or SS1 Ramp.
Features of the safety function
The safety function Safe Stop 1 corresponds to a
•
category 1 stop (controlled braking) in
accordance with EN IEC 60204-1
Monitoring the speed deceleration after which
•
the energy supply to the motor is safely
interrupted
The motor becomes torque-free and removes
•
hazardous movements
3.5.4.1
Select SS1 Delay to activate Safe Stop 1 function while a
parameterised safety delay timer expires.
Safe Torque Off is activated immediately when the
configured Stop Delay has expired, regardless of speed,
see chapter 6.1 Configuration for parameter settings.
Selecting the SS1 settings
1.
Enter 42-41 Ramp Profile
33
2.Select
2a
[0] Linear, if the ramp must follow a
linear curve
2b
[2] S-ramp Const Time, if the ramp
should follow an S-ramp
By using SS1 Delay, the frequency converter attempts to
follow the selected ramp. After a specified delay time, Safe
Torque Off is activated and the motor is made torque free.
Operating Instructions
CAUTION
Using SS1 Delay may result in the motor still spinning
when the Safe Torque Off is activated. The risk analysis
for the machine must indicate that this behaviour can be
tolerated. An interlock may be required.
Default value in 42-40 Type is [0] Delay. If this value is
selected, the Safe Stop 1 function activates a braking ramp
defined from a selected time delay in 42-42 Delay Time.
This means that the braking ramp is linear. Select the value
of 42-43 Delta T (the % of the delay time), which is a
reasonable tolerance after the SS1 Delay Time has expired.
NOTICE
The SS1 delayu function does not monitor the stopping
of the frequency converter!
The safety relevant time, Delta T, allows the frequency
converter to come to a stop before Safe Torque Off is
activated. Thus ensuring that the system is also stopped
before Safe Torque Off is activated. If a fault occurs, the
frequency converter does not come to a stop. It coasts
after the time delay no matter of the speed of the
frequency converter.
AActual frequency
1Activation of SS1 Delay Timer
2Activation of Safe Torque Off
342-42 Delay Time
442-43 Delta T
Illustration 3.7 SS1 Delay
When Safe Stop 1 function is active, the frequency
converter brings the motor to zero speed. The Safe Torque
Off function is triggered after a specified safety-relevant
time. This safety function corresponds to a controlled stop
of the frequency converter according to EN IEC 60204-1,
stop category 1.
3.5.4.2
An S-ramp gives non-linear deceleration, compensating for
jerks in the application.
SS1 Delay with S-ramp Stop Profile
1.Define a speed profile by a delay (a ”worst case”
delay from actual frequency to zero speed) and a
delay tolerance. The safety relevant time, Delta T,
allows the frequency converter to come to a stop
before Safe Torque Off is activated. Thus ensuring
that the system is also stopped before Safe
Torque Off is activated. If a fault occurs, the
frequency converter does not come to a stop. It
coasts after the time delay regardless of the
frequency converter speed.
2.Define an S-ramp configuration, which achieves
zero speed within the delay.
3.Configure the S-Ramp ratio at deceleration start
in 42-48 S-ramp Ratio at Decel. Start and set
42-49 S-ramp Ratio at Decel. End for S-Ramp ratio
at deacceleration end.
ParameterUnit RangeDefault
42-42 Delay Times0.1-3600.0 s 1.0 s
42-43 Delta T%0-50%5%
42-48 S-ramp Ratio at Decel. Start%1-9950
42-49 S-ramp Ratio at Decel. End%1-9950
Table 3.1 Parameters for SS1 Delay with S-ramp Stop Profile
AActual frequency
1Activation of SS1 Ramp Delay
2Activation of Safe Torque Off
342-42 Delay Time
442-43 Delta T
542-48 S-ramp Ratio at Decel. Start
642-49 S-ramp Ratio at Decel. End
Illustration 3.8 SS1 Delay with S-ramp Stop Profile
3.5.4.3
SS1 Ramp
NOTICE
The SS1 Ramp function can only be used when an
encoder is connected to the safety option.
This Safe Stop type allows access to the hazard area
immediately after motion is detected as stopped rather
than waiting until a specific time has elapsed.
The safety option monitors the following functions
Braking ramp
•
In the MCT 10 Set-up Software Safe
-
Plug-in, the braking ramp is specified
and monitoring is activated. The braking
period depends on the speed of the
motor when braking is started. The
braking ramp can be monitored via a
maximum speed error specified in the
MCT 10 Set-up Software tolerable in
42-45 Delta V.
Braking ramp in normal operation
•
The frequency converter starts with the
-
configured braking ramp when safety
function Safe Stop 1 has been activated.
Once the speed is at zero speed limit,
Safe Torque Off is activated.
Safety function Safe Torque Off is activated when
•
the configured limit value for the position error is
exceeded
A standstill threshold Zero speed (42-46 Zero Speed) for
activating the safety function Safe Torque Off can be
specified in MCT 10 Set-up Software.
Safety function Safe Torque Off is activated when zero
speed is achieved.
Prerequisites for normal operation
Input DI1 or DI2: "1" Signal (+24 V DC)
•
S37 output: "1" Signal (+24 V DC). The safety
•
option is ready for operation
A 1/0 transition at the selected DI1 or DI2 input activates
the safety function.
Signal status of the inputs DI1 and DI2
The Safe Stop 1 ramp starts when one of the 2 inputs is
set to “0”. The safety function Safe Torque Off is activated
once the braking ramp has reached zero speed.
3.5.4.4
For the stopping process, the safety option initiates a stop
signal to the frequency converter and monitors the
controlled braking by monitoring the braking ramp. The
admissible deceleration ramp is specified in
42-44 Deceleration Rate. The frequency converter must
decelerate at least with the steepness of this deceleration
ramp in the event of a Safe Stop 1 request from the safety
option, even under heavy load. If the frequency converter
does not fulfill the admissible deceleration ramp during a
Safe Stop 1 requested by the safety option, a Safe Torque
Off is triggered immediately. The motor then performs an
uncontrolled stop. This action prevents the frequency
converter from continuing to run or even accelerating in
the event of an error.
AActual frequency
BSS1 Ramp
1Activation of SS1 Ramp Slope
2Activation of STO
342-44 Deceleration Rate
442-45 Delta V
542-46 Zero Speed
6Safety function monitors
7Activation of failure function
Illustration 3.9 SS1 Ramp Slope
AActual frequency
BSS1 ramp
1Activation of SS1 Ramp Time
2Activation of STO
342-47 Ramp Time
442-45 Delta V
542-46 Zero Speed
6Safety function monitors
7Activation of failure function Safe Torque Off
Illustration 3.10 SS1 Ramp Time
When the Safe Stop 1 function is active, the frequency
converter brings the motor to zero speed. The deceleration
is monitored. If the monitored deceleration is slower than
expected or at zero speed, Safe Torque Off is triggered.
This safety function corresponds to a controlled stop of the
frequency converter according to EN IEC 60204-1, stop
category.
3.5.4.5
Define a speed monitoring profile by a deceleration time
and a tolerable speed (Delta V).
The Safely Limited Speed function can only be used
when an encoder is connected to the safety option.
This function is used to limit a machine speed. The main
goal is to monitor the motor speed and to adjust the
speed to a set point. There are 2 types of Safely Limited
Speed
SLS without ramp: Monitors the motor speed and,
•
depending on the setting of 42-52 Fail Safe
time
1
2
4
5
3
6
frequency
130BC324.10
A
B
Functions and System Overvi...Operating Instructions
Reaction, trips in Safe Torque Off or Safe Stop 1 if
an overspeed occurs
SLS with ramp: Limits the motor speed to a set
•
point and, depending on the setting of 42-52 Fail
Safe Reaction, trips in Safe Torque Off or Safe
Stop 1, if an overspeed occurs
The Safe Limited Speed is given as speed limit in
42-51 Speed Limit. The value for the cut-off speed partly
depends on the motor that is being used. A suggested
value from MCT 10 Set-up Software calculates a value for
which Danfoss guarantees functionality. This value is called
delta speed limit and is added to the selected speed limit
and suggested as value in 42-50 Cut Off Speed.
33
3.5.5.1
SLS without Ramp
The safety function Safely Limited Speed monitors whether
a specified velocity value is exceeded since it was activated
via DI1 or DI2. The function is active until the selected
input has been put to high again.
If 2 Safe Speed limits must be monitored, set one of the 2
Safe Digital Inputs DI1 or DI2 in 42-20 Safe Function to SLSa or SLS-b. Then select the input type under 42-21 Type.
The cut-off speed represents the maximum allowed
frequency of the actual motor frequency. If the motor
frequency accelerates above that value, the safety option
enters external fault selected (STO or SS1 Ramp), and the
error is given. The frequency value at which a shutdown is
realised should be parameterised in 42-50 Cut Off Speed.
A
BSLS limit
1SLS is activated
242-51 Speed Limit
342-50 Cut Off Speed
4Delta speed limit
5
Activation of failure function set in 42-52 Fail Safe Reaction
6
Fixed value of 120 RPM in 42-19 Zero Speed Limit
Illustration 3.11 SLS without Ramp
If speed exceeds the limit, 42-52 Fail Safe Reaction is
activated. The safety function can either be Safe Torque
Off or SS1 Ramp Time. Safe Stop 1 can only be triggered
as error response if one Safe Stop 1 function has been set
as Safe Stop 1 with ramp time function, set in 42-40 Type.
Functions and System Overvi...Operating Instructions
Safe jog in combination with SLS
Limited Speed limit, the limit comes into effect
immediately without ramping. When the Safely Limited
Speed function is deactivated, the speed limits are ramped
up back to the values defined in parameter group 3-1*References, and the actual speed returns to the reference
value if it was limited by this function.
33
Follow these steps to configure the Safely Limited Speed
operation
1.If a safe speed limit must be monitored, set one
of the 2 safe digital inputs, DI1 or DI2, to [1] SLS-a
or [2] SLS-b in 42-20 Safe Function.
2.
Select input type in 42-21 Type.
3.
Select 42-53 Start Ramp to run Safely Limited
Speed with monitored braking ramp. The default
AActual frequency
BSLS limit
1SLS is activated
242-51 Speed Limit
342-50 Cut Off Speed
4Delta speed limit
5
Activation of failure function set in 42-52 Fail Safe Reaction
6
Fixed value of 120 RPM in 42-19 Zero Speed Limit
Illustration 3.12 Safe Jog
When the safety option actively monitors Safely Limited
Speed, and the motor speed is at or below the configured
safe speed limit, the function monitors the speed until the
function is deactivated.
value is [0] No for applications without SLS Ramp
control.
4.Set the time allowed to reach Safe Limited Speed
in 42-54 Ramp Down Time.
5.
Set the value in 42-50 Cut Off Speed.
Access under specific conditions of reduced risk
Under specific conditions of reduced risk, safe jog allows
for access to areas for fault-finding, commissioning, etc. On
machines where safe jog (jogging or inching) is needed,
this is also possible from zero speed setpoint.
By activating Safely Limited Speed, the motor can be
moved at safe jog resulting in a number of cycles and with
safely monitored movements. The motor can be started
and stopped continuously also from zero speed.
3.5.5.2
SLS with Ramp
If this safety function is needed, configure the safety
option for Safely Limited Speed (SLS). When the inputs DI1
or DI2 are selected as SLS, input is OFF, feedback velocity
is monitored and compared against a configurable safe
speed limit.
Select 42-53 Start Ramp to configure an SLS Monitoring
Ramp. The ramping begins when SLS monitoring is
requested by the selected input for SLS transition from ON
to OFF. The safety option starts monitoring for safe limited
speed when the ramp-down times out. If the system speed
exceeds or is equal to the configured safe speed limit
during Safely Limited Speed monitoring, a Safely Limited
Speed fault occurs and the safety option initiates the
configured Safe Stop type selected in 42-52 Fail SafeReaction.
The ramping begins at the absolute value of the actual
speed. If the actual speed is already below the Safely
Shorts between the 2 lines of a dual channel input are not
detected. Therefore the cables of the channels must be
routed separately to exclude short circuits.
NOTICE
AActual frequency
BSLS limit
1Safely Limited Speed is activated with SS1 Ramp
2Safely Limited Speed speed limit reached
3Ramp down time
4Delta speed limit
5Zero speed limit, fixed value of 120 RPM
6Cut-off speed
7
Activation of failure function set in 42-52 Fail Safe Reaction
Illustration 3.13 SLS with Ramp
Routing of the sensor cables
All proximity switch sensor/encoder cables must be
shielded when laid. The shielding must be connected to
chassis at both ends.
3.6.1 Inputs
The Dual-pole digital inputs are used to activate the safety
functions. DI 1 can be
STO: Safe Torque Off
•
SS1: Safe stop 1
•
SLS: Safely limited speed
•
Signals at DI 1
1/0 transition at the input: Activates the safety
•
function
“0” signal (0 V) at the input: Activates the safety
•
function
“1” signal (+24 V) at the input: Does not activate
•
the safety function
DI 2 can be
33
STO: Safe Torque Off
Activation of failure function set in 42-52 Fail Safe Reaction.
ParameterUnit RangeDefault
42-50 Cut Off SpeedRPM 120-10000 RPM270 RPM
42-51 Speed LimitRPM 1-9999 RPM150 RPM
42-52 Fail Safe
Reaction
42-53 Start Rampn/a No/YesNo
42-54 Ramp Down
Time
Table 3.5 Parameters for SLS with Ramp
If the speed exceeds the limit, 42-52 Fail Safe Reaction is
activated. The safety function can either be Safe Torque
Off or SS1 Ramp Time. SS1 can only be triggered as error
response if one digital input is selected as SS1 with ramp
time function, set in 42-40 Type.
3.6
Inputs and Output
An internal diagnostic function in the safety option
cyclically tests the correct function of the output. A
detected fault sets the safety option into an alarm status.
At the same time, the option output S37 goes low.
option after an error, or after deactivating a
safety function on input DI1
Signals at DI 2
1/0 transition at the input: Activates the safety
•
function
“0” signal (0 V) at the input: Activates the safety
•
function
“1” signal (+24 V) at the input: Does not activate
•
the safety function
0/1 transition at the DI2 input if configured to
•
reset: Resets the safety option
3.6.2
Reset Input (DI2)
The reset input is for resetting the safety circuit selected
on DI1. Configure the reset input for automatic or manual
reset types. If manual reset is configured, wire the DI2A
reset input terminal to a 24 V DC via an NO switch.
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.