General aspects of EMC emissions ...................................................................... 114
2
MG.50.N4.02 - VLT is a registered Danfoss trademark
VLT® 5000 Crane
VLT 5000 Crane
175ZA522.12
Operating instructions
Software version: 20.3x
These operating instructions can be used for VLT 5000
Crane frequency converters with software version 20.3x.
See software version number in parameter 624.
Introduction
MG.50.N4.02 - VLT is a registered Danfoss trademark
3
VLT® 5000 Crane
■Safety
The voltage of the frequency converter
is dangerous whenever the equipment is
connected to mains. Incorrect installation
of the motor or the frequency converter may cause
damage to the equipment, serious personal injury
or death. Consequently, the instructions in this
manual, as well as national and local rules and safety
regulations, must be complied with
■Safety Regulations
1. The frequency converter must be disconnected
from mains if repair work is to be carried out. Check
that the mains supply has been disconnected
and that the necessary time has passed before
removing motor and mains plugs.
2. The [STOP/RESET] key on the control panel of
the frequency converter does n
the equipment from mains and is thus n
be used as a safety switch.
3. Correct protective earthing of the equipment
must be established, the user must be protected
against supply voltage, and the motor must be
protected against overload in accordance with
applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is n
in the factory setting. If this function is desired,
set parameter 128 to data value ETR trip or
data value ETR warning.
N
ote: The function is initialised at 1.16 x rated
motor current and rated motor frequency. For
the North American market: The ETR function
ot disconnect
ot to
ot included
provide class 20 motor overload protection
in accordance with NEC.
6. Do n
7. Please note that the frequency converter has more
■Warning Against Unintended Start
1. The motor can be brought to a stop by means
2. While parameters are being changed, the
3. A motor that has been stopped may start if faults
4. Immediate stop. Direct stop input (term. 37). When
s
ot remove the plugs for the motor and mains
supply while the frequency converter is connected
to mains. Check that the mains supply has been
disconnected and that the necessary time has
passed before removing motor and mains plugs.
voltage inputs than L1, L2 and L3, when loadsharing
terminals (linking of DC intermediate circuit) and
external 24 V DC have been installed. Check
that all voltage inputs have been disconnected
and that the necessary time has passed before
repair work is commenced.
of digital commands, bus commands, references
or a local stop, while the frequency converter
is connected to mains. If personal safety
considerations make it necessary to ensure
that no unintended start occurs, these stop
functions are not sufficient.
motor may start. Consequently, the stop key
[STOP/RESET] must always be activated, following
which data can be modified.
occur in the electronics of the frequency converter,
or if a temporary overload or a fault in the supply
mains or the motor connection ceases.
contact is open, the drive will stop (coast).
Warning:
Touching the electrical parts may be fatal - even after the
equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load-sharing (linkage of
DC intermediate circuit), as well as the motor connection for
kinetic back-up.
Using VLT 5042-5062: wait at least 15 minutes.
Using VLT 5072-5202: wait at least 20 minutes.
175ZA523.11
4
MG.50.N4.02 - VLT is a registered Danfoss trademark
VLT® 5000 Crane
■General Instructions
These Operating Instructions are intended for
persons who are to install, operate and program
the VLT 5000 Crane.
They comprise the specific technical publications on
the VLT 5000 Crane and are delivered with the product.
When reading these Operating Instructions you come across different symbols that require special attention:
The symbols used are the following:
Indicates a general warning
Indicates a high-voltage warning
NB!:
Indicates something to be noted by the reader
Introduction
MG.50.N4.02 - VLT is a registered Danfoss trademark
5
■Abbreviations and Definitions
■Frequency converter
Abbreviation/DefinitionDescription
I
VLT,MAX
I
VLT,N
U
VLT,MAX
■Output
Abbreviation/DefinitionDescription
I
M
U
M
f
M
Break-away torque
VLT® 5000 Crane
The maximum output current
The rated output current supplied by the frequency converter
The maximum output voltage
The current transmitted to the motor
The voltage transmitted to the motor
The frequency transmitted to the motor
η
VLT
The efficiency of the frequency converter is defined as the ratio between the
power output and power input
■NO/NC
Abbreviation/DefinitionDescription
NONormally open
NCNormally closed
■Input
Abbreviation/DefinitionDescription
Control command
Immediate stop
Stop command
By means of LCP and the digital inputs, it is possible to start and stop the
connected motor.
6
MG.50.N4.02 - VLT is a registered Danfoss trademark
■Motor
I
M,N
f
M,N
U
M,N
P
M,N
n
M,N
T
M,N
■References
VLT® 5000 Crane
Abbreviation/DefinitionDescription
The rated motor current (nameplate data)
The rated motor frequency (nameplate data)
The rated motor voltage (nameplate data)
The rated power delivered by the motor (nameplate data)
The rated motor speed (nameplate data)
The rated torque (motor)
Abbreviation/DefinitionDescription
Analogue ref.A signal transmitted to input 53, 54 or 60. Can be voltage or current
Binary ref.A signal transmitted to the serial communication port
Ref
MAX
The maximum value which the reference signal may have. Set in parameter 205
■Miscellaneous
Abbreviation/DefinitionDescription
ELCBEarth Leakage Circuit Breaker
TripA state which occurs in different situations, eg. if the frequency converter is subject to a live zero warning.
A trip can be cancelled by pressing Reset
Trip lockedA state which occurs in different situations, eg. if the frequency converter is subject to an overtemperature.
A locked trip can be cancelled by cutting off mains and restarting the frequency converter and pressing
Reset
InitializingIf initializing is carried out (see parameter 620), the frequency converter returns to the factory setting
LCPThe Local Control Panel, which makes up a complete interface for control and programming of VLT 5000
Crane. The control panel is detachable and may, as an alternative, be installed up to 3 metres away from
the frequency converter, ie. in a front panel, by means of the installation kit option
Flux VectorIf compared with standard voltage/frequency ratio control, Flux Vector improves the dynamics and the
stability, both when the speed reference is changed and in relation to the load torque
ThermistorA temperature-dependent resistor placed where the temperature is to be monitored (frequency converter
or motor)
Analogue inputsThe analogue inputs can be used for controlling various functions of the frequency converter. There are
two types of analogue inputs:
Current input and voltage input
Analogue outputsThere are two analogue current outputs
Digital inputsThe digital inputs can be used for controlling various functions of the frequency converter
Digital outputsThere are four digital outputs, two of which activate relay switches.
Brake resistorThe brake resistor is a module capable of absorbing the brake power that is generated in regenerative
braking. This regenerative braking power increases the intermediate circuit voltage and a brake chopper
ensures that the power is transmitted to the brake resistor
Incremental encoderAn external, digital pulse transmitter used for feeding back information on motor speed. The encoder is
used in applications where high accuracy in speed control is required
AWGMeans American Wire Gauge, ie. the American measuring unit for cable cross-section
Introduction
MG.50.N4.02 - VLT is a registered Danfoss trademark
7
VLT® 5000 Crane
■Miscellaneous- continued
Abbreviations/DefinitionsDescription
Manual initialisationPress the [CHANGE DATA] + [MENU] + [OK] keys at the same time to carry out
manual initialisation. See also Parameter 620.
Note that manual initialisation is only to be used if the reset function does not work!
SFAVMSwitching pattern called Stator Flux oriented Asynchronous Vector Modulation
On-line/off-line parametersOn-line parameters are activated immediately after the data value is changed.
Off-line parameters are not activated until OK has been entered on the control unit
CT characteristicsConstant torque characteristics, used for all applications, such as conveyor belt
and cranes.
MCMStands for Mille Circular Mil, an American measuring unit for cable cross-section
1 MCM=0.5067mm
ETRElectronic thermal relay is a thermal load calculation based on present load and
time. Its purpose is to estimate the motor temperature
CPConstant power
2
s
8
MG.50.N4.02 - VLT is a registered Danfoss trademark
■Brief Product Description
The VLT 5000 Crane frequency converter supplies
a motor with variable voltage and frequency and
thereby enables infinitely variable speed control of
three-phased standard AC-motors.
The VLT 5000 Crane features the Flux Vector
control system.
The VLT 5000 Crane uses a digital technique
making it possible to program the different control
inputs and signal outputs.
The user can easily program the desired functions
by means of the VLT 5000 Crane control panel or
the user interfaces RS485 and RS232.
The VLT 5000 Crane is protected against the transients
occurring in the mains supply. Furthermore, a
good power factor and low peak current, reducing
the load on the mains installation, are ensured
through intermediate circuit coils.
Current measurement on all three motor phases
perfectly protects VLT 5000 Crane against earthing and
short-circuiting faults on the motor connenction.
VLT® 5000 Crane
Introduction
VLT 5000 Crane offers:
•Full utilisation of control range
•130% torque for acceleration
•Fine adjustment at standstill + full load possible
without activating the system brake
■System Description
The sketch on next page shows how a tower crane
works together with VLT Crane Control.
The system consists of the following:
Efficient monitoring of the mains supply phases
ensures that the unit stops in case of phase failure.
This eliminates the risk of overloading the inverter an
the capacitors in the intermediate circuit and thereby
prolongs the service life of the frequency converter.
As standard, VLT 5000 Crane features integral
thermal protection. If a situation of thermal overload
occurs, this function cuts out the inverter.
The VLT 5000 Crane features reliable galvanic isolation
on all control terminals and integrated electronic
thermal protection on the motor.
■Function and System Description
With VLT 5000 Crane the speed is infinitely varied in the
whole speed range from standstill (0 RPM) until rated
speed (750 RPM for VLT 5052-5072, 1125 RPM for
VLT 5102) according to the CT characteristic and rated
power up to max. speed (3000 or 4500 RPM).
There is full torque in the whole speed range.
1. VLT 5000 Flux Vector Control
2. Brake resistor
d
3. Motor
4. Cable drum
5. Angular gear box
6. NC system brake
7. Electric 2-step-gears: Normal load and heavy load
8. Optical encoder: Motor speed information for
flux vector control with closed loop
9. Load signals: VLT 5000 Crane checks on the basis of
load signals that the working range is not exceeded
10. Control signal: Analogue reference as well as
hoist, lowering and position operation
11. Quick stop with brake
12. Digital outputs: For combination of warning
and alarm at your operation
13. Crane ready signal
14. Gear step selection signal
15. VLT ready signal
16. RS 485 bus
17. RS 232 bus
18. Local control panel
MG.50.N4.02 - VLT is a registered Danfoss trademark
Installation and mains connection of brake resistor
and motor are described in Electrical installation
9
VLT® 5000 Crane
■Description of Functions
With Danfoss VLT 5000 Crane the hoist/lower function
can be infinitely varied in the whole speed range.
Up to 750 RPM for VLT 5052-5072, 1125 RPM for
VLT 5102, 1500 RPM for VLT 5152-5202, respectively
themax. torquecurveappliesandabove750
RPM for VLT 5052-5072, 1125 RPM for VLT 5102,
1500 RPM for VLT 5152-5202, respectively the
max. power curve. There is up to 130% torque for
acceleration in the whole speed range.
Working curve, motor:
1: Speed limit at heavy load (parameter 702)
2: Speed limit at normal load (parameter 701)
The 2-step gear box (see System description )
increases the working range, as it is possible to switch
between normal load and heavy load.
VLT 5000 will optimise the motor control to the selected
gear stage on the basis of the signal on terminal
29, see System Description, position 14.
ignal definition
S
24 V signal: Normal load
0 V signal: Heavy load
■Operating Status at Remote Control
Control ready
Voltage on VLT 5000 Crane. The frequency
converter is ready for use and the control card
receives supply voltage.
No faults were found during initialisation.
Inverter section disabled.
10
Normal operation
The reference signal is higher than minimum. Up to
750 RPM the working range is limited by max. torque.
Above 750 RPM it is working in field weakening range.
Here the working range is limited by constant power.
MG.50.N4.02 - VLT is a registered Danfoss trademark
VLT 5000 Crane controls the mechanical brake
of the crane. It holds the load when speed is
below the set minimum value.
VLT 5000 Crane monitors that the system brake
holds and releases the load as required. In case
of faults, Brake fault 2 is displayed.
Load determination and speed measuring will ensure
that the working range is not exceeded. For each
load contact the max. allowed motor speed is set
(parameters 701 and 702). VLT 5000 Crane cuts off
automatically when motor speed for the activated
load contact exceeds the value recorded
Positioning
The reference signal is higher than minimum. The
condition for VLT ready is fulfilled. 24V is applied
to terminal 17 (parameter 301).
During positioning the speed is limited to 750 RPM
for VLT 5052-5072, 1125 RPM for VLT 5102, 1500
RPM for VLT 5152-5202, respectively, and system
brake is not activated at 0 RPM.
Quick stop with brake
If control signal to terminal 27(parameter 304)
is removed, the motor ramps down according
to the alternative ramp (parameter 212) and the
brake is activated momentarily.
■Operating Status at Local Operation
It is only possible to change to local operation from
Control Ready. Besides, parameter 003 must be
set for Local and parameter 010 for Enable.VLT
5000 Crane can be operated over the control panel
or over parameters 004 - 009. This state acts
as Normal operating state, however there are no
load functions and monitoring of system brake.
This means that the whole working range from 0
- 3000 RPM can be used and the crane system
brake is controlled at approx. 0 RPM.
VLT® 5000 Crane
Brake fault 2
VLT 5000 Crane monitors in the state normal operation,
that the system brake releases the load as required.
If that is not the case Brake fault 2 applies. The unit
will cut in the system brake again. This means that the
system brake signal is deactivated. This ensures that
the load is held. Then the inverter section is disabled.
Brake fault 2 may also occur during commissioning
if the encoder connection is not correct.
Atreference0theunitgoesbacktothestateVLTready.
Function fault
VLT 5000 Crane monitors several functions. Should
severe faults occur, the unit will trip automatically.
For fault types, see Trouble-shooting
To reset the fault switch off/switch on the mains
supply and press the stop/reset button.
■System Components
Motor
Select the motor type for the rated output in question
in parameters 102-106, 150-155..
Incremental Encoder
The encoder must meet the following requirements:
•Pulses pr. revolution, see parameter 329
•Out puts: A (0º ), inv. A, B ( 9 0 º), inv. B, Z, i nv. Z
•Supply: +5 V ±5%
•Max. current (5V supply): 200mA
Note that outputs must be compatible with RS 422!
Brake resistor
See data for calculation in Control with brake function.
Introduction
■Fault Status at Remote and Local Control
Brake fault 1
VLT 5000 Crane monitors in the state VLT ready that
the system brake holds the load as required. If that is
not the case, Brake fault 1 appliesandtheloadisslowly
lowered according to the speed set in parameter 704.
MG.50.N4.02 - VLT is a registered Danfoss trademark
11
VLT® 5000 Crane
■Control Principle
A frequency converter rectifies AC voltage from mains
into DC voltage. This DC voltage is then converted into
aACvoltagewithavariableamplitudeandfrequency.
1. Mains voltage
3 x 400 - 500 V AC, 50 / 60 Hz.
2
. Rectifier
A three-phase rectifier bridge that rectifies AC
voltage into DC voltage.
3
. Intermediate circuit
The motor is thus supplied with variable voltage and
frequency, which enables infinitely variable speed
control of three-phased, standard AC motors.
5
. Intermediate circuit capacitors
Smooth the intermediate circuit voltage.
. Inverter
6
Converts DC voltage into variable AC voltage
with a variable frequency.
. Motor voltage
7
Variable AC voltage, 0-100% of mains supply voltage.
Variable frequency: 0 - 300 Hz.
4. Intermediate circuit coils
Smooth the intermediate circuitcurrent and limit the
load on mains and components (mains transformer,
wires, fuses and contactors).
■Flux Vector Control Principle
TheaimofdevelopingtheFluxVectorcontrol
principle has been to obtain a robust motor control
that is tolerant to different motor characteristics
without motor derating being required.
The current is split into magnetising and
torque-generating parts and provides for much
better and quicker estimation of the actual motor
loads. It is now possible to compensate for rapid
load changes. Full torque as well as extremely
accurate speed control can now be obtained even
at low speeds or even at standstill.
Good torque control properties and smooth transitions
to and from current limit operation are ensured.
Advantages of the Flux Vector control system:
-Accurate speed control down to 0 speed
-Quick response from received signal to
full motor shaft torque
-Good compensation for step loads
-Controlled transition from normal operation to
current limit operation (and vice versa)
. Control circuit
8
On basis of parameters, reference settings and input
signals, pulse patterns are generated for forming
thevariablemotorvoltageandfrequency.
-Torque control, comprising control of both
the torque-generating and the magnetising
component of the current
-Full holding torque
P
rogrammable signal outputs
VLT 5000 Crane uses a digital technique which makes
it possible to program the signal outputs.
For the user, it is easy to program the desired functions
by means of the control panel on VLT 5000 Crane
or the RS 485/RS 232 user interfaces.
rotection against mains interference
P
VLT 5000 Crane is protected against the transients
that occur in the mains supply, eg. when switching
power factor correction or when fuses blow.
The rated motor voltage and full torque can be
maintained all the way down to 10% undervoltage
in the mains supply.
12
MG.50.N4.02 - VLT is a registered Danfoss trademark
VLT® 5000 Crane
Minor interference on mains
Since as standard the VLT 5000 Crane features
intermediate circuit coils, there is only a small amount
of harmonic mains supply interference. This ensures
a good power factor and lower peak current, which
reduces the load on the mains installation.
A
dvanced VLT protection
Current measurement on all three motor phases
provides perfect protection of VLT 5000 Crane
against earthing and short-circuiting faults on
the motor connection.
Efficient monitoring of the three mains supply phases
ensures that the unit stops in the case of phase failure.
This avoids overloading the inverter and the capacitors
in the intermediate circuit, which would dramatically
reduce the service life of the frequency converter.
As standard, VLT 5000 Crane features integral
thermal protection. If a situation of thermal overload
occurs, this function cuts out the inverter.
ncoder supervisory circuit
E
The signals from the incremental encoder and hence
the cabling are continuously supervised.
The encoder signals are made up of three channels,
each of which are supervised, and status is given
on LEDs placed near the encoder terminals for each
channel as well as for the supply voltage for the encoder.
Green LED turned on means channel or voltage OK.
fan fails, a thermistor can be integrated and connected
to the thermistor input of the frequency converter
(terminals 53), see parameters 128 and 308.
Introduction
R
eliable galvanic isolation
In the VLT 5000 Crane all of the control circuits are
separated from mains potential through isolation
meeting the PELV requirements.
One set of relay contacts, terminals 01 - 03, is
separated from the remaining control circuits through
isolation also complying with PELV.
Furthermore, the control circuits are placed in blocks
individually separated through functional isolation
(< 100 V), see General Technical Data.
A
dvanced motor protection
VLT 5000 Crane features integrated
thermal motor protection.
The frequency converter calculates the motor
temperature on the basis of current, frequency and time.
As opposed to the traditional bimetallic protection,
electronic protection takes ac
cooling at low frequencies that comes from reduced
fan speed (motors with internal ventilation).
To obtain maximum protection against overheating of
the motor if the motor is covered or blocked, or if the
count of the reduction in
electronic,
MG.50.N4.02 - VLT is a registered Danfoss trademark
13
■Key Diagram for VLT 5000 Crane 5042,
5102 400-500 V
VLT® 5000 Crane
14
MG.50.N4.02 - VLT is a registered Danfoss trademark
■Key Diagram for VLT 5000 Crane 5122-
5202 400-500 V
VLT® 5000 Crane
Introduction
MG.50.N4.02 - VLT is a registered Danfoss trademark
15
VLT® 5000 Crane
■General Technical Data
Mains Supply (L1, L2, L3)
Supply voltage 400 - 500 V units3 x 400/415/440/460/500 V ± 10%
Supply frequency50/60 Hz ± 1%
Max. imbalance of supply voltage
VLT 5052 - 5062/400 - 500 V
VLT 5072 - 5202/400 - 500 V
Power factor/cos ϕ
No. of switches on supply input L1, L2, L3Appr. 1 time/minute
Derating for high ambient temperature, see Special Conditions in Appendix
*For more information on derating, see Special
Conditions in Appendix.
■VLT 5000 Crane Protection
•Electronic motor thermal protection against overload
•Electronic thermal protection against overload
•Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature reaches
90°C. An overtemperature fault can only be reset when the temperature of the heat-sink has fallen below 60°C
•The frequency converter is protected against short-circuiting on motor terminals U, V, W
•The frequency converter is protected against earth fault on motor terminals U, V, W
•Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if
the intermediate circuit voltage gets too high or too low
•If a motor phase is missing, the frequency converter cuts out, see parameter 234 Motor Phase Monitor
•If a mains phase is missing, the frequency converter will cut out when a load is applied to the motor
Data
Technical
MG.50.N4.02 - VLT is a registered Danfoss trademark
19
VLT® 5000 Crane
■Mains Supply 400 - 500 V
According to international requirementsVLT type504250525062
I
(S3 60%) [A]
Output current
Output
Typical shaft outputP
Typical shaft outputP
Max. cable cross-section to motor and
brake [mm
2
Rated input currentI
Max. cable cross-section
power[mm2]/[AWG]
Max. pre-fuses[-]/UL1)[A]100/100125/125150/50
Efficiency0.960,960.96
Weight IP 20 SB[kg]414243
Power loss at max. load.100412101500
EnclosureIP20IP20IP20
1. For type of fuse see section Fuses.
2. American wire gauge.
3. Connection stud 1 x M8/2 x M8.
]/[AWG]
I
VLT, MAX
2)3)
2)3)
VLT,N
(400-500 V)
586985
(60 s) [A] (400-500 V)97.6116.8135
S
(S3 60%) [kVA]
VLT,N
(400-500 V)
VLT,N
VLT,N
39.2
46.657.4
[kW]223037
[HP]304150
IP2050/050/0
(S3 60%) [A] (400 V)516276
L,N
35/250/050/0
20
MG.50.N4.02 - VLT is a registered Danfoss trademark
VLT® 5000 Crane
■Mains supply 3 x 400-500 V
According to international
requirementsVLT type5072510251525202
Output
current
Output
Typical shaft output P
Typical shaft output P
Max. cable cross-section to motor
(400-500 V) [mm
Max. cable cross-section to brake
(400-500 V) [mm2]
Max. cable cross-section to motor
(400-500 V) AWG]
Max. cable cross-section to brake
(400-500 V) AWG]
Max input currentI
Max. cable cross-section to power
(400-500 V) [mm
Max. cable cross-section to power
(400-500V) [AWG]
Efficiency
Weight IP 20 EB/IP 00[kg]10910989134
Power loss at max. load [W]1860225028283231
EnclosureIP20IP20IP00IP00
1. For type of fuse see section Fuses.
2. American wire gauge.
3. Connection Dual M10 screws.
4. Connection Dual M8 screws.
I
[A] (S3 60%) (400-500 V)100139201246
VLT,N
I
VLT, MAX
(60 s) [A] (400-500 V)159221301369
S
(S3 60%) [kVA]
VLT,N
(400-500 V)67.593.9135.8166.2
[kW]456590110
VLT,N
[HP]6189125150
VLT,N
2]3)
2) 3)
2) 4)
2]3)
4)
2) 3)
(S3 60%) [A] (400 V)89124186224
L,MAX
951202x702x185
951202x352x70
3/04/02x2/0
3/04/02x32x2/0
951202x702x185
3/04/02x2/0
0.96-
0.97
0.96-
0.97
0.97-
0.98
2x350
MCM
Data
Technical
2x350
MCM
0.97-
0.98
MG.50.N4.02 - VLT is a registered Danfoss trademark
21
VLT® 5000 Crane
■Fuses
UL compliance
BussmannSIBALittel fuseFerraz-Shawmut
5042KTS-R1002028220-125KLS-R100A6K-100R
5052KTS-R1252028220-125KLS-R125A6K-125R
5062KTS-R1502028220-160KLS-R150A6K-150R
5072FWH-2202028220-200L50S-225A50-P225
5102FWH-2502028220-250L50S-250A50-P250
5122FWH-3002028220-315L50S-300A50-P300
5152FWH-3502028220-315L50S-350A50-P350
5202FWH-400206xx32-400L50S-400A50-P400
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drive
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL
compliance
380-500 V
s.
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027200-240 Vtype gG
VLT 5001-5062380-500 Vtype gG
VLT 5032-5052200-240 Vtype gR
VLT 5072-5500380-500 Vtype gR
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
(symmetrical), 500/600 V maximum.
rms
22
MG.50.N4.02 - VLT is a registered Danfoss trademark
ab: Min. space above enclosure.
be: Min. space below enclosure.
l/r: Min. distance between frequency converter and
other plant components, left and right sides.
VLT 5042-5102/400-500 V
Data
Technical
VLT 5152-5202/400-500 V
MG.50.N4.02 - VLT is a registered Danfoss trademark
23
VLT® 5000 Crane
■General Warning before Installation
Before starting the installation, please
be aware of heavy weight and sharp
edges. Furthermore, make sure that
no mains are connected
■Mechanical Installation
The frequency converter must be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the minimum distance over and below the unit
must be as shown in the illustration below. To protect
■Installation of VLT 5042–5062 400-500 V
Compact IP20/IP00
Cooling
the unit from overheating, it must be ensured that the
ambient temperature does not rise above the max.temperature stated for the frequency converter and
that the 24-hour average temperature is not exceeded.
The max. temperature and 24-hour average can be
seen from the General Technical Data.
■Enclosure Protection
Compact
VLT 5042 - 5102 400-500 VIP 20
VLT 5152 - 5202 400-500 VIP 00
Side-by-side
All Compact units in the above-mentioned series
require a minimum space of 200 mm above and
below the enclosure and must be installed on a
plane, vertical surface (no spacers).
Compact IP 00/IP20
All units in the above-mentioned series can be installed
side by side without any space between them, since
these units do not require cooling on the sides.
24
MG.50.N4.02 - VLT is a registered Danfoss trademark
■Installation of VLT 5072-5202 400-500 V
Compact IP20/IP00
Cooling
All Compact units in the above-mentioned series
require a minimum space of 225 mm above and
below the enclosure and must be installed on a
plane, vertical surface (no spacers).
VLT® 5000 Crane
Side-by-side
Compact IP 00/IP20
All units in the above-mentioned series can be installed
side by side without any space between them.
■Ventilation when Panelmounted
The quantity of air needed to cool VLT 5000 Crane
can be calculated as follows:
1. Add up the values of P
to be installed at the same panel (
2. Determine the air inlet temperature (t
air outlet temperature (t
for all VLT 5000 Crane
P )[W]
)andthe
IN
)[ºCorK]
OUT
3. Calculate the necessary air quantity in m
Insert t
OUT-tIN
in Kelvin
•The output from the fan must be located above
the highest mounted frequency converter
•Remember to take pressure drops over filters
into account and that the pressure decreases
as the filters are choked
•The max. cooling air temperature (t
)must
IN
be lower than 55ºC. The average of day/night
temperature may be 5ºC lower than that stated
in VDE 160. The cooling outlet temperature
(t
) may not exceed 60ºC
OUT
3
/h:
Installation
MG.50.N4.02 - VLT is a registered Danfoss trademark
25
■Electrical Installation
The voltage on the frequency converter is
dangerous when the unit is connected to
mains. Incorrect installation of the motor
or frequency converter may lead to material damage
or serious injury or it may be fatal. Consequently, the
instructions in this manual as well as national and
local rules and safety regulations must be complied
with. Touching the electrical parts may be fatal, even
after the mains supply has been disconnected. Wait
at least 15 minutes if using VLT 5052-5102.
NB!:
It is the user’s or certified electrician’s
responsibility to ensure correct earthing and
protection in accordance with applicable
national and local norms and standards.
All terminals for the control cables are located under
the protective cover of the frequency converter. The
protective cover (see drawing) can be removed by
means of a pointed object - a screwdriver or similar.
VLT® 5000 Crane
Once the protective cover has been removed, the
actual EMC-correct installation can start.
26
Wiring diagram VLT 5000 Crane
A: Encoder
B: Brake resistor
12: +24 V
16 Crane ready (NO)
17: Positioning (NO)
18: Lower (NO)
19: Hoist (NO)
20: Ground for digital inputs
26: Digital output
27: Quick stop (NC)
29: Gear ratio select (NO)
32: Load low (NO)
MG.50.N4.02 - VLT is a registered Danfoss trademark
33: Load high (NO)
37: Hardware coast (NC)
39: Ground for analogue/digital outputs
42: Analogue output warning/alarm
45: Analogue output warning/alarm
46: Digital output
50: 10 V supply
53: Reference voltage
55: Common for anal. ref.
60: Reference current
68, 69: RS 485
01, 02: System brake signal
04, 05: Ready signal
73: Pulse signal A from encoder (0°)
74: Inverted pulse signal from encoder (0°)
75: Pulse signal B from encoder (90°)
76: Inverted pulse signal B from encoder (90°)
77: Zero pulse signal from encoder
78: Inverted zero pulse signal from encoder
49: 5 V supply to encoder
47: Common for encoder supply
VLT® 5000 Crane
■Electrical Installation, Power Cables
Compact IP 20 VLT Type 5042–5062
Compact IP 00 VLT 5125-5250 400-500 V
■Connection of Mains
Connect the three mains phases to terminals L
■Connection of Motor
All types of 3-phased asynchronous standard motors
can be used with the VLT 5000 Crane.
1,L2,L3
.
Installation
Compact IP 20/IP 00 VLT Types 5072-5102
MG.50.N4.02 - VLT is a registered Danfoss trademark
27
Normally, small motors are star-connected.
Large motors are delta-connected.
Note the voltage value at the type plate.
■Installation of Motor Cables
NB!:
If an unscreened cable is used, some EMC
requirements are not complied with, see
Special conditions in Appendix.IftheEMC
specifications regarding emission are to be complied
with, the motor cable must be screened, unless
otherwise stated for the RFI filter in question. It is
important to keep the motor cable as short as possible
to reduce the noise level and leakage currents to a
minimum. The motor cable screen must be connected
to the metal cabinet of the frequency converter and to
the metal housing of the motor. The screen connections
are to be made with the biggest possible surface
(cable clamp). This is enabled by different installation
devices in the different frequency converters.
Mounting with twisted screen ends (pigtails) is to
be avoided, since these spoil the screening effect
at higher frequencies. If it is necessary to break
the screen to install a motor isolator or motor
contactor, the screen must be continued at the
lowest possible HF impedance.
VLT® 5000 Crane
LEDs on encoder board:
When all LEDs are on the connection to encoder
and encoder condition are OK.
LED 403 OFF: 5 V supply missing
LED 400 OFF: Channel A or inv. A missing
or shortcircuited
LED 401 OFF: Channel B or inv. B missing
or shortcircuited
LED 402 OFF: Channel Z or inv. Z missing
or shortcircuited.
The frequency converter has been tested with a given
length of cable and a given cross-section of that cable.
If the cross-section is increased, the cable capacitance
- and thus the leakage current - increases, and the
cable length must be reduced correspondingly.
■Installation of Control Cables
Tightening-up torque: 0.22 - 0.25 Nm
Screw size: M2
Screw driver type: 0.4 x 2.5 x 80 mm
See Earthing of Braided Screened/ArmouredControl Cables for correct earthing.
28
MG.50.N4.02 - VLT is a registered Danfoss trademark
Connection of shield:
VLT® 5000 Crane
The connection cable to the brake resistor must
be screened/armoured. Connect the screen to the
metal cabinet of the frequency converter and to
the metal cabinet of the brake resistor by means of
cable clamps. Dimension the cross-section of the
brake cable to match the brake torque.
NB!:
Please note that voltages up to 850 V DC
occur on the terminals.
No.Function
12, 13Voltage supply to digital inputs.
Forthe24VDCtobeusable
for the digital inputs, switch 4 on
the control card must be closed
position "ON".
Max. current 350 mA
■Installation of Brake Resistor Temperature Switch
Torque: 0.5-0.6 Nm
Screw size: M3
No.Function
106, 104,
Brake resistor temperature switch.
105
NB!:
This function is only available on VLT
5072-5202 400-500 V.
If the temperature of the brake resistor gets too high and
the terminal switch drops out, the frequency converter
will stop braking. The motor will start coasting.
A terminal switch must be installed that can either be
‘normally closed’ or ‘normally open’. If this function is
not used, 106 and 104 must be short-circuited together.
Installation
■Brake Connection
No. 81 82Brake resistor
R-R+ terminals
MG.50.N4.02 - VLT is a registered Danfoss trademark
29
Loading...
+ 93 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.