Danfoss VLT 5000 Operating guide

VLT® 5000 Series

Contents

Safety

3

Safety regulations

4

Warning against unintended start

5

Installation of mechanical brake

5

Quick Setup

6

Introduction

9

Available literature

9

Technical data

10

General technical data

10

Electrical data

16

Fuses

33

Mechanical dimensions

35

Installation

38

Mechanical installation

38

Safety earthing

41

Extra protection (RCD)

41

Electrical installation - mains supply

41

Electrical installation - motor cables

42

Connection of motor

42

Direction of motor rotation

42

Electrical installation - brake cable

43

Electrical installation - brake resistor temperature switch

43

Electrical installation - loadsharing

43

Electrical installation - 24 Volt external DC supply

45

Electrical installation - relay outputs

45

Electrical installation - control cables

53

Electrical installation - bus connection

56

Electrical installation - EMC precautions

57

Use of emc-correct cables

60

Electrical installation - earthing of control cables

61

RFI switch

62

Operation of the frequency converter

65

Control panel (LCP)

65

Control panel - display

65

Control panel - LEDs

65

Control panel - control keys

66

Quick Setup

68

Parameter selection

68

Menu mode

68

Initialisation to factory setting

70

MG.52.A3.02 - VLT® is a registered Danfoss trademark

1

VLT® 5000 Series

 

Application configuration

72

Connection examples

72

Setting of parameters

74

Special functions

77

Local and remote control

77

Control with brake function

78

References - single references

79

References - multi-references

81

Automatic Motor Adaptation, AMA

85

Mechanical brake control

87

PID for process control

89

PID for speed control

90

Quick discharge

91

Flying start

93

Normal/high overload torque control,open loop

94

Programming of Torque limit and stop

94

Programming

96

Parameters - Operation and Display

96

Parameters - Load and motor

103

Parameters - References and limits

114

Parameters - Inputs and outputs

122

Parameters - Special functions

138

Parameters - Serial communication

152

Parameters - Technical functions and diagnostics

159

Miscellaneous

166

Trouble-shooting

166

Display - Status messages

167

Warnings and alarms

170

Warnings

171

Index

190

2

MG.52.A3.02 - VLT® is a registered Danfoss trademark

VLT® 5000 Series

VLT 5000 Series

Operating Instructions

Software version: 3.9x

These Operating Instructions can be used for all VLT 5000 Series frequency converters with software version 3.9x.

The software version number can be seen from parameter 624.

CE and C-tick labelling do not cover VLT 5001-5062, 525-600 V units.

These Operating Instructions are a tool intended for persons who are to install, operate and program the VLT 5000 Series.

Operating Instructions:

Gives instructions in optimum installation, commissioning and service.

Design Guide:

Gives all required information for design purposes, and gives a good insight

 

into the technology, product range, technical data, etc.

<![if ! IE]>

<![endif]>Safety

The Operating Instructions including Quick Setup are delivered with the unit.

When reading these Operating Instructions, you will come across different symbols that require special attention. The symbols used are the following:

Indicates a general warning

Indicates a high-voltage warning

NB!

Indicates something to be noted by the reader

MG.52.A3.02 - VLT® is a registered Danfoss trademark

3

VLT® 5000 Series

The voltage of the frequency converter is dangerous whenever the equipment is connected to mains. Incorrect installation of the motor or the frequency converter may cause damage to the equipment, serious personal injury or death.

Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.

Installation in high altitudes:

By altitudes above 2km, please contact Danfoss Drives regarding PELV

Safety regulations

1.The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.

2.The [STOP/RESET] key on the control panel of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a safety switch.

3.Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.

4.The earth leakage currents are higher than 3.5 mA.

5.Protection against motor overload is not included in the factory setting. If this function is desired, set parameter 128 to data value ETR trip or data value ETR warning.

Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.

6.Do not remove the plugs for the motor and main supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the

necessary time has expired before removing motor and mains plugs.

7.Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when loadsharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before repair work is commenced.

4

MG.52.A3.02 - VLT® is a registered Danfoss trademark

VLT® 5000 Series

Warning against unintended start

1.The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains.

If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.

2.While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated, following which data can be modified.

3.A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.

Installation of mechanical brake

Do not connect a mechanical brake to the output from the frequency converter before the relevant parameters for brake control are parameterised.

(Selection of output in parameter 319, 321, 323 or 326 and cut-in current and frequency in parameter 223 and 225).

Use on isolated mains

See section RFI Switch regarding use on isolated mains.

It is important to follow the recommendations regarding installation on IT-mains, since sufficient protection of the complete installation must be observed. Not taking care using relevant monitoring devices for ITmains may result in damage.

Warning:

<![if ! IE]>

<![endif]>Safety

Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.

Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load-sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back-up.

VLT 5001 - 5006, 200-240 V:

wait at least 4 minutes

VLT 5008 - 5052, 200-240 V:

wait at least 15 minutes

VLT 5001 - 5006, 380-500 V:

wait at least 4 minutes

VLT 5008 - 5062, 380-500 V:

wait at least 15 minutes

VLT 5072 - 5302, 380-500 V:

wait at least 20 minutes

VLT 5352 - 5552, 380-500 V:

wait at least 40 minutes

VLT 5001 - 5005, 525-600 V

wait at least 4 minutes

VLT 5006 - 5022, 525-600 V:

wait at least 15 minutes

VLT 5027 - 5062, 525-600 V:

wait at least 30 minutes

VLT 5042 - 5352, 525-690 V:

wait at least 20 minutes

VLT 5402 - 5602, 525-690 V:

wait at least 30 minutes

MG.52.A3.02 - VLT® is a registered Danfoss trademark

5

VLT® 5000 Series

Introduction to Quick Setup

This Quick Setup will guide you through EMC correct installation of the frequency converter by connecting power, motor and control wiring (fig. 1). Start/stop of motor is to be done with the switch.

For VLT 5122 - 5552 380 - 500 V, VLT 5032 - 5052 200 - 240 V AC and VLT 5042-5602, 525-690 V, please refer to Technical data and Installation regarding mechanical and electrical installation.

Fig. 1

1. Mechanical Installation

VLT 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a free air passage of 100 mm above and below the frequency converter (5016-5062 380-500 V, 5008-5027 200-240 V and 5016-5062 525-600 V must have 200 mm, 5072-5102, 380-500 V 225 mm).

Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Place the frequency converter on the wall. Tighten up all four screws.

All the below listed measurements are in mm

VLT type

A

B

C

a

b

Bookstyle IP 20, 200–240 V, (Fig. 2)

 

 

 

 

 

5001 - 5003

395

90

260

384

70

5004 - 5006

395

130

260

384

70

Bookstyle IP 20, 380–500 V (Fig. 2)

 

 

 

 

 

5001 - 5005

395

90

260

384

70

5006 - 5011

395

130

260

384

70

Compact IP 54, 200–240 V (Fig. 3)

 

 

 

 

 

5001 - 5003

460

282

195

260

258

5004 - 5006

530

282

195

330

258

5008 - 5011

810

350

280

560

326

5016 - 5027

940

400

280

690

375

Compact IP 54, 380–500 V (Fig. 3)

 

 

 

 

 

5001 - 5005

460

282

195

260

258

5006 - 5011

530

282

195

330

258

5016 - 5027

810

350

280

560

326

5032 - 5062

940

400

280

690

375

5072 - 5102

940

400

360

690

375

Compact IP 20, 200–240 V (Fig. 4)

 

 

 

 

 

5001 - 5003

395

220

160

384

200

5004 - 5006

395

220

200

384

200

5008

560

242

260

540

200

5011 - 5016

700

242

260

680

200

5022 - 5027

800

308

296

780

270

Compact IP 20, 380–500 V (Fig. 4)

 

 

 

 

 

5001 - 5005

395

220

160

384

200

5006 - 5011

395

220

200

384

200

5016 - 5022

560

242

260

540

200

5027 - 5032

700

242

260

680

200

5042 - 5062

800

308

296

780

270

5072 - 5102

800

370

335

780

330

Fig. 2

Fig. 3

Fig. 4

6

MG.52.A3.02 - VLT® is a registered Danfoss trademark

VLT® 5000 Series

2. Electrical Installation, power

NOTE: The terminals are detachable on VLT 5001 - 5006, 200 - 240 V, VLT 5001 - 5011, 380 - 500 V and VLT 5001 - 5011, 525 - 600 V

Connect the mains supply to the mains terminals L1, L2, L3 of the frequency converter and to the earth connection (fig. 5-8). Cable relief fitting is placed on the wall for Bookstyle units. Mount screened motor cable to the motor terminals U, V, W, PE of the frequency converter. Make sure, the screen is connected electrically to the drive.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 5

 

 

 

 

 

 

 

 

 

 

 

 

Bookstyle IP 20

Compact IP 20

 

 

 

 

 

 

 

 

 

 

 

 

5001 - 5011 380 - 500 V

5016 - 5102 380 - 500 V

 

 

 

 

 

 

 

 

 

 

 

 

5001 - 5006 200 - 240 V

5008 - 5027 200 - 240 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5016 - 5062 525 - 600 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 8

 

Compact IP 54

Fig. 6

5016 - 5062 380 - 500 V

5008 - 5027 200 - 240 V

Compact IP 20 and IP 54

 

5001 - 5011 380 - 500 V

 

5001 - 5006 200 - 240 V

 

5001 - 5011 525 - 600 V

 

Fig. 9

Compact IP 54

5072 - 5102 380 - 500 V

<![if ! IE]>

<![endif]>Quick Setup

MG.52.A3.02 - VLT® is a registered Danfoss trademark

7

VLT® 5000 Series

3. Electrical installation, control leads

Use a screw driver to remove the front cover under the control panel.

NOTE: The terminals are detachable. Connect a jumber between terminals 12 and 27 (Fig. 10)

Mount screened cable to external start/stop of control terminals 12 and 18.

Fig. 10

4. Programming

The frequency converter is programmed over the control panel.

Press the QUICK MENU button. The Quick Menu appears in the display. You choose parameters by means of arrow up and arrow down. Press the CHANGE DATA button to change parameter value. Data values are changed using the up and down arrows. Press the left or right buttons to move the cursor. Press OK to save your parameter setting.

Set the desired language in parameter 001. You have six possibilities: English, German, French, Danish, Spanish and Italian.

Set the motor parameters according to the motorplate:

Motor power

Parameter 102

Motor voltage

Parameter 103

Motor frequency

Parameter 104

Motor current

Parameter 105

Rated motor speed

Parameter 106

Set frequency interval and ramp times (Fig. 11)

Min. reference

Parameter 204

Max. reference

Parameter 205

Ramp up time

Parameter 207

Ramp down time

Parameter 208

Set Operation site, Parameter 002 for Local.

Fig. 11

5. Motor Start

Press the START button to start the motor. Set motor speed in Parameter 003. Check if the direction of rotations is as shown in the display. It can be changed by swapping two phases of the motor cable.

Press the STOP button to stop the motor.

Select total or reduced Automatic Motor Adaption (AMA) in Parameter 107. For further description of AMA, see section Automatic Motor Adaption, AMA.

Press the START button to start the Automatic Motor Adaption (AMA).

Press the DISPLAY/STATUS button to leave the Quick Menu.

8

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

VLT® 5000 Series

 

Available literature

Below is a list of the literature available for VLT 5000.

 

It must be noted that there may be deviations from one

 

country to another.

 

Supplied with the unit:

 

 

Operating instructions

 

MG.51.AX.YY

High Power Installation Guide

 

MI.90.JX.YY

Communication with VLT 5000:

 

 

VLT 5000 Profibus manual

 

MG.10.EX.YY

VLT 5000 DeviceNet manual

 

MG.50.HX.YY

VLT 5000 LonWorks manual

 

MG.50.MX.YY

VLT 5000 Modbus manual

 

MG.10.MX.YY

VLT 5000 Interbus manual

 

MG.10.OX.YY

Application options for VLT 5000:

 

 

VLT 5000 SyncPos option manual

 

MG.10.EX.YY

VLT 5000 Positioning controller manual

 

MG.50.PX.YY

VLT 5000 Synchronising controller manual

 

MG.10.NX.YY

Ring spinning option

 

MI.50.ZX.02

Wobble function option

 

MI.50.JX.02

Winder and Tension control option

 

MG.50.KX.02

Instructions for VLT 5000:

 

 

Loadsharing

 

MI.50.NX.02

VLT 5000 Brake resistors

 

MI.90.FX.YY

Brake resistors for horizontal applications (VLT 5001 - 5011) (Only in English and German)

MI.50.SX.YY

LC filter modules

 

MI.56.DX.YY

Converter for encoder inputs (5V TTL to 24 V DC) (Only in combined English/German)

MI.50.IX.51

Back Plate to VLT 5000 Series

 

MN.50.XX.02

Various literature for VLT 5000:

 

 

Design Guide

 

MG.51.BX.YY

Incorporating a VLT 5000 Profibus in a Simatic S5 SYSTEM

MC.50.CX.02

Incorporating a VLT 5000 Profibus in a Simatic S7 SYSTEM

MC.50.AX.02

Hoist and the VLT 5000 series

 

MN.50.RX.02

Miscellaneous (only in English):

 

 

Protection against electrical hazards

 

MN.90.GX.02

Choice of prefuses

 

MN.50.OX.02

VLT on IT mains

 

MN.90.CX.02

Filtering of harmonic currents

 

MN.90.FX.02

Handling aggressive environments

 

MN.90.IX.02

CI-TITM contactors - VLT® frequency converters

 

MN.90.KX.02

VLT® frequency converters and UniOP operator panels

 

MN.90.HX.02

X = version number

YY = language version

<![if ! IE]>

<![endif]>Introduction

MG.52.A3.02 - VLT® is a registered Danfoss trademark

9

Danfoss VLT 5000 Operating guide

 

VLT® 5000 Series

General technical data

 

 

Mains supply (L1, L2, L3):

 

 

 

 

 

Supply voltage 200-240 V units

 

3 x 200/208/220/230/240 V ±10%

Supply voltage 380-500 V units

3 x 380/400/415/440/460/500 V ±10%

Supply voltage 525-600 V units

 

3 x 525/550/575/600 V ±10%

Supply voltage 525-690 V units

 

3 x 525/550/575/600/690 V ±10%

Supply frequency

 

48-62 Hz +/- 1 %

See the section on special conditions in the Design Guide

 

 

Max imbalance of supply voltage:

 

 

VLT 5001-5011, 380-500 V and 525-600 V and VLT 5001-5006, 200-240 V

±2.0% of rated supply voltage

VLT 5016-5062, 380-500 V and 525-600 V and VLT 5008-5027, 200-240 V

±1.5% of rated supply voltage

VLT 5072-5552, 380-500 V and VLT 5032-5052, 200-240 V

 

±3.0% of rated supply voltage

VLT 5042-5602, 525-690 V

 

±3.0% of rated supply voltage

True Power factor (λ)

 

0.90 nominal at rated load

Displacement Power Factor (cos φ)

 

near unity (>0.98)

No. of switchings on supply input L1, L2, L3

 

approx. 1 time/min.

See the section on special conditions in the Design Guide

 

 

VLT output data (U, V, W):

 

 

 

 

 

Output voltage

 

0-100% of supply voltage

Output frequency VLT 5001-5027, 200-240 V

 

0-132 Hz, 0-1000 Hz

Output frequency VLT 5032-5052, 200-240 V

 

0-132 Hz, 0-450 Hz

Output frequency VLT 5001-5052, 380-500 V

 

0-132 Hz, 0-1000 Hz

Output frequency VLT 5062-5302, 380-500 V

 

0-132 Hz, 0-450 Hz

Output frequency VLT 5352-5552, 380-500 V

 

0-132 Hz, 0-300 Hz

Output frequency VLT 5001-5011, 525-600 V

 

0-132 Hz, 0-700 Hz

Output frequency VLT 5016-5052, 525-600 V

 

0-132 Hz, 0-1000 Hz

Output frequency VLT 5062, 525-600 V

 

0-132 Hz, 0-450 Hz

Output frequency VLT 5042-5302, 525-690 V

 

0-132 Hz, 0-200 Hz

Output frequency VLT 5352-5602, 525-690 V

 

0-132 Hz, 0-150 Hz

Rated motor voltage, 200-240 V units

 

200/208/220/230/240 V

Rated motor voltage, 380-500 V units

 

380/400/415/440/460/480/500 V

Rated motor voltage, 525-600 V units

 

525/550/575 V

Rated motor voltage, 525-690 V units

 

525/550/575/690 V

Rated motor frequency

 

50/60 Hz

Switching on output

 

Unlimited

Ramp times

 

0.05-3600 sec.

Torque characteristics:

 

 

Starting torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V

160% for 1 min.

Starting torque, VLT 5032-5052, 200-240 V

 

150% for 1 min.

Starting torque, VLT 5001-5062, 525-600 V

 

160% for 1 min.

Starting torque, VLT 5042-5602, 525-690 V

 

160% for 1 min.

Starting torque

 

180% for 0.5 sec.

Acceleration torque

 

100%

Overload torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V,

 

VLT 5001-5062, 525-600 V, and VLT 5042-5602, 525-690 V

 

160%

Overload torque, VLT 5032-5052, 200-240 V

 

150%

Arresting torque at 0 rpm (closed loop)

 

100%

The torque characteristics given are for the frequency converter at the high overload torque level (160%). At the normal overload torque (110%), the values are lower.

10

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

 

VLT® 5000 Series

Braking at high overload torque level

 

 

 

Cycle time (s)

Braking duty cycle at 100% torque

Braking duty cycle at over torque

 

 

 

(150/160%)

200-240 V

 

 

 

5001-5027

120

Continuous

40%

5032-5052

300

10%

10%

380-500 V

 

 

 

5001-5102

120

Continuous

40%

5122-5252

600

Continuous

10%

5302

600

40%

10%

5352-5552

600

40%1)

10%2)

525-600 V

 

 

 

5001-5062

120

Continuous

40%

525-690 V

 

 

 

5042-5352

600

40%

10%

5402-5602

600

40%3)

10%4)

1)VLT 5502 at 90% torque. At 100% torque the braking duty cycle is 13%. At mains rating 441-500 V 100% torque the braking duty cycle is 17%.

VLT 5552 at 80% torque. At 100% torque the braking duty cycle is 8%.

2)Based on 300 second cycle:

For VLT 5502 the torque is 145%.

For VLT 5552 the torque is 130%.

3)VLT 5502 at 80% torque. VLT 5602 at 71% torque.

4)Based on 300 second cycle. For VLT 5502 the torque is 128%. For VLT 5602 the torque is 114%.

Control card, digital inputs:

Number of programmable digital inputs

8

Terminal nos.

16, 17, 18, 19, 27, 29, 32, 33

Voltage level

0-24 V DC (PNP positive logics)

Voltage level, logical '0'

< 5 V DC

Voltage level, logical '1'

>10 V DC

Maximum voltage on input

28 V DC

Input resistance, Ri

2 kΩ

Scanning time per input

3 msec.

Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition, the digital inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4. VLT 5001-5062, 525-600 V do not meet PELV.

Control card, analogue inputs:

No. of programmable analogue voltage inputs/thermistor inputs

2

Terminal nos.

53, 54

Voltage level

0 - ±10 V DC (scalable)

Input resistance, Ri

10 kΩ

No. of programmable analogue current inputs

1

Terminal no.

60

Current range

0/4 - ±20 mA (scalable)

Input resistance, Ri

200 Ω

Resolution

10 bit + sign

Accuracy on input

Max. error 1% of full scale

Scanning time per input

3 msec.

Terminal no. ground

55

Reliable galvanic isolation: All analogue inputs are galvanically isolated from the supply voltage (PELV)* as well as other inputs and outputs.

* VLT 5001-5062, 525-600 V do not meet PELV.

<![if ! IE]>

<![endif]>Technical data

MG.52.A3.02 - VLT® is a registered Danfoss trademark

11

 

VLT® 5000 Series

Control card, pulse/encoder input:

 

No. of programmable pulse/encoder inputs

4

Terminal nos.

17, 29, 32, 33

Max. frequency on terminal 17

5 kHz

Max. frequency on terminals 29, 32, 33

20 kHz (PNP open collector)

Max. frequency on terminals 29, 32, 33

65 kHz (Push-pull)

Voltage level

0-24 V DC (PNP positive logics)

Voltage level, logical '0'

< 5 V DC

Voltage level, logical '1'

>10 V DC

Maximum voltage on input

28 V DC

Input resistance, Ri

2 kΩ

Scanning time per input

3 msec.

Resolution

10 bit + sign

Accuracy (100-1 kHz), terminals 17, 29, 33

Max. error: 0.5% of full scale

Accuracy (1-5 kHz), terminal 17

Max. error: 0.1% of full scale

Accuracy (1-65 kHz), terminals 29, 33

Max. error: 0.1% of full scale

Reliable galvanic isolation: All pulse/encoder inputs are galvanically isolated from the supply voltage (PELV)*. In addition, pulse and encoder inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4.

* VLT 5001-5062, 525-600 V do not meet PELV.

Control card, digital/pulse and analogue outputs:

No. of programmable digital and analogue outputs

2

Terminal nos.

42, 45

Voltage level at digital/pulse output

0 - 24 V DC

Minimum load to ground (terminal 39) at digital/pulse output

600 Ω

Frequency ranges (digital output used as pulse output)

0-32 kHz

Current range at analogue output

0/4 - 20 mA

Maximum load to ground (terminal 39) at analogue output

500 Ω

Accuracy of analogue output

Max. error: 1.5% of full scale

Resolution on analogue output.

8 bit

Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the supply voltage (PELV)*, as well as other inputs and outputs.

* VLT 5001-5062, 525-600 V do not meet PELV.

Control card, 24 V DC supply:

Terminal nos.

12, 13

Max. load (short-circuit protection)

200 mA

Terminal nos. ground

20, 39

Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage (PELV)*, but has the same potential as the analogue outputs.

* VLT 5001-5062, 525-600 V do not meet PELV.

Control card, RS 485 serial communication:

Terminal nos.

68 (TX+, RX+), 69 (TX-, RX-)

Reliable galvanic isolation: Full galvanic isolation.

 

Relay outputs: 1)

 

No. of programmable relay outputs

2

Terminal nos., control card (resistive load only)

4-5 (make)

12

MG.52.A3.02 - VLT® is a registered Danfoss trademark

4 mm2 /10 AWG
2.5 mm2 /12 AWG
1.5 mm 2 /16 AWG
1.5 mm2 /16 AWG

 

VLT® 5000 Series

Max. terminal load (AC1) on 4-5, control card

50 V AC, 1 A, 50 VA

Max. terminal load (DC1 (IEC 947)) on 4-5, control card

25 V DC, 2 A / 50 V DC, 1 A, 50 W

Max. terminal load (DC1) on 4-5, control card for UL/cUL applications

30 V AC, 1 A / 42.5 V DC, 1A

Terminal nos., power card (resistive and inductive load)

1-3 (break), 1-2 (make)

Max. terminal load (AC1) on 1-3, 1-2, power card

250 V AC, 2 A, 500 VA

Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, power card

25 V DC, 2 A / 50 V DC, 1A, 50 W

Min. terminal load (AC/DC) on 1-3, 1-2, power card

24 V DC, 10 mA / 24 V AC, 100 mA

1) Rated values for up to 300,000 operations.

At inductive loads the number of operations are reduced by 50%, alternatively the current can be reduced by 50%, thus the 300,000 operations are maintained.

Brake resistor terminals (only SB, EB, DE and PB units):

Terminal nos.

81, 82

External 24 Volt DC supply:

 

Terminal nos.

35, 36

Voltage range

24 V DC ±15% (max. 37 V DC for 10 sec.)

Max. voltage ripple

2 V DC

Power consumption

15 W - 50 W (50 W for start-up, 20 msec.)

Min. pre-fuse

6 Amp

Reliable galvanic isolation: Full galvanic isolation if the external 24 V DC supply is also of the PELV type.

Cable lengths, cross-sections and connectors:

 

Max. motor cable length, screened cable

150 m

Max. motor cable length, unscreened cable

300 m

Max. motor cable length, screened cable VLT 5011 380-500 V

100 m

Max. motor cable length, screened cable VLT 5011 525-600 V

 

and VLT 5008, normal overload mode, 525-600 V

50 m

Max. brake cable length, screened cable

20 m

Max. loadsharing cable length, screened cable

25 m from frequency converter to DC bar.

Max. cable cross-section for motor, brake and loadsharing, see Electrical data

Max. cable cross-section for 24 V external DC supply

- VLT 5001-5027 200-240 V; VLT 5001-5102 380-500 V; VLT 5001-5062 525-600 V - VLT 5032-5052 200-240 V; VLT 5122-5552 380-500 V; VLT 5042-5602 525-690 V Max. cross-section for control cables

Max. cross-section for serial communication

If UL/cUL is to be complied with, copper cable with temperature class 60/75°C must be used (VLT 5001 - 5062 380 - 500 V, 525 - 600 V and VLT 5001 - 5027 200 - 240 V).

If UL/cUL is to be complied with, copper cable with temperature class 75°C must be used (VLT 5072 - 5552 380 - 500 V, VLT 5032 - 5052 200 - 240 V, VLT 5042 - 5602 525 - 690 V). Connectors are for use of both copper and aluminium cables, unless other is specified.

<![if ! IE]>

<![endif]>Technical data

Accuracy of display readout (parameters 009-012):

Motor current [6] 0-140% load

Max. error: ±2.0% of rated output current

Torque % [7], -100 - 140% load

Max. error: ±5% of rated motor size

Output [8], power HP [9], 0-90% load

Max. error: ±5% of rated output

Control characteristics:

 

Frequency range

0 - 1000 Hz

Resolution on output frequency

±0.003 Hz

MG.52.A3.02 - VLT® is a registered Danfoss trademark

13

 

 

VLT® 5000 Series

System response time

 

3 msec.

Speed, control range (open loop)

 

1:100 of synchro. speed

Speed, control range (closed loop)

 

1:1000 of synchro. speed

Speed, accuracy (open loop)

 

< 1500 rpm: max. error ± 7.5 rpm

Speed, accuracy (closed loop)

 

< 1500 rpm: max. error ± 1.5 rpm

Torque control accuracy (open loop)

0- 150 rpm: max. error ±20% of rated torque

Torque control accuracy (speed feedback)

Max. error ±5% of rated torque

All control characteristics are based on a 4-pole asynchronous motor

Externals:

 

 

Enclosure (dependent on power size)

IP 00, IP 20, IP 21, Nema 1, IP 54

Vibration test

0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)

Max. relative humidity

 

93 % (IEC 68-2-3) for storage/transport

Max. relative humidity

95 % non condensing (IEC 721-3-3; class 3K3) for operation

Aggressive environment (IEC 721 - 3 - 3)

Uncoated class 3C2

Aggressive environment (IEC 721 - 3 - 3)

Coated class 3C3

Ambient temperature IP 20/Nema 1 (high overload torque 160%)

Max. 45°C (24-hour average max. 40°C)

Ambient temperature IP 20/Nema 1 (normal overload torque 110%)

Max. 40°C (24-hour average max. 35°C)

Ambient temperature IP 54 (high overload torque 160%)

Max. 40°C (24-hour average max. 35°C)

Ambient temperature IP 54 (normal overload torque 110%)

Max. 40°C (24-hour average max. 35°C)

Ambient temperature IP 20/54 VLT 5011 500 V

Max. 40°C (24-hour average max. 35°C)

Ambient temperature IP 54 VLT 5042-5602, 525-690 V; and

5122-5552, 380-500 V (high overload torque 160%)

Max. 45°C (24-hour average max. 40°C)

Derating for high ambient temperature, see the Design Guide

 

Min. ambient temperature in full operation

0°C

Min. ambient temperature at reduced performance

-10°C

Temperature during storage/transport

-25 - +65/70°C

Max. altitude above sea level

 

1000 m

Derating for altitude over 1000 m above sealevel, see the Design Guide

EMC standards applied, Emission

EN 61000-6-3, EN 61000-6-4, EN 61800-3, EN 55011

 

EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4

EMC standards applied, Immunity

EN 61000-4-5, EN 61000-4-6, VDE 0160/1990.12

See section on special conditions in the Design Guide

VLT 5001-5062, 525 - 600 V do not comply with EMC or Low Voltage Directives.

IP54 units are not intended for direct outdoor installation. The IP54 rating does not relate to other exposures as sun, icing, wind blown driving rain. Under such circumstances Danfoss recommends to install the units in an enclosure designed for these environmental conditions. Alternatively, an installation at minimum 0.5 m above surface and covered by a shed is recommended

14

MG.52.A3.02 - VLT® is a registered Danfoss trademark

VLT® 5000 Series

VLT 5000 Series protection:

Electronic motor thermal protection against overload.

Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature reaches 90° C for IP 00, IP 20 and Nema 1. For IP 54, the cut-out temperature is 80°C. An overtemperature can only be reset when the temperature of the heat-sink has fallen below 60°C.

For the units mentioned below, the limits are as follows:

-VLT 5122, 380-500 V, cuts out at 75°C and can be reset if the temperature has fallen below 60°C.

-VLT 5152, 380-500 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.

-VLT 5202, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.

-VLT 5252, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.

-VLT 5302, 380-500 V, cuts out at 105°C and can be reset if the temperature has fallen below 75°C.

-VLT 5352-5552, 380-500 V, cut out at 85°C and can be reset if the temperature has fallen below 60°C.

-VLT 5042-5122, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.

-VLT 5152, 525-690 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.

-VLT 5202-5352, 525-690 V, cut out at 100°C and can be reset if the temperature has fallen below 70°C.

-VLT 5402-5602, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.

The frequency converter is protected against short-circuiting on motor terminals U, V, W.

The frequency converter is protected against earth fault on motor terminals U, V, W.

Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage becomes too high or too low.

If a motor phase is missing, the frequency converter cuts out, see parameter 234 Motor phase monitor.

If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.

If a mains phase is missing, the frequency converter will cut out when a load is placed on the motor.

<![if ! IE]>

<![endif]>Technical data

MG.52.A3.02 - VLT® is a registered Danfoss trademark

15

 

 

 

VLT® 5000 Series

 

 

Electrical data

Bookstyle and Compact, Mains supply 3 x 200 -

240 V

 

 

 

 

 

 

 

 

 

 

 

According to international requirements

VLT type

5001

5002

5003

5004

5005

5006

Output current

IVLT,N [A]

3.7

5.4

7.8

10.6

12.5

15.2

 

IVLT, MAX (60 s) [A]

5.9

8.6

12.5

17

20

24.3

Output (240 V)

SVLT,N [kVA]

1.5

2.2

3.2

4.4

5.2

6.3

Typical shaft output

PVLT,N [kW]

0.75

1.1

1.5

2.2

3.0

3.7

Typical shaft output

PVLT,N [HP]

1

1.5

2

3

4

5

Max. cable cross-section to motor,

4/10

4/10

4/10

4/10

4/10

4/10

brake and loadsharing [mm 2 ]/[AWG]2 )

 

 

 

 

 

 

Rated input current

(200 V)IL,N [A]

3.4

4.8

7.1

9.5

11.5

14.5

Max. cable

 

4/10

4/10

4/10

4/10

4/10

4/10

cross-section power [mm2 ]/[AWG] 2 )

 

 

 

 

 

 

Max. pre-fuses

[-]/UL1) [A]

16/10

16/10

16/15

25/20

25/25

35/30

Efficiency3)

 

0.95

0.95

0.95

0.95

0.95

0.95

Weight IP 20 EB Bookstyle

[kg]

7

7

7

9

9

9.5

Weight IP 20 EB Compact [kg]

8

8

8

10

10

10

Weight IP 54 Compact

[kg]

11.5

11.5

11.5

13.5

13.5

13.5

Power loss at

[W]

58

76

95

126

172

194

max. load.

 

 

 

 

 

 

 

Enclosure

 

IP 20/

IP 20/

IP 20/

IP 20/

IP 20/

IP 20/

 

IP54

IP54

IP54

IP54

IP54

IP54

 

 

1.For type of fuse see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

16

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

 

 

VLT® 5000 Series

 

 

Compact, Mains supply 3 x 200 - 240 V

 

 

 

 

 

 

 

According to international requirements

VLT type

 

5008

5011

5016

5022

5027

Normal overload torque (110 %):

 

 

 

 

 

 

Output current

IVLT,N [A]

 

32

46

61.2

73

88

 

IVLT, MAX (60 s)

 

35.2

50.6

67.3

80.3

96.8

 

[A]

 

 

 

 

 

 

 

 

Output (240 V)

SVLT,N [kVA]

 

13.3

19.1

25.4

30.3

36.6

Typical shaft output

PVLT,N [kW]

 

7.5

11

15

18.5

22

Typical shaft output

PVLT,N [HP]

 

10

15

20

25

30

High overload torque (160 %):

 

 

 

 

 

 

Output current

IVLT,N [A]

 

25

32

46

61.2

73

 

IVLT, MAX (60 s)

 

40

51.2

73.6

97.9

116.8

 

[A]

 

 

 

 

 

 

 

 

Output (240 V)

SVLT,N [kVA]

 

10

13

19

25

30

Typical shaft output

PVLT,N [kW]

 

5.5

7.5

11

15

18.5

Typical shaft output

PVLT,N [HP]

 

7.5

10

15

20

25

Max. cable cross-section to motor,

IP 54

16/6

16/6

35/2

35/2

50/0

brake and loadsharing [mm2 /AWG]2) 5)

IP 20

16/6

35/2

35/2

35/2

50/0

Min. cable cross-section to motor, brake and

 

10/8

10/8

10/8

10/8

16/6

loadsharing4) [mm2 /AWG]2)

 

 

 

 

 

 

 

Rated input current

(200 V) IL,N [A]

 

32

46

61

73

88

Max. cable cross-section,

 

IP 54

16/6

16/6

35/2

35/2

50/0

power [mm2 ]/[AWG]2) 5)

 

IP 20

16/6

35/2

35/2

35/2

50/0

Max. pre-fuses

[-]/UL1) [A]

 

50

60

80

125

125

Efficiency3)

 

 

0.95

0.95

0.95

0.95

0.95

Weight IP 20 EB

[kg]

 

21

25

27

34

36

Weight IP 54

[kg]

 

38

40

53

55

56

Power loss at max. load.

 

 

 

 

 

 

 

- high overload torque

[W]

 

340

426

626

833

994

(160 %)

 

 

 

 

 

 

 

 

 

- normal overload torque

[W]

 

426

545

783

1042

1243

(110 %)

 

 

 

 

 

 

 

 

 

Enclosure

 

 

IP 20/

IP 20/

IP 20/

IP 20/

IP 20/

 

 

IP 54

IP 54

IP 54

IP 54

IP 54

 

 

 

1. For type of fuse see section Fuses

2. American Wire Gauge.

3. Measured using 30 m screened motor cables at rated load and rated frequency.

4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.

5. Aluminium cables with cross-section above 35 mm2 must be connected by use of a AI-Cu connector. dataTechnical

MG.52.A3.02 - VLT® is a registered Danfoss trademark

17

 

VLT® 5000 Series

 

Compact, Mains supply 3 x 200 - 240 V

 

 

 

 

According to international requirements

VLT type

5032

5042

5052

Normal overload torque (110 %):

 

 

 

 

Output current

IVLT,N [A] (200-230 V) 115

143

170

 

IVLT, MAX (60 s) [A] (200-230 V)

127

158

187

 

IVLT,N [A] (231-240 V)

104

130

154

 

IVLT, MAX (60 s) [A] (231-240 V)

115

143

170

Output

SVLT,N [kVA] (208 V)

41

52

61

 

SVLT,N [kVA] (230 V)

46

57

68

 

SVLT,N [kVA] (240 V)

43

54

64

Typical shaft output

[HP] (208 V)

40

50

60

Typical shaft output

[kW] (230 V)

30

37

45

High overload torque (160 %):

 

 

 

 

Output current

IVLT,N [A] (200-230 V)

88

115

143

 

IVLT, MAX [A] (200-230 V)

132

173

215

 

IVLT,N [A] (231-240 V)

80

104

130

 

IVLT, MAX [A] (231-240 V)

120

285

195

Output

SVLT,N [kVA] (208 V)

32

41

52

 

SVLT,N [kVA] (230 V)

35

46

57

 

SVLT,N [kVA] (240 V)

33

43

54

Typical shaft output

[HP] (208 V)

30

40

50

 

[kW] (230 V)

22

30

37

Max. cable cross-section to motor

[mm2 ]4,6

 

120

 

and loadsharing

[AWG]2,4,6

 

300 mcm

 

Max. cable cross-section to brake

[mm2 ]4,6

 

25

 

[AWG]2,4,6

 

4

 

 

 

 

Normal overload torque (110 %):

 

 

 

 

Rated input current

IL,N [A] (230 V) 101.3

126.6

149.9

Normal overload torque (150 %):

 

 

 

 

Rated input current

IL,N [A] (230 V)

77,9

101,3

126,6

Max. cable cross-section

[mm2]4,6

 

120

 

power supply

[AWG]2,4,6

 

300 mcm

 

Min. cable cross-section to motor,

[mm2]4,6

 

6

 

power

[AWG]2,4,6

 

8

 

supply, brake and loadsharing

 

 

 

 

Max. pre-fuses (mains) [-]/UL

[A]1

150/15

200/200

250/250

 

 

0

 

 

Efficiency3

 

 

0,96-0,97

 

Power loss

Normal overload [W]

1089

1361

1612

 

High overload [W]

838

1089

1361

Weight

IP 00 [kg]

101

101

101

Weight

IP 20 Nema1 [kg]

101

101

101

Weight

IP 54 Nema12 [kg]

104

104

104

Enclosure

IP 00 / Nema 1 (IP 20) / IP 54

 

1.For type of fuse see section Fuses

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Min. cable cross-section is the minimum allowed cross-section. Always comply with national and local regulations on min. cable cross-section.

5.Weight without shipping container.

6.Connection stud: M8 Brake: M6.

18

MG.52.A3.02 - VLT® is a registered Danfoss trademark

VLT® 5000 Series

Bookstyle and Compact, Mains supply 3 x 380 - 500 V

According to international requirements

VLT type

5001

5002

5003

5004

Output current

IVLT,N [A] (380-440 V)

2.2

2.8

4.1

5.6

 

IVLT, MAX (60 s) [A] (380-440 V)

3.5

4.5

6.5

9

 

IVLT,N [A] (441-500 V)

1.9

2.6

3.4

4.8

 

IVLT, MAX (60 s) [A] (441-500 V)

3

4.2

5.5

7.7

Output

SVLT,N [kVA] (380-440 V)

1.7

2.1

3.1

4.3

 

SVLT,N [kVA] (441-500 V)

1.6

2.3

2.9

4.2

Typical shaft output

PVLT,N [kW]

0.75

1.1

1.5

2.2

Typical shaft output

PVLT,N [HP]

1

1.5

2

3

Max. cable cross-section to motor,

4/10

4/10

4/10

4/10

brake and loadsharing [mm2 ]/[AWG]2 )

 

 

 

 

Rated input current

IL,N [A] (380 V)

2.3

2.6

3.8

5.3

 

IL,N [A] (460 V)

1.9

2.5

3.4

4.8

Max. cable cross-section, power [mm2 ]/[AWG]2)

4/10

4/10

4/10

4/10

Max. pre-fuses [-]/UL1) [A]

 

16/6

16/6

16/10

16/10

Efficiency 3)

 

0.96

0.96

0.96

0.96

Weight IP 20 EB Bookstyle [kg]

 

7

7

7

7.5

Weight IP 20 EB Compact [kg]

 

8

8

8

8.5

Weight IP 54 Compact [kg]

 

11.5

11.5

11.5

12

Power loss at max. load

[W]

55

67

92

110

Enclosure

 

IP 20/

IP 20/

IP 20/

IP 20/

 

IP 54

IP 54

IP 54

IP 54

 

 

1.For type of fuse see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

<![if ! IE]>

<![endif]>Technical data

MG.52.A3.02 - VLT® is a registered Danfoss trademark

19

VLT® 5000 Series

Bookstyle and Compact, Mains supply 3 x 380 - 500

V

According to international requirements

VLT type

5005

5006

5008

5011

Output current

IVLT,N [A] (380-440 V)

7.2

10

13

16

 

IVLT, MAX (60 s) [A] (380-440 V)

11.5

16

20.8

25.6

 

IVLT,N [A] (441-500 V)

6.3

8.2

11

14.5

 

IVLT, MAX (60 s) [A] (441-500 V)

10.1

13.1

17.6

23.2

Output

SVLT,N [kVA] (380-440 V)

5.5

7.6

9.9

12.2

 

SVLT,N [kVA] (441-500 V)

5.5

7.1

9.5

12.6

Typical shaft output

PVLT,N [kW]

3.0

4.0

5.5

7.5

Typical shaft output

PVLT,N [HP]

4

5

7.5

10

Max. cable cross-section to motor,

4/10

4/10

4/10

4/10

brake and loadsharing [mm2 ]/[AWG]2 )

 

 

 

 

Rated input current

IL,N [A] (380 V)

7

9.1

12.2

15.0

 

IL,N [A] (460 V)

6

8.3

10.6

14.0

Max. cable cross-section power [mm2 ]/[AWG]2)

4/10

4/10

4/10

4/10

Max. pre-fuses [-]/UL1) [A]

 

16/15

25/20

25/25

35/30

Efficiency 3)

 

0.96

0.96

0.96

0.96

Weight IP 20 EB Bookstyle [kg]

 

7.5

9.5

9.5

9.5

Weight IP 20 EB Compact [kg]

 

8.5

10.5

10.5

10.5

Weight IP 54 EB Compact [kg]

 

12

14

14

14

Power loss at max. load.

[W]

139

198

250

295

Enclosure

 

IP 20/

IP 20/

IP 20/

IP 20/

 

IP 54

IP 54

IP 54

IP 54

 

 

1.For type of fuse see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

20

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

VLT® 5000 Series

 

 

Compact, Mains supply 3 x 380 - 500 V

 

 

 

 

 

According to international requirements

VLT type

 

5016

5022

5027

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

 

32

37.5

44

 

IVLT, MAX (60 s) [A] (380-440 V)

 

35.2

41.3

48.4

 

IVLT,N [A] (441-500 V)

 

27.9

34

41.4

 

IVLT, MAX (60 s) [A] (441-500 V)

 

30.7

37.4

45.5

Output

SVLT,N [kVA] (380-440 V)

 

24.4

28.6

33.5

 

SVLT,N [kVA] (441-500 V)

 

24.2

29.4

35.8

Typical shaft output

PVLT,N [kW]

 

15

18.5

22

Typical shaft output

PVLT,N [HP]

 

20

25

30

High overload torque (160 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

 

24

32

37.5

 

IVLT, MAX (60 s) [A] (380-440 V)

 

38.4

51.2

60

 

IVLT,N [A] (441-500 V)

 

21.7

27.9

34

 

IVLT, MAX (60 s) [A] (441-500 V)

 

34.7

44.6

54.4

Output

SVLT,N [kVA] (380-440 V)

 

18.3

24.4

28.6

 

SVLT,N [kVA] (441-500 V)

 

18.8

24.2

29.4

Typical shaft output

PVLT,N [kW]

 

11

15

18.5

Typical shaft output

PVLT,N [HP]

 

15

20

25

Max. cable cross-section to motor,

 

IP 54

16/6

16/6

16/6

brake and loadsharing [mm2 ]/[AWG]2)

IP 20

16/6

16/6

35/2

Min. cable cross-section to motor,

 

 

 

 

 

brake and loadsharing [mm2]/[AWG]2) 4)

 

10/8

10/8

10/8

Rated input current

IL,N [A] (380 V)

 

32

37.5

44

 

IL,N [A] (460 V)

 

27.6

34

41

Max. cable cross-section,

 

IP 54

16/6

16/6

16/6

power [mm 2 ]/[AWG]

 

IP 20

16/6

16/6

35/2

Max. pre-fuses

[-]/UL1) [A]

 

63/40

63/50

63/60

Efficiency3)

 

 

0.96

0.96

0.96

Weight IP 20 EB

[kg]

 

21

22

27

Weight IP 54

[kg]

 

41

41

42

Power loss at max. load.

 

 

 

 

 

- high overload torque (160 %)

[W]

 

419

559

655

- normal overload torque (110 %)

[W]

 

559

655

768

Enclosure

 

 

IP 20/

IP 20/

IP 20/

 

 

IP 54

IP 54

IP 54

 

 

 

1. For type of fuse see section Fuses.

2. American Wire Gauge.

3. Measured using 30 m screened motor cables at rated load and rated frequency.

4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.

<![if ! IE]>

<![endif]>dataTechnical

MG.52.A3.02 - VLT® is a registered Danfoss trademark

21

 

VLT® 5000 Series

 

 

Compact, Mains supply 3 x 380 - 500 V

 

 

 

 

 

According to international requirements

VLT type

 

5032

5042

5052

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

 

61

73

90

IVLT, MAX (60 s) [A] (380-440 V)

 

67.1

80.3

99

 

IVLT,N [A] (441-500 V)

 

54

65

78

IVLT, MAX (60 s) [A] (441-500 V)

 

59.4

71.5

85.8

Output

SVLT,N [kVA] (380-440 V)

 

46.5

55.6

68.6

 

SVLT,N [kVA] (441-500 V)

 

46.8

56.3

67.5

Typical shaft output

PVLT,N [kW]

 

30

37

45

Typical shaft output

PVLT,N [HP]

 

40

50

60

High overload torque (160 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

 

44

61

73

IVLT, MAX (60 s) [A] (380-440 V)

 

70.4

97.6

116.8

 

IVLT,N [A] (441-500 V)

 

41.4

54

65

IVLT, MAX (60 s) [A] (441-500 V)

 

66.2

86

104

Output

SVLT,N [kVA] (380-440 V)

 

33.5

46.5

55.6

 

SVLT,N [kVA] (441-500 V)

 

35.9

46.8

56.3

Typical shaft output

PVLT,N [kW]

 

22

30

37

Typical shaft output

PVLT,N [HP]

 

30

40

50

Max. cable cross-section to motor,

 

IP 54

35/2

35/2

50/0

brake and loadsharing [mm2 ]/[AWG]2) 5)

IP20

35/2

35/2

50/0

Min. cable cross-section to motor,

 

 

 

 

 

brake and loadsharing [mm2 ]/[AWG]2) 4)

 

10/8

10/8

16/6

Rated input current

IL,N [A] (380 V)

 

60

72

89

 

IL,N [A] (460 V)

 

53

64

77

Max. cable cross-section

 

IP 54

35/2

35/2

50/0

power[mm 2 ]/[AWG]2) 5)

 

IP 20

35/2

35/2

50/0

Max. pre-fuses

[-]/UL1) [A]

 

80/80

100/100

125/125

Efficiency3)

 

 

0.96

0.96

0.96

Weight IP 20 EB

[kg]

 

28

41

42

Weight IP 54

[kg]

 

54

56

56

Power loss at max. load.

 

 

 

 

 

- high overload torque (160 %)

[W]

 

768

1065

1275

- normal overload torque (110 %)

[W]

 

1065

1275

1571

Enclosure

 

 

IP 20/

IP 20/

IP 20/

 

 

IP 54

IP 54

IP 54

 

 

 

1.For type of fuse see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.

5.Aluminium cables with cross-section above 35 mm2 must be connected by use of a AI-Cu connector.

22

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

VLT® 5000 Series

 

 

Compact, Mains supply 3 x 380 - 500 V

 

 

 

 

 

According to international requirements

VLT type

 

5062

5072

5102

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

 

106

147

177

 

IVLT, MAX (60 s) [A] (380-440 V)

 

117

162

195

 

IVLT,N [A] (441-500 V)

 

106

130

160

 

IVLT, MAX (60 s) [A] (441-500 V)

 

117

143

176

Output

SVLT,N [kVA] (380-440 V)

 

80.8

102

123

 

SVLT,N [kVA] (441-500 V)

 

91.8

113

139

Typical shaft output

PVLT,N [kW] (400 V)

 

55

75

90

 

PVLT,N [HP] (460 V)

 

75

100

125

 

PVLT,N [kW] (500 V)

 

75

90

110

High overload torque (160 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

 

90

106

147

 

IVLT, MAX (60 s) [A] (380-440 V)

 

135

159

221

 

IVLT,N [A] (441-500 V)

 

80

106

130

 

IVLT, MAX (60 s) [A] (441-500 V)

 

120

159

195

Output

SVLT,N [kVA] (380-440 V)

 

68.6

73.0

102

 

SVLT,N [kVA] (441-500 V)

 

69.3

92.0

113

Typical shaft output

PVLT,N [kW] (400 V)

 

45

55

75

 

PVLT,N [HP] (460 V)

 

60

75

100

 

PVLT,N [kW] (500 V)

 

55

75

90

Max. cable cross-section to motor,

IP 54

50/05)

150/300

150/300

mcm6)

mcm6)

 

 

 

 

brake and loadsharing [mm2 ]/[AWG]2)

IP20

50/05)

120/250

120/250

mcm5)

mcm5)

 

 

 

 

Min. cable cross-section to motor,

 

 

 

 

brake and loadsharing [mm2 ]/[AWG]4)

 

16/6

25/4

25/4

Rated input current

IL,N [A] (380 V)

 

104

145

174

 

IL,N [A] (460 V)

 

104

128

158

Max. cable cross-section

 

IP 54

50/05)

150/300

150/300

 

mcm

mcm

 

 

 

 

power[mm 2 ]/[AWG]2)

 

IP 20

50/05)

120/250

120/250

 

mcm5)

mcm5)

 

 

 

 

Max. pre-fuses

[-]/UL1) [A]

 

160/150

225/225

250/250

Efficiency3)

 

 

>0.97

>0.97

>0.97

Weight IP 20 EB

[kg]

 

43

54

54

Weight IP 54

[kg]

 

60

77

77

Power loss at max. load.

 

 

 

 

 

- high overload torque (160 %)

[W]

 

1122

1058

1467

- normal overload torque (110 %)

[W]

 

1322

1467

1766

Enclosure

 

 

IP20/

IP20/

IP20/

 

 

IP 54

IP 54

IP 54

 

 

 

1.For type of fuse see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.

5.Aluminium cables with cross-section above 35 mm2 must be connected by use of a AI-Cu connector.

used.

6. Brake and loadsharing: 95 mm2 / AWG 3/0

<![if ! IE]>

<![endif]>Technical data

MG.52.A3.02 - VLT® is a registered Danfoss trademark

23

 

VLT® 5000 Series

 

 

Compact, Mains supply 3 x 380 - 500 V

 

 

 

 

 

 

According to international requirements

VLT type

5122

5152

5202

5252

5302

Normal overload current (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

212

260

315

395

480

 

IVLT, MAX (60 s) [A] (380-440

233

286

347

434

528

 

V)

 

 

 

 

 

 

IVLT,N [A] (441-500 V)

190

240

302

361

443

 

IVLT, MAX (60 s) [A] (441-500

209

264

332

397

487

 

V)

 

 

 

 

 

Output

SVLT,N [kVA] (400 V)

147

180

218

274

333

 

SVLT,N [kVA] (460 V)

151

191

241

288

353

 

SVLT,N [kVA] (500 V)

165

208

262

313

384

Typical shaft output

[kW] (400 V)

110

132

160

200

250

 

[HP] (460 V)

150

200

250

300

350

 

[kW] (500 V)

132

160

200

250

315

High overload torque (160 %):

 

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

177

212

260

315

395

 

IVLT, MAX (60 s) [A] (380-440

266

318

390

473

593

 

V)

 

 

 

 

 

 

IVLT,N [A] (441-500 V)

160

190

240

302

361

 

IVLT, MAX (60 s) [A] (441-500

240

285

360

453

542

 

V)

 

 

 

 

 

Output

SVLT,N [kVA] (400 V)

123

147

180

218

274

 

SVLT,N [kVA] (460 V)

127

151

191

241

288

 

SVLT,N [kVA] (500 V)

139

165

208

262

313

Typical shaft output

[kW] (400 V)

90

110

132

160

200

 

[HP] (460 V)

125

150

200

250

300

 

[kW] (500 V)

110

132

160

200

250

Max. cable cross-section to

[mm2]4,6

 

2 x 70

 

2 x 185

 

motor

[AWG]2,4,6

2 x 2/0

 

2 x 350 mcm

Max. cable cross-section to

[mm2]4,6

 

2 x 70

 

2 x 185

 

loadsharing and brake

[AWG]2,4,6

2 x 2/0

 

2 x 350 mcm

Normal overload current (110 %):

 

 

 

 

 

Rated input current

IL,N [A] (380-440 V)

208

256

317

385

467

 

IL,N [A] (441-500 V)

185

236

304

356

431

High overload torque (160 %):

 

 

 

 

 

Rated input current

IL,N [A] (380-440 V)

174

206

256

318

389

 

IL,N [A] (441-500 V)

158

185

236

304

356

Max. cable cross-section

[mm2]4,6

 

2 x 70

 

2 x 185

 

power supply

[AWG]2,4,6

2 x 2/0

 

2 x 350 mcm

Max. pre-fuses (mains) [-]/

1

300/

350/

450/

500/

630/

UL

[A]

300

350

400

500

600

Efficiency3

 

 

 

0,98

 

 

Power loss

Normal overload [W]

2619

3309

4163

4977

6107

 

High overload [W]

2206

2619

3309

4163

4977

Weight

IP 00 [kg]

82

91

112

123

138

Weight

IP 21/Nema1 [kg]

96

104

125

136

151

Weight

IP 54/Nema12 [kg]

96

104

125

136

151

Enclosure

IP 00, IP 21/Nema 1 and IP 54/Nema12

 

 

1.For type of fuse see section Fuses

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.

5.Weight without shipping container.

6.Connection bolt power supply and motor: M10; Brake and loadsharing: M8

24

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

 

VLT® 5000 Series

 

Compact, Mains supply 3 x 380 - 500 V

 

 

 

 

 

According to international requirements

VLT type

5352

5452

5502

5552

Normal overload current (110 %):

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

600

658

745

800

 

IVLT, MAX (60 s) [A] (380-440

660

724

820

880

 

V)

 

 

 

 

 

IVLT,N [A] (441-500 V)

540

590

678

730

 

IVLT, MAX (60 s) [A] (441-500

594

649

746

803

 

V)

 

 

 

 

Output

SVLT,N [kVA] (400 V)

416

456

516

554

 

SVLT,N [kVA] (460 V)

430

470

540

582

 

SVLT,N [kVA] (500 V)

468

511

587

632

Typical shaft output

[kW] (400 V)

315

355

400

450

 

[HP] (460 V)

450

500

550/600

600

 

[kW] (500 V)

355

400

500

530

High overload torque (160 %):

 

 

 

 

Output current

IVLT,N [A] (380-440 V)

480

600

658

695

 

IVLT, MAX (60 s) [A] (380-440

720

900

987

1042

 

V)

 

 

 

 

 

IVLT,N [A] (441-500 V)

443

540

590

678

 

IVLT, MAX (60 s) [A] (441-500

665

810

885

1017

 

V)

 

 

 

 

Output

SVLT,N [kVA] (400 V)

333

416

456

482

 

SVLT,N [kVA] (460 V)

353

430

470

540

 

SVLT,N [kVA] (500 V)

384

468

511

587

Typical shaft output

[kW] (400 V)

250

315

355

400

 

[HP] (460 V)

350

450

500

550

 

[kW] (500 V)

315

355

400

500

Max. cable cross-section

[mm2]4,6

 

 

4x240

 

to motor and loadsharing

[AWG]2,4,6

 

4x500 mcm

 

Max. cable cross-section

[mm2]4,6

 

 

2x185

 

to brake

[AWG]2,4,6

 

2x350 mcm

 

Normal overload current (110 %):

 

 

 

 

Rated input current

IL,N [A] (380-440 V)

590

647

733

787

 

IL,N [A] (441-500 V)

531

580

667

718

High overload torque (160 %):

 

 

 

 

Rated input current

IL,N [A] (380-440 V)

472

590

647

684

 

IL,N [A] (441-500 V)

436

531

580

667

Max. cable cross-section

[mm2]4,6

 

 

4x240

 

power supply

[AWG]2,4,6

 

4x500 mcm

 

Max. pre-fuses (mains)

[A]1

700/700

900/900

900/900

900/900

[-]/UL

 

 

 

 

 

Efficiency3

 

 

 

0,98

 

Power loss

Normal overload [W]

7630

7701

8879

9428

 

High overload [W]

6005

6960

7691

7964

Weight

IP 00 [kg]

221

234

236

277

Weight

IP 21/Nema1 [kg]

263

270

272

313

Weight

IP 54/Nema12 [kg]

263

270

272

313

Enclosure

IP 00, IP 21/Nema 1 and IP 54/Nema12

 

1.For type of fuse see section Fuses

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.

5.Weight without shipping container.

6.Connection bolt power supply, motor and loadsharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)

<![if ! IE]>

<![endif]>Technical data

MG.52.A3.02 - VLT® is a registered Danfoss trademark

25

 

VLT® 5000 Series

 

Compact, Mains supply 3 x 525 - 600 V

 

 

 

 

 

According to international requirements

VLT type

5001

5002

5003

5004

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (550 V)

2.6

2.9

4.1

5.2

 

IVLT, MAX (60 s) [A] (550 V)

2.9

3.2

4.5

5.7

 

IVLT,N [A] (575 V)

2.4

2.7

3.9

4.9

 

IVLT, MAX (60 s) [A] (575 V)

2.6

3.0

4.3

5.4

Output

SVLT,N [kVA] (550 V)

2.5

2.8

3.9

5.0

 

SVLT,N [kVA] (575 V)

2.4

2.7

3.9

4.9

Typical shaft output

PVLT,N [kW]

1.1

1.5

2.2

3

Typical shaft output

PVLT,N [HP]

1.5

2

3

4

Highl overload torque (160%):

 

 

 

 

 

Output current

IVLT,N [A] (550 V)

1.8

2.6

2.9

4.1

 

IVLT, MAX (60 s) [A] (550 V)

2.9

4.2

4.6

6.6

 

IVLT,N [A] (575 V)

1.7

2.4

2.7

3.9

 

IVLT, MAX (60 s) [A] (575 V)

2.7

3.8

4.3

6.2

Output

SVLT,N [kVA] (550 V)

1.7

2.5

2.8

3.9

 

SVLT,N [kVA] (575 V)

1.7

2.4

2.7

3.9

Typical shaft output

PVLT,N [kW]

0.75

1.1

1.5

2.2

Typical shaft output

PVLT,N [HP]

1

1.5

2

3

Max. cable cross-section to motor,

4/10

4/10

4/10

4/10

brake and loadsharing [mm2 ]/[AWG]2)

 

 

 

 

Normal overload torque (110 %):

 

 

 

 

Rated input current

IL,N [A] (550 V)

2.5

2.8

4.0

5.1

 

IL,N [A] (600 V)

2.2

2.5

3.6

4.6

High overload torque ( 160 %):

 

 

 

 

 

Rated input current

IL,N [A] (550 V)

1.8

2.5

2.8

4.0

 

IL,N [A] (600 V)

1.6

2.2

2.5

3.6

Max. cable cross-section, power [mm2 ]/[AWG]2)

4/10

4/10

4/10

4/10

Max. pre-fuses

[-]/UL1) [A]

3

4

5

6

Efficiency 3)

 

0.96

0.96

0.96

0.96

Weight IP 20 EB

[kg]

10.5

10.5

10.5

10.5

Power loss at max.

[W]

63

71

102

129

load.

 

 

 

 

 

Enclosure

 

 

IP 20 / Nema 1

 

1.For type of fuses see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

26

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

VLT® 5000 Series

 

Compact, Mains supply 3 x 525 - 600 V

 

 

 

 

 

According to international requirements

VLT type

5005

5006

5008

5011

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (550 V)

6.4

9.5

11.5

11.5

 

IVLT, MAX (60 s) [A] (550 V)

7.0

10.5

12.7

12.7

 

IVLT,N [A] (575 V)

6.1

9.0

11.0

11.0

 

IVLT, MAX (60 s) [A] (575 V)

6.7

9.9

12.1

12.1

Output

SVLT,N [kVA] (550 V)

6.1

9.0

11.0

11.0

 

SVLT,N [kVA] (575 V)

6.1

9.0

11.0

11.0

Typical shaft output

PVLT,N [kW]

4

5.5

7.5

7.5

Typical shaft output

PVLT,N [HP]

5

7.5

10.0

10.0

Highl overload torque (160%):

 

 

 

 

 

Output current

IVLT,N [A] (550 V)

5.2

6.4

9.5

11.5

 

IVLT, MAX (60 s) [A] (550 V)

8.3

10.2

15.2

18.4

 

IVLT,N [A] (575 V)

4.9

6.1

9.0

11.0

 

IVLT, MAX (60 s) [A] (575 V)

7.8

9.8

14.4

17.6

Output

SVLT,N [kVA] (550 V)

5.0

6.1

9.0

11.0

 

SVLT,N [kVA] (575 V)

4.9

6.1

9.0

11.0

Typical shaft output

PVLT,N [kW]

3

4

5.5

7.5

Typical shaft output

PVLT,N [HP]

4

5

7.5

10

Max. cable cross-section to motor,

4/10

4/10

4/10

4/10

brake and loadsharing [mm2 ]/[AWG]2)

 

 

 

 

Normal overload torque (110 %):

 

 

 

 

Rated input current

IL,N [A] (550 V)

6.2

9.2

11.2

11.2

 

IL,N [A] (600 V)

5.7

8.4

10.3

10.3

High overload torque ( 160 %):

 

 

 

 

 

Rated input current

IL,N [A] (550 V)

5.1

6.2

9.2

11.2

 

IL,N [A] (600 V)

4.6

5.7

8.4

10.3

Max. cable cross-section, power [mm2 ]/[AWG]2)

4/10

4/10

4/10

4/10

Max. pre-fuses

[-]/UL1) [A]

8

10

15

20

Efficiency 3)

 

0.96

0.96

0.96

0.96

Weight IP 20 EB

[kg]

10.5

10.5

10.5

10.5

Power loss at max.

[W]

160

236

288

288

load.

 

 

 

 

 

Enclosure

 

IP 20 / Nema 1

 

 

1.For type of fuses see section Fuses.

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

<![if ! IE]>

<![endif]>Technical data

MG.52.A3.02 - VLT® is a registered Danfoss trademark

27

 

VLT® 5000 Series

 

Compact, Mains supply 3 x 525 - 600 V

 

 

 

 

According to international requirements

VLT type

5016

5022

5027

Normal overload torque (110 %):

 

 

 

 

Output current

IVLT,N [A] (550 V)

23

28

34

 

IVLT, MAX (60 s) [A] (550 V)

25

31

37

 

IVLT,N [A] (575 V)

22

27

32

 

IVLT, MAX (60 s) [A] (575 V)

24

30

35

Output

SVLT,N [kVA] (550 V)

22

27

32

 

SVLT,N [kVA] (575 V)

22

27

32

Typical shaft output

PVLT,N [kW]

15

18.5

22

Typical shaft output

PVLT,N [HP]

20

25

30

High overload torque (160 %):

 

 

 

 

Output current

IVLT,N [A] (550 V)

18

23

28

 

IVLT, MAX (60 s) [A] (550 V)

29

37

45

 

IVLT,N [A] (575 V)

17

22

27

 

IVLT, MAX (60 s) [A] (575 V)

27

35

43

Output

SVLT,N [kVA] (550 V)

17

22

27

 

SVLT,N [kVA] (575 V)

17

22

27

Typical shaft output

PVLT,N [kW]

11

15

18.5

Typical shaft output

PVLT,N [HP]

15

20

25

Max. cable cross-section to motor,

 

16

16

35

brake and loadsharing [mm2 ]/[AWG]2)

 

6

6

2

Min. cable cross-section to motor,

 

0.5

0.5

10

brake and loadsharing [mm2]/[AWG]4)

 

20

20

8

Normal overload torque (110 %):

 

 

 

 

Rated input current

IL,N [A] (550 V)

22

27

33

 

IL,N [A] (600 V)

21

25

30

High overload torque (160 %):

 

 

 

 

Rated input current

IL,N [A] (550 V)

18

22

27

 

IL,N [A] (600 V)

16

21

25

Max. cable cross-section,

 

16

16

35

power [mm 2 ]/[AWG]2)

 

6

6

2

Max. pre-fuses

[-]/UL1) [A]

30

35

45

Efficiency3)

 

0.96

0.96

0.96

Weight IP 20 EB

[kg]

23

23

30

Power loss at max. load

[W]

576

707

838

Enclosure

 

 

IP 20 / Nema 1

1.For type of fuse see section Fuses

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.

28

MG.52.A3.02 - VLT® is a registered Danfoss trademark

 

VLT® 5000 Series

 

 

Compact, Mains supply 3 x 525 - 600 V

 

 

 

 

 

According to international requirements

VLT type

5032

5042

5052

5062

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (550 V)

43

54

65

81

 

IVLT, MAX (60 s) [A] (550 V)

47

59

72

89

 

IVLT,N [A] (575 V)

41

52

62

77

 

IVLT, MAX (60 s) [A] (575 V)

45

57

68

85

Output

SVLT,N [kVA] (550 V)

41

51

62

77

 

SVLT,N [kVA] (575 V)

41

52

62

77

Typical shaft output

PVLT,N [kW]

30

37

45

55

Typical shaft output

PVLT,N [HP]

40

50

60

75

High overload torque (160 %):

 

 

 

 

 

Output current

IVLT,N [A] (550 V)

34

43

54

65

 

IVLT, MAX (60 s) [A] (550 V)

54

69

86

104

 

IVLT,N [A] (575 V)

32

41

52

62

 

IVLT, MAX (60 s) [A] (575 V)

51

66

83

99

Output

SVLT,N [kVA] (550 V)

32

41

51

62

 

SVLT,N [kVA] (575 V)

32

41

52

62

Typical shaft output

PVLT,N [kW]

22

30

37

45

Typical shaft output

PVLT,N [HP]

30

40

50

60

Max. cable cross-section to motor,

35

50

50

50

brake and loadsharing [mm2 ]/[AWG]2) 5)

2

1/0

1/0

1/0

Min. cable cross-section to motor,

10

16

16

16

brake and loadsharing [mm2 ]/[AWG]4)

8

6

6

6

Normal overload torque (110 %):

 

 

 

 

Rated input current

IL,N [A] (550 V)

42

53

63

79

 

IL,N [A] (600 V)

38

49

58

72

High overload torque (160 %):

 

 

 

 

 

Rated input current

IL,N [A] (550 V)

33

42

53

63

 

IL,N [A] (600 V)

30

38

49

58

Max. cable cross-section

 

35

50

50

50

power[mm 2 ]/[AWG]2) 5)

 

2

1/0

1/0

1/0

Max. pre-fuses

[-]/UL1) [A]

60

75

90

100

Efficiency3)

 

0.96

0.96

0.96

0.96

Weight IP 20 EB

[kg]

30

48

48

48

Power loss at max. load

[W]

1074

1362

1624

2016

 

Enclosure

IP 20 / Nema 1

1.

For type of fuse see section Fuses

 

2.

American Wire Gauge.

 

3.

Measured using 30 m screened motor cables at rated load and rated frequency.

 

4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply

with national and local regulations on min. cable cross-section. data 5. Aluminium cables with cross-section above 35 mm2 must be connected by use of a AI-Cu connector. Technical

MG.52.A3.02 - VLT® is a registered Danfoss trademark

29

 

VLT® 5000 Series

 

 

Mains supply 3 x 525 - 690 V

 

 

 

 

 

 

According to international requirements

VLT type

5042

5052

5062

5072

5102

Normal overload torque (110 %):

 

 

 

 

 

Output current

IVLT,N [A] (525-550 V)

56

76

90

113

137

 

IVLT, MAX (60 s) [A] (525-550

62

84

99

124

151

 

V)

 

 

 

 

 

 

IVLT,N [A] (551-690 V)

54

73

86

108

131

 

IVLT, MAX (60 s) [A] (551-690

59

80

95

119

144

 

V)

 

 

 

 

 

Output

SVLT,N [kVA] (550 V)

53

72

86

108

131

 

SVLT,N [kVA] (575 V)

54

73

86

108

130

 

SVLT,N [kVA] (690 V)

65

87

103

129

157

Typical shaft output

[kW] (550 V)

37

45

55

75

90

 

[HP] (575 V)

50

60

75

100

125

 

[kW] (690 V)

45

55

75

90

110

High overload torque (160 %):

 

 

 

 

 

Output current

IVLT,N [A] (525-550 V)

48

56

76

90

113

 

IVLT, MAX (60 s) [A] (525-550

77

90

122

135

170

 

V)

 

 

 

 

 

 

IVLT,N [A] (551-690 V)

46

54

73

86

108

 

IVLT, MAX (60 s) [A] (551-690

74

86

117

129

162

 

V)

 

 

 

 

 

Output

SVLT,N [kVA] (550 V)

46

53

72

86

108

 

SVLT,N [kVA] (575 V)

46

54

73

86

108

 

SVLT,N [kVA] (690 V)

55

65

87

103

129

Typical shaft output

[kW] (550 V)

30

37

45

55

75

 

[HP] (575 V)

40

50

60

75

100

 

[kW] (690 V)

37

45

55

75

90

Max. cable cross-section

[mm2]4,6

 

 

2 x 70

 

 

to motor

[AWG]2,4,6

 

 

2 x 2/0

 

 

Max. cable cross-section

[mm2]4,6

 

 

2 x 70

 

 

to loadsharing and brake

[AWG]2,4,6

 

 

2 x 2/0

 

 

Normal overload torque (110 %):

 

 

 

 

 

Rated input current

IL,N [A] (550 V)

60

77

89

110

130

 

IL,N [A] (575 V)

58

74

85

106

124

 

IL,N [A] (690 V)

58

77

87

109

128

High overload torque (160 %):

 

 

 

 

 

Rated input current

IL,N [A] (550 V)

53

60

77

89

110

 

IL,N [A] (575 V)

51

58

74

85

106

 

IL,N [A] (690 V)

50

58

77

87

109

Max. cable cross-section

[mm2]4,6

 

 

2 x 70

 

 

power supply

[AWG]2,4,6

 

 

2 x 2/0

 

 

Max. pre-fuses (mains) [-]/

[A]1

125

160

200

200

250

UL

 

 

 

 

 

 

Efficiency3

 

0.97

0.97

0.98

0.98

0.98

Power loss

Normal overload [W]

1458

1717

1913

2262

2662

 

High overload [W]

1355

1459

1721

1913

2264

Weight

IP 00 [kg]

 

 

82

 

 

Weight

IP 21/Nema1 [kg]

 

 

96

 

 

Weight

IP 54/Nema12 [kg]

 

 

96

 

 

Enclosure

IP 00, IP 21/Nema 1 and IP 54/Nema12

 

 

1.For type of fuse see section Fuses

2.American Wire Gauge.

3.Measured using 30 m screened motor cables at rated load and rated frequency.

4.Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.

5.Weight without shipping container.

6.Connection bolt power supply and motor: M10; Brake and loadsharing: M8

30

MG.52.A3.02 - VLT® is a registered Danfoss trademark

Loading...
+ 162 hidden pages