Danfoss VLT 3032, VLT 3052, VLT 3042 Service Manual

Table of Contents
Page
Introduction 2 Safety 2
Section One
Section Two
Section Three Static Test Procedures
Section Three Dynamic Test Procedures
Section Four
Description of Operation 5 Sequence of Operation 9
Status Messages 11 Warning Messages 12 Alarm Messages 13 Troubleshooting T ips 17 Flow Charts 18 Symptom/Cause Charts 21
Testing the Soft Charge Circuit 23 Testing the Input Rectifiers 25 Testing the Inverter Section 26 Testing the Heatsink Temperature Sensor 27
Testing for Output Phase Imbalance 27 Testing Gate Drive Firing Circuits 28 Testing Input Rectifiers 30 Testing for Current Feedback 30
Removing and Replacing the Control Card 31 Removing and Replacing the Interface Board 31 Removing and Replacing Gate/Snubber/IGBT 32 Removing and Replacing Input Rectifiers 33
Section Five
Appendix
Current Limit Trips 35 Unstable Motor Operation 35 Ground Fault Trips 37 Overcurrent Trips 37 Overvoltage Trips 38 Overtemperature Trips 39
Additional Fault Codes I Spare Parts List II Block Diagram VLT 3032 III Block Diagram VLT 3042 IV Block Diagram VLT 3052 V
1
INTRODUCTION
The purpose of this manual is to provide technical information and instructions that will enable the user to identify faults and affect repairs on Danfoss series 3000 Adjustable Frequency Drives, VL T 3032 through VLT 3052, 230 Volt models.
The manual has been divided into five sections. The first section covers the description and sequence of operations. Section two covers fault messages and provides troubleshooting charts both in the form of flow and symptom/cause. Section three describes the various tests and methods used to evaluate the drives' condition. Section four covers the removal and replacement of the various components. Section five discusses application-specific information.
ESD SAFETY
Electrostatic discharge. Many electronic components are sensitive to static electricity . Voltages so low that they cannot be felt, seen or heard can reduce the life, affect performance, or completely destroy sensitive electronic components.
When performing service, proper ESD equipment should be used to prevent possible damage from occurring.
2
SAFETY
WARNING:
FOR YOUR SAFETY:
The Adjustable Frequency Drive (AFD) contains dangerous voltages when connected to the line voltage. Only a competent technician should carry out the service.
1) DO NOT touch the electrical parts of the AFD when the AC line is connected. After the AC line is disconnected wait at least 15 minutes before touching any of the components.
2) When repairs or inspection is made the AC line must be disconnected.
3) The STOP key on the control panel does not disconnect the AC line.
4) During operation and programming of the parameters the motor may start without warning. Activate the STOP key when changing data.
3
4
SECTION ONE
DESCRIPTION OF OPERATION
LOGIC SECTION
MICROPROCESSOR
RAM
CONTROL
DATA
ADRESS
EPROM
EEPROM
VVC
POWER
KEYBOARD DISPLAY
Refer to the overall schematic in the Appendix. It is not the intention of this manual to enter into a detailed description
of the unit's operation. Moreover, it is intended to provide the reader with a general view of the unit's main assemblies. With this information, the repair technician should have a better understanding of the unit's operation and therefore aid in the troubleshooting process.
The VLT is divided primarily into three sections commonly referred to as: logic, power, and interface.
The control card itself primarily makes up the logic section. The heart of the control card is a microprocessor which controls and supervises all functions of the unit's operation. In addition, a separate PROM contains the parameter sets which characterize the unit and provide the user with the definable data enabling the unit to be adjusted to meet the customer's specific application. This definable data is then stored in an EEPROM which provides security during power-down and also allows flexibility for future changes as needed. A custom integrated circuit generates the PWM waveform which is then sent on to the interface board for distribution to the individual gate drive circuits.
Also, part of the logic section is the keyboard/display mounted on the control card. The keyboard provides the interface between the digital logic and the human programmer. The LCD (Liquid Crystal Display) provides the operator/programmer with menu selection, unit status and fault diagnostic information. Programming is accomplished through the use of four
D
A
POWER
FEEDBACK
2
1
ANALOG INPUTS
DIGITAL INPUTS
of the eight keys available on the keyboard. The additional four keys provide Local Start, Stop, Forward/ Reverse and Jog.
A series of customer terminals are provided for the input of remote commands such as: Run, Stop and Speed Reference. Terminals are also provided to supply outputs to peripheral devices for the purpose of monitoring and control. Two programmable relay
D
ANALOG OUTPUTS
A
1
outputs are also available to interface the unit with other devices.
In addition, the control card is capable of
DIGITAL CHANNEL
1
communicating via a serial link with outside devices such as a personal computer or a programmable logic controller.
RELAY
The control card provides two voltages for use from the customer terminal strip. The 24VDC is used primarily to control functions such as: Start, Stop and Forward/Reverse. The 24VDC is provided from a separate section of the unit's power supply and is delivered to the control card from the interface board via the two conductor ribbon cable.
5
LOGIC SECTION (continued)
A 10VDC supply is also available for use as a speed reference when connected to an appropriate potentiometer. These two voltage references are limited in the amount of available current they can provide (see specifications in Instruction Manual). Attempting to power devices which draw currents in excess of that available may result in an eventual failure of the power supply. In addition, if the supply is loaded too heavily, sufficient voltage will not be available to activate the control inputs.
During the troubleshooting process it is important to remember that the control card can only carry out instructions as it has been commanded. Of course, it is possible that as a result of a failure the control card may fail to respond to commands. For this reason lies the necessity to isolate the fault to the control commands, the control program or the control card itself. If, for example, the unit does not run, but yet an obvious reason is not apparent, check for proper control signals. Has a run command been provided on the correct terminal; and if so, has that terminal been designated as such in the programming of the control card. In addition, be sure to verify that commands are being received by testing for the presence of voltage on the appropriate terminals. Never assume the signal is present because it is suppose to be. If ever in doubt of whether the remote controls are functioning properly , it is possible to take local control of the unit to verify if the control card is operational. A word of caution here: prior to taking local control, insure all other equipment associated with the drive is prepared to operate. In many cases, safety interlocks are installed which can only be activated through the use of a normal remote control start. In the same sense that the control card can only respond to commands, comes the situation that the control card makes a response without the presence of an actual command. By the term response, it is not meant to infer that the control card initiates such actions as Run or Stop, but rather suggests that the control card displays unknown data or its performance is affected as in what might be speed instability. In these cases, the first instinct may be to replace the control card; however, in most instances, this type of erroneous operation is usually due to electrical noise being injected onto the remote control signal wiring. Although the control card has been designed to reject such interference, noise levels of sufficient amplitude can, in fact, affect the performance of the control card.
As mentioned, sufficient levels of electrical noise can cause such things as speed fluctuations as a result of interference with the speed reference or with the operation of the microprocessor. In these situations it is necessary to investigate the wiring practices of the installation. For example, are the control signal wires running in parallel with other higher voltage signals such as the input or output power wiring? As wires are passed in close proximity to one another, voltages are induced through capacitive or inductive coupling. This type of problem can be corrected by rerouting the wiring or through the use of shielded cable. When employing the use of shielded cable, it is important to properly terminate the drain wire. The drain wire is terminated only at the control card end of the wire. Specific terminals are designated for this purpose. The opposite end of the shielded cable drain wire is then cut back and taped off to prevent it from coming in contact with ground or acting as an antenna.
6
LOGIC TO POWER INTERFACE
The logic to power interface isolates the high voltage components of the power section from the low voltage signals of the logic. This is accomplished by use of the interface board. All communication between the control logic and the rest of the unit passes through the interface board. This communication includes: feedback from the current sensors, input from the heatsink temperature sensor, line voltage monitoring, DC Bus voltage monitoring, control of the fans , control of the input thyristor rectifiers and control of the gate drive firing signals. Also on the interface board is the power supply which provides the unit with low voltage power such as 24VDC, 16VDC, 13VDC and 5VDC. The power supply is a Switch Mode Power Supply (SMPS). The switch mode type supply is used due to its efficiency and linearity. Another benefit of the switch mode supply is that it obtains its power from the DC Bus; in the event of a power loss the power supply remains active for a longer period of time versus conventional power supplies.
During the troubleshooting process it is important to determine whether the interface board is receiving or sending the signal that appears to be at fault. For example, the loss of a gate-drive signal is a waveform generated by the interface board and conversely a heatsink over­temperature fault is a result of the interface board receiving an input from the heatsink temperature sensor . If the signal is of the later type (received), it is then necessary to isolate the fault to either the sending device or the interface board. It is generally assumed that a component within the unit is usually at fault; and although this may in fact be the case, it is critical to check all possibilities to avoid costly errors and lengthy downtime. In any case, the interface board is a relatively quick and easy assembly to exchange; and so if it is suspect, a quick exchange will prove the assumption.
7
POWER SECTION
The power section is made up of the SCR/Diode modules (input rectifiers), the soft charge circuit, the DC capacitor bank, the gate drive and snubber cards and the IGBT power devices. Also located in the power section are the DC Bus coil, the motor coils and, although not typically considered part of the power section, the output phase current sensors.
During the troubleshooting process, extreme care is required when probing into the power section components. The DC Bus, when fully charged, can be as high as 350VDC. Although this voltage begins to decrease upon the removal of input power , it takes up to approximately fifteen minutes to fully discharge the DC capacitor bank. Located on the interface board is the Bus Charged Indicator. The red LED is visible through the shield covering the lower portion of the interface board; and as long as it is lit it indicates the DC Bus voltage is greater than 50VDC. A fault in the power section will usually result in at least one of the incoming line fuses being blown. If one or more line fuses have blown, it is not recommended to replace them and reapply power without further investigation. In a case such as this, it would be suggested to conduct the tests listed under Static Test Procedures in Section Three. These tests will result in a thorough check of all the components operating in the power section. In addition, following the identification and replacement of power section components, it is recommended to disconnect the motor wires prior to reapplying power . This precaution opens the path for short circuit currents through the motor in the case that all faulty components have not been replaced.
DC BUSRECTIFIER
R S
T
SIMPLFIED PWM POWER SECTION
INVERTER
M
3Ø
8
SEQUENCE OF OPERATION
When input power is first applied, the SCR/Diode modules (input rectifiers) are not gated so the incoming line voltage is rectified by the soft charge rectifier (BR1). As the DC Bus capacitors charge, the inrush current is limited by the series soft charge resistors (R2 and R3). Following a time delay of approximately one second, the interface board monitors the DC Bus voltage and, providing it has reached an acceptable level, begins sending gate pulses to the SCR/Diode Modules. Once the SCR's have been gated on, they remain in this state and the SCR/ Diode modules act as a normal rectifier. This scenario will only be interrupted if the DC Bus fails to charge. This can be caused by insufficient line voltage, a fault in the Power Section, a fault in the soft charge circuit, and also by an open connection at PINS 1 and 2 of MK15. The SCR Disable input at MK15 is provided as a means to disable the SCR/Diode modules in the case of an external failure such as in the Dynamic Brake option. Note that although the SCR/Diode modules may be disabled, line voltage is still applied to the unit through the soft charge circuit.
Providing the charging process proceeds normally , the power supplies will come up and provide the control card and all other sections of the unit with low voltage control power. At this time the display in the control card will indicate the unit is ready for operation.
Following a run command and a speed reference, the control card delivers the PWM signals (one for each phase) to the interface board. The interface board in turn receives these three signals and creates the six individual gate drive pulses. The gate drive pulses are sent to the respective gate drive circuits located on the gate drive card. From here the output power devices (IGBTS) are switched on and off to develop the PWM waveform which is ultimately delivered to the motor .
As the unit operates, the interface board monitors the status of the units operating condition. Currents in excess of limits, temperatures being exceeded, and voltages out of specification will result in the interface board responding with a fault and sending the appropriate fault message to the control card. When a fault occurs, the interface board will indicate the condition via a series of LED's. The control card will also display a fault message, and in virtually all cases trip the unit off line. Section 2 of this manual describes the fault LED's and messages and provides direction in determining the cause and the solution for the fault condition.
9
SECTION TWO
FAULT INDICATORS AND MESSAGES
A variety of messages are displayed by the control card. Some of these indicate the operational status of the unit while others provide warnings of an impending fault. In addition, there are the alarm messages which indicate that the unit's operation has stopped due to a fault condition. In this section we will deal with only those messages which interrupt the unit's operation. A complete list of status messages can be found in the Instruction Manual. Along with the control card message, the interface board contains several Light Emitting Diodes (LED's) which aid in the identification of the fault condition.
STATUS MESSAGES
CURRENT LIMIT
This message will flash in the display when the unit is operating above the current limit setting as recorded in parameter 209. Parameter 310 may be set to provide a fixed time delay after which the unit will trip.
REF FAULT
This message will flash in the display should any live zero signal be operating outside of its range. For example, 4-20ma has been selected as the speed reference. Should the current loop be broken, the display will flash "REF FAULT". Parameters 414 and 415 may be used to select the unit's response to this condition.
NO 24 VOLT
This message will flash if the 24 volt power supply is missing or out of tolerance. The 24 volt supply is used only for the customer's remote connections.
NO MOTOR
This message will flash if Motor Check has been activated in parameter 313, terminal 27 is enabled and no motor is detected.
11
WARNING MESSAGES
VOLTAGE LOW
This message will flash when the DC Bus voltage has fallen below the lower limit. This is an indication of low line voltage. This is only a warning message, however. If the condition persists, it will result in a unit trip on "Under Voltage".
VOLTAGE HIGH
This message will flash when the DC Bus voltage has exceeded the upper limit. This is an indication of high line voltage or regenerative energy being returned to the bus. This is only a warning message, however. If the condition persists, it will result in a unit trip on "Over Voltage".
INVERT TIME
This message will flash when the inverter ETR value has reached 98%. The inverter ETR begins counting up as soon as the output current exceeds 105% of the unit's continuous current rating. At an inverter ETR value of 100%, the unit trips on "Invert Time".
MOTOR TIME
This message will flash if Motor Thermal Protection has been activated in parameter 315 and the motor ETR value has reached 98%. The motor ETR value begins counting up if the motor is run at slow speed or if the motor is consuming more than 116% of the motor's nominal rated current as entered in parameter 107. At a motor ETR value of 100%, the unit will respond based on the setting in parameter 315. If Trip has been selected, the unit will trip on "Motor Time".
OVERCURRENT
This message indicates at least one of the three output phases has reached the peak current rating. In addition, the "Overcurrent" LED (D8) on the interface board will flicker. During this time the control card is attempting to initiate current limit. If the current rises to fast or the control card cannot control the condition by means of current limit, the unit will trip on "Over Current".
12
ALARM MESSAGES
Alarm messages will be indicated by the following messages appearing in the display and the red alarm LED being lit on the control panel. All alarm messages result in the unit's operation being interrupted and require a Manual or Automatic reset. Automatic reset can be selected in parameters 309 and 312. In addition, the message "Trip" or "Trip Locked" will be displayed. If "Trip Locked" is displayed, the only possible reset is to cycle power and then perform a manual reset. Manual reset is accomplished by means of the front panel push button or by a remote contact closure on the appropriate control terminal. Remedies listed with each alarm message give a basic description of the corrective action which can be taken to correct the fault condition. For a more detailed explanation, see the Sympton/Cause section beginning on page 21 and the application section on page 35. Also note the numbers in parenthesis by each alarm message. These are the codes which will appear in the Fault memory , Parameter 602. See APPENDIX I for more on the Fault memory.
INVERTER FAULT (1)
This message indicates a fault in the power section of the unit. This message may also be displayed if the unit has detected a phase loss on the input. If a phase loss has been detected, the "Loss of Phase" LED (D9) on the interface board will be illuminated and the "Inverter OK" LED (D4) on the interface board will be out. This fault returns a "Trip Locked". Also see Testing The Inverter Section, page 26.
OVER VOLTAGE (2)
This message indicates the DC Bus voltage upper limit has been exceeded. In addition, the "High Bus Voltage" LED (D5) on the interface board will be illuminated and the "Inverter OK" LED (D4) on the interface board will be out. This fault can be caused by high line voltage or regenerative energy being returned from the motor. To remedy this fault condition, reduce the line voltage or extend the Decel Ramp. This fault returns a "Trip". Also see Over Voltage Trips, page 38.
UNDER VOLTAGE (3)
This message indicates the DC bus voltage has fallen below the lower limit. In addition, the "Low Bus Voltage" LED (D6) on the interface board will be illuminated and the "Inverter OK" LED (D4) on the interface board will be out. To remedy this fault, increase the line voltage to the correct value for the unit rating. This fault returns a "Trip". Also see Testing The Soft Charge Circuit, page 23.
OVER CURRENT (4)
This message indicates a short circuit on the output of the inverter. This fault may also be caused by the unit reaching the peak current rating too rapidly for the unit to respond with current limit. An example may be closing an output contactor with the unit at speed and a high inertia load. The "Overcurrent Trip" LED (D7) on the interface board will be illuminated and the "Inverter OK" LED (D4) on the interface board will be out. To remedy this fault, check the output wiring and motor for short circuits. This fault returns a "Trip Locked". Also see Over Current Trips, page 37.
13
ALARM MESSAGES (continued)
GROUND FAULT (5)
This message indicates a leakage to ground on the output of the inverter. The "Ground Fault Trip" LED (D2) on the interface board will be illuminated and the "Inverter OK" LED on the interface board will be out. This fault will also be present if the programming card on the interface board is not installed. To remedy this fault, check the output wiring and motor for ground faults. This fault returns a "Trip Locked". Also see Ground Fault Trips, page 37.
OVER TEMP (6)
This message indicates that the unit's heatsink temperature or the unit's internal ambient temperature has exceeded permissible limits. This fault may also be caused by a trip received from the optional external temperature sensor if a sensor has been connected to terminal MK15 on the interface board. The interface board LED's indicate the nature of the specific trip. In all cases below the "Inverter OK" LED will be out. "Over Temperature Trip" LED (D3) only indicates the unit's heatsink sensor has caused the trip. "Over Temperature Trip" LED (D3) and Internal Over T emperature" LED (D109) illuminated indicates the thermal sensor located on the interface board has detected high ambient temperature within the unit and caused the trip. "Over Temperature Trip" LED (D3) and "External Over Temperature" LED (D108) illuminated indicates the external temperature sensor has caused the trip. To remedy this fault, correct the over-temperature condition. This fault returns a "Trip". Also see Overtemp Trips, page 39.
INVERT TIME (7)
This message indicates the unit has delivered greater than 105% of the unit's continuous current rating for too long (inverse time function). Prior to this fault condition the "Invert Time" warning will be displayed. An indication from the interface board status LED's does not apply . To remedy this fault, reduce the motor load to at or below the unit's continuous current rating. This fault returns a "Trip Locked". During the trip the counter will count down. Upon reaching 90%, the "Trip Locked" will change to "Trip".
MOTOR TIME (8)
This message indicates the motor has consumed greater than 1 16% of the motor's nominal current rating for too long as entered in parameter
107. This fault may also be caused from running the motor at a low speed and high current for too long a period of time. This trip will only occur if the "Motor Thermal Protection" has been activated in parameter
315. Prior to the trip the "Motor Time" warning will be displayed. In addition, this fault may be displayed if an external thermistor has been connected to input 16 and is defective, disconnected or indicating an over-temperature condition. Also note that by selecting "Thermistor" in parameter 400 in error will result in a "Motor Time" fault. An indication from the interface board status LED's does not apply. To remedy this fault, reduce the load on the motor or raise the motor's speed. This fault returns a "Trip Locked". During the trip the counter will count down. Upon reaching 0% the "Trip Locked" will change to "Trip".
14
Loading...
+ 30 hidden pages