Drives and Controls
VLT
®
Instruction
Instruction for
exchange of a Power Card
VLT® Frequency converters
type 4002-4032, 200-240 V/4002-4072, 380-460 V, 600 V
type 5001-5027, 200-240 V/5001-5062, 380-500 V, 600 V
type 6002-6032, 200-240 V/6002-6072, 380-460 V, 600 V
type 8002-8032, 200-240 V/8002-8072, 380-460 V, 600 V
InstructionInstruction
Instruction
InstructionInstruction
■■
■
■■
This power card can be used for Standard, Standard with brake chopper. Therefore the following
programming is necessary.
After the exchange of the power card the VLT
automatically starts in SERVICE MODE after power
up.
All 11 questions in the display of the SERVICE
MODE must be answered. Please see enclosure.
MI.56.E3.02 - VL T is a registered Danfoss trademark
175R0031
VLT® 4000/5000/6000 HVAC/8000 AQUA
Sparepart S erv ice Mode data for VL T® 4000/5000/ 6000 H VAC/ 8000 AQU A
Menu P a ram e ter
00 BRAND
01 VLT SALES NUMBER
02 POWER SECTION
03 ENCLOSURE TYPE
04 ENCAPSULATION IP
05 ENCAPSULAT. NEMA
06 RFI FILTER
1
07 FAN TYP E
08 BRAKE TYPE
09 EXTERNAL 24V
10 FAST DISCHARGE
11 LOAD SHARING T YPE
V alu e (Wh e r e to fi n d )
1: Danfoss
2: Bauer
2
3 4
Notes
Pos s ible to change brand, meaning
brand specific tex ts .
3: Brook Hans en
4: Neutral brand
Red label on V LT Pos s ible to change x in 17??xx x x
Red la bel on V L T Se lect t y pe :
Only VLT 5000
STANDARD
STANDARD W ITH BRAKE
EXTENDED W ITH BRAKE
Look on VLT Selec t ty pe:
BOOKSTYLE
COMPACT
IP54
Compact
(
)
Red la bel on V L T Se lect t y pe :
IP00
IP20
IP54
Red la bel on V L T Se lect t y pe :
CHASSIS
NEM A 1
NEM A 1 2
VLT 5001-11: Then RFI Selec t ty pe:
CLASS B1 NONE
VLT 5016-62+VLT6000 with
RFI
: Then RFI CLASS B1
RFI CLASS A1
RFI CLASS B1
(No built-in RFI filter)
else NONE
VLT 5000 + VLT 6000:
Select type:
Then ON-OFF CO NTROL NO FAN
ON-OF F CO NTROL
PWM CONTROL
If (VLT 5000)
Then WITH SHORT NONE
Brake: Select type:
with
(No brake function in drive)
PROTECT else NONE WITH SHORT PROTECT
If (VLT 5000)
extended:
Then YES else NO NO
If (VLT 5000)
extended:
Then YES else NO NO
If (VLT 5000)
extended:
Then TY P E 5 els e NO NE NONE
Select type:
(No external 24V in drive)
YES
(With 24V external s up ply )
Select type:
(No f ast dischar ge possible)
YES
(With fast discharge)
Select type:
(No load sharing possible)
TYPE 5
Inr ush after lo ad sharing.
2 coils
(With load shar ing betw een
rectifier and DC-coils.
1
Menu parameter after a power-up (only the first time) with a sparepart power card.
To re-start Service Mode push [QUICK MENU] + [CANCEL] + [<] at power-up.
2
Value as it i s today (POWER UNIT DB ID, par. 627 = 1,31), which may change!
3
In the Design Guide for VLT 5000, the values for menu parameter 01, 02, 03, 04, 05 and 06 can be found.
4
Only the most used Select types are shown.
175R0031