Danfoss VLT 4000, VLT5000, VLT6000 HVAC, VLT8000 AQUA Installation guide

Danfoss VLT 4000, VLT5000, VLT6000 HVAC, VLT8000 AQUA Installation guide

VLT® Instruction

Drives and Controls

Instruction for exchange of a Power Card

VLT® Frequency converters

type 4002-4032, 200-240 V/4002-4072, 380-460 V, 600 V type 5001-5027, 200-240 V/5001-5062, 380-500 V, 600 V type 6002-6032, 200-240 V/6002-6072, 380-460 V, 600 V type 8002-8032, 200-240 V/8002-8072, 380-460 V, 600 V

Instruction

This power card can be used for Standard, Standard with brake chopper. Therefore the following programming is necessary.

After the exchange of the power card the VLT automatically starts in SERVICE MODE after power up.

All 11 questions in the display of the SERVICE MODE must be answered. Please see enclosure.

MI.56.E3.02 - VLT is a registered Danfoss trademark

175R0031

 

 

VLT® 4000/5000/6000 HVAC/8000 AQUA

 

 

Sparepart Service Mode data for VLT® 4000/5000/6000 HVAC/8000 AQUA

 

 

 

 

 

 

 

 

 

Va lue (W here to find)2

 

 

 

Me nu Pa ra m e te r1

 

Note s3 4

 

 

00

BRAND

1: Danfoss

Possible to change brand, meaning

 

 

 

2: Bauer

brand specific texts.

 

 

 

3: Brook Hansen

 

 

 

 

 

4: Neutral brand

 

 

 

 

 

 

 

 

01

VLT SALES NUMBER

Red label on VLT

Possible to change x in 17??xxxx

 

02

POW ER SECTION

Red label on VLT

Select type:

 

 

 

Only VLT 5000

STANDARD

 

 

 

 

STANDARD W ITH BRAKE

 

 

 

 

EXTENDED W ITH BRAKE

 

03

ENCLOSURE TYPE

Look on VLT

Select type:

 

 

 

 

BOOKSTYLE

 

 

 

 

COMPACT

 

 

 

 

IP54

(Compact)

 

04

ENCAPSULATION IP

Red label on VLT

Select type:

 

 

 

 

IP00

 

 

 

 

 

IP20

 

 

 

 

 

IP54

 

 

 

 

 

 

 

05

ENCAPSULAT. NEMA

Red label on VLT

Select type:

 

 

 

 

CHASSIS

 

 

 

 

 

NEMA 1

 

 

 

 

 

NEMA 12

 

 

 

 

 

 

 

06

RFI FILTER

VLT 5001-11: Then RFI

Select type:

 

 

 

CLASS B1

NONE

(No built-in RFI filter)

 

 

 

VLT 5016-62+VLT6000 with

RFI CLASS A1

 

 

 

RFI: Then RFI CLASS B1

RFI CLASS B1

 

 

 

else NONE

 

 

 

07 FAN TYPE

VLT 5000 + VLT 6000:

Select type:

 

 

 

Then ON-OFF CONTROL

NO FAN

 

 

 

 

 

ON-OFF CONTROL

 

 

 

 

PW M CONTROL

 

 

 

 

 

 

08

BRAKE TYPE

If (VLT 5000) with Brake:

Select type:

 

 

 

Then W ITH SHORT

NONE

(No brake function in drive)

 

 

 

PROTECT else NONE

W ITH SHORT PROTECT

 

09

EXTERNAL 24V

If (VLT 5000) extended:

Select type:

 

 

 

Then YES else NO

NO

(No external 24V in drive)

 

 

 

 

YES

(With 24V external supply)

 

10

FAST DISCHARGE

If (VLT 5000) extended:

Select type:

 

 

 

Then YES else NO

NO

(No fast discharge possible)

 

 

 

 

YES

(With fast discharge)

 

11 LOAD SHARING TYPE

If (VLT 5000) extended:

Select type:

 

 

 

Then TYPE 5 else NONE

NONE

(No load sharing possible)

 

 

 

 

TYPE 5

(With load sharing betw een

 

 

 

 

 

rectifier and DC-coils.

 

 

 

 

 

Inrush after load sharing.

 

 

 

 

 

2 coils

 

 

 

 

 

 

 

1 Menu param eter after a power-up (only the first tim e) with a s parepart power card. To re-s tart Service Mode push [QUICK MENU] + [CANCEL] + [<] at power-up.

2

Value as it is today (POWER UNIT DB ID, par. 627 = 1,31), which m ay change!

3

In the Design Guide for VLT 5000, the values for m enu param eter 01, 02, 03, 04, 05 and 06 can be found.

4

Only the m ost us ed Select types are s hown.

 

 

 

 

 

2

175R0031

*MI56E302*

MI.56.E3.02 - VLT is a registered Danfoss trademark

 

 

 

Loading...