Setup of the converter software ........................................................................3
Bus connection ..................................................................................................4
Mapping list ........................................................................................................5
MG.50.Q2.02 – VL T is a registered Danfoss trade mark
1
VLT® 3000 to 5000 Converter
Software version
VLT 3000 to 5000 converter
This manual can be used for the VLT 3000 to
5000 converter, software version 17.xx. The
software version can be seen in VLT 5000
Manual
Option card software version: 17.1x
Profibus DP Norm
parameter 624.
MG.50.Q2.02 – VL T is a registered Danfoss trade mark2
VLT® 3000 to 5000 converter
■Introduction
This VLT 3000 to 5000 converter is a tool intended
for the conversion of a VLT 3000 to a VLT 5000,
which replaces the VLT 3000. The conversion is
possible for all VLT 3000s with the serial numbers
from XXXXXXG265.
To purchase (obligatory):
- VLT 5000 175X
- Software version 17.1x incl. memory option for
standard RS 485 communication,
ordering no. 175z3389
- Software version 17.1x incl. memory option and
Profibus option,
ordering no. 175z4668
Optional:
- Backplate for 5001-5005 Compact IP 20, ordering
no. 175Z2349
- Separate relay card, ordering no.
175Z1814
If two high voltage relays are needed in VLT 5000 a
separate relay card must be purchased
Ordering number 176F1814
For the VL T 5001-5005 Compact IP20 the conversion
the purchase of a backplate (ordering number
175Z2349) is optional aswell.
Please notify some parameters in the VLT 3000 are
not supported in the VLT 5000 (see for example
page 5, parameter 107) and some VLT 5000
parameters can not be accessed via serial
communication.
■Configuration
With the 17.1x software the VLT 5000 will react on
the Profibus network or the Standard Serial RS485
as a VLT 3000; it means that it is not necessary to
change anything in the PLC programme. A write
command to for example ramp up time in VLT 3000
is automatically linked to the corresponding ramp
up time parameter in VLT 5000. The GSD file in the
VLT 5000 will also be as the VLT 3000.
Introduction
IM 308-B ver. 6IM 308-C
This master supportsThis master supports
Profibus DP NormProfibus DP Norm
We support Profibus DP Norm by VLT 3000 with a
software version that should be higher than version
3.00. The software version number can be read
out in parameter 603, choice 3. The master must
be a Profibus DP Norm master. If a master from
Siemens S5 series is used the master must be an
IM-308C or IM-308B and higher or equal to version
6. All Siemens S7 series are Profibus DP Norm.
■Setup of the converter software
Before VLT 3000 can be replaced with a VLT 5000
some parameters need to be setup in the VL T 5000.
Ensure that the parameters in the below table have
the same setting in VLT 5000 as in VLT 3000.
VLT 3000 VLT 5000
Par. 820 Baud Ra te Par. 801 Bau d ra te
Par. 904 PPO ty pe Par. 904 PPO ty pe
Par. 918 St ati on A dd ress Par. 918 Station Addre s s
After copying the baud rate, PPO type and station
address from the VLT 3000 to the VLT 5000, power
must be re-cycled to the VLT 5000 as these
parameters are only valid after power up. The
master should now recognize VLT 5000.
Please note that the converter software will only
work on a Profibus DP Norm network. It will
work on a Sinec L2 or a Siemens DP network. You
can check your Profibus network either by the VLT
3000 or by the master.
MG.50.Q2.02 – VL T is a registered Danfoss trade mark
not
The two LED next to the Profibus connector should
now be solid green which indicates that
communication between master and slave is
established.
3
If LED 1 or LED 4 flashes, the master has not
recognized the LVT 5000. Check if Baud rate, PPO
type and station address are the same in the VLT
5000 as the VLT 3000.
VLT® 3000 to 5000 Converter
Bus connection
■ Bus connection
NOTE:
VLT 5000 has other physical connections
compared to VLT 3000.
VLT 3000
VLT 5000
MG.50.Q2.02 – VL T is a registered Danfoss trade mark4
VLT® 3000 to 5000 converter
V
V
■Mapping list
The below listed VLT 3000 parameters in the left column have the corresponding VLT 5000 parameters as
shown in the right column. Please be notify that the opposite is not the case. the 5000 series using the LCP.
LT 3000 Series
000 Language Select001 Language
001 Se tu p Selecti on Opera ti o n004 Ac tive Setup
002 Setup Copy006 Copying of Setups
003 Operation Site002 Local/remote Control
004 Local referenceNot available via serial com.
005 Display Value008 Display Scaling of M ot or Fre quency
006 Lo cal Reset017 Local Rese t of Tr i p
007 Local stopNot available via serial com.
008 Local reversingNot available via serial com.
009 Lo cal Jo gging015 Lo cal Jo g
010 Local referenceNot available via serial com.
011 Reset Energy Counter618 Reset of kWh Counter
012 Reset Hour Counter619 Reset of Hour-Run Counter
014 Power-Up Mode019 Operating State at Power-Up, Lo cal
015 Set-up Selection005 Programming Set-up
100 Load101 Torque characteristics
101 Speed Control100 Configuration
102 Current Limit Control308, 311 and 314, Analogue input function
103 Motor power102 Motor power
104 Motor voltage103 Motor voltage
105 Motor frequency104 Motor frequency
106 Automatic motor adaption107 Automatic motor adaption
107 Motor current105 Motor current
108 Motor magnetizing currentNo valid parameter
109 Start voltageNo valid parameter
110 Start compensationNo valid parameter
111 U/f ratioNo valid parameter
112 Slip compensationNo valid parameter
113 Negative slip compensationNo valid parameter
114 Feedback type308, 311 and 314, Analogue inpu t fun cti on
115 Display Value at min. Feedback414 Minimum Feedback
116 Display Value at max. Feedback415 Maximum Feedback
117 Feedback Type416 Reference/feedback Unit
121 Proport ional Gain440 Process PID Proportiona l Gain
122 Integral Time441 Process PID Integral Time
123 Differentiation Time442 Process PID Differentiation Time
124 Low Pass Filter444 Process PID Low Pass Filter
LT 5000 series
Mapping list
MG.50.Q2.02 – VL T is a registered Danfoss trade mark
5
VLT® 3000 to 5000 Converter
V
V
221 T
Mapping list
LT 3000 Series
200 Frequency Range200 O utput Frequency Range/Direction
201 Min. Frequency201 Out put Fre quency Low L imit
Mapping list
203 Jog frequency213 Jog frequency
204 Digital Reference Type214 Reference Function
205 Digital Reference 1215 Preset Reference 1
206 Digital Reference 2216 Preset Reference 2
207 Digital Reference 3217 Preset Reference 3
208 Digital Reference 4218 Preset Reference 4
209 Current Limit
210 Warning Frequency Low225 Warning: Low Frequency
211 Warning Frequency High226 Warning: High Frequency
212 Warning Current Low223 War ni n g: Low Cu rrent
213 Warning Current High,224 Warning: High Current
214 Ramp type206 Ramp type
215 Ramp-Up Time207 Ramp-Up Time 1
216 Ramp-Down Time208 Ramp-Down Time 1
217 Alternative Ramp-Up Time209 Ramp-Up Time 2
218 Alternative Ramp-Down Time210 Ramp-Down Time 2
219 Frequency bypass 1230 Frequency bypass 1
220 Frequency bypass 2231 Frequency bypass 2
221 Frequency bypass 3232 Frequency bypass 3
222 Frequency bypass 4233 Frequency bypass 4
223 Frequency bypass, bandwidth229 Frequency bypass, bandwidth
224 Carrier Frequency411 Switching Frequency
225 Output Frequency Depend a nt Switch
Frequency
orque Limit in Motor Mode
Parameter 222, Torque limit in Generating
Operation, is set to the same value as parameter
221.
412 Output Frequency Depend a nt Switchin g
Frequency
This parameter is used for setting the level for
general warnings at too low frequencies. In
combination selection of "Mechanical Brake
Control" in parameter 323 and 326 the fun cti onali ty
of this parameter is control of the cut-in frequency
232 Current, Minimum Value223 Warning: Low Current
233 Current, Delay Time120 Start Delay Time
MG.50.Q2.02 – VL T is a registered Danfoss trade mark6
VLT® 3000 to 5000 converter
V
V
q
y
k
Mapping list
LT 3000 Series
300 Brake Option400 Brake Function
301 Start frequency130 Start frequency
302 Start delay120 Start delay
303 High starting torque119 High starti ng torque
304 Mains failure407 Mains failure
305 Flying start445 Flying start
306 DC braking time126 DC braking time
307 DC Brake Cut-in Frequency at Stop
309 Reset Mode405 Reset Function
310 Trip Delay at Current Limit
311 Trip Delay at Inverter Fault410 Trip Delay Inverter
312 Max. Auto Restart Time406 Automatic Restart Time
313 Motor Chec
314 Motor Preheat122 Function at Stop
315 Motor thermal protection128 Motor thermal protection
316 Relay ON-delay324 Relay 01 ON-delay
317 Relay OFF-delay325 Relay 01 OFF-delay
400 Binary Input 16300 Terminal 16 Input
401Binary Input 17301 Terminal 17 Input
402 Binary Input 18302 Terminal 18 Input
403 Binary Input 19303 Terminal 19 Input
404 Binary Input 27304 Terminal 27 Input
405 Binary Input 29305 Terminal 29 Input
406 Binary Input 32306, 307 Terminal 32/33 Input
407 Signal Output 42319 Terminal 42 Output
408 Signal Output 45321 Terminal 45 Output
409 Relay output 01323 Relay output 01
410 Relay output 04326 Relay output 04
411 Analog reference type203, 204, 205 Reference scaling
412 Term. 53 Analog input Voltage309, 310 Analog input 53 scaling
413 Term. 60 Analog input mA315, 316 Analog input 60 scaling
414 Time out317 Time out
415 Time Out Function318 Function after Time Out
LT 5000 series
127 DC Brake Cut-in Fre
409 Trip Delay Torque
Note VLT 5000 is using a Torque limit and not a
Current limit.
122 Function at Stop
uenc
MG.50.Q2.02 – VL T is a registered Danfoss trade mark
7
VLT® 3000 to 5000 Converter
V
V
LT 3000 Series
500 Address500 Adress
501 Baud rate501Baud rate
502 Data read-out009 Display line 2
Mapping list
503 Coasting502 Coasting
504 Q-stop503 Quick Stop
505 DC-brake504 Dc-brake
506 Start505 Start
507 Direction506 Reversing
509 Set-up Select507 Selection of Set-up
510 Digital Speed Select508 Selection of Speed
511 Bus Jogging 1509 Bus Jog 1
512 Bus Jogging 2510 Bus Jog 2
513 Catch up/Slow down value219 Catch up/Slow down value
514 Bus bit 4No valid parameter
515 Bus bit 11/12No valid parameter
516 Bus referenceNo valid parameter
517 Store data valuesNo valid parameter
600 Index 1. Total Operating Hours600 Operating Data: Operating Hours
600 Index 2. Running Hours601 Operating Data: Hours Run Hours
600 Index 3. kWh counter602 Operating Data: kWh Counter
600 Index 4. Number of Cut-ins603 Operating Data: Number of Power-ups
600 Index 5. Number of Overheatings604 Operating Data: Number of Overtemperatures
600 Index 6. Number of Overvoltages605 Operating Data: Number of Overvoltages
604 Operation mode620 Operation mode
650 VLT type621 VLT type
LT 5000 series
700 U
701 f
702 U
703 f
704 U
705 f
706 U
707 f
708 U
709 f
voltage
a
frequency
a
voltage
b
frequency
b
voltage
c
frequency
c
voltage
d
frequency
d
voltage
e
frequency
e
423 U1 voltage
424 F1 frequency
425 U2 voltage
426 F2 frequency
427 U3 voltage
428 F3 frequency
429 U4 voltage
430 F4 frequency
431 U5 voltage
432 F5 frequency
MG.50.Q2.02 – VL T is a registered Danfoss trade mark8
VLT® 3000 to 5000 converter
V
V
k
Mapping list
LT 3000 Series
800 Data read-out: Reference %515 Data Read-Out: Reference %
801 Data read-out: Frequency518 Data read-out: Frequency
802 Data read-out: Feedback517 Data Read-Out: Feedbac
803 Data read-out: Current520 Data read-out: Current
804 Data read-out: Torque521 Data read-out: Torque
805 Data read-out: Power kW522 Data read-out: Power kW
806 Data read-out: Power hp523 Data read-out: Power hp
807 Data read-out: Energy602 Operating data kWh counter
808 Data read-out: Output voltage524 Data read-out: Motor voltage
809 Data read-out: DC voltage5 25 Data read-out: DC voltage
810 Data read-out: Motor Therm %526 Data Read-Out: Motor Temp
811 Data read-out: Inverter Therm %527 Data Read-Out: VLT Temp
812 Data read-out: Digital input528 Data read-out: Digital input
813 Data read-out: Analogue Input te rm. 53529 Data Read-Out: Terminal 53; Anal ogue In pu t
814 Data read-out: Analogue Input te rm. 60531 Data Read-Out: Terminal 60; Anal ogue In pu t
816 Alarm Parameters538 Data Read-Out: Alarm Word
817 Relay 01 function32 3 Relay 01, Ou tpu t
818 Relay 04 function32 6 Relay 04, Ou tpu t
819 SAP Select806 SAP Number Select
820 Baud rate select801 Baud rate
821 FMS/DP Select
822 Minimum station delay802 Minimum station delay
823 Bus time out802 Bus time out
824 Time Out Function804 Bus Time Out Function
LT 5000 series
800 Protocol Select
1 byte PPO is not supported.
904 PPO type select904 PPO type select
915 Assign Parameter no.s to PCD’s write915 PCD config. Write
916 Assign Parameter no.s to PCD’s Read916 PCD config. Read
917 Activate Spontaneous/event Messages917 Activate Spontaneous messages
918 Station Address918 Station Address
927 Access to Parameter Change927 Parameter Edit
928 Access to Process Control928 Process Control
953 Bitstream (35)540 Data Read-Out: Warning word
967 Control Word967 Control Word
968 Status Word968 Status Word
970 Set-up Selection, Programming970 Edit Set-up Selection
971 Store data values971 Store data values
MG.50.Q2.02 – VL T is a registered Danfoss trade mark
9