Danfoss VLT 5000 Operating guide

Contents
VLT® 5000 Series
Safety
Safety regulations 4 Warning against unintended start 5 Installation of mechanical brake 5
Quick Setup
Introduction
Available literature 9
Technical data
Installation
3
6
9
10
38
Operation of the frequency converter
MG.52.A3.02 - VLT® is a registered Danfoss trademark 1
65
VLT® 5000 Series
Application configuration
Special functions
Programming
72
77
96
Miscellaneous
Trouble-shooting 166 Display - Status messages 167 Warnings and alarms 170 Warnings 171
Index
166
190
2 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
VLT 5000 Series
Operating Instructions Software version: 3.9x
These Operating Instructions can be used for all VLT 5000 Series frequency converters with software version
3.9x. The software version number can be seen from parameter 624. CE and C-tick labelling do not cover VLT 5001-5062, 525-600 V units.
These Operating Instructions are a tool intended for persons who are to install, operate and program the VLT 5000 Series.
Operating Instructions: Gives instructions in optimum installation, commissioning and service.
Design Guide: Gives all required information for design purposes, and gives a good insight
into the technology, product range, technical data, etc.
Safety
The Operating Instructions including Quick Setup are delivered with the unit. When reading these Operating Instructions, you will come across different symbols that require special attention. The symbols used are the following:
Indicates a general warning
NB!
Indicates something to be noted by the reader
Indicates a high-voltage warning
MG.52.A3.02 - VLT® is a registered Danfoss trademark 3
The voltage of the frequency converter is dangerous whenever the equipment is connected to mains. Incorrect installation of the motor or the frequency converter may cause damage to the equipment, se­rious personal injury or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.
Installation in high altitudes:
By altitudes above 2km, please contact Danfoss Drives regarding PELV
Safety regulations
1. The frequency converter must be disconnec­ted from mains if repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
VLT® 5000 Series
necessary time has expired before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when loadsharing (linking of DC intermediate cir­cuit) and external 24 V DC have been instal­led. Check that all voltage inputs have been disconnected and that the necessary time has passed before repair work is com­menced.
2. The [STOP/RESET] key on the control panel of the frequency converter does not discon­nect the equipment from mains and is thus not to be used as a safety switch.
3. Correct protective earthing of the equipment must be established, the user must be pro­tected against supply voltage, and the motor must be protected against overload in ac­cordance with applicable national and local regulations.
4. The earth leakage currents are higher than
3.5 mA.
5. Protection against motor overload is not in­cluded in the factory setting. If this function is desired, set parameter 128 to data value ETR trip or data value ETR warning. Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For the North American market: The ETR func­tions provide class 20 motor overload pro­tection in accordance with NEC.
6. Do
4 MG.52.A3.02 - VLT® is a registered Danfoss trademark
not remove the plugs for the motor and main supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the
VLT® 5000 Series
Warning against unintended start
1. The motor can be brought to a stop by means of digital commands, bus commands, refer­ences or a local stop, while the frequency converter is connected to mains. If personal safety considerations make it nec­essary to ensure that no unintended start occurs, cient.
2. While parameters are being changed, the motor may start. Consequently, [STOP/RESET] must always be activated, following which data can be modified.
3. A motor that has been stopped may start if faults occur in the electronics of the frequen­cy converter, or if a temporary overload or a fault in the supply mains or the motor con­nection ceases.
these stop functions are not suffi-
the stop key
Warning:
Installation of mechanical brake
not connect a mechanical brake to the output from
Do the frequency converter before the relevant parame­ters for brake control are parameterised.
(Selection of output in parameter 319, 321, 323 or 326 and cut-in current and frequency in parameter 223 and
225).
Use on isolated mains
See section RFI Switch regarding use on isolated mains.
It is important to follow the recommendations regard­ing installation on IT-mains, since sufficient protection of the complete installation must be observed. Not tak­ing care using relevant monitoring devices for IT­mains may result in damage.
Safety
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load-sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back-up. VLT 5001 - 5006, 200-240 V: wait at least 4 minutes VLT 5008 - 5052, 200-240 V: wait at least 15 minutes VLT 5001 - 5006, 380-500 V: wait at least 4 minutes VLT 5008 - 5062, 380-500 V: wait at least 15 minutes VLT 5072 - 5302, 380-500 V: wait at least 20 minutes VLT 5352 - 5552, 380-500 V: wait at least 40 minutes VLT 5001 - 5005, 525-600 V wait at least 4 minutes VLT 5006 - 5022, 525-600 V: wait at least 15 minutes VLT 5027 - 5062, 525-600 V: wait at least 30 minutes VLT 5042 - 5352, 525-690 V: wait at least 20 minutes VLT 5402 - 5602, 525-690 V: wait at least 30 minutes
MG.52.A3.02 - VLT® is a registered Danfoss trademark 5
VLT® 5000 Series
Introduction to Quick Setup
This Quick Setup will guide you through EMC correct installation of the frequency converter by connecting power, motor and control wiring (fig. 1). Start/stop of motor is to be done with the switch. For VLT 5122 - 5552 380 - 500 V, VLT 5032 - 5052 200 - 240 V AC and VLT 5042-5602, 525-690 V, please refer to Technical data and Installation regarding mechanical and electrical installation.
Fig. 1
1. Mechanical Installation
VLT 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a free air passage
100 mm above and below the frequency converter (5016-5062 380-500 V, 5008-5027 200-240 V and
of 5016-5062 525-600 V must have 200 mm, 5072-5102, 380-500 V 225 mm). Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Place the frequency converter on the wall. Tighten up all four screws. All the below listed measurements are in mm
VLT type A B C a b
Bookstyle IP 20, 200–240 V, (Fig. 2)
5001 - 5003 395 90 260 384 70 5004 - 5006 395 130 260 384 70
Bookstyle IP 20, 380–500 V (Fig. 2)
5001 - 5005 395 90 260 384 70 5006 - 5011 395 130 260 384 70
Compact IP 54, 200–240 V (Fig. 3)
5001 - 5003 460 282 195 260 258 5004 - 5006 530 282 195 330 258 5008 - 5011 810 350 280 560 326 5016 - 5027 940 400 280 690 375
Compact IP 54, 380–500 V (Fig. 3)
5001 - 5005 460 282 195 260 258 5006 - 5011 530 282 195 330 258 5016 - 5027 810 350 280 560 326 5032 - 5062 940 400 280 690 375 5072 - 5102 940 400 360 690 375
Compact IP 20, 200–240 V (Fig. 4)
5001 - 5003 395 220 160 384 200 5004 - 5006 395 220 200 384 200 5008 560 242 260 540 200 5011 - 5016 700 242 260 680 200 5022 - 5027 800 308 296 780 270
Compact IP 20, 380–500 V (Fig. 4)
5001 - 5005 395 220 160 384 200 5006 - 5011 395 220 200 384 200 5016 - 5022 560 242 260 540 200 5027 - 5032 700 242 260 680 200 5042 - 5062 800 308 296 780 270 5072 - 5102 800 370 335 780 330
Fig. 2
Fig. 3
Fig. 4
6 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
2. Electrical Installation, power
NOTE: The terminals are detachable on VLT 5001 - 5006, 200 - 240 V, VLT 5001 - 5011, 380 - 500 V and VLT 5001 - 5011, 525 - 600 V Connect the mains supply to the mains terminals L1, L2, L3 of the frequency converter and to the earth connection (fig. 5-8). Cable relief fitting is placed on the wall for Bookstyle units. Mount screened motor cable to the motor terminals U, V, W, PE of the frequency converter. Make sure, the screen is connected electrically to the drive.
Fig. 5
Bookstyle IP 20 5001 - 5011 380 - 500 V 5001 - 5006 200 - 240 V
Fig. 6
Compact IP 20 and IP 54 5001 - 5011 380 - 500 V 5001 - 5006 200 - 240 V 5001 - 5011 525 - 600 V
Fig. 7
Compact IP 20 5016 - 5102 380 - 500 V 5008 - 5027 200 - 240 V 5016 - 5062 525 - 600 V
Compact IP 54 5016 - 5062 380 - 500 V 5008 - 5027 200 - 240 V
Quick Setup
Fig. 8
Fig. 9
Compact IP 54 5072 - 5102 380 - 500 V
MG.52.A3.02 - VLT® is a registered Danfoss trademark 7
3. Electrical installation, control leads
Use a screw driver to remove the front cover under the control panel. NOTE: The terminals are detachable. Connect a jum­ber between terminals 12 and 27 (Fig. 10)
Mount screened cable to external start/stop of control terminals 12 and 18.
VLT® 5000 Series
Fig. 10
4. Programming
The frequency converter is programmed over the con­trol panel.
Press the QUICK MENU button. The Quick Menu ap­pears in the display. You choose parameters by means of arrow up and arrow down. Press the CHANGE DATA button to change parameter value. Data values are changed using the up and down ar­rows. Press the left or right buttons to move the cursor. Press OK to save your parameter setting.
Set the desired language in parameter 001. You have six possibilities: English, German, French, Danish, Spanish and Italian.
Set the motor parameters according to the motorplate:
Motor power Motor voltage Motor frequency Motor current Rated motor speed
Set frequency interval and ramp times (Fig. 11)
Parameter 102 Parameter 103 Parameter 104 Parameter 105 Parameter 106
Min. reference Max. reference Ramp up time Ramp down time
Set Operation site, Parameter 002 for Local.
Parameter 204 Parameter 205 Parameter 207 Parameter 208
Fig. 11
5. Motor Start
Press the START button to start the motor. Set motor speed in Parameter 003. Check if the direction of rota­tions is as shown in the display. It can be changed by swapping two phases of the motor cable.
Press the STOP button to stop the motor.
Select total or reduced Automatic Motor Adaption (AMA) in Parameter 107. For further description of AMA, see section Automatic Motor Adaption, AMA.
8 MG.52.A3.02 - VLT® is a registered Danfoss trademark
Press the START button to start the Automatic Motor Adaption (AMA).
Press the DISPLAY/STATUS button to leave the Quick Menu.
VLT® 5000 Series
Available literature
Supplied with the unit:
Operating instructions MG.51.AX.YY High Power Installation Guide MI.90.JX.YY
Communication with VLT 5000:
VLT 5000 Profibus manual MG.10.EX.YY VLT 5000 DeviceNet manual MG.50.HX.YY VLT 5000 LonWorks manual MG.50.MX.YY VLT 5000 Modbus manual MG.10.MX.YY VLT 5000 Interbus manual MG.10.OX.YY
Application options for VLT 5000:
VLT 5000 SyncPos option manual MG.10.EX.YY VLT 5000 Positioning controller manual MG.50.PX.YY VLT 5000 Synchronising controller manual MG.10.NX.YY Ring spinning option MI.50.ZX.02 Wobble function option MI.50.JX.02 Winder and Tension control option MG.50.KX.02
Instructions for VLT 5000:
Loadsharing MI.50.NX.02 VLT 5000 Brake resistors MI.90.FX.YY Brake resistors for horizontal applications (VLT 5001 - 5011) (Only in English and German) MI.50.SX.YY LC filter modules MI.56.DX.YY Converter for encoder inputs (5V TTL to 24 V DC) (Only in combined English/German) MI.50.IX.51 Back Plate to VLT 5000 Series MN.50.XX.02
Below is a list of the literature available for VLT 5000. It must be noted that there may be deviations from one country to another.
Introduction
Various literature for VLT 5000:
Design Guide MG.51.BX.YY Incorporating a VLT 5000 Profibus in a Simatic S5 SYSTEM MC.50.CX.02 Incorporating a VLT 5000 Profibus in a Simatic S7 SYSTEM MC.50.AX.02 Hoist and the VLT 5000 series MN.50.RX.02
Miscellaneous (only in English):
Protection against electrical hazards MN.90.GX.02 Choice of prefuses MN.50.OX.02 VLT on IT mains MN.90.CX.02 Filtering of harmonic currents MN.90.FX.02 Handling aggressive environments MN.90.IX.02 CI-TITM contactors - VLT® frequency converters MN.90.KX.02 VLT® frequency converters and UniOP operator panels MN.90.HX.02
X = version number YY = language version
MG.52.A3.02 - VLT® is a registered Danfoss trademark 9
VLT® 5000 Series
General technical data
Mains supply (L1, L2, L3): Supply voltage 200-240 V units 3 x 200/208/220/230/240 V ±10% Supply voltage 380-500 V units 3 x 380/400/415/440/460/500 V ±10% Supply voltage 525-600 V units 3 x 525/550/575/600 V ±10% Supply voltage 525-690 V units 3 x 525/550/575/600/690 V ±10% Supply frequency 48-62 Hz +/- 1 %
See the section on special conditions in the Design Guide
Max imbalance of supply voltage: VLT 5001-5011, 380-500 V and 525-600 V and VLT 5001-5006, 200-240 V ±2.0% of rated supply voltage VLT 5016-5062, 380-500 V and 525-600 V and VLT 5008-5027, 200-240 V ±1.5% of rated supply voltage VLT 5072-5552, 380-500 V and VLT 5032-5052, 200-240 V ±3.0% of rated supply voltage VLT 5042-5602, 525-690 V ±3.0% of rated supply voltage True Power factor (λ) Displacement Power Factor (cos φ) No. of switchings on supply input L1, L2, L3 approx. 1 time/min.
See the section on special conditions in the Design Guide
VLT output data (U, V, W): Output voltage 0-100% of supply voltage Output frequency VLT 5001-5027, 200-240 V 0-132 Hz, 0-1000 Hz Output frequency VLT 5032-5052, 200-240 V 0-132 Hz, 0-450 Hz Output frequency VLT 5001-5052, 380-500 V 0-132 Hz, 0-1000 Hz Output frequency VLT 5062-5302, 380-500 V 0-132 Hz, 0-450 Hz Output frequency VLT 5352-5552, 380-500 V 0-132 Hz, 0-300 Hz Output frequency VLT 5001-5011, 525-600 V 0-132 Hz, 0-700 Hz Output frequency VLT 5016-5052, 525-600 V 0-132 Hz, 0-1000 Hz Output frequency VLT 5062, 525-600 V 0-132 Hz, 0-450 Hz Output frequency VLT 5042-5302, 525-690 V 0-132 Hz, 0-200 Hz Output frequency VLT 5352-5602, 525-690 V 0-132 Hz, 0-150 Hz Rated motor voltage, 200-240 V units 200/208/220/230/240 V Rated motor voltage, 380-500 V units 380/400/415/440/460/480/500 V Rated motor voltage, 525-600 V units 525/550/575 V Rated motor voltage, 525-690 V units 525/550/575/690 V Rated motor frequency 50/60 Hz Switching on output Unlimited Ramp times 0.05-3600 sec.
0.90 nominal at rated load near unity (>0.98)
Torque characteristics: Starting torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V 160% for 1 min. Starting torque, VLT 5032-5052, 200-240 V 150% for 1 min. Starting torque, VLT 5001-5062, 525-600 V 160% for 1 min. Starting torque, VLT 5042-5602, 525-690 V 160% for 1 min. Starting torque 180% for 0.5 sec. Acceleration torque 100% Overload torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V, VLT 5001-5062, 525-600 V, and VLT 5042-5602, 525-690 V Overload torque, VLT 5032-5052, 200-240 V 150% Arresting torque at 0 rpm (closed loop) 100%
The torque characteristics given are for the frequency converter at the high overload torque level (160%). At the normal overload torque (110%), the values are lower.
10 MG.52.A3.02 - VLT® is a registered Danfoss trademark
160%
VLT® 5000 Series
Braking at high overload torque level
200-240 V
5001-5027 5032-5052
380-500 V
5001-5102 5122-5252 5302 5352-5552
525-600 V
5001-5062
525-690 V
5042-5352 5402-5602
1) VLT 5502 at 90% torque. At 100% torque the braking duty cycle is 13%. At mains rating 441-500 V 100% torque the braking duty cycle is 17%. VLT 5552 at 80% torque. At 100% torque the braking duty cycle is 8%.
2) Based on 300 second cycle: For VLT 5502 the torque is 145%. For VLT 5552 the torque is 130%.
3) VLT 5502 at 80% torque. VLT 5602 at 71% torque.
4) Based on 300 second cycle. For VLT 5502 the torque is 128%. For VLT 5602 the torque is 114%.
Cycle time (s) Braking duty cycle at 100% torque Braking duty cycle at over torque
120 Continuous 40% 300 10% 10%
120 Continuous 40% 600 Continuous 10% 600 40% 10% 600
120 Continuous 40%
600 40% 10% 600
40%
40%
1)
3)
(150/160%)
2)
10%
4)
10%
Control card, digital inputs: Number of programmable digital inputs 8 Terminal nos. 16, 17, 18, 19, 27, 29, 32, 33 Voltage level 0-24 V DC (PNP positive logics) Voltage level, logical '0' < 5 V DC Voltage level, logical '1' >10 V DC Maximum voltage on input 28 V DC Input resistance, R
i
2 k
Scanning time per input 3 msec.
Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition, the digital inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4. VLT 5001-5062, 525-600 V do not meet PELV.
Control card, analogue inputs: No. of programmable analogue voltage inputs/thermistor inputs 2 Terminal nos. 53, 54 Voltage level 0 - ±10 V DC (scalable) Input resistance, R
i
10 k No. of programmable analogue current inputs 1 Terminal no. 60 Current range 0/4 - ±20 mA (scalable) Input resistance, R
i
200
Resolution 10 bit + sign Accuracy on input Max. error 1% of full scale Scanning time per input 3 msec. Terminal no. ground 55
Technical data
Reliable galvanic isolation: All analogue inputs are galvanically isolated from the supply voltage (PELV)* as well as other inputs and outputs. * VLT 5001-5062, 525-600 V do not meet PELV.
MG.52.A3.02 - VLT® is a registered Danfoss trademark 11
VLT® 5000 Series
Control card, pulse/encoder input: No. of programmable pulse/encoder inputs 4 Terminal nos. 17, 29, 32, 33 Max. frequency on terminal 17 5 kHz Max. frequency on terminals 29, 32, 33 20 kHz (PNP open collector) Max. frequency on terminals 29, 32, 33 65 kHz (Push-pull) Voltage level 0-24 V DC (PNP positive logics) Voltage level, logical '0' < 5 V DC Voltage level, logical '1' >10 V DC Maximum voltage on input 28 V DC Input resistance, R
i
Scanning time per input 3 msec. Resolution 10 bit + sign Accuracy (100-1 kHz), terminals 17, 29, 33 Max. error: 0.5% of full scale Accuracy (1-5 kHz), terminal 17 Max. error: 0.1% of full scale Accuracy (1-65 kHz), terminals 29, 33 Max. error: 0.1% of full scale
Reliable galvanic isolation: All pulse/encoder inputs are galvanically isolated from the supply voltage (PELV)*. In ad­dition, pulse and encoder inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4. * VLT 5001-5062, 525-600 V do not meet PELV.
2 k
Control card, digital/pulse and analogue outputs: No. of programmable digital and analogue outputs 2 Terminal nos. 42, 45 Voltage level at digital/pulse output 0 - 24 V DC Minimum load to ground (terminal 39) at digital/pulse output
600
Frequency ranges (digital output used as pulse output) 0-32 kHz Current range at analogue output 0/4 - 20 mA Maximum load to ground (terminal 39) at analogue output
500
Accuracy of analogue output Max. error: 1.5% of full scale Resolution on analogue output. 8 bit
Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the supply voltage (PELV)*, as well as other inputs and outputs. * VLT 5001-5062, 525-600 V do not meet PELV.
Control card, 24 V DC supply: Terminal nos. 12, 13 Max. load (short-circuit protection) 200 mA Terminal nos. ground 20, 39
Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage (PELV)*, but has the same potential as the analogue outputs. * VLT 5001-5062, 525-600 V do not meet PELV.
Control card, RS 485 serial communication: Terminal nos. 68 (TX+, RX+), 69 (TX-, RX-)
Reliable galvanic isolation: Full galvanic isolation.
Relay outputs:
1)
No. of programmable relay outputs 2 Terminal nos., control card (resistive load only) 4-5 (make)
12 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Max. terminal load (AC1) on 4-5, control card 50 V AC, 1 A, 50 VA Max. terminal load (DC1 (IEC 947)) on 4-5, control card 25 V DC, 2 A / 50 V DC, 1 A, 50 W Max. terminal load (DC1) on 4-5, control card for UL/cUL applications 30 V AC, 1 A / 42.5 V DC, 1A Terminal nos., power card (resistive and inductive load) 1-3 (break), 1-2 (make) Max. terminal load (AC1) on 1-3, 1-2, power card 250 V AC, 2 A, 500 VA Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, power card 25 V DC, 2 A / 50 V DC, 1A, 50 W Min. terminal load (AC/DC) on 1-3, 1-2, power card 24 V DC, 10 mA / 24 V AC, 100 mA
1) Rated values for up to 300,000 operations. At inductive loads the number of operations are reduced by 50%, alternatively the current can be reduced by 50%, thus the 300,000 operations are maintained.
Brake resistor terminals (only SB, EB, DE and PB units): Terminal nos. 81, 82
External 24 Volt DC supply: Terminal nos. 35, 36 Voltage range 24 V DC ±15% (max. 37 V DC for 10 sec.) Max. voltage ripple 2 V DC Power consumption 15 W - 50 W (50 W for start-up, 20 msec.) Min. pre-fuse 6 Amp
Reliable galvanic isolation: Full galvanic isolation if the external 24 V DC supply is also of the PELV type.
Cable lengths, cross-sections and connectors: Max. motor cable length, screened cable 150 m Max. motor cable length, unscreened cable 300 m Max. motor cable length, screened cable VLT 5011 380-500 V 100 m Max. motor cable length, screened cable VLT 5011 525-600 V and VLT 5008, normal overload mode, 525-600 V Max. brake cable length, screened cable 20 m Max. loadsharing cable length, screened cable 25 m from frequency converter to DC bar.
Max. cable cross-section for motor, brake and loadsharing, see Electrical data
Max. cable cross-section for 24 V external DC supply
- VLT 5001-5027 200-240 V; VLT 5001-5102 380-500 V; VLT 5001-5062 525-600 V
- VLT 5032-5052 200-240 V; VLT 5122-5552 380-500 V; VLT 5042-5602 525-690 V 2.5 mm2 /12 AWG Max. cross-section for control cables 1.5 mm 2 /16 AWG Max. cross-section for serial communication 1.5 mm2 /16 AWG
If UL/cUL is to be complied with, copper cable with temperature class 60/75°C must be used (VLT 5001 - 5062 380 - 500 V, 525 - 600 V and VLT 5001 - 5027 200 - 240 V). If UL/cUL is to be complied with, copper cable with temperature class 75°C must be used (VLT 5072 - 5552 380 - 500 V, VLT 5032 - 5052 200 - 240 V, VLT 5042 - 5602 525 - 690 V). Connectors are for use of both copper and aluminium cables, unless other is specified.
4 mm2 /10 AWG
50 m
Technical data
Accuracy of display readout (parameters 009-012): Motor current [6] 0-140% load Max. error: ±2.0% of rated output current Torque % [7], -100 - 140% load Max. error: ±5% of rated motor size Output [8], power HP [9], 0-90% load Max. error: ±5% of rated output
Control characteristics: Frequency range 0 - 1000 Hz Resolution on output frequency ±0.003 Hz
MG.52.A3.02 - VLT® is a registered Danfoss trademark 13
VLT® 5000 Series
System response time 3 msec. Speed, control range (open loop) 1:100 of synchro. speed Speed, control range (closed loop) 1:1000 of synchro. speed Speed, accuracy (open loop) < 1500 rpm: max. error ± 7.5 rpm Speed, accuracy (closed loop) < 1500 rpm: max. error ± 1.5 rpm Torque control accuracy (open loop) 0- 150 rpm: max. error ±20% of rated torque Torque control accuracy (speed feedback) Max. error ±5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Externals: Enclosure (dependent on power size) IP 00, IP 20, IP 21, Nema 1, IP 54 Vibration test 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36) Max. relative humidity 93 % (IEC 68-2-3) for storage/transport Max. relative humidity 95 % non condensing (IEC 721-3-3; class 3K3) for operation Aggressive environment (IEC 721 - 3 - 3) Uncoated class 3C2 Aggressive environment (IEC 721 - 3 - 3) Coated class 3C3 Ambient temperature IP 20/Nema 1 (high overload torque 160%) Max. 45°C (24-hour average max. 40°C) Ambient temperature IP 20/Nema 1 (normal overload torque 110%) Max. 40°C (24-hour average max. 35°C) Ambient temperature IP 54 (high overload torque 160%) Max. 40°C (24-hour average max. 35°C) Ambient temperature IP 54 (normal overload torque 110%) Max. 40°C (24-hour average max. 35°C) Ambient temperature IP 20/54 VLT 5011 500 V Max. 40°C (24-hour average max. 35°C) Ambient temperature IP 54 VLT 5042-5602, 525-690 V; and 5122-5552, 380-500 V (high overload torque 160%)
Max. 45°C (24-hour average max. 40°C)
Derating for high ambient temperature, see the Design Guide
Min. ambient temperature in full operation Min. ambient temperature at reduced performance -10°C Temperature during storage/transport -25 - +65/70°C Max. altitude above sea level 1000 m
Derating for altitude over 1000 m above sealevel, see the Design Guide
EMC standards applied, Emission
EMC standards applied, Immunity
See section on special conditions in the Design Guide VLT 5001-5062, 525 - 600 V do not comply with EMC or Low Voltage Directives. IP54 units are not intended for direct outdoor installation. The IP54 rating does not relate to other exposures as sun, icing, wind blown driving rain. Under such circumstances Danfoss recommends to install the units in an enclosure designed for these environmental conditions. Alternatively, an installation at minimum 0.5 m above surface and covered by a shed is recommended
EN 61000-6-3, EN 61000-6-4, EN 61800-3, EN 55011
EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, VDE 0160/1990.12
0°C
14 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
VLT 5000 Series protection:
Electronic motor thermal protection against overload.
Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature reaches 90°
C for IP 00, IP 20 and Nema 1. For IP 54, the cut-out temperature is 80°C. An overtemperature can only be reset when the temperature of the heat-sink has fallen below 60°C.
For the units mentioned below, the limits are as follows:
- VLT 5122, 380-500 V, cuts out at 75°C and can be reset if the temperature has fallen below 60°C.
- VLT 5152, 380-500 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.
- VLT 5202, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.
- VLT 5252, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.
- VLT 5302, 380-500 V, cuts out at 105°C and can be reset if the temperature has fallen below 75°C.
- VLT 5352-5552, 380-500 V, cut out at 85°C and can be reset if the temperature has fallen below 60°C.
- VLT 5042-5122, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.
- VLT 5152, 525-690 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.
- VLT 5202-5352, 525-690 V, cut out at 100°C and can be reset if the temperature has fallen below 70°C.
- VLT 5402-5602, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.
The frequency converter is protected against short-circuiting on motor terminals U, V, W.
The frequency converter is protected against earth fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage becomes
too high or too low.
If a motor phase is missing, the frequency converter cuts out, see parameter 234 Motor phase monitor.
If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
If a mains phase is missing, the frequency converter will cut out when a load is placed on the motor.
MG.52.A3.02 - VLT® is a registered Danfoss trademark 15
Technical data
VLT® 5000 Series
Electrical data
Bookstyle and Compact, Mains supply 3 x 200 ­240 V
According to international requirements VLT type 5001 5002 5003 5004 5005 5006
Output current
I
VLT, MAX
Output (240 V) S Typical shaft output Typical shaft output
Max. cable cross-section to motor, brake and loadsharing [mm
2
]/[AWG]2 )
Rated input current Max. cable cross-section power [mm
2
]/[AWG] 2 ) Max. pre-fuses Efficiency
3)
Weight IP 20 EB Bookstyle [kg] 7 7 7 9 9 9.5 Weight IP 20 EB Compact [kg] 8 8 8 10 10 10 Weight IP 54 Compact [kg] 11.5 11.5 11.5 13.5 13.5 13.5 Power loss at max. load.
Enclosure
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
I
(60 s) [A]
VLT,N
P
VLT,N
P
VLT,N
(200 V)I
[-]/UL1) [A]
[A]
VLT,N
3.7 5.4 7.8 10.6 12.5 15.2
5.9 8.6 12.5 17 20 24.3
[kVA]
1.5 2.2 3.2 4.4 5.2 6.3
[kW]
0.75 1.1 1.5 2.2 3.0 3.7
[HP]
1 1.5 2 3 4 5
4/10
[A]
3.4 4.8 7.1 9.5 11.5 14.5
L,N
4/10
4/10 4/10 4/10 4/10 4/10
4/10 4/10 4/10 4/10 4/10
16/10 16/10 16/15 25/20 25/25 35/30
0.95 0.95 0.95 0.95 0.95 0.95
[W] 58 76 95 126 172 194
IP 20/ IP54
IP 20/ IP54
IP 20/ IP54
IP 20/ IP54
IP 20/ IP54
IP 20/ IP54
16 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Compact, Mains supply 3 x 200 - 240 V
According to international requirements VLT type 5008 5011 5016 5022 5027
Normal overload torque (110 %):
I
[A]
Output current
I
VLT, MAX
Output (240 V) S Typical shaft output Typical shaft output
VLT,N
P
VLT,N
P
VLT,N
VLT,N
32 46 61.2 73 88
(60 s)
35.2 50.6 67.3 80.3 96.8
[A]
[kVA]
13.3 19.1 25.4 30.3 36.6
[kW]
7.5 11 15 18.5 22
[HP]
10 15 20 25 30
High overload torque (160 %):
I
[A]
Output current
Output (240 V) S Typical shaft output Typical shaft output Max. cable cross-section to motor, IP 54 16/6 16/6 35/2 35/2 50/0 brake and loadsharing [mm Min. cable cross-section to motor, brake and loadsharing
4)
[mm2 /AWG]
2
2)
I
VLT, MAX
VLT,N
P
VLT,N
P
VLT,N
/AWG]2)
VLT,N
25 32 46 61.2 73
(60 s)
40 51.2 73.6 97.9 116.8
[A]
[kVA]
10 13 19 25 30
[kW]
5.5 7.5 11 15 18.5
[HP]
7.5 10 15 20 25
5)
IP 20 16/6 35/2 35/2 35/2 50/0
10/8 10/8 10/8 10/8 16/6
Rated input current Max. cable cross-section, IP 54 16/6 16/6 35/2 35/2 50/0 power [mm
2
]/[AWG]2)
(200 V) I
5)
Max. pre-fuses Efficiency
3)
[A]
L,N
[-]/UL1) [A]
32 46 61 73 88
IP 20 16/6 35/2 35/2 35/2 50/0 50 60 80 125 125
0.95 0.95 0.95 0.95 0.95 Weight IP 20 EB [kg] 21 25 27 34 36 Weight IP 54 [kg] 38 40 53 55 56 Power loss at max. load.
- high overload torque (160 %)
- normal overload torque (110 %)
Enclosure
[W]
[W]
340 426 626 833 994
426 545 783 1042 1243
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
Technical data
MG.52.A3.02 - VLT® is a registered Danfoss trademark 17
VLT® 5000 Series
Compact, Mains supply 3 x 200 - 240 V
According to international requirements VLT type 5032 5042 5052
Normal overload torque (110 %):
Output current
I Output
S
(60 s) [A] (200-230 V)
I
VLT, MAX
[A] (231-240 V)
I
VLT,N
(60 s) [A] (231-240 V)
VLT, MAX
[kVA] (208 V)
S
VLT,N
[kVA] (230 V)
S
VLT,N
[kVA] (240 V)
VLT,N
[A] (200-230 V)
VLT,N
115 143 170
127 158 187 104 130 154 115 143 170
41 52 61 46 57 68 43 54 64
I
Typical shaft output [HP] (208 V) 40 50 60 Typical shaft output [kW] (230 V) 30 37 45
High overload torque (160 %):
Output current
I Output
S
I
[A] (200-230 V)
VLT,N
[A] (200-230 V)
I
VLT, MAX
[A] (231-240 V)
I
VLT,N
[A] (231-240 V)
VLT, MAX
[kVA] (208 V)
S
VLT,N
S
[kVA] (230 V)
VLT,N
[kVA] (240 V)
VLT,N
88 115 143
132 173 215
80 104 130
120 285 195
32 41 52 35 46 57
33 43 54 Typical shaft output [HP] (208 V) 30 40 50 [kW] (230 V) 22 30 37 Max. cable cross-section to motor and loadsharing
Max. cable cross-section to brake
Normal overload torque (110 %):
Rated input current
Normal overload torque (150 %):
Rated input current Max. cable cross-section power supply Min. cable cross-section to motor, power
[mm2 ] [AWG] [mm2 ] [AWG]
I
[A] (230 V)
L,N
4,6
[mm2] [AWG]
4,6
[mm2] [AWG]
4,6 2,4,6 4,6 2,4,6
2,4,6
2,4,6
I
[A] (230 V)
L,N
120 300 mcm
25 4
101.3 126.6 149.9
77,9 101,3 126,6
120 300 mcm
6 8
supply, brake and loadsharing Max. pre-fuses (mains) [-]/UL
Efficiency
3
Power loss
1
[A]
Normal overload [W]
150/15
200/200 250/250
0
0,96-0,97
1089 1361 1612 High overload [W] 838 1089 1361 Weight Weight Weight
IP 00 [kg] IP 20 Nema1 [kg] IP 54 Nema12 [kg] 104 104 104
101 101 101 101 101 101
Enclosure IP 00 / Nema 1 (IP 20) / IP 54
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Min. cable cross-section is the minimum allowed cross-section. Always comply with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection stud: M8 Brake: M6.
18 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Bookstyle and Compact, Mains supply 3 x 380 ­500 V
According to international requirements VLT type 5001 5002 5003 5004
Output current
I
I Output S Typical shaft output Typical shaft output Max. cable cross-section to motor, brake and loadsharing [mm
2
]/[AWG]2 )
Rated input current
Max. cable cross-section, power [mm2 ]/[AWG] Max. pre-fuses [-]/UL1) [A] Efficiency
3)
Weight IP 20 EB Bookstyle [kg] 7 7 7 7.5 Weight IP 20 EB Compact [kg] 8 8 8 8.5 Weight IP 54 Compact [kg] 11.5 11.5 11.5 12 Power loss at max. load [W] 55 67 92 110
Enclosure
I
VLT,N
(60 s) [A] (380-440 V)
VLT, MAX
I
VLT,N
(60 s) [A] (441-500 V)
VLT, MAX
[kVA] (380-440 V)
S
VLT,N
[kVA] (441-500 V)
VLT,N
2)
[A] (380-440 V)
[A] (441-500 V)
P
[kW]
VLT,N
P
[HP]
VLT,N
[A] (380 V)
I
L,N
I
[A] (460 V)
L,N
2.2 2.8 4.1 5.6
3.5 4.5 6.5 9
1.9 2.6 3.4 4.8 3 4.2 5.5 7.7
1.7 2.1 3.1 4.3
1.6 2.3 2.9 4.2
0.75 1.1 1.5 2.2 1 1.5 2 3
4/10
4/10 4/10 4/10
2.3 2.6 3.8 5.3
1.9 2.5 3.4 4.8 4/10 4/10 4/10 4/10 16/6 16/6 16/10 16/10
0.96 0.96 0.96 0.96
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
Technical data
MG.52.A3.02 - VLT® is a registered Danfoss trademark 19
VLT® 5000 Series
Bookstyle and Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5005 5006 5008 5011
Output current
I
I Output S Typical shaft output Typical shaft output Max. cable cross-section to motor, brake and loadsharing [mm
2
]/[AWG]2 )
Rated input current I Max. cable cross-section power [mm2 ]/[AWG] Max. pre-fuses [-]/UL1) [A] Efficiency
3)
Weight IP 20 EB Bookstyle [kg] 7.5 9.5 9.5 9.5 Weight IP 20 EB Compact [kg] 8.5 10.5 10.5 10.5 Weight IP 54 EB Compact [kg] 12 14 14 14 Power loss at max. load. [W] 139 198 250 295
Enclosure
I
VLT,N
(60 s) [A] (380-440 V)
VLT, MAX
I
VLT,N
(60 s) [A] (441-500 V)
VLT, MAX
[kVA] (380-440 V)
S
VLT,N
[kVA] (441-500 V)
VLT,N
[A] (380-440 V)
[A] (441-500 V)
P
[kW]
VLT,N
P
[HP]
VLT,N
[A] (380 V)
I
L,N
[A] (460 V)
L,N
2)
7.2 10 13 16
11.5 16 20.8 25.6
6.3 8.2 11 14.5
10.1 13.1 17.6 23.2
5.5 7.6 9.9 12.2
5.5 7.1 9.5 12.6
3.0 4.0 5.5 7.5 4 5 7.5 10
4/10
4/10 4/10 4/10
7 9.1 12.2 15.0 6 8.3 10.6 14.0 4/10 4/10 4/10 4/10 16/15 25/20 25/25 35/30
0.96 0.96 0.96 0.96
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
20 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5016 5022 5027
Normal overload torque (110 %): Output current
Output
Typical shaft output Typical shaft output
I
VLT, MAX
I
VLT, MAX
VLT,N
(60 s) [A] (380-440 V)
I
VLT,N
(60 s) [A] (441-500 V)
[kVA] (380-440 V)
S
VLT,N
S
[kVA] (441-500 V)
VLT,N
[A] (380-440 V)
[A] (441-500 V)
P
VLT,N
P
VLT,N
32 37.5 44
35.2 41.3 48.4
27.9 34 41.4
30.7 37.4 45.5
24.4 28.6 33.5
[kW]
15 18.5 22
[HP]
20 25 30
24.2 29.4 35.8
I
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S
S Typical shaft output Typical shaft output Max. cable cross-section to motor, IP 54 16/6 16/6 16/6 brake and loadsharing [mm Min. cable cross-section to motor, brake and loadsharing [mm2]/[AWG]
2
]/[AWG]
2)
2) 4)
Rated input current
Max. cable cross-section, IP 54 16/6 16/6 16/6 power [mm
2
]/[AWG] Max. pre-fuses Efficiency
3)
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440 V)
I
[A] (441-500 V)
VLT,N
(60 s) [A] (441-500 V)
[kVA] (380-440 V)
VLT,N
[kVA] (441-500 V)
VLT,N
P
VLT,N
P
VLT,N
I
[A] (380 V)
L,N
I
[A] (460 V)
L,N
[-]/UL1) [A]
24 32 37.5
38.4 51.2 60
21.7 27.9 34
34.7 44.6 54.4
18.3 24.4 28.6
[kW]
11 15 18.5
[HP]
15 20 25
18.8 24.2 29.4
IP 20 16/6 16/6 35/2
10/8 10/8 10/8 32 37.5 44
27.6 34 41
IP 20
16/6 16/6 35/2
63/40 63/50 63/60
0.96 0.96 0.96 Weight IP 20 EB [kg] 21 22 27 Weight IP 54 [kg] 41 41 42 Power loss at max. load.
- high overload torque (160 %)
[W] 419 559 655
- normal overload torque (110 %) [W] 559 655 768 Enclosure
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.
Technical data
MG.52.A3.02 - VLT® is a registered Danfoss trademark 21
VLT® 5000 Series
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5032 5042 5052
Normal overload torque (110 %): Output current
Output
Typical shaft output Typical shaft output
I
VLT, MAX
I
VLT, MAX
VLT,N
(60 s) [A] (380-440 V)
I
VLT,N
(60 s) [A] (441-500 V)
[kVA] (380-440 V)
S
VLT,N
S
[kVA] (441-500 V)
VLT,N
[A] (380-440 V)
[A] (441-500 V)
P
VLT,N
P
VLT,N
61 73 90
67.1 80.3 99 54 65 78
59.4 71.5 85.8
46.5 55.6 68.6
[kW]
30 37 45
[HP]
40 50 60
46.8 56.3 67.5
I
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S
S Typical shaft output Typical shaft output Max. cable cross-section to motor, IP 54 35/2 35/2 50/0 brake and loadsharing [mm Min. cable cross-section to motor, brake and loadsharing [mm
2
]/[AWG]2)
2
]/[AWG]2) Rated input current I Max. cable cross-section IP 54 35/2 35/2 50/0 power[mm
2
]/[AWG]
2) 5)
Max. pre-fuses Efficiency
3)
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440 V)
I
[A] (441-500 V)
VLT,N
(60 s) [A] (441-500 V)
[kVA] (380-440 V)
VLT,N
[kVA] (441-500 V)
VLT,N
5)
4)
P
VLT,N
P
VLT,N
I
[A] (380 V)
L,N
[A] (460 V)
L,N
[-]/UL1) [A]
44 61 73
70.4 97.6 116.8
41.4 54 65
66.2 86 104
33.5 46.5 55.6
[kW]
22 30 37
[HP]
30 40 50
35.9 46.8 56.3
IP20 35/2 35/2 50/0
10/8 10/8 16/6 60 72 89 53 64 77
IP 20 35/2 35/2 50/0 80/80 100/100 125/125
0.96 0.96 0.96 Weight IP 20 EB [kg] 28 41 42 Weight IP 54 [kg] 54 56 56 Power loss at max. load.
- high overload torque (160 %)
[W] 768 1065 1275
- normal overload torque (110 %) [W] 1065 1275 1571 Enclosure
IP 20/ IP 54
IP 20/ IP 54
IP 20/ IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
22 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5062 5072 5102
Normal overload torque (110 %): Output current
Output
Typical shaft output
VLT,N
I
(60 s) [A] (380-440 V)
VLT, MAX
I
I
VLT, MAX
VLT,N
(60 s) [A] (441-500 V)
[kVA] (380-440 V)
S
VLT,N
S
[kVA] (441-500 V)
VLT,N
P P P
[A] (380-440 V)
[A] (441-500 V)
[kW] (400 V)
VLT,N
[HP] (460 V)
VLT,N
[kW] (500 V)
VLT,N
106 147 177
117 162 195
106 130 160 117 143 176
80.8 102 123
91.8 113 139 55 75 90 75 100 125 75 90 110
I
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S
S
Typical shaft output
Max. cable cross-section to motor, IP 54
brake and loadsharing [mm2 ]/[AWG] Min. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2)
4)
Rated input current I
Max. cable cross-section IP 54
power[mm
2
]/[AWG]
2)
Max. pre-fuses Efficiency
3)
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440 V)
I
[A] (441-500 V)
VLT,N
(60 s) [A] (441-500 V)
[kVA] (380-440 V)
VLT,N
[kVA] (441-500 V)
VLT,N
P
[kW] (400 V)
VLT,N
[HP] (460 V)
P
VLT,N
P
[kW] (500 V)
VLT,N
I
[A] (380 V)
L,N
[A] (460 V)
L,N
[-]/UL1) [A]
90 106 147
135 159 221 80 106 130 120 159 195
68.6 73.0 102
69.3 92.0 113 45 55 75 60 75 100 55 75 90
IP20
50/0
50/0
5)
5)
150/300 mcm 120/250 mcm
6)
5)
150/300 mcm 120/250 mcm
16/6 25/4 25/4 104 145 174 104 128 158
IP 20
50/0
50/0
5)
5)
150/300 mcm 120/250 mcm
5)
150/300 mcm 120/250 mcm
160/150 225/225 250/250
>0.97 >0.97 >0.97 Weight IP 20 EB [kg] 43 54 54 Weight IP 54 [kg] 60 77 77 Power loss at max. load.
- high overload torque (160 %)
[W] 1122 1058 1467
- normal overload torque (110 %) [W] 1322 1467 1766 Enclosure
IP20/ IP 54
IP20/ IP 54
IP20/ IP 54
6)
5)
5)
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm used.
6. Brake and loadsharing: 95 mm
2
/ AWG 3/0
2
must be connected by use of a AI-Cu connector.
MG.52.A3.02 - VLT® is a registered Danfoss trademark 23
Technical data
VLT® 5000 Series
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5122 5152 5202 5252 5302
Normal overload current (110 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S Typical shaft output
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440
[A] (441-500 V)
I
VLT,N
(60 s) [A] (441-500
[kVA] (400 V)
S
VLT,N
[kVA] (460 V)
S
VLT,N
[kVA] (500 V)
VLT,N
[kW] (400 V) [HP] (460 V) 150 200 250 300 350 [kW] (500 V) 132 160 200 250 315
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S Typical shaft output
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440
[A] (441-500 V)
I
VLT,N
(60 s) [A] (441-500
[kVA] (400 V)
S
VLT,N
[kVA] (460 V)
S
VLT,N
[kVA] (500 V)
VLT,N
[kW] (400 V) [HP] (460 V) 125 150 200 250 300
Max. cable cross-section to motor
Max. cable cross-section to loadsharing and brake
[kW] (500 V) 110 132 160 200 250
[mm2]
[AWG]
[mm2]
[AWG]
Normal overload current (110 %):
I
Rated input current I
[A] (380-440 V)
L,N
[A] (441-500 V)
L,N
High overload torque (160 %):
I
Rated input current I Max. cable cross-section power supply
[A] (380-440 V)
L,N
[A] (441-500 V)
L,N
[mm2]
[AWG] Max. pre-fuses (mains) [-]/ UL Efficiency Power loss
Weight Weight Weight
3
Normal overload [W]
High overload [W] 2206 2619 3309 4163 4977
IP 00 [kg]
IP 21/Nema1 [kg]
IP 54/Nema12 [kg] 96 104 125 136 151
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
212 260 315 395 480 233 286 347 434 528
V)
190 240 302 361 443 209 264 332 397 487
V)
147 180 218 274 333 151 191 241 288 353 165 208 262 313 384 110 132 160 200 250
177 212 260 315 395 266 318 390 473 593
V)
160 190 240 302 361 240 285 360 453 542
V)
123 147 180 218 274 127 151 191 241 288 139 165 208 262 313 90 110 132 160 200
4,6
2,4,6
4,6
2,4,6
2 x 70
2 x 2/0
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
2 x 185
2 x 350 mcm
208 256 317 385 467 185 236 304 356 431
174 206 256 318 389 158 185 236 304 356
4,6
2,4,6
[A]
2 x 70
2 x 2/0
300/
1
300
350/ 350
450/ 400
2 x 185
2 x 350 mcm
500/ 500
0,98
2619 3309 4163 4977 6107
82 91 112 123 138 96 104 125 136 151
630/ 600
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and loadsharing: M8
24 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5352 5452 5502 5552
Normal overload current (110 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output S
Typical shaft output
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440
[A] (441-500 V)
I
VLT,N
(60 s) [A] (441-500
[kVA] (400 V)
VLT,N
[kVA] (460 V)
S
VLT,N
[kVA] (500 V)
S
VLT,N
[kW] (400 V) 315 355 400 450 [HP] (460 V)
[kW] (500 V) 355 400 500 530
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output S
Typical shaft output
Max. cable cross-section to motor and loadsharing
Max. cable cross-section to brake
[A] (380-440 V)
VLT,N
(60 s) [A] (380-440
[A] (441-500 V)
I
VLT,N
(60 s) [A] (441-500
[kVA] (400 V)
VLT,N
[kVA] (460 V)
S
VLT,N
[kVA] (500 V)
S
VLT,N
[kW] (400 V) 250 315 355 400 [HP] (460 V) [kW] (500 V) 315 355 400 500
[mm2]
[AWG]
[mm2]
[AWG]
Normal overload current (110 %):
I
Rated input current I
[A] (380-440 V)
L,N
[A] (441-500 V)
L,N
High overload torque (160 %):
I
Rated input current I Max. cable cross-section power supply
[A] (380-440 V)
L,N
[A] (441-500 V)
L,N
[mm2]
[AWG] Max. pre-fuses (mains) [-]/UL Efficiency Power loss
Weight Weight Weight
3
Normal overload [W]
High overload [W] 6005 6960 7691 7964
IP 00 [kg]
IP 21/Nema1 [kg]
IP 54/Nema12 [kg] 263 270 272 313
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
600 658 745 800 660 724 820 880
V)
540 590 678 730 594 649 746 803
V)
416 456 516 554 430 470 540 582 468 511 587 632
450 500 550/600 600
480 600 658 695 720 900 987 1042
V)
443 540 590 678 665 810 885 1017
V)
333 416 456 482 353 430 470 540 384 468 511 587
350 450 500 550
4,6
2,4,6
4,6
2,4,6
4x240
4x500 mcm
2x185
2x350 mcm
590 647 733 787 531 580 667 718
472 590 647 684 436 531 580 667
4,6
2,4,6
1
700/700 900/900 900/900 900/900
[A]
4x240
4x500 mcm
0,98
7630 7701 8879 9428
221 234 236 277 263 270 272 313
Technical data
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply, motor and loadsharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)
MG.52.A3.02 - VLT® is a registered Danfoss trademark 25
VLT® 5000 Series
Compact, Mains supply 3 x 525 - 600 V
According to international requirements VLT type 5001 5002 5003 5004
Normal overload torque (110 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output S
Typical shaft output Typical shaft output
Highl overload torque (160%):
Output current
I
VLT, MAX
I
VLT, MAX
Output
Typical shaft output Typical shaft output Max. cable cross-section to motor, brake and loadsharing [mm
2
]/[AWG]
2)
S
S S
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
[A] (575 V)
I
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V)
VLT,N
[kVA] (575 V)
VLT,N
P
[kW]
VLT,N
P
[HP]
VLT,N
I
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
I
[A] (575 V)
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V)
VLT,N
[kVA] (575 V)
VLT,N
P
[kW]
VLT,N
P
[HP]
VLT,N
2.6 2.9 4.1 5.2
2.9 3.2 4.5 5.7
2.4 2.7 3.9 4.9
2.6 3.0 4.3 5.4
2.5 2.8 3.9 5.0
2.4 2.7 3.9 4.9
1.1 1.5 2.2 3
1.5 2 3 4
1.8 2.6 2.9 4.1
2.9 4.2 4.6 6.6
1.7 2.4 2.7 3.9
2.7 3.8 4.3 6.2
1.7 2.5 2.8 3.9
1.7 2.4 2.7 3.9
0.75 1.1 1.5 2.2 1 1.5 2 3
4/10 4/10 4/10 4/10
Normal overload torque (110 %):
Rated input current
[A] (550 V)
I
L,N
I
[A] (600 V)
L,N
High overload torque ( 160 %):
I
Rated input current I Max. cable cross-section, power [mm2 ]/[AWG] Max. pre-fuses Efficiency
3)
[A] (550 V)
L,N
[A] (600 V)
L,N
2)
[-]/UL1) [A]
2.5 2.8 4.0 5.1
2.2 2.5 3.6 4.6
1.8 2.5 2.8 4.0
1.6 2.2 2.5 3.6 4/10 4/10 4/10 4/10 3 4 5 6
0.96 0.96 0.96 0.96 Weight IP 20 EB [kg] 10.5 10.5 10.5 10.5 Power loss at max. load.
[W] 63 71 102 129
Enclosure IP 20 / Nema 1
1. For type of fuses see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
26 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Compact, Mains supply 3 x 525 - 600 V
According to international requirements VLT type 5005 5006 5008 5011
Normal overload torque (110 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output S
Typical shaft output Typical shaft output
Highl overload torque (160%):
Output current
I
VLT, MAX
I
VLT, MAX
Output
Typical shaft output Typical shaft output Max. cable cross-section to motor, brake and loadsharing [mm
2
]/[AWG]
2)
S
S S
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
[A] (575 V)
I
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V)
VLT,N
[kVA] (575 V)
VLT,N
P
[kW]
VLT,N
P
[HP]
VLT,N
I
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
I
[A] (575 V)
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V)
VLT,N
[kVA] (575 V)
VLT,N
P
[kW]
VLT,N
P
[HP]
VLT,N
6.4 9.5 11.5 11.5
7.0 10.5 12.7 12.7
6.1 9.0 11.0 11.0
6.7 9.9 12.1 12.1
6.1 9.0 11.0 11.0
6.1 9.0 11.0 11.0
4 5.5 7.5 7.5 5 7.5 10.0 10.0
5.2 6.4 9.5 11.5
8.3 10.2 15.2 18.4
4.9 6.1 9.0 11.0
7.8 9.8 14.4 17.6
5.0 6.1 9.0 11.0
4.9 6.1 9.0 11.0
3 4 5.5 7.5 4 5 7.5 10
4/10 4/10 4/10 4/10
Normal overload torque (110 %):
Rated input current I
[A] (550 V)
I
L,N
[A] (600 V)
L,N
High overload torque ( 160 %):
I
Rated input current I Max. cable cross-section, power [mm2 ]/[AWG] Max. pre-fuses Efficiency
3)
[A] (550 V)
L,N
[A] (600 V)
L,N
2)
[-]/UL1) [A]
6.2 9.2 11.2 11.2
5.7 8.4 10.3 10.3
5.1 6.2 9.2 11.2
4.6 5.7 8.4 10.3
4/10 4/10 4/10 4/10 8 10 15 20
0.96 0.96 0.96 0.96 Weight IP 20 EB [kg] 10.5 10.5 10.5 10.5 Power loss at max. load.
[W] 160 236 288 288
Enclosure IP 20 / Nema 1
1. For type of fuses see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
Technical data
MG.52.A3.02 - VLT® is a registered Danfoss trademark 27
VLT® 5000 Series
Compact, Mains supply 3 x 525 - 600 V
According to international requirements VLT type 5016 5022 5027
Normal overload torque (110 %): Output current
Output
Typical shaft output Typical shaft output
I
VLT, MAX
I
VLT, MAX
S
S
VLT,N
VLT,N
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
I
[A] (575 V)
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V) [kVA] (575 V)
P
VLT,N
P
VLT,N
23 28 34 25 22 24 22 27 32 22
[kW]
15 18.5 22
[HP]
20 25 30
31 37 27 32 30 35
27 32
I
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S
S Typical shaft output Typical shaft output Max. cable cross-section to motor, 16 16 35 brake and loadsharing [mm Min. cable cross-section to motor, 0.5 0.5 10 brake and loadsharing [mm2]/[AWG]
2
]/[AWG]
2)
4)
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
I
[A] (575 V)
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V)
VLT,N
[kVA] (575 V)
VLT,N
P
VLT,N
P
VLT,N
Normal overload torque (110 %):
[A] (550 V)
Rated input current I
I
L,N
[A] (600 V)
L,N
High overload torque (160 %):
[A] (550 V)
Rated input current
Max. cable cross-section, 16 16 35 power [mm
2
]/[AWG]
2)
Max. pre-fuses Efficiency
3)
I
L,N
I
[A] (600 V)
L,N
[-]/UL1) [A]
18 23 28 29 17 27
37 45 22 27
35 43 17 22 27 17
[kW]
11 15 18.5
[HP]
15 20 25
22 27
6 6 2
20 20 8
22 27 33 21 25 30
18 22 27 16 21 25
6 6 2 30 35 45
0.96 0.96 0.96 Weight IP 20 EB [kg] 23 23 30 Power loss at max. load [W] 576 707 838 Enclosure IP 20 / Nema 1
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.
28 MG.52.A3.02 - VLT® is a registered Danfoss trademark
VLT® 5000 Series
Compact, Mains supply 3 x 525 - 600 V
According to international requirements VLT type 5032 5042 5052 5062
Normal overload torque (110 %): Output current
Output
Typical shaft output Typical shaft output
I
(60 s) [A] (550 V)
VLT, MAX
I
(60 s) [A] (575 V)
VLT, MAX
S
VLT,N
S
VLT,N
[A] (550 V)
VLT,N
I
[A] (575 V)
VLT,N
[kVA] (550 V) [kVA] (575 V)
P
VLT,N
P
VLT,N
43 54 65 81 47 41 45
59 72 89 52 62 77
57 68 85 41 51 62 77 41
[kW]
30 37 45 55
[HP]
40 50 60 75
52 62 77
I
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S
S Typical shaft output Typical shaft output Max. cable cross-section to motor, 35 50 50 50 brake and loadsharing [mm Min. cable cross-section to motor, 10 16 16 16 brake and loadsharing [mm
2
]/[AWG]2)
2
]/[AWG]
4)
[A] (550 V)
VLT,N
(60 s) [A] (550 V)
I
[A] (575 V)
VLT,N
(60 s) [A] (575 V)
[kVA] (550 V)
VLT,N
[kVA] (575 V)
VLT,N
P
VLT,N
P
VLT,N
5)
Normal overload torque (110 %):
[A] (550 V)
Rated input current I
I
L,N
[A] (600 V)
L,N
High overload torque (160 %):
I
Rated input current I Max. cable cross-section 35 50 50 50 power[mm
2
]/[AWG]
2) 5)
Max. pre-fuses Efficiency
3)
[A] (550 V)
L,N
[A] (600 V)
L,N
[-]/UL1) [A]
34 43 54 65 54 32 51
69 86 104 41 52 62
66 83 99 32 41 51 62 32
[kW]
22 30 37 45
[HP]
30 40 50 60
41 52 62
2 1/0 1/0 1/0
8 6 6 6
42 53 63 79 38 49 58 72
33 42 53 63 30 38 49 58
2 1/0 1/0 1/0 60 75 90 100
0.96 0.96 0.96 0.96 Weight IP 20 EB [kg] 30 48 48 48 Power loss at max. load [W] 1074 1362 1624 2016 Enclosure IP 20 / Nema 1
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
Technical data
MG.52.A3.02 - VLT® is a registered Danfoss trademark 29
VLT® 5000 Series
Mains supply 3 x 525 - 690 V
According to international requirements VLT type 5042 5052 5062 5072 5102
Normal overload torque (110 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S Typical shaft output
[A] (525-550 V)
VLT,N
(60 s) [A] (525-550
[A] (551-690 V)
I
VLT,N
(60 s) [A] (551-690
[kVA] (550 V)
S
VLT,N
[kVA] (575 V)
S
VLT,N
[kVA] (690 V)
VLT,N
[kW] (550 V) [HP] (575 V) 50 60 75 100 125 [kW] (690 V) 45 55 75 90 110
High overload torque (160 %):
I
Output current
I
VLT, MAX
I
VLT, MAX
Output
S Typical shaft output
[A] (525-550 V)
VLT,N
(60 s) [A] (525-550
[A] (551-690 V)
I
VLT,N
(60 s) [A] (551-690
[kVA] (550 V)
S
VLT,N
[kVA] (575 V)
S
VLT,N
[kVA] (690 V)
VLT,N
[kW] (550 V) [HP] (575 V) 40 50 60 75 100
Max. cable cross-section to motor
Max. cable cross-section to loadsharing and brake
[kW] (690 V) 37 45 55 75 90
[mm2]
[AWG]
[mm2]
[AWG]
Normal overload torque (110 %):
I
Rated input current
I
[A] (550 V)
L,N
[A] (575 V)
I
L,N
[A] (690 V)
L,N
High overload torque (160 %):
I
Rated input current
I Max. cable cross-section power supply
[A] (550 V)
L,N
[A] (575 V)
I
L,N
[A] (690 V)
L,N
[AWG]
[mm2]
Max. pre-fuses (mains) [-]/ UL Efficiency Power loss
Weight
3
Normal overload [W]
High overload [W] 1355 1459 1721 1913 2264
IP 00 [kg] Weight IP 21/Nema1 [kg] 96 Weight
IP 54/Nema12 [kg] 96
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
56 76 90 113 137 62 84 99 124 151
V)
54 73 86 108 131 59 80 95 119 144
V)
53 72 86 108 131 54 73 86 108 130 65 87 103 129 157 37 45 55 75 90
48 56 76 90 113 77 90 122 135 170
V)
46 54 73 86 108 74 86 117 129 162
V)
46 53 72 86 108 46 54 73 86 108 55 65 87 103 129 30 37 45 55 75
2,4,6
2,4,6
4,6
4,6
2 x 70 2 x 2/0
2 x 70 2 x 2/0
60 77 89 110 130 58 74 85 106 124 58 77 87 109 128
53 60 77 89 110 51 58 74 85 106 50 58 77 87 109
4,6
2,4,6
1
125 160 200 200 250
[A]
2 x 70 2 x 2/0
0.97 0.97 0.98 0.98 0.98 1458 1717 1913 2262 2662
82
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and loadsharing: M8
30 MG.52.A3.02 - VLT® is a registered Danfoss trademark
Loading...
+ 162 hidden pages