General information about electrical installation11
EMC-correct electrical installation12
Grounding of shielded/armored control cables13
Diagram14
Electrical installation15
Safety clamp17
Prefuses17
AC line connection17
Motor connection18
Direction of motor rotation19
Motor thermal protection19
Parallel connection of motors19
Motor cables19
Brake connection20
Ground connection20
Load sharing20
Tightening Torque, Power Terminals21
Calculation of brake resistance21
Access to control terminals21
Electrical installation, control circuitry21
Tightening torques, control cables22
Electrical installation, control terminals22
Relay connection23
VLT Software Dialog23
Connection examples24
Control unit26
Manual initialization26
Automatic motor tuning27
Display readout29
Hand Auto29
Warnings/alarms30
Special conditions31
Temperature-related switching frequency31
Derating for long motor cables31
3
6
MG.27.A2.22 - VLT® is a registered Danfoss trademark 1
VLT® 2800 Series
VLT 2800 start-up31
Programming
Operation & Display33
Load and Motor41
References & Limits52
Inputs and Outputs59
Special functions69
Enhanced Sleep Mode79
Serial communication84
Technical functions93
All about VLT 2800
Warnings/alarm messages98
Warning words, extended status words and alarmwords102
Special conditions103
Extreme environments103
Galvanic Isolation (PELV)103
UL Standard104
General technical data105
Technical data, mains supply 1 x 220 - 240 V/3 x 200-240V110
Technical data, mains supply 3 x 380 - 480 V111
Available literature112
Supplied with the unit112
33
98
2 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
VLT 2800
Instruction Manual
Software version: 3.1x
This Design Guide can be used for all VLT 2800 series adjustable frequency drives with software version 3.1x.
The software version number is indicated in parameter 640.
Warning
It can be extremely dangerous to touch the electrical parts, even when the line supply has been disconnected.
Also ensure that other voltage inputs are disconnected from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been removed before servicing the drive.
Introduction to VLT 2800
MG.27.A2.22 - VLT® is a registered Danfoss trademark 3
VLT® 2800 Series
High voltage warning
The voltage of the frequency converter is
dangerous whenever the converter is connected to mains. Incorrect fitting of the
motor or frequency converter may cause
damage to the equipment, serious injury
or death. Consequently, it is essential to
comply with the instructions in this manual
as well as local and national rules and
safety regulations.
The Protective Extra Low Voltage (PELV)
requirements stated in IEC 61800-5-1 are
not fulfilled at altitudes above 2000 m
(6562 ft.). For 200V frequency converters
the requirements are not fulfilled at altitudes above 5000 m (16 404 ft.). Please
contact Danfoss Drives for further information.
These rules concern your safety.
1.The adjustable frequency drive must be disconnected from AC line if repair work is to be
carried out. Ensure that the line supply has
been disconnected and that the prescribed
time has passed before removing motor and
AC line plugs.
2.The [STOP/RESET] key on the control panel
of the adjustable frequency drive
disconnect the equipment from line power
and is therefore not to be used as a safety
switch.
does not
tion of the motor, class 20, in accordance with
NEC.
6.Do
7.Note that the adjustable frequency drive has
Warning against unintended start
1.The motor can be brought to a stop by means
2.While parameters are being changed, the
3.A motor that has been stopped may start if
not remove either the plugs for the motor
or line supply while the adjustable frequency
drive is connected to line power. Ensure that
the line supply has been disconnected and
that the prescribed time has passed before
removing motor and AC line plugs.
more voltage inputs than L1, L2 and L3 when
the DC bus terminals are used. Check that all
voltage inputs are disconnected and that the
prescribed time has passed before repair
work is commenced.
of digital commands, bus commands, references or a local stop, while the frequency
converter is connected to mains. If personal
safety considerations make it necessary to
ensure that no unintended start occurs,
stop functions are not sufficient.
motor may start. Consequently,
[STOP/RESET] must always be activated,
following which data can be modified.
faults occur in the electronics of the frequency converter, or if a temporary overload or a
fault in the supply mains or the motor connection ceases.
the stop key
these
3.The unit must be properly grounded, the user
must be protected against the supply voltage,
and the motor must be protected against
overloading in accordance with prevailing national and local regulations.
4.The ground leakage currents are higher than
3.5 mA.
5.Protection against motor overload is not included in the factory setting. If this function is
required, set parameter 128 Motor thermal
protection to data value ETR trip or data value
ETR warning. For the North American market:
The ETR functions provide overload protec-
4 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Motor overload protection
The electronic thermal relay (ETR) in UL listed VLTs
provides Class 20 motor overload protection in accordance with the NEC in single motor applications
when parameter 128 is set for "ETR TRIP" and pa-
Warning
It can be extremely dangerous to touch the electrical parts, even when the line supply has been disconnected.
Also ensure that other voltage inputs are disconnected from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been removed before servicing the drive.
rameter 105 Motor current is set for the rated motor
current.
Introduction to VLT 2800
MG.27.A2.22 - VLT® is a registered Danfoss trademark 5
VLT® 2800 Series
Mechanical dimensions
The drawings below describe the mechanical dimensions. All dimensions are given in mm.
NOTE
Please note that all filter options must be
vertically mounted.
VLT 2803-2815 200-240 Volt
VLT 2805-2815 380-480 Volt
The drawing below gives the mechanical dimensions
of VLT 2822 (3 HP) 200-240 Volts and VLT 2822-2840
(3 - 5 HP) 380-480 Volts. All dimensions are in inches.
VLT 2822 220 - 240 V, PD2
VLT 2840 200 - 240 Volt
VLT 2855-2875 380 - 480 Volt
VLT 2840 220 - 240 V, PD2
VLT 2880-82 380 - 480 V
VLT 2822 200-240 Volt
VLT 2822-2840 380-480 Volt
6 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Motor coils (195N3110)
RFI 1B filter (195N3103)
Terminal cover
The drawing below gives the dimensions for NEMA 1
terminal covers for VLT 2803-2875.
Dimension 'a' depends on the unit type.
Installation
IP 21 solution
MG.27.A2.22 - VLT® is a registered Danfoss trademark 7
8 MG.27.A2.22 - VLT® is a registered Danfoss trademark
192H4720
VLT® 2800 Series
Installation
192H4893
MG.27.A2.22 - VLT® is a registered Danfoss trademark 9
VLT® 2800 Series
Mechanical installation
The adjustable frequency drive is cooled by air circulation. For proper cooling, allow a minimum of 4 inches
(100 mm) of open space above and below the unit. To
protect the unit from overheating, ensure that both the
ambient temperature and the 24-hour average temperature are not exceeded. The maximum temperature and 24-hour average are listed in Generaltechnical data in this manual. If the ambient temperature is in the range of 113°F - 131°F (45°C - 55°C),
derating of the drive must be carried out. See Deratingfor ambient temperature in this manual. The service life
of the unit will be reduced without applicable derating.
The requirements that apply to enclosures
and remote mounting must be complied
with to avoid serious injury or equipment
damage, especially when installing large
units.
Enclosures
In the USA and some other countries, a NEMA 1 terminal cover enclosing terminal connectors is required
if the drive is not installed within another enclosure.
Side-by-side
All VLT 2800 units can be installed side-by-side and in
any position, as the units do not require ventilation on
the side.
Spacing for mechanical installation
All units require a minimum of 4 in of air from other
components above and below the enclosure.
NOTE
With the IP 21 solution all units require a
minimum of 4 in air on each side. This
means that side-by-side mounting is
allowed.
not
10 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
General information about electrical installation
High voltage warning
The voltage of the adjustable frequency
drive is dangerous whenever the drive is
connected to the AC line. Incorrect installation of the motor or drive may cause
damage to the equipment, serious injury
or death. Comply with the safety instructions in this manual as well as local and
national rules and safety regulations.
Touching electrical parts may be fatal even after the equipment has been disconnected from the AC line. Wait at least
4 minutes for current to dissipate.
NOTE
It is the responsibility of the user or installer to ensure correct grounding and protection in accordance with national and
local standards.
High voltage test
A high voltage test can be performed by short-circuiting terminals U, V, W, L1, L2 and L3, and applying a
max. of 2,160 V DC in 1 sec. between this short-circuit
and terminal 95.
Do not perform a high voltage test between the control terminals and the chassis, because the voltage potential of the
control card cannot exceed approximately
100 volts with respect to chassis due to a
voltage limiting circuitry.
The terminals are protected against direct
hazardous access through barriers.
Installation
Earthing
Comply with the following at installation:
•Safety earthing: The drive has a high leakage
current and must be earthed properly for
safety. Follow all local safety regulations.
•High frequency earthing: Keep earthing connections as short as possible.
Connect all earthing SYSTEMs to ensure the lowest
possible conductor impedance. The lowest possible
conductor impedance is achieved by keeping the conductor as short as possible and by grounding with the
greatest possible surface area. If multiple drives are
installed in a cabinet, the cabinet backplate, which
must be made of metal, should be used as a joint earth
reference plate. The drives must be fitted to the backplate at the lowest possible impedance.
To achieve low impedance, connect the drive to the
backplate with the drive fastening bolts. Remove all
paint from the contact points.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 11
VLT® 2800 Series
EMC-correct electrical installation
General points to be observed to ensure EMC-correct
electrical installation.
Use only shielded/armoured motor cables
-
and shielded/armoured control cables.
Connect the screen to ground at both ends.
-
Avoid installation with twisted shield ends
-
(pigtails), since this ruins the shielding effect
at high frequencies. Use cable clamps instead.
It is important to ensure good electrical con-
-
tact from the installation plate through the
installation screws to the metal cabinet of the
variable frequency drive.
Use starwashers and galvanically conductive
-
installation plates.
Do not use unshielded/unarmoured motor
-
cables in the installation cabinets.
The illustration below shows EMC-correct electrical installation, in which the variable frequency drive has
been fitted in an installation cabinet and connected to
a PLC.
12 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Grounding of shielded/armored control cables
In general, control cables must be shielded/armored,
and the shield must be connected to the unit's metal
cabinet with a cable clamp at each end.
The drawing below shows the correct way to perform
the grounding, and what to do when in doubt.
1.
Correct grounding
Control cables and cables for serial communication must be attached with cable clamps
at both ends to ensure the maximum possible
electrical contact.
2.
Incorrect grounding
Do not use twisted shield ends that are plaited together (pigtails), as these increase
shield impedance at higher frequencies.
3.
Protection with respect to ground potential between the PLC and VLT
If the ground potential between the VLT adjustable frequency drive and the PLC, etc. is
different, electric noise may occur that will
disturb the whole system. This problem can
be solved by fitting an equalizing cable next
to the control cable. Minimum cable cross-
2
section: 0.025 in
[16 mm2].
VLT® 2800 Series
Installation
4.
In the event of a 50/60 Hz ground loop
If very long control cables are used, 50/60 Hz
ground loops can arise, and these can interfere with the whole system. This problem is
resolved by attaching one end of the shield to
the ground via a 100 nF capacitor (short pin
length).
MG.27.A2.22 - VLT® is a registered Danfoss trademark 13
Diagram
* Integrated 1A RFI filter and brake is an option.
** VLT 2803-2815 200-240 V is not supplied with intermediate circuit coils.
VLT® 2800 Series
14 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Electrical installation
See also the section Brake Connection.
VLT® 2800 Series
Installation
VLT 2822 200-240 V, 2822-2840 380-480 V
VLT 2803-2815 200-240 V, 2805-2815 380-480 V
MG.27.A2.22 - VLT® is a registered Danfoss trademark 15
VLT® 2800 Series
VLT 2840 200-240 V, VLT 2822 PD2, 2855-2875
380-480 V
VLT 2880-2882 380-480 V, VLT 2840 PD2
Please note that the units will be supplied with two
bottom plates, one for metric glands and one for conduits.
16 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Safety clamp
To maintain the galvanic isolation (PELV) between the
control terminals and high-voltage terminals, the accompanying safety clamp must be attached to VLT
2803-2815, 200-240 V, and VLT 2805-2815, 380-480
V. Attach the safety clamp to the strain relief plate with
the two screws provided.
For all unit types, external prefuses must be fitted in
the line supply to the adjustable frequency drive. For
UL/cUL applications with a line voltage of 200-240
Volt, use prefuses type Bussmann KTN-R (200-240
Volt) or Ferraz Shawmut type ATMR (max. 30A). For
UL/cUL applications with a line voltage of 380-480
Volt, use prefuses type Bussmann KTS-R (380-480
Volt).
Prefuses for UL application /cUL
Prefuses
Alternative fuses 380-500 V drives
VLT 2800Bussmann
All drives that are equipped with an RFI
filter cannot be connected to a grounded
DELTA or IT mains/AC line system.
NOTE
Check that the AC voltage matches the
voltage rating of the drive. The drive rating
is on the drive nameplate. See Technicaldata in this manual for correct dimensioning of cable cross-section.
For single phase 220-240 Volts input, attach the neutral wire to terminal N
to terminal L1
No.N
(L2)L1(L1) (L3)
NL1
(L1)
.
and connect the phase wire
(L2)
AC line voltage 1 x 220-240 V
No.95Ground connection
No.N
(L2)L1(L1) (L3)
L2L1L3
AC line voltage 3 x 220-240 V
No.95Ground connection
No.91 92 93 AC line voltage 3 x 380-480 V
L1 L2 L3
No.95Ground connection
380-460 Volt units with RFI-filters may
not be connected to AC line supplies in
which the voltage between phase and
ground is more than 300 Volts. Please
note that for the AC line for IT and the delta
ground the AC line voltage can exceed
300 Volts between phase and ground.
Units with type code R5 can be connected
MG.27.A2.22 - VLT® is a registered Danfoss trademark 17
to mains supplies with up to 400 V between phase and ground.
See Technical data for correct dimensioning of cable
cross-section.
Motor connection
Connect the motor to terminals 96, 97, 98. Connect
ground to terminal 99.
96 97 98 Motor voltage 0-100% of line
No.
voltage.
UVW
U1W2V1U2W1V2 6 wires out of motor, Delta-con-
U1 V1 W1 6 wires out of motor, Star-con-
3 wires of motor
nected
nected
U2, V2, W2 to be interconnected separately (optional terminal block)
VLT® 2800 Series
No. PE Ground connection
See Technical data for correct dimensioning of cable
cross-section.
18 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
All types of three-phase asynchronous standard motors can be connected to an adjustable frequency
drive. Normally, small motors are star-connected
(230/400 V, / Y), while large motors are delta-con-
nected (400/690 V, / Y). The correct connection
mode and voltage can be read from the motor nameplate.
NOTE
In motors without phase insulation paper,
an LC filter should be fitted on the output
of the adjustable frequency drive.
Direction of motor rotation
To change the direction of motor rotation, switch any
two phases at the drive output or at motor terminals.
Motor thermal protection
The electronic thermal relay in UL approved variable
frequency drives has received the UL approval for single motor protection, when parameter 128 Motor ther-mal protection has been set for ETR Trip and
parameter 105 Motor current, I
has been program-
M, N
med to the rated motor current (see motor nameplate).
The adjustable frequency drive is able to control several motors connected in parallel. If the motors are to
have different rpm values, use motors with different
rated rpm values. Motor rpm is changed simultaneously, which means that the ratio between the rated
rpm values is maintained across the range. The total
current consumption of the motors is not to exceed the
maximum rated output current I
for the adjustable
INV
frequency drive.
Problems may arise at the start and at low rpm values
if the motor sizes are widely different. This is because
the small motors' relatively high ohmic resistance in
the stator calls for a higher voltage at the start and at
low rpm values.
In systems with motors connected in parallel, the electronic thermal relay (ETR) of the adjustable frequency
drive cannot be used as motor protection for the individual motor. For this reason, further motor protection
must be used, such as thermistors in each motor or an
individual thermal relay, for example (circuit breakers
are not a suitable means of protection).
NOTE
Parameter 107 Automatic motor adaptation, AMT cannot be used when motors
are connected in parallel. Parameter 101
Torque characteristic must be set to Special motor characteristics [8] when motors
are connected in parallel.
Motor cables
See Technical data for correct dimensioning of motor
cable cross-section and length. Always comply with
national and local regulations on cable cross-section.
Installation
Parallel connection of motors
NOTE
If an unshielded/unarmored cable is used,
some EMC requirements are not complied with, see EMC test results in the Design Guide.
If the EMC specifications regarding emissions are to
be complied with, the motor cable must be shielded/
armored unless otherwise stated for the RFI filter in
question. It is important to keep the motor cable as
short as possible so as to reduce the noise level and
leakage currents to a minimum. The motor cable shield
must be connected to the metal cabinets of the adjust-
MG.27.A2.22 - VLT® is a registered Danfoss trademark 19
VLT® 2800 Series
able frequency drive and the motor. The shield connections are to be made with the largest possible
surface area (cable clamp). This is enabled by different
installation devices in different adjustable frequency
drives. Connecting with twisted shield ends (pigtails)
is to be avoided, as these spoil the shielding effect at
high frequencies. If it is necessary to break the shield
to install a motor isolator or motor relay. The shield
must be continued at the lowest possible HF impedance.
Brake connection
NOTE
Voltages up to 850 VDC occur on the terminals.
81 82 Brake resistor
No.
R- R+
terminals
Connect the brake resistor wiring to drive terminals 81
and 82. The connection cable to the brake resistor
must be shielded/armored. Connect the shield to both
the ground of the drive and the brake resistor by means
of cable clamps. Dimension the cross-section of the
brake cable to match the brake torque.
Ground connection
Since the leakage currents to ground may be higher
than 3.5 mA, the adjustable frequency drive must always be connected to ground in accordance with applicable national and local regulations. To ensure that
the ground cable has good mechanical connection to
terminal 95, the cable cross section must be a mini-
2
mum 7 AWG (10 mm
). To improve protection even
further, a Recidual Current Device (RCD) can be fitted
to ensure that the adjustable frequency drive cuts out
when the leakage currents get too high. Also see RCD
Application note MN.90.GX.02.
Load sharing
Load sharing provides the facility to connect several
frequency converters' DC intermediate circuits. This
requires that the installation is extended using extra
fuses and AC coils (see drawing below). For load sharing parameter 400 Brake function must be set to Loadsharing [5].
Use 6.3 mm Faston Plugs for DC (Load Sharing).
Contact Danfoss or see instructions no. MI.50.NX.02
for further information.
8889 Loadsharing
No.
-+
20 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Note that voltage levels of up to 850 V DC
may occur between terminals 88 and 89.
Tightening Torque, Power Terminals
Power and ground terminals must be tightened with
the following torques:
VLT
28032875
28802882, 2840
PD2
TerminalsTorque [Nm]
Power AC line brake0.5-0.6
Ground2-3
Power AC line brake1.2-1.5
Ground2-3
VLT® 2800 Series
Installation
NOTE
This application is only for lifting/lowering
without a counterbalance.
Access to control terminals
All control terminals are located underneath the protective plate on the front of the adjustable frequency
drive. Remove the protective plate by sliding it downwards (see drawing).
Calculation of brake resistance
In lifting/lowering applications you need to be able to
control an electromagnetic brake. The brake is controlled using a relay output or digital output (terminal
46). The output must be kept closed (voltage-free) for
the period of time during which the variable frequency
drive is not able to 'support' the motor, for example due
to the load being too great. Select Mechanical brakecontrol in parameter 323 or 341 for applications with
an electromagnetic brake.
When the output frequency exceeds the brake cut out
value set in par. 138, the brake is released if the motor
current exceeds the preset value in parameter 140.
When stopping the brake is engaged when the output
frequency is less than the brake engaging frequency,
which is set in par. 139.
If the variable frequency drive is placed at alarm status
or in an overvoltage situation the mechanical brake is
cut in immediately.
Electrical installation, control circuitry
NOTE
Using unshielded/unarmored cable may
not comply with some EMI/RFI requirements.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 21
Control wires must be shielded/armored. Connect the
shield to the drive chassis with a clamp. Normally, the
VLT® 2800 Series
shield must also be connected to the chassis of the
controlling device. (See the instructions for the specific
device.) In analog signals or connections using very
long wires, 50/60 Hz ground loops may occur because
of noise transmitted from the AC line. It may be necessary to break the shield and insert a 100 F capacitor between the shield and the chassis.
Tightening torques, control cables
Control wires must be connected with a tightening torque of 0.22-0.25 Nm.
Electrical installation, control terminals
See section entitled Grounding of shielded/armored
control cables in the VLT 2800 Design Guide for the
correct termination of control cables.
22 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
No.Function
01-03Relay outputs 01-03 can be used for
indicating status and alarms/warnings.
1224 V DC voltage supply.
18-33Digital inputs.
20, 55Common frame for input
and output terminals.
42Analog output for displaying frequency,
reference, current or torque.
46
Digital output for displaying status,
1
warnings or alarms, as well as
frequency output.
50+10 V DC supply
voltage for potentiometer or thermistor.
53Analogue voltage input 0-10 V DC.
60Analogue current input 0/4 - 20 mA.
67
+ 5 V DC supply voltage
1
to Profibus.
68, 691RS-485, Serial communication.
70
Frame for terminals 67, 68 and 69.
1
Normally, this terminal is not to be used.
1. The terminals are not valid for DeviceNet/CANopen.
See also the DeviceNet manual, MG.90.BX.YY for further details.
Profibus DIP switches setting
The dip switch is only on the control card with Profibus
DP communication. The switch position shown is the
factory setting. Switches 1 and 2 are used as cable
termination for the RS-485 interface. If the adjustable
frequency drive is located as the first or last (or only)
unit in the bus system, switches 1 and 2 must be ON.
On the remaining adjustable frequency drives,
switches 1 and 2 must be OFF. Switches 3 and 4 are
not applied.
VLT Software Dialog
Connection to terminals 68-70 or
Sub D:
PIN 3 GND
-
PIN 8 P-RS 485
-
PIN 9 N-RS 485
-
Sub D plug
Installation
Relay connection
See parameter 323 Relay output for programming of
relay output.
01 - 02 1 - 2 make (normally open)
Nr.
01 - 03
1 - 3 break (normally closed)
NOTE
Please note that the cable jacket for the
relay must cover the first row of control
card terminals - otherwise the galvanic
isolation (PELV) cannot be maintained.
Max. cable diameter: 4 mm. See drawing.
An LCP 2 control unit can be connected to the Sub D
plug on the control card. Ordering number: 175N0131.
The LCP control unit with ordering number 175Z0401
is not to be connected.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 23
VLT® 2800 Series
Connection examples
Start/stop
Start/stop using terminal 18 and coasting stop using
terminal 27.
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coasting stop inver-ted [2]
For Precise start/stop the following settings are made:
Par. 302 Digital input = Precise start/stop [27]
Par. 304 Digital input = Coasting stop inver-ted [2]
Speed up/slow down
Speed up/slow down using terminals 29/33.
Par. 302 Digital input = Start [7]
Par. 303 Digital input = Freeze reference [14]
Par. 305 Digital input = Speed up [16]
Par. 307 Digital input = Slow down [17]
Potentiometer reference
Voltage reference via a potentiometer.
Pulse start/stop
Pulse start using terminal 18 and pulse stop using terminal 19. In addition, the jog frequency is activated via
terminal 29.
Par. 302 Digital input = Pulse start [8]
Par. 303 Digital input = Stop inverted [6]
Par. 304 Digital input = Coasting stop inver-ted [2]
Par. 305 Digital input = Jog [13]
Par. 308 Analog input = Reference [1]
Par. 309 Terminal 53, min. scaling = 0 Volt
Par. 310 Terminal 53, max. scaling = 10 Volt
Connection of a 2-wire transmitter
Connection of a 2-wire transmitter as feedback to terminal 60.
24 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Par. 314 Analog input = Feedback [2]
Par. 315 Terminal 60, min. scaling = 4 mA
Par. 316 Terminal 60, max. scaling = 20 mA
VLT® 2800 Series
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 25
VLT® 2800 Series
Control unit
On the front of the variable frequency drive there is a
control panel.
The control panel is divided into five functional groups:
1.Status LED
2.Keys for changing parameters and shifting
display function.
3.LEDs.
4.Keys for local operation.
The [CHANGE DATA] key is also used for confirming
a change of parameter settings.
[+] / [-] are used for selecting parameters and for
changing parameter values.
These keys are also used in Display mode for selecting
the display of an operating value.
The [QUICK MENU] + [+] keys must be pressed at the
same time to give access to all parameters. See Menu
mode.
[STOP/RESET] is used for stopping the connected
motor or for resetting the variable frequency drive after
a trip.
Can be selected as Active [1] or Not active [0] via parameter 014 Local stop/reset. In Display mode, the
display will flash if the stop function is activated.
NOTE
If the [STOP/RESET] key is set at Not active [0] in parameter 014 Local stop/reset,and there is no stop command via the
digital inputs or serial communication, the
motor can only be stopped by disconnecting the electrical voltage to the variable
frequency drive.
[START] is used for starting the variable frequency
drive. It is always active, but the [START] key cannot
override a stop command.
All displays of data are in the form of a six-digit LED
display capable of showing one item of operating data
continuously during normal operation. As a supplement to the display, there are three LEDs for indication
of electrical connection (ON), warning (WARNING)
and alarm (ALARM). Most of the variable frequency
drive's parameter Setups can be changed immediately
via the control panel, unless this function has been
programmed as Locked [1] via parameter 018 Lock fordata changes.
Control keys
[QUICK MENU] allows access to the parameters used
for the Quick menu.
The[QUICK MENU] key is also used if a change to a
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
[CHANGE DATA] is used for changing a setting.
26 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Manual initialization
To manually initialize the adjustable frequency drive to
factory default settings, first disconnect AC line voltage. Hold the [QUICK MENU] and [+] and [CHANGE
DATA] keys down while simultaneously reconnecting
the AC line voltage. Release the keys. The drive has
now been programmed for factory settings.
Display readout states
Display mode
VLT® 2800 Series
In normal operation, one item of operating data can be
displayed continuously at the operator's discretion. By
means of the [+/-] keys, the following options can be
selected in Display mode:
Output frequency [Hz]
-
Output current [A]
-
Output voltage [V]
-
Intermediate circuit voltage [V]
-
Output power [kW]
-
Scaled output frequency f
-
x p008
out
Menu mode
In order to enter the Menu mode, [QUICK MENU] + [+]
must be activated at the same time.
In Menu mode, most of the adjustable frequency drive
parameters can be changed. Scroll through the parameters using the [+/-] keys. While scrolling in the
Menu mode proceeds, the parameter number will
flash.
The display shows that in parameter 128 Motor thermalprotection, the selection made is Thermistor trip [2].
Quick menu
Using the [QUICK MENU] key, it is possible to access
the 12 most important parameters of the adjustable
frequency drive. After programming, the adjustable
frequency drive is, in most cases, ready for operation.
When the [QUICK MENU] key is activated in Display
mode, the Quick menu starts. Scroll through the quick
menu using the [+/-] keys and change the data values
by first pressing [CHANGE DATA] and then changing
the parameter value with the [+/-] keys.
TheQuick menu parameters are:
•
Par. 100 Configuration
•
Par. 101 Torque characteristic
•
Par. 102 Motor power P
•
Par. 103 Motor voltage U
•
Par. 104 Motor frequency f
•
Par. 105 Motor current I
M,N
M,N
M,N
M,N
Installation
The display shows that the setting in parameter 102
Motor power P
is 0.75. In order to change the value
M,N
of 0.75, [CHANGE DATA] must first be activated; the
parameter value can then be changed using the [+/-]
keys.
If a given parameter display shows three dots to the
right, it means that the parameter value has more than
three digits. In order to see the entire value, activate
[CHANGE DATA].
•
Par. 106 Rated motor speed n
•
Par. 107 Automatic motor adaptation
•
Par. 202 Output frequency high limit f
•
Par. 203 Reference range
•
Par. 204 Minimum reference Ref
•
Par. 205 Maximum reference Ref
•
Par. 207 Ramp-up time
•
Par. 208 Ramp-down time
•
Par. 002 Local/remote operation
•
Par. 003 Local reference
M,N
MAX
MIN
MAX
Parameter 102 - 106 can be read out from the motor's
nameplate.
Automatic motor tuning
Automatic motor tuning (AMT) is performed as follows:
MG.27.A2.22 - VLT® is a registered Danfoss trademark 27
1.
In parameter 107 Automatic motor tuning, select data value [2]. "107" will now flash, and
"2" will not flash.
2.AMT is activated by pressing start. "107" will
now flash and dashes will move from left to
right in the data value field.
3.When "107" appears once more with the data
value [0], AMT is complete. Press [STOP/
RESET] to save the motor data.
4."107" will then continue to flash with the data
value [0]. You can now proceed.
NOTE
VLT 2880-2882 do not have AMT function.
VLT® 2800 Series
28 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Display readout
Fr
The variable frequency drive shows the present output
frequency in Hertz [Hz].
Io
The variable frequency drive shows the present output
current in Amps [A].
Uo
The variable frequency drive shows the present output
voltage in Volt [V].
Ud
The variable frequency drive shows the intermediate
circuit voltage in Volt [V].
Po
The variable frequency drive shows the calculated output in kilowatt [kW].
notrun
This message is shown if an attempt is made to
change a parameter value while the motor is running.
Stop the motor to change the parameter value.
LCP
This message is shown if an LCP 2 control unit is fitted
and the [QUICK MENU] or [CHANGE DATA] key is
activated. If an LCP 2 control unit is fitted you can only
change parameters with that.
Ha
The variable frequency drive shows the present Hand
mode reference frequency in Herz (Hz).
SC
The variable frequency drive shows scaled output frequency (the present output frequency x parameter
008).
Hand Auto
During normal operation the adjustable frequency
drive is in auto mode, where the reference signal is
given externally, analog or digital via the control terminals. However, in hand mode, it is possible to give
the reference signal locally via the control panel.
On the control terminals, the following control signals
will remain active when hand mode is activated:
•Hand Start (LCP2)
•Off Stop (LCP2)
•Auto Start (LCP2)
•Reset
•Coasting Stop Inverse
•Reset and Coasting Stop Inverse
•Quick Stop Inverse
•Stop Inverse
•Reversing
•DC Braking Inverse
•Set-up Select LSB
•Set-up Select MSB
•Thermistor
•Precise Stop Inverse
•Precise Stop/Start
•Jog
•Stop Command Via Serial Comm.
Switching between Auto Mode and Hand mode:
By activating the [Change Data] key in [Display Mode],
the display will indicate the mode of the adjustable frequency drive.
Installation
Scroll up/down in order to switch to hand mode:
When the adjustable frequency drive is in hand mode,
the readout will appear as follows:
and the reference can be changed by using the following keys:
MG.27.A2.22 - VLT® is a registered Danfoss trademark 29
NOTE
Please note that parameter 020 may block
the choice of mode.
VLT® 2800 Series
Warnings/alarms
Warnings or alarms appear in the LED display as a
numerical code [Err. xx]. A warning is displayed until
the fault has been corrected, while an alarm will flash
until the [STOP/RESET] key is pressed. The table in
Warnings/alarms messages in this manual explains the
various warnings and alarms, and whether a fault locks
the adjustable frequency drive. After a Trip locked
fault, cut off the AC line supply and correct the fault.
Then reconnect the AC line supply and press the
[STOP/RESET] key. The adjustable frequency drive is
now reset and ready. See Warnings/alarms messages
in this manual for more detail.
30 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Special conditions
Derating for ambient temperature
The ambient temperature (T
AMB,MAX
temperature allowed. The average (T
) is the maximum
AMB,AVG
) measured over 24 hours, must be at least 5 °C lower. If the
frequency converter operates at temperatures above
45 °C, a derating of the rated output current is necessary.
Derating for long motor cables
The adjustable frequency drive has been designed for
a 240 ft (75 m) unscreened/unarmored cable or a 80
ft (25 m) screened/armored cable and a motor cable
with a rated cross-section. If a cable with a larger
cross-section is required, it is recommended to reduce
the output current by 5% for each step that the cable
cross-section is increased. (Increased cable crosssection leads to increased capacitance to ground, and
thus to an increased ground leakage current.)
VLT 2800 start-up
Pre-installation checks
1.Compare drive model number to what was
ordered.
2.Ensure each of following are rated for same
voltage:
•Drive
•Power line
•Motor
Installation
Temperature-related switching frequency
This function ensures the highest possible switching
frequency without the adjustable frequency drive becoming thermally overloaded. The internal temperature determines the switching frequency based on the
load, the ambient temperature, the supply voltage and
the cable length. The function ensures that the drive
automatically adjusts the switching frequency between
the minimum and maximum switching frequency (parameter 411), see drawing below.
When using the LC filter the minimum switch frequency is 4.5 kHz.
3.Record following motor data:
•Voltage
•Frequency
•Full load current
•Full load speed
•Power - convert HP to kW (See conversion table in parameter 102, Mo-tor Power, in this manual.)
4.Ensure that rated drive current is equal to or
greater than total full load current.
•
Drive can be at most one size smaller than motor.
•For multiple motor operations, add
full load current ratings of all motors.
•If drive rating is less than motor(s),
full motor output cannot be achieved.
5.Check motor wiring:
•Any disconnect between drive and
motor should be interlocked to drive
MG.27.A2.22 - VLT® is a registered Danfoss trademark 31
VLT® 2800 Series
safety interlock circuit to avoid unwanted drive trips.
•No power factor correction capacitors can be connected between
drive and motor.
•Two speed motors must be wired
permanently for full speed.
•Y-start, -run motors must be wired
permanently for run.
Installation checks
1.Input fusing in power supply for all drives
must be provided.
2.Environmental concerns - for standard
NEMA 1 drive:
•Clean air supply
•Dry air (5% to 85% relative humidity,
non-condensing)
•32°F (0°C) to 104°F (40°C) ambient
temperature operating range, or as
rated
•1000m (3,300 ft) maximum elevation with no derating
•Keep any construction dirt out of
drive.
3.Wiring
1.Parameter 102, MOTOR POWER (in kW)
(See conversion table in parameter 102, Mo-tor Power, in this manual.)
2.Parameter 103, MOTOR VOLTAGE
3.Parameter 104, MOTOR FREQUENCY
4.Parameter 105, MOTOR CURRENT
5.Parameter 106, MOTOR SPEED
6.Parameter 107, select AUTOMATIC MOTOR
TUNING
Operational tests - HAND
1.Check motor rotation from drive. If incorrect,
disconnect input power from drive and reverse two leads between drive and motor.
2.Accelerate motor quickly to full speed and
verify operation.
3.Decelerate motor quickly to stop and verify
operation.
4.Operate motor over entire speed range while
closely checking for resonance.
Operational tests - AUTO
1.Ensure that drive follows run/stop and safety
interlock commands from system.
2.Ensure drive follows speed reference, or
feedback, from system.
•Wire drive in accordance with instructions and diagrams received
with drive.
•Separate conduits must be provided to drive for input power, output
power, and control wiring.
•Protect signal wires from noise.
•Ground each drive individually.
•Double check input and output power wiring for correct location.
Setting up drive for motor start
Ensure that all warnings provided in this manual have
been adhered to. Apply power to the unit. Enter motor
nameplate data into drive through Quick Menu.
32 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Operation & Display
001Language
(language)
Value:
English (english)[0]
German (deutsch)[1]
French (francais)[2]
Danish (dansk)[3]
Spanish (espanol)[4]
Italian (italiano)[5]
Function:
This parameter is used to choose the language to be
shown in the display whenever the LCP control unit is
connected.
Description of choice:
There is a choice of the languages shown. The factory
setting may vary.
002Local/remote operation
(OPERATION SITE)
Value:
Remote operation (REMOTE)[0]
Local operation (LOCAL)[1]
Function:
There is a choice of two different modes of operation
of the adjustable frequency drive; Remote operation [0]
or Local operation [1]. See also parameter 013 Localcontrol if Local operation [1] is selected.
Description of choice:
If Remote operation [0] is selected, the adjustable frequency drive is controlled via:
1.the control terminals or via serial communication.
2.the [START] key. This cannot, however,
override stop commands transmitted via the
digital inputs or via serial communication.
3.the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If Local operation [1], is selected, the adjustable fre-
quency drive is controlled via:
1.the [START] key. This cannot, however,
override stop commands via the digital inputs
(see parameter 013 Local control).
2.the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
3.the [FWD/REV] key, on the condition that is
has been selected as active in parameter 016
Local reversing, and that parameter 013 Local
control is set at Local control and open loop
[1] or Local control as parameter 100 [3]. Parameter 200 Output frequency range is set
at Both directions.
4.
parameter 003 Local reference where the reference can be set using the [+] and [-] keys.
5.an external control command that can be
connected to the digital inputs (see parameter 013 Local control).
NOTE
The [JOG] and [FWD/REV] keys are located on the LCP control unit.
003Local reference
(LOCAL REFERENCE)
Value:
Par. 013 Local control must be set to [1]
or [2]:
0 - f
(par. 205)
MAX
50 Hz
Par. 013 Local control must be set to [3] or
[4].
Ref
MIN
- Ref
(par. 204-205)
MAX
0,0
Function:
In this parameter, the local reference can be set manually. The unit of the local reference depends on the
configuration selected in parameter 100 Configura-tion.
Description of choice:
In order to protect the local reference, parameter 002
Local/remote operation must be set to Local operation [1]. Local reference cannot be set via serial com-
munication.
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 33
004Active Setup
(active Setup)
Value:
Factory Setup (FACTORY SETUP)[0]
setup 1 (setup 1)[1]
setup 2 (setup 2)[2]
Setup 3 (setup 3)[3]
setup 4 (setup 4)[4]
Multi Setup (MULTI SETUP)[5]
Function:
The active parameter Setup is selected here. All parameters can be programmed in four individual parameter Setups. Shifts between Setups can be made
in this parameter via a digital input or via serial communication.
Description of choice:
Factory Setup [0] contains the factory-set parameter
values. Setup 1-4 [1]-[4] are four individual Setups
which can be selected as required. Multi Setup [5] is
used where remote-controlled shifts between the four
Setups via a digital input or via serial communication
is required.
005Programming Set-up
(EDIT SET-UP)
Value:
Factory Set-up (FACTORY SET-UP)[0]
Set-up 1 (set-up 1)[1]
Set-up 2 (set-up 2)[2]
Set-up 3 (set-up 3)[3]
Set-up 4 (set-up 4)[4]
Active Set-up (ACTIVE SET-UP)[5]
VLT® 2800 Series
Description of choice:
Factory Set-up [0] contains the factory-set data and
can be used as a source of data if the other set-ups
are to be reset to a known status. Set-up 1-4 [1]-[4]
consists of individual set-ups that can be programmed
freely during operation. If Active Set-up [5] is selected,
the programming set-up will be equal to parameter 004
Active Set-up.
NOTE
If data is modified or copied to the active
set-up, the modifications have an immediate effect on the unit's operation.
006Setup copying
(SETUP COPY)
Value:
No copying (NO COPY)[0]
Copy to Setup 1 from #
(COPY TO SETUP 1)[1]
Copy to Setup 2 from #
(COPY TO SETUP 2)[2]
Copy to Setup 3 from #
(COPY TO SETUP 3)[3]
Copy to Setup 4 from #
(COPY TO SETUP 4)[4]
Copy to all Setups from # (copy to all)[5]
Function:
You can copy from the selected active Setup in parameter 005 Programming setup to the selected Setup
or Setups in this parameter.
NOTE
Copying is only possible in Stop (motor
stopped in connection with a stop command).
Function:
You can select the desired set-up to program during
operation (this applies both via the control panel and
the serial communication port). For example, it is possible to program Set-up 2 [2] while the active set-up is
set to Set-up 1 [1] in parameter 004 Active Set-up.
= factory setting, () = display text, [] = value for use in communication via serial communication port
34 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA] key
has been pushed. The display indicates when copying
is in progress.
Parameter 007 LCP copy is used if you want to use the
LCP 2 control panel's integral copy function. The function is used if you want to copy all parameter setups
from one adjustable frequency drive to another by
moving the LCP 2 control panel.
Description of choice:
Select Upload all parameters [1] if you want all parameter values to be transferred to the control panel. Select Download all parameters [2] if all parameter values
transferred are to be copied to the adjustable frequency drive to which the control panel is attached. Select
Download size-independent par. [3] if you only want to
downloade the size-independent parameters. This is
used when downloading to a adjustable frequency
drive with a different rated power size than that from
which the parameter setup originates.
NOTE
Upload/download can only be performed
in stop mode. Download can
formed to a adjustable frequency drive
with the same software version number,
see parameter 626 Database identification
no.
008Display scaling of output frequency
(FREQUENCY SCALE)
Value:
0.01 - 100.00
Function:
In this parameter, the factor is selected by which the
output frequency is to be multiplied. The value is
shown in the display, provided parameters 009-012
only be per-
1.00
Display readout have been set to Output frequency x
scaling [5].
Description of choice:
Set the required scaling factor.
009Large display readout
(DISPLAY LINE 2)
Value:
No readout (none)[0]
Resulting reference [%]
(reference [%])[1]
Resulting reference [unit]
(reference [unit])[2]
Feedback [unit] (feedback [unit])[3]
Frequency [Hz] (Frequency [Hz])[4]
Output frequency x scaling
(frequency x scale)[5]
Motor current [A] (Motor current [A])[6]
Torque [%] (Torque [%])[7]
Power [kW] (Power [kW])[8]
Power [HP] (Power [HP][US])[9]
Motor voltage [V]
(Motor voltage [V])[11]
DC link voltage [V]
(DC link voltage [V])[12]
Thermal load motor [%]
(Motor thermal [%])[13]
Thermal load [%]
(FC. thermal[%])[14]
Running hours [Hours]
(RUNNING HOURS])[15]
Digital input [Bin]
(Digital input[bin])[16]
Analog input 53 [V]
(analog input 53 [V])[17]
Analog input 60 [mA]
(analog input 60 [mA])[19]
Pulse reference [Hz]
(Pulse ref. [Hz])[20]
External reference [%]
(external ref. [%])[21]
Status word [Hex] (Status word [hex])[22]
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 35
VLT® 2800 Series
Heatsink temperature [°C]
(Heatsink temp [°C])[25]
Alarm word [Hex] (Alarm word [hex])[26]
Control word [Hex] (Control word [Hex])[27]
Warning word [Hex]
(warning word [Hex])[28]
Extended status word [Hex]
(Ext. status [hex])[29]
Communication option card warning
(COMM OPT WARN [HEX])[30]
Pulse count
(PULSE COUNTER)[31]
Function:
In this parameter you can select the data value that
you wish to display in the LCP 2 control unit display
line 2 when the adjustable frequency drive is switched
on. The display will also be included in the scrollbar in
display mode. In parameters 010-012 Display readout
you can select a further three data values, which are
displayed in display line 1.
Power [kW] gives the present power that the motor is
absorbing in kW.
Power [HP] gives the present power that the motor is
absorbing in HP.
Motor voltage[V] gives the voltage supplied to the motor.
DC link voltage [V] gives the intermediate circuit voltage
of the adjustable frequency drive.
Thermal load motor [%] gives the calculated/estimated
load on the motor. 100 % is the cut-out limit.
Thermal load [%] gives the calculated/estimated thermal load on the adjustable frequency drive. 100 % is
the cut-out limit.
Running hours [Hours] gives the number of hours that
the motor has tun since the last reset in parameter 619
Reset of running hours counter.
Digital input [Binary code] gives the signal status from
the 5 digital inputs (18, 19, 27, 29 and 33). Terminal
18 corresponds to the bit on the extreme left. `0' = no
signal, `1' = signal connected.
Description of choice:
No readout can only be selected in parameters
010-012 Small display readout.
Resulting reference [%] gives, as a percentage, the resulting reference in the range from Minimum reference, Ref
to Maximum reference, Ref
MIN
MAX
.
Reference [unit] gives the resulting reference with unit
Hz in Open loop. In Closed loop the reference unit is
selected in parameter 416 Process units.
Feedback [unit] gives the resulting signal value using
the unit/scaling selected in parameter 414 Minimum
feedback, FB
, 415 Maximum feedback, FB
LOW
HIGH
and
416 Process units.
Frequency [Hz] gives the output frequency of the ad-
justable frequency drive.
Output frequency x scaling [-] equals the present output
frequency f
multiplied by the factor set in parameter
M
008 Display scaling of output frequency .
Motor current [A] gives the phase current of the motor
measured as an effective value.
Torque [%] denotes the motor's present load in relation
to the motor's rated torque.
Analog input 53 [V] gives the voltage value of terminal
53.
Analog input 60 [mA] gives the present value of terminal 60.
Pulse reference [Hz] gives the reference in Hz connected to terminal 33.
External reference [%] gives the sum of external references as a percentage (sum of analogue/pulse/serial
communication) in the range from Minimum reference,
Ref
to Maximum reference, Ref
MIN
MAX
.
Status word [Hex] gives one or several status conditions in a Hex code. See Serial communication in the
VLT 2800 Design Guide for further information.
Heatsink temp.[°C] gives the present heatsink temper-
ature of the adjustable frequency drive. The cut-out
limit is 90-100°C, while cutting back in occurs at 70 ±
5°C.
Alarm word [Hex] gives one or several alarms in hex
code. See Serial communication in the VLT 2800 De-
sign Guide for further information.
Control word [Hex] gives the control word for the ad-
justable frequency drive. See Serial communication in
the VLT 2800 Design Guide for further information.
= factory setting, () = display text, [] = value for use in communication via serial communication port
36 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Warning word [Hex] gives one or several warnings in
hex code. See Serial communication in the VLT 2800
Design Guide for further information.
Extended status word [Hex] gives one or several statusmodes in Hex code. See Serial communication in the
VLT 2800 Design Guide for further information.
Communication option card warning [Hex] gives a
warning word if there is a fault in the communication
bus. Only active if communication options are installed.
If there are no communication options 0 Hex is displayed.
Pulse count gives the number of pulses that the unit
has registered.
010Small display line 1.1
(DISPLAY LINE 1.1)
Value:
See par. 009 Large display
readout
Function:
In this parameter, the first of three data values can be
selected that is to be displayed in the LCP control unit
display, line 1, position 1. This is a useful function, e.g.
when setting the PID regulator, as it gives a view of
process reactions to reference changes. The display
readout is activated by pushing the [DISPLAY STATUS] key.
Description of choice:
See parameter 009 Large display readout.
Analog input 53
[V] [17]
012Small display readout 1.3
(DISPLAY LINE 1.3)
Value:
See parameter 009 Large display
readout
Function:
See the functional description given under parameter
010 Small display readout.
Description of choice:
See parameter 009 Large display readout.
013Local control
(LOC CTRL/CONFIG.)
Value:
Local not active (DISABLE)[0]
Local control and open loop without slip compensation
(LOC CTRL/OPEN LOOP)[1]
Remote-operated control and open loop without slip compensation
(LOC+DIG CTRL)[2]
Local control as parameter 100
(LOC CTRL/AS P100)[3]
Remote-operated control as parameter 100
(LOC+DIG CTRL/AS P100)[4]
Function:
This is where the required function is selected if, in
parameter 002 Local/remote operation, Local opera-tion [1] has been chosen.
Feedback
[unit] [3]
Programming
Description of choice:
011Small display readout 1.2
(DISPLAY LINE 1.2)
Value:
See parameter 009 Large display
readout
Function:
See the functional description given under parameter
010 Small display readout.
Description of choice:
See parameter 009 Large display readout.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 37
Motor cur-
rent [A][6]
If Local not active [0] is selected, it is not possible to
set a reference via parameter 003 Local reference.
In order to enable a shift to Local not active [0], parameter 002 Local/remote operation must be set to Remote
operation [0].
Local control and open loop [1] is used if the motor
speed is to be set via parameter 003 Local reference.
When this choice is made, parameter 100 Configura-
tion automatically shifts to Speed regulation, open
loop [0].
Remote-operated control and open loop [2] functionsin the same way as Local control and open loop [1];
VLT® 2800 Series
however, the adjustable frequency drive can also be
controlled via the digital inputs.
For selections [1-2] control is shifted to open loop, no
slip compensation.
Local control as parameter 100 [3] is used when the
motor speed is to be set via parameter 003 Local ref-erence, but
matically shifting to Speed regulation, open loop [0].
Remote-operated control as parameter 100 [4] works
the same way as Local control as parameter 100 [3];
however, the adjustable frequency drive can also be
controlled via the digital inputs.
Shifting from Remote operation to Local operation in
parameter 002 Local/remote operation, while this parameter has been set to Remote-operated control andopen loop [1]: The present motor frequency and direction of rotation will be maintained. If the present direction of rotation does not respond to the reversing signal
(negative reference), the reference will be set to 0.
Shifting from Local operation to Remote operation in
parameter 002 Local/remote control, while this parameter has been set to Remote-operated control and open
loop [1]: The configuration selected in parameter 100
Configuration will be active. The shift will be smooth.
without parameter 100 Configuration auto-
Function:
In this parameter, the local [STOP]-key can be engaged or disengaged on the control panel and on the LCP
control panel.
Description of choice:
If Not active [0] is selected in this parameter, the
[STOP]-key will be inactive.
NOTE
If Not active [0] is selected, the motor cannot be stopped by means of the [STOP]key.
015Local jog
(LOCAL JOGGING)
Value:
Not active (DISABLE)[0]
Active (ENABLE)[1]
Function:
In this parameter, the jog function on the LCP control
panel can be engaged/disengaged.
Shifting from Remote control to Local control in parameter 002 Local/remote operation, while this parameter
has been set to Remote-operated control as parameter100 [4]: the present reference will be maintained. If the
reference signal is negative, the local reference will be
set to 0.
Shifting from Local operation to Remote operation in
parameter 002 Local/remote operation, while this parameter has been set to Remote operation: The local
reference will be replaced by the remote-operated reference signal.
014Local stop
(LOCAL STOP)
Value:
Not active (DISABLE)[0]
Active (ENABLE)[1]
Description of choice:
If Not active [0] is selected in this parameter, the [JOG]-
key will be inactive.
016Local reverse
(LOCAL REVERSE)
Value:
Not active (DISABLE)[0]
Active (ENABLE)[1]
Function:
In this parameter you can select/deselect the reverse
function on the LCP control panel. The key can only
be used if parameter 002 Local/remote operation is set
to Local operation [1] and parameter 013 Localcon-
trol to Local control, open loop [1] or Local control as
parameter 100 [3].
= factory setting, () = display text, [] = value for use in communication via serial communication port
38 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Description of choice:
If Disable [0] is selected in this parameter, the [FWD/
REV] key will be disabled. See also parameter 200
Output frequency range.
017Local reset of trip
(LOCAL RESET)
Value:
Not active (DISABLE)[0]
Active (ENABLE)[1]
Function:
In this parameter, the reset function on the control
panel can be engaged/disengaged.
Description of choice:
If Not active [0] is selected in this parameter, the reset
function will be inactive.
NOTE
Select Not active [0], only if an external
reset signal has been connected via the
digital inputs.
018Lock for data changes
(DATA CHANGE LOCK)
Value:
Not locked (NOT LOCKED)[0]
Locked (LOCKED)[1]
Function:
In this parameter, it is possible to 'lock' the controls to
disable data changes via the control keys.
Description of choice:
If Locked [1] is selected, data changes in the parameters cannot be made; however, it will still be possible
to make data changes via serial communication. Parameter 009-012 Display readout can be changed via
the control panel.
019
Value:
Auto restart, use saved reference
(AUTO RESTART)[0]
Forced stop, use saved reference
(LOCAL=STOP)[1]
Forced stop, set ref. to 0
(LOCAL=STOP, REF=0)[2]
Function:
Setting of the required operating mode when the mains
voltage is engaged. This function can only be active if
Local operation [1] has been selected in parameter
002 Local/remote operation.
Description of choice:
Auto restart, use saved ref. [0] is selected if the adjustable frequency drive is to start using the local reference (set in parameter 003 Local reference) and the
start/stop state given via the control keys immediately
prior to the mains voltage being cut out.
Forced stop, use saved ref. [1] is selected if the adjustable frequency drive is to remain stopped when the
mains voltage is engaged, until the [START]-key is activated. After a start command the motor speed is
ramped up to the saved reference in parameter 003
Local reference.
Forced stop, set ref. to 0 [2] is selected if the adjustable
frequency drive is to remain stopped when the mains
voltage is cut back in. Parameter 003 Local reference
is to be zeroed.
Operating mode at power-up, local operation
(POWER UP ACTION)
NOTE
In remote operation (parameter 002 Local/remote operation) the start/stop state
at the time of mains connection will depend on the external control signals. If
Pulse start [8] is selected in parameter 302
Digital input, the motor will remain stopped
after mains connection.
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 39
020Hand operation
(HAND OPERATION)
Value:
Not active (DISABLE)[0]
Active (ENABLE)[1]
Function:
In this parameter you can select whether it should be
possible or not to switch between Auto- and Hand
mode. In Auto mode the adjustable frequency drive is
controlled by external signals whereas the adjustable
frequency drive in Hand mode is controlled via a local
reference directly from the control unit.
Description of choice:
If Not active [0] is selected in this parameter, the Hand
mode function will be inactive. If Active [1] is selected
you can switch between Auto- and Hand mode. For
further information, see the Control Unit section.
VLT® 2800 Series
025Quick Menu setup
(Quick Menu setup)
Value:
[Index 1 - 20] Value: 0 - 999
Function:
In this parameter you define which parameters are required in the Quick Menu when parameter 024 User-defined Quick Menu is set to Active [1].´
Up to 20 parameters can be selected for the user-defined Quick Menu.
NOTE
Please note that this parameter can only
be set using an LCP 2 control panel. See
Order form.
Description of choice:
The Quick Menu is set up as follows:
1.
Select parameter 025 Quick Menu setup and
press [CHANGE DATA].
000
024Userdefined Quick Menu
(user quickmenu)
Value:
Not active (Disable)[0]
Active (Enable)[1]
Function:
In this parameter you can select the standard setup of
the Quick menu key on the control panel and the LCP
2 control panel.
Using this function, in parameter 025 Quick Menu set-up the user can select up to 20 parameters for the
Quick Menu key.
Description of choice:
If not active [0] is selected, the standard setup of the
Quick Menu key is active.
If Active [1] is selected, the user-defined Quick Menu
is active.
2.Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index
numbers using the [+ / -] keys. Select Index
1.
3.Using [< >] you can scroll between the three
figures. Press the [<] key once ad the last
number in the parameter number can be selected using the [+ / -] keys. Set Index 1 to
100 for parameter 100 Configuration.
4.Press [OK] when Index 1 has been set to 100.
5.Repeat steps 2 - 4 until all parameters required have been set to the Quick Menu key.
6.Press [OK] to complete the Quick Menu setup.
If parameter 100 Configuration is selected at Index 1,
Quick Menu will start with this parameter every time
Quick Menu is activated.
Please note that parameter 024 User-defined QuickMenu and parameter 025 Quick Menu setup are reset
to the factory setting during initialisation.
= factory setting, () = display text, [] = value for use in communication via serial communication port
40 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Load and Motor
100Configuration
(Configuration)
Value:
Speed control, open-loop
(SPEED OPEN-LOOP)[0]
Speed control, closed-loop
(SPEED CLOSED-LOOP)[1]
Process control, closed-loop
(PROCESS CLOSED-LOOP)[3]
Function:
This parameter is used to select the configuration to
which the adjustable frequency drive is to be adapted.
This makes adaptation to a given application simple,
since the parameters not used in a given configuration
are hidden (not active).
Description of choice:
If Speed control, open-loop [0] is selected, normal
speed control is obtained (without feedback signal)
with automatic load and slip compensation to ensure
a constant speed at varying loads. Compensations are
active, but may be disabled in parameter 134 Loadcompensation and parameter 136 Slip compensation
as required.
If Speed control, closed-loop [1] is selected, better
speed accuracy is obtained. A feedback signal must
be added, and the PID regulator must be set in parameter group 400 Special functions.
If Process control, closed-loop [3] is selected, the in-
ternal process regulator is activated to enable precise
control of a process in relation to a given process signal. The process signal can be set to the relevant
process unit or as a percentage. A feedback signal
must be added from the process, and the process regulator must be set in parameter group 400 Specialfunctions. Process closed-loop is not active if a DeviceNet card is mounted and Instance 20/70 or 21/71 is
chosen in parameter 904 Instance types.
101Torque characteristic
(TORQUE CHARACT)
Value:
Constant torque
(Constant torque)[1]
Variable torque low
(torque: low)[2]
Variable torque medium
(torque: med)[3]
Variable torque high
(torque: high)[4]
Variable torque low with CT start
(VT LOW CT START)[5]
Variable torque medium with CT start
(VT MED CT START)[6]
Variable torque high with CT start
(VT HIGH CT START)[7]
Special motor mode
(Special motor mode)[8]
CT = Constant torque
Function:
This parameter enables a choice of principle for adaptation of the U/f ratio of the variable frequency drive to
the torque characteristic of the load. See par. 135 U/f
ratio.
Description of choice:
If Constant torque [1] is selected, a load-dependent U/
f characteristic is obtained, in which output voltage and
output frequency are increased at increasing loads in
order to maintain constant magnetization of the motor.
Select Variable torque low [2], Variable torque medium
[3] or Variable torque high [4], if the load is square (centrifugal pumps, fans).
Variable torque - low with CT start [5], - medium with
CT start [6] or high with CT start [7], are selected if you
need a greater breakaway torque than can be achieved with the three first characteristics.
NOTE
Load and slip compensation are not active
if variable torque or special motor mode
have been selected.
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 41
Select Special motor mode [8], if a special U/f setting
is needed that is to be adapted to the present motor.
The break points are set in parameters 423-428 Volt-age/frequency .
VLT® 2800 Series
North American HP to kW
Conversion Chart
HP
1/20.37
3/40.55
10.75
1 1/21.1
21.5
32.2
43.0
54
7 1/25.5
107.5
kW
NOTE
If a value set in the name-plate parameters 102-106 is changed, parameters 108
Stator resistance and 109 Stator reactance change automatically. Enter motor
name plate data in sequence from parameter 102 to 106. The relationship between
values are interdependent.
102
Motor power P
M,N
(motor power)
Value:
0.25 - 22 kW
Depends on unit
Function:
Here you must set a power value [kW] P
M,N
, corre-
sponding to the motor's rated power.
Description of choice:
Set a value that matches the nameplate data on the
motor. Settings between one size below and one size
over the factory setting are possible.
103
Motor voltage U
M,N
(MOTOR VOLTAGE)
Value:
For 200 V units: 50 - 999 V
For 400 V units: 50 - 999 V
230 V
400 V
Function:
This is where to set the rated motor voltage.
Description of choice:
Select a value that corresponds to the nameplate data
on the motor, regardless of the adjustable frequency
drive's AC line voltage.
104
Motor frequency f
M,N
(MOTOR FREQUENCY)
Value:
24-1000 Hz
50 Hz
Function:
This is where to select the rated motor frequency
.
f
M,N
Description of choice:
Select a value that corresponds to the nameplate data
on the motor.
105
Motor current I
M,N
(MOTOR CURRENT)
Value:
0,01 - I
MAX
= factory setting, () = display text, [] = value for use in communication via serial communication port
42 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Depends on choice of motor
Function:
The nominal, rated current of the motor I
forms part
M,N
of the variable frequency drive calculation of features
such as torque and motor thermal protection.
Description of choice:
Set a value that corresponds to the nameplate data on
the motor. Set the motor current I
taking into ac-
M,N
count whether the motor is star-connected Y or deltaconnected .
106Rated motor speed
(MOTOR NOM. SPEED)
Value:
M,N
x 60
Depends on parameter 104 Mo-
tor frequency, f
M,N
100 - f
(max. 60000
rpm)
Function:
This is where to set the value that corresponds to the
rated motor speed n
that can be seen from the
M,N
nameplate data.
VLT® 2800 Series
For AMT to define the motor parameters ac-
-
ccurately, the correct nameplate data for the
motor connected to the adjustable frequency
drive must be keyed into parameters 102 to
106.
Alarms will appear in the display if faults arise
-
during tuning of the motor. See Warnings/
alarms messages in this manual.
As a rule, the AMT function can measure the
-
R
values for motors that are 1-2 sizes larger
S
or smaller than the adjustable frequency
drive’s nominal size.
If you wish to interrupt automatic motor tun-
-
ing, press the [STOP/RESET] key.
NOTE
AMT may not be performed on motors
connected in parallel, nor may setup
changes be made while AMT is running.
See Automatic motor tuning in this manual for the AMT
procedure.
Description of choice:
Select a value that corresponds to the nameplate data
on the motor.
NOTE
The max. value equals f
M,N
x 60. f
M,N
to be
set in parameter 104 Motor frequency,
.
f
M,N
107Automatic motor tuning, AMT
(auto motor tun.)
Value:
Optimisation off (AMT off)[0]
Optimisation on (AMT start)[2]
Function:
NOTE
AMT is not possible on VLT 2880-82.
Description of choice:
Select Optimization on [2] as part of the AMT procedure
if you want the adjustable frequency drive to perform
automatic motor tuning.
108
Stator resistance R
S
(STATOR RESISTAN)
Value:
0.000 - X.XXX
Depends on choice of motor
Function:
After setting of parameters 102-106 Nameplate data, a
number of adjustments of various parameters is carried out automatically, including stator resistance R
A manually entered R
must apply to a cold motor. The
S
S
shaft performance can be improved by fine-tuning R
and XS, see procedure below.
NOTE
Parameters 108 Stator resistance R
109 Stator reactance X
are normally not
S
and
S
to be changed if nameplate data has been
set.
Programming
.
S
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 43
Description of choice:
can be set as follows:
R
S
1.Use the factory settings of R
which the ad-
S
justable frequency drive itself chooses on the
basis of the motor nameplate data.
2.The value is stated by the motor supplier.
3.The value is obtained through manual measurements: R
ing the resistance R
phase terminals. Where R
can be calculated by measur-
S
PHASE-PHASE
between two
PHASE-PHASE
is lower than 1-2 Ohms (typical for motors > 7.5
HP, 400 V), a special Ohm-meter should be
used (Thomson-bridge or similar). R
.
4.R
R
PHASE-PHASE
is set automatically when AMT has been
S
= 0.5 x
S
completed. See parameter 107 Auto motor
tuning.
109
Stator reactance X
S
(STATOR REACTANCE)
Value:
0.00 - X,XX
Depends on choice of motor
Function:
After parameters 102-106 Nameplate data are set, a
number of parameters are adjusted automatically, including stator reactance X
can be improved by fine-tuning R
. The shaft performance
S
and XS; see proce-
S
dure below.
VLT® 2800 Series
117Resonance damping
(resonance damping)
Value:
OFF 100[OFF 100]
Off[OFF]
Function:
It is possible to optimize the resonance damping in CT
mode. The grade of the influence is adjusted in this
parameter.
The value may be set between 0% (OFF) and 100%.
100% corresponds to 50% reduction of U/F ratio.
Default value is OFF.
Internal settings (fixed):
The resonance filter is active from 10% of nominal
speed and above.
In this case 5Hz and above.
Speed to go from 0 to nominal flux level: 500ms
Speed to go from nominal to 0 flux level: 500 ms
Description of functionality:
The filter monitors the active motor current and
changes the motor voltage according to the figure below. The filter reacts on levels referring to the nominal
motor current.
Description of choice:
can be set as follows:
X
S
1.The value is stated by the motor supplier.
2.The value is obtained through manual measurements; X
is obtained by connecting a
S
motor to line power and measuring the
phase-phase voltage U
.
U
X
=
s
M
3×
I
ϕ
and the idle current
M
X
L
−
2
XL: See parameter 142.
3.Use the factory settings of X
, which the ad-
S
justable frequency drive itself chooses on the
If the active motor current is below 10%, the motor
voltage will be decreased by the speed mentioned
above until the voltage reaches the setting for Par.
117. If the active motor current comes over 20% the
voltage will be increased by the above-mentioned
speed. If the active motor current reaches 40% the
motor voltage will be increased immediately to normal
motor voltage.
The reduction in motor voltage depends on the parameter 117 setting.
basis of the motor nameplate data.
= factory setting, () = display text, [] = value for use in communication via serial communication port
44 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Description of choice:
Set the grade of Motor current [Imact] influence on the
U/F ratio between 0% (OFF) and 100%. 100% corresponds to 50% reduction of U/F ratio. Default value is
OFF.
119High start torque
(High start torq.)
Value:
0.0 - 0.5 sec.
0.0 sec.
Function:
To ensure a high start torque approx. 1.8 x I
INV.
can be
permitted for max. 0.5 sec. The current is, however,
limited by the variable frequency drive's (inverter's)
safety limit. 0 sec. corresponds to no high start torque.
Description of choice:
Set the necessary time for which a high start torque is
required.
Start frequency/voltage in reference direction
(VERTICAL OPERATION)[4]
Function:
This is where to choose the required mode during the
start delay time (parameter 120 Start delay time).
Description of choice:
Select DC hold during start delay time [0] to energize
the motor with a DC hold voltage during the start delay
time. Set voltage in parameter 137 DC hold voltage.
Choose DC brake during start delay time [1] to energize
the motor with a DC brake voltage during the start delay time. Set voltage in parameter 132 DC brake volt-age.
Choose Coasting during start delay time [2] and the
motor will not be controlled by the adjustable frequency drive during the start delay time (inverter turned off).
120Start delay
(START DELAY)
Value:
0.0 - 10.0 sec.
0.0 sec.
Function:
This parameter enables a delay of the start-up time
after the conditions for start have been fulfilled. When
the time has passed, the output frequency will start by
ramping up to the reference.
Description of choice:
Set the necessary time before commencing to accelerate.
121Start function
(START FUNCTION)
Value:
DC hold during start delay time
(DC HOLD/DELAY TIME)[0]
DC brake during start delay time
(DC BRAKE/DELAY TIME)[1]
Coasting during start delay time[2]
Choose Start frequency/voltage clockwise [3] to obtain
the function described in parameter 130 Start frequen-cy and 131 Voltage at start during start delay time.
Regardless of the value assumed by the reference
signal, the output frequency equals the setting in parameter 130 Start frequency and the output voltage will
correspond to the setting in parameter 131 Voltage atstart .
This functionality is typically used in hoist applications.
It is used in particular in applications in which a cone
anchor motor is applied, where the direction of rotation
is to start clockwise followed by the reference direction.
Select Start frequency/voltage in reference direction [4]
to obtain the function described in parameter 130 Startfrequency and 131 Voltage at start during the start delay time.
The direction of rotation of the motor will always follow
in the reference direction. If the reference signal
equals zero, the output frequency will equal 0 Hz, while
the output voltage will correspond to the setting in parameter 131 Voltage at start. If the reference signal is
different from zero, the output frequency will equal parameter 130 Start frequency and the output voltage will
equal parameter 131 Voltage at start. This functionality
is used typically for hoist applications with counter-
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 45
weight. It is used in particular for applications in which
a cone anchor motor is applied. The cone anchor motor can break away using parameter 130 Start frequen-cy and parameter 131 Voltage at start.
122Function at stop
(FUNCTION AT STOP)
Value:
Coasting (COAST)[0]
DC hold (DC HOLD)[1]
Function:
This is where to choose the function of the variable
frequency drive after the output frequency has become
lower than the value in parameter 123 The min. fre-quency for activation of function at stop or after a stop
command and when the output frequency has been
ramped down to 0 Hz.
Description of choice:
Select Coasting [0] if the variable frequency drive is to
'let go' of the motor (inverter turned off).
Select DC hold [1] if parameter 137 DC hold voltage is
to be activated.
123
Min. frequency for activation of function at stop
(MIN.F.FUNC.STOP)
Value:
0,1 - 10 Hz
0,1 Hz
Function:
In this parameter, the output frequency is set at which
the function selected in parameter 122 Function atstop is to be activated.
Description of choice:
Set the required output frequency.
NOTE
If parameter 123 is set higher than parameter 130, then the start delay function (parameter 120 and 121) will be skipped.
VLT® 2800 Series
NOTE
If parameter 123 is set too high, and DC
hold has been chosen in parameter 122,
the output frequency will jump to the value
in parameter 123 without ramping up. This
may cause an overcurrent warning /
alarm.
126DC brake time
(DC BRAKING TIME)
Value:
0 - 60 sec.
Function:
In this parameter, the DC brake time is set at which
parameter 132 DC brake voltage is to be active.
Description of choice:
Set the required time.
127DC brake cut-in frequency
(DC BRAKE CUT-IN)
Value:
0.0 (OFF) - par. 202
Output frequency high limit, f
MAX
Function:
In this parameter, the DC brake cut-in frequency is set
at which the DC brake is to be activated in connection
with a stop command.
Description of choice:
Set the required frequency.
128Thermal motor protection
(MOT.THERM PROTEC)
Value:
No protection (NO PROTECTION)[0]
Thermistor warning
(THERMISTOR WARN)[1]
Thermistor trip (THERMISTOR TRIP)[2]
ETR warning 1 (ETR WARNING 1)[3]
ETR trip 1 (ETR TRIP 1)[4]
10 sec
OFF
= factory setting, () = display text, [] = value for use in communication via serial communication port
46 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
ETR warning 2 (ETR WARNING 2)[5]
ETR trip 2 (ETR TRIP 2)[6]
ETR warning 3 (ETR WARNING 3)[7]
ETR trip 3 (ETR TRIP 3)[8]
ETR warning 4 (ETR WARNING 4)[9]
ETR trip 4 (ETR TRIP 4)[10]
Function:
The adjustable frequency drive can monitor the motor
temperature in two different ways:
Via a PTC thermistor that is mounted on the
-
motor. The thermistor is connected between
terminal 50 (+10V) and one of the digital input
terminals 18, 19, 27 or 29. See parameter
300 Digital inputs.
Thermal load calculation (ETR - Electronic
-
Thermal Relay), based on present load and
time. This is compared with the rated motor
current I
and rated motor frequency f
M,N
M,N
The calculations take into account the need
for lower loading at low speeds due to the
motor's internal ventilation being reduced.
Select ETR warning 1-4 if you want a warning when the
motor is overloaded according to the calculations. You
can also program the adjustable frequency drive to
give a warning signal via one of the digital outputs.
Select ETR Trip 1-4 if you want a trip when the motor
is overloaded according to the calculations.
NOTE
This function cannot protect the individual
motors in the case of motors linked in parallel.
130Start frequency
(Start frequency)
Value:
0.0 - 10.0 Hz
Function:
The start frequency is active for the time set in param-
.
eter 120 Start delay, after a start command. The output
frequency will 'jump' to the next preset frequency. Certain motors, such as conical anchor motors, need an
extra voltage/start frequency (boost) at start to disengage the mechanical brake. To achieve this parameters 130 Start frequency and 131 Initial voltage are
used.
0.0 Hz
Programming
ETR functions 1-4 do not begin to calculate the load
until you switch to the Setup in which they have been
selected. This means that you can use the ETR function even when changing between two or more motors.
Description of choice:
Select No protection [0] if you do not want a warning
or trip when a motor is overloaded.
Select Thermistor warning [1] if you want a warning
when the connected thermistor becomes too hot.
Select Thermistor trip [2] if you want a trip when the
connected thermistor becomes too hot.
Description of choice:
Set the required start frequency. It is a precondition
that parameter 121 Start function, is set to Start fre-
quency/voltage clockwise [3] or Start frequency voltage
in reference direction [4] and that in parameter 120 Start
delay a time is set and a reference signal is present.
NOTE
If parameter 123 is set higher than parameter 130, the start delay function (parameter 120 and 121) will be skipped.
131Initial voltage
(INITIAL VOLTAGE)
Value:
0.0 - 200.0 V
0.0 V
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 47
Function:
Initial voltage is active for the time set in parameter 120
Start delay , after a start command. This parameter can
be used for example for lifting/dropping applications
(conical anchor motors).
Description of choice:
Set the required voltage necessary to cut out the mechanical brake. It is assumed that parameter 121 Startfunction, is set to Start frequency/voltage clockwise [3]
or Start frequency/voltage in reference direction [4] and
that in parameter 120 Start delay a time is set, and that
a reference signal is present.
132DC brake voltage
(DC BRAKE VOLTAGE)
Value:
0 - 100% of max. DC brake voltage
Function:
In this parameter, the DC brake voltage is set which is
to be activated at stop when the DC brake frequency
set in parameter 127 DC brake cut-in frequency is
reached, or if DC braking inverse is active via a digital
input or via serial communication. Subsequently, the
DC brake voltage will be active for the time set in parameter 126 DC brake time.
Description of choice:
To be set as a percentage value of the max. DC brake
voltage, which depends on the motor.
0%
VLT® 2800 Series
Description of choice:
The factory setting will be suitable for must applications, the value may need to be increase gradually for
high torque application.
Warning: If the use of start voltage is exaggerated, this may lead to over-energizing and overheating of the motor and the
variable frequency drive may cut out.
134Load compensation
(LOAD COMPENSATIO)
Value:
0.0 - 300.0%
Function:
In this parameter, the load characteristic is set. By increasing the load compensation, the motor is given an
extra voltage and frequency supplement at increasing
loads. This is used e.g. in motors/applications in which
there is a big difference between the full-load current
and idle-load current of the motor.
100.0%
NOTE
133Start voltage
(START VOLTAGE)
Value:
0.00 - 100.00 V
Function:
A higher start torque can be obtained by increasing the
start voltage. Small motors (< 1.0 HP) normally require
a high start voltage.
= factory setting, () = display text, [] = value for use in communication via serial communication port
48 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Depends on unit
Description of choice:
If the factory setting is not adequate, load compensation must be set to enable the motor to start at the given
load.
If this value is set too high, the variable
frequency drive may cut out because of
overcurrent.
Warning: Should be set to 0% in connection with synchronous and parallel-coupled motors and in the case of quick load
changes. Too high load compensation
may lead to instability.
135U/f-ratio
(U/f RATIO)
Value:
0.00 - 20.00 at Hz
Depends on unit
Function:
This parameter enables a linear shift in the ratio between output voltage (V) and output frequency (f) to
ensure correct energizing of the motor and thus optimum dynamics, accuracy and efficiency. The V/f-ratio
only affects the voltage characteristic if Constant tor-
que [1] has been selected in parameter 101 Torque
characteristic .
Description of choice:
Change the V/f-ratio only if it is not possible to set the
correct motor data in parameters 102-109. The value
programmed in the factory settings is based on idle
operation.
VLT® 2800 Series
Function:
This parameter is used to keep the motor (holding torque) at start/stop.
Description of choice:
This parameter can only be used if a selection has
been made of DC hold in parameter 121 Start func-tion or 122 Function at stop . To be set as a percentage
value of the max. DC hold voltage, which depends on
the choice of motor.
138Brake cut out value
(Brake cut out)
Value:
0.5 - 132.0/1000.0 Hz
Function:
Select the frequency at which the external brake is released, via the output defined in parameter 323 Relayoutput 1-3 or 341 Digital output, terminal 46.
3.0 Hz
136Slip compensation
(SLIP COMP.)
Value:
-500 - +500% of rated slip compensation
100%
Function:
Slip compensation is calculated automatically, on the
basis of such data as the rated motor speed n
M,N
. In
this parameter, the slip compensation can be finetuned, thereby compensating for tolerances on the
value for n
. Slip compensation is only active if a se-
M,N
lection has been made of Speedregulation, open
loop [0] in parameter 100 Configuration and Constant
torque [1] in parameter 101 Torque characteristic.
Description of choice:
Key in a % value.
137DC hold voltage
(DC HOLD VOLTAGE)
Value:
0 - 100% of max. DC hold voltage
0%
Description of choice:
Set the required frequency.
139Brake cut in frequency
(Brake cut in)
Value:
0.5 - 132.0/1000.0 Hz
3.0 Hz
Function:
Select the frequency at which the external brake is activated; this takes place via the output defined in parameter 323 Relay output 1-3 or 341 Digital outputterminal 46.
Description of choice:
Set the required frequency.
140Current, minimum value
(CURRENT MIN VAL)
Value:
0 % - 100 % of inverter output current
0 %
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 49
VLT® 2800 Series
Function:
This is where the user selects the minimum motor current running for the mechanical brake to be released.
Current monitoring is only active from stop until the
point when the brake is released.
Description of choice:
This is an extra safety precaution, aimed at guaranteeing that the load is not lost during start of a lifting/
lowering operation.
142
Leakage reactance X
L
(LEAK. REACTANCE)
Value:
0.000 - XXX,XXX
Depends on choice of mo-
tor
is the sum of rotor and sta-
X
L
tor leakage reactance.
Function:
After setting of parameters 102-106 Nameplate data, a
number of adjustments of various parameters is made
automatically, including the leakage reactance X
. The
L
shaft performance can be improved by fine-tuning the
leakage reactance X
.
L
NOTE
Parameter 142 The leakage reactance X
is normally not to be changed if the nameplate data has been set, parameters
102-106.
Description of choice:
can be set as follows:
X
L
1.The value is stated by the motor supplier.
2.Use the factory settings of X
, which the ad-
L
justable frequency drive itself chooses on the
basis of the motor nameplate data.
143Internal fan control
(fan control)
Value:
Automatic (automatic)[0]
Always switched on (always on)[1]
Always switched off (always off)[2]
Function:
This parameter can be set so that the internal fan is
automatically switched on and off. You can also set the
internal fan to be permanently switched on or off.
Description of choice:
If Automatic [0] is selected, the internal fan is switched
on or off depending on the ambient temperature and
the loading of the adjustable frequency drive.
If Always switched on [1] or Always switched off [2] is
selected, the internal fan will be permanently switched
on or off, respectively.
NOTE
If Always switched off [2] is selected in
combination with high switch frequency,
long motor cables or high output power,
the adjustable frequency drive's life span
is reduced. This applies in particular to
1.5, 2, 4 and 5 HP units.
144Gain AC brake
(Gain AC brake)
Value:
L
1.00 - 1.50
1.30
Function:
This parameter is used to set the AC brake. Using par.
144 it is possible to adjust the size of the generator
torque that can be applied to the motor without the intermediate circuit voltage exceeding the warning level.
Description of choice:
The value is increased if a greater possible brake torque is required. If 1.0 is selected, this corresponds to
the AC brake being inactive.
NOTE
If the value in par. 144 is increased, the
motor current will simultaneously increase
significantly when generator loads are applied. The parameter should therefore only be changed if it is guaranteed during
measurement that the motor current in all
= factory setting, () = display text, [] = value for use in communication via serial communication port
50 MG.27.A2.22 - VLT® is a registered Danfoss trademark
operating situations will never exceed the
maximum permitted current in the motor.
Please note: that the current
read out from the display.
146Reset voltage vector
(RESET VECTOR)
Value:
*Off (OFF)[0]
Reset (RESET)[1]
Function:
When the voltage vector is reset it is set to the same
starting point each time a new process commences.
Description of choice:
Select reset (1) when running unique processes each
time they arise. This will enable repetitive precision
when stopping to be improved. Select Off (0) for example for lifting/lowering operations or synchronous
motors. It is an advantage that the motor and the variable frequency drive are always synchronized.
cannot be
VLT® 2800 Series
Programming
MG.27.A2.22 - VLT® is a registered Danfoss trademark 51
VLT® 2800 Series
References & Limits
200Output frequency range
(OUT FREQ. RNG/ROT)
Value:
Only clockwise, 0 - 132 Hz
(132 Hz CLOCKWISE)[0]
Both directions, 0 - 132 Hz
(132 Hz BOTH DIRECT)[1]
This parameter guarantees protection against unwanted reversing. Furthermore, the maximum output frequency that is to apply regardless of the settings of
other parameters can be selected. This parameter has
no function if Process regulation, closed-loop has been
selected in parameter 100 Configuration.
Description of choice:
Select the required direction of rotation as well as the
maximum output frequency. Please note that if Clock-wise only [0]/[3] or Counter-clockwise only [2]/[5] is
selected, the output frequency will be limited to the
range f
MIN-f MAX
output frequency will be limited to the range ± f
. If Both directions [1]/[4] is selected, the
(the
MAX
minimum frequency is of no significance).
201
Output frequency low limit, f
MIN
(MIN OUTPUT FREQ)
Value:
0.0 - f
MAX
0.0 Hz
Function:
In this parameter, a minimum motor frequency limit
can be selected that corresponds to the minimum
speed at which the motor is allowed to run. If Both di-
rections has been selected in parameter 200 Output
frequency range, the minimum frequency is of no sig-
nificance.
Description of choice:
The value chosen can range from 0.0 Hz to the frequency set in parameter 202 Output frequency high
limit, f
202
.
MAX
Output frequency high limit, f
MAX
(max. output freq)
Value:
f
- 132/1,000 Hz (par. 200 Output fre-
MIN
quency range)
132 Hz
Function:
In this parameter, a maximum output frequency limit
can be selected that corresponds to the highest speed
at which the motor is allowed to run.
NOTE
The output frequency of the adjustable
frequency drive can never assume a value
higher than 1/10 of the switching frequency (parameter 411Switching frequency).
Description of choice:
A value can be selected from f
to the value chosen
MIN
in parameter 200 Output frequency range.
= factory setting, () = display text, [] = value for use in communication via serial communication port
52 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
203Reference range
(REFERENCE RANGE)
Value:
Min. reference - Max reference (min - max)[0]
-Max. reference - Max. reference
(-max - +max)[1]
Function:
In this parameter you select whether the reference
signal must be positive or whether it can be both positive and negative. The minimum limit may be a negative value, unless in parameter 100 Configuration a
selection has been made of Speed regulation, closed
loop. You should select Min ref. - Max. ref. [0], if Process regulation, closed loop [3] has been selected inparameter 100 Configuration.
Minimum reference is an expression of the minimum
possible value of the total of all references. If in parameter 100 Configuration, Speed regulation, closedloop [1] or Process regulation, closed loop [3] is selected, the minimum reference is limited by parameter
414 Minimum feedback. Minimum reference is ignored
if the local reference is active.
The reference unit can be defined from the following
table:
Par. 100 Configuration
Unit
Open loop [0]Hz
Speed reg, closed loop [1]rpm
Process reg, closed loop [3]Par. 416
Description of choice:
The minimum reference is preset if the motor has to
run at a minimum speed, regardless of whether the
resulting reference is 0.
The maximum reference gives the highest value that
can be assumed by the sum of all references. If Closedloop [1]/[3] is selected in parameter 100 Configuration
the maximum reference cannot exceed the value in
parameter 415 Maximum feedback.
Maximum reference is ignored if the local reference is
active.
The reference unit can be defined from the following
table:
Par. 100 Configuration
Unit
Open loop [0]Hz
Speed reg, closed loop [1]rpm
Process reg, closed loop [3]Par. 416
Description of choice:
Maximum reference is set, if the speed of the motor is
to be max. the set value, regardless of the whether the
resulting reference is greater than the maximum reference.
206Ramp type
(Ramp type)
Value:
Linear (Linear)[0]
Sine shaped (S-SHAPED)[1]
2
Sine
shaped (S-SHAPED 2)[2]
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 53
VLT® 2800 Series
Function:
You can choose between a linear, a sine-shaped and
2
-shaped ramp process.
a sine
Description of choice:
Select the required ramp type depending on requirementsfor the acceleration/deceleration process.
207Ramp-up time 1
(Ramp-up time 1)
Value:
0.02 - 3600.00 sec
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
The ramp-up time is the acceleration time from 0 Hz to
the rated motor frequency f
frequency, f
). It is assumed that the output current
M,N
(parameter 104 Motor
M,N
will not reach the current limit (set in parameter 221
Current limit I
LIM
).
208Ramp-down time 1
(ramp down time 1)
Value:
0.02 - 3600.00 sec
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
The ramp-down time is the deceleration time from the
rated motor frequency f
quency, f
) to 0 Hz, provided no overvoltage arises
M,N
(parameter 104 Motor fre-
M,N
in the inverter because of generating operation of the
motor.
Description of choice:
Set the required ramp-down time.
2092 Ramp-up time
(2 Ramp-up time)
Value:
0.02 - 3600.00 sec.
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
See description of parameter 207 Ramp-up time 1.
Description of choice:
Set the required ramp-up time. Shift from ramp 1 to
ramp 2 by activating Ramp 2 via a digital input.
2102 Ramp-down time
(ramp down time 2)
Value:
0.02 - 3600.00 sec.
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
See description of parameter 208 Ramp-down time 1.
Description of choice:
Set the required ramp-down time. Shift from ramp 1 to
ramp 2 by activating Ramp 2 via a digital input.
211Jog ramp time
Description of choice:
Set the required ramp-up time.
Value:
0.02 - 3600.00 sec.
= factory setting, () = display text, [] = value for use in communication via serial communication port
54 MG.27.A2.22 - VLT® is a registered Danfoss trademark
(Jog ramp time)
3.00 sec (VLT 2803-2875)
VLT® 2800 Series
10.00 sec (VLT 2880-2882)
Function:
The jog ramp time is the acceleration/deceleration
time from 0 Hz to the rated motor frequency f
rameter 104 Motor frequency, f
). It is assumed that
M,N
M,N
(pa-
the output current will not reach the current limit (set in
parameter 221 Current limit I
LIM
).
The jog ramp time starts if a jog-signal is given via the
LCP control panel, one of the digital inputs or the serial
communication port.
Description of choice:
Set the required ramp time.
213Jog frequency
(Jog frequency)
Value:
0.0 - Par. 202 Output frequency high
limit, f
MAX
10.0 Hz
Function:
Jog frequency f
means a fixed output frequency
JOG
that the variable frequency drive supplies to the motor
when the Jog function is activated. Jog can be activated via the digital inputs, serial communication or via
the LCP control panel, on the condition that this is active in parameter 015 Local jog.
Description of choice:
Set the required frequency.
214Reference function
(Ref function)
Value:
Sum (sum)[0]
Relative (relative)[1]
External/preset (external/preset)[2]
Programming
212Quick-stop ramp-down time
(Q STOP RAMP TIME)
Value:
0.02 - 3600.00 sec.
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
The quick-stop ramp-down time is the deceleration
time from the rated motor frequency to 0 Hz, provided
no overvoltage arises in the inverter because of generating operation of the motor, or if the generated
current exceeds the current limit in parameter 221
Current limit I
. Quick-stop is activated via one of the
LIM
digital inputs or the serial communication.
Description of choice:
Set the required ramp-down time.
Function:
It is possible to define how preset references are to be
added to the other references; for this purpose, use
Sum or Relative. It is also possible by using the External/preset to select whether a shift between external
references and preset references is required.
External reference is the sum of the analog references,
pulse references and any references from serial communication.
Description of choice:
If Sum [0] is selected, one of the adjusted preset references (parameters 215-218 Preset reference) is
summarized as a percentage of the reference range
(Ref
MIN
- Ref
), added to the other external referen-
MAX
ces.
If Relative [1] is selected, one of the added preset references (parameters 215-218 Preset reference) is
summarized as a percentage of the sum of present
external references.
If External/preset [2] is selected, it is possible via a digital input to shift between external references or preset
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 55
VLT® 2800 Series
references. Preset references will be a percentage
value of the reference range.
NOTE
If Sum or Relative is selected, one of the
preset references will always be active. If
the preset references are to be without influence, they must be set to 0% (factory
setting).
Four different preset references can be programmed
in parameters 215-218 Preset reference.
The preset reference is stated as a percentage of the
reference range (Ref
MIN
- Ref
) or as a percentage
MAX
of the other external references, depending on the
choice made in parameter 214 Reference function.
The choice between preset references can be made
via the digital inputs or via serial communication.
Set the preset reference(s) that is/are to be the options.
219Catch up/Slow down reference
(Catch up/Slw dwn)
Value:
0.00 - 100% of the given reference
0.00%
Function:
In this parameter, the percentage value can be set
which will either be added to or deducted from the remote-controlled references.
The remote-controlled reference is the sum of preset
references, analog references, pulse reference and
any references from serial communication.
Description of choice:
If Catch up is active via a digital input, the percentage
value in parameter 219 Catch up/Slow down refer-ence will be added to the remote-controlled reference.
If Slow down is active via a digital input, the percentage
value in parameter 219 Catch up/Slow down refer-ence will be deducted from the remote-controlled reference.
221
Current limit, I
LIM
(current limit)
Value:
0 - XXX.X % of par. 105
160 %
Function:
In this parameter, the maximum output current I
LIM
is
set. The factory-set value corresponds to the maximum output current I
. If the current limit is to be
MAX
used as motor protection, set the rated motor current.
f the current limit is set above 100% (the rated output
current of the variable frequency drive, I
), the vari-
INV.
able frequency drive can only handle a load intermittently, i.e. for short periods at a time. After the load has
been higher than I
period the load is lower than I
the current limit is set at a lower value than I
, it must be ensured that for a
INV.
. Please note that if
INV
INV.
, the
acceleration torque will be reduced to the same extent.
Description of choice:
Set the required maximum output current I
223
Warning: Low current, I
LOW
LIM
.
(warn. current lo)
Value:
0.0 - par. 224 Warning: High current,
I
HIGH
0.0 A
Function:
If the output current falls below the preset limit I
LOW
a
warning is given.
= factory setting, () = display text, [] = value for use in communication via serial communication port
56 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Parameters 223-228 Warning functions are out of function during ramp-up after a start command and after a
stop command or during stop. The warning functions
are activated when the output frequency reaches the
resulting reference. The signal outputs can be programmed to give a warning signal via terminal 46 and
via the relay output.
Description of choice:
The lower signal limit of the output current I
LOW
must
be programmed within the normal working range of the
unit.
225
Warning: Low frequency, f
LOW
(warn.freq. low)
Value:
0.0 - par. 226
Warn.: High frequency, f
HIGH
0.0 Hz
Function:
If the output frequency falls below the preset limit
f
, a warning is given.
LOW
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and after stop command or during stop. The warning functions are activated when the output frequency has
reached the resulting reference. The signal outputs
can be programmed to give a warning signal via terminal 46 and via the relay output.
Description of choice:
The lower signal limit of the output frequency f
LOW
must
be programmed within the normal operating range of
the variable frequency drive. See drawing at parameter 223 Warning: Low current, I
LOW
.
224
Warning: High current, I
HIGH
(warn. current hi)
Value:
0 - I
MAX
I
MAX
Function:
If the output current exceeds the preset limit I
HIGH
a
warning is given.
Parameters 223-228 Warning functions do not work
during ramp-up after a start command and after stop
command or during stop. The warning functions are
activated when the output frequency has reached the
resulting reference. The signal outputs can be programmed to give a warning signal via terminal 46 and
via the relay output.
Description of choice:
The output current's upper signal limit I
HIGH
must be
programmed within the variable frequency drive's normal operating range. See drawing at parameter 223
Warning: Low current, I
LOW
.
226
Warning: High frequency f
HIGH
(warn.freq.high)
Value:
Par. 200 Frequency range = 0-132 Hz
[0]/[1].par. 225 f
- 132 Hz
LOW
132.0 Hz
Par. 200 Frequency range = 0-1000
Hz [2]/[3].par. 225 f
- 1000 Hz
LOW
132.0 Hz
Function:
If the output frequency exceeds the preset limit f
HIGH
warning is given.
Parameters 223-228 Warning functions do not work
during ramp-up after a start command and after stop
command or during stop. The warning functions are
activated when the output frequency has reached the
resulting reference. The signal outputs can be programmed to give a warning signal via terminal 46 and
via the relay output.
Description of choice:
The output frequency's upper signal limit f
HIGH
must be
programmed within the variable frequency drive's normal operating range. See drawing at parameter 223
Warning: Low current, I
LOW
.
Programming
a
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 57
VLT® 2800 Series
227
Warning: Low feedback, FB
LOW
(warn.feedb. low)
Value:
-100,000.000 - par. 228 Warn.:
FB
HIGH
-4000.000
Function:
If the feedback signal falls below the preset limit
, a warning is given.
FB
LOW
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and after a stop command or during stop. The warning functions are activated when the output frequency has
reached the resulting reference.The signal outputs
can be programmed to give a warning signal via terminal 46 and via the relay output.The unit for feedback
in Closed loop is programmed in parameter 416 Proc-ess units.
Description of choice:
Set the required value within the feedback range (parameter 414 Minimum feedback, FB
imum feedback, FB
228
Warning: High feedback, FB
MAX
).
and 415 Max-
MIN
HIGH
(warn.feedb high)
Value:
Par. 227 Warn.: FB
- 100,000.000
LOW
4000.000
Function:
If the feedback signal gets above the preset limit
, a warning is given.
FB
HIGH
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and after a stop command or during stop. The warning functions are activated when the output frequency has
reached the resulting reference. The signal outputs
can be programmed to give a warning signal via terminal 46 and via the relay output. The unit for feedback
in Closed loop is programmed in parameter 416 Proc-ess units.
229Frequency bypass, bandwidth
(FREQ BYPASS B.W.)
Value:
0 (OFF) - 100 Hz
0 Hz
Function:
Some systems call for some output frequencies to be
avoided because of mechanical resonance problems
in the system. In parameters 230-231 Frequency by-pass, these output frequencies can be programmed.
In this parameter, a bandwidth can be defined on either
side of these frequencies.
Description of choice:
The frequency set in this parameter will be centered
around parameters 230 Frequency bypass 1 and 231
Frequency bypass 2.
1. All functions on terminals 18 and 19 are controlled
by an interrupter, which means that the repetitive accuracy of the response time is constant. Can be used
for start/stop, set-up switch, and especially for chang-
Function:
In these parameters, 302-307 Digital inputs, it is possible to choose between the different enabled functions related to the digital inputs (terminals 18-33).
ing digital preset, i.e., to obtain a reproducible stop
point when using creep speed. For further information,
see VLT 2800 Precise Stop Instruction, MI.28.CX.02.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 59
Description of choice:
No operation is selected if the adjustable frequency
drive is not to react to signals transmitted to the terminal.
Reset resets the adjustable frequency drive after an
alarm; however, a few alarms cannot be reset (trip
locked) without first disconnecting the line supply and
reconnecting it. See table under List of warnings andalarms. Reset is activated on the leading edge of the
signal.
Coasting stop inverse is used for making the adjustable
frequency drive "let go" of the motor immediately (output transistors are "turned off"), which means that the
motor runs freely to a stop. Logic '0' leads to coasting
to stop.
Reset and coasting inverse are used to activate motor
coast simultaneously with reset. Logical '0' means motor coast stop and reset. Reset is activated on the
falling edge.
Quick stop inverse is used for activating the quick stop
ramp-down set in parameter 212 Quick stop ramp-
down time. Logic '0' leads to quick stop.
DC braking inverse is used for stopping the motor by
energizing it with a DC voltage for a given time; see
parameters 126, 127 and 132 DC brake. Please note
that this function is only active if the value in parameter
126 DC braking time and 132 DC brake voltage is dif-
ferent from 0. Logic '0' leads to DC braking.
VLT® 2800 Series
Latched start - if a pulse is applied for at least 14 ms,
the adjustable frequency drive will start the motor, provided no stop command has been given. The motor
can be stopped by briefly activating Stop inverse.
Reversing is used for changing the direction of rotation
of the motor shaft. Logic '0' will not lead to reversing.
Logic '1' will lead to reversing. The reverse signal only
changes the direction of rotation, it does not activate
the start. Is not active at Process regulation, closed-
loop. See also parameter 200 Output frequency range/
direction.
Reversing and start is used for start/stop and for re-
versing with the same signal. No active start command
is allowed at the same time. Acts as latch start reversing, provided latch start has been chosen for terminal
18. Is not active for Process regulation, closed-loop.
See also parameter 200 Output frequency range/di-
rection.
Start clockwise is used if you want the motor shaft only
to be able to rotate clockwise when started. Should not
be used for Process regulation, closed-loop.
Stop inverse, a logic '0' means that the motor speed is
ramped down to stop via the selected ramp.
None of the stop commands mentioned
above are to be used as repair switches.
Note that the adjustable frequency drive
has more voltage inputs than L1, L2 and
L3 when the DC bus terminals are used.
Make sure that all voltage inputs are disconnected and that the prescribed time (4
minutes.) has passed before repair work
is commenced.
Start is selected if a start/stop command is required.
Logic '1' = start, logic '0' = stop.
= factory setting, () = display text, [] = value for use in communication via serial communication port
60 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Start counter-clockwise is used if you want the motor
shaft only to be able to rotate counter-clockwise when
started. Should not be used for Process regulation,
closed-loop. See also parameter 200 Output frequency
range/direction.
Jog is used to override the output frequency to the jog
frequency set in parameter 213 Jog frequency. Jog is
active regardless of whether a start command has
been given, yet not when Coast stop, Quick stop or DC
braking are active.
Freeze reference freezes the present reference. Thereference can now only be changed via Speed up and
Slow. If freeze reference is active, it will be saved after
a stop command and in the event of line failure.
Freeze output freezes the present output frequency (in
Hz). The output frequency can now only be changed
via Speed up and Slow.
VLT® 2800 Series
NOTE
If Freeze output is active, the adjustable
frequency drive can only be stopped by
selecting Motor coast, Quick stop, or DC
braking via a digital input.
Speed up and Slow are selected if digital control of the
up/down speed is required. This function is only active
if Freeze reference or Freeze output frequency has been
selected.
If Speed up is active, the reference or output frequency
will be increased; and if Slow is active, the reference
or output frequency will be reduced. The output frequency is changed via the preset ramp times in parameters 209-210 Ramp 2.
One pulse (logic '1' minimum high for 14 ms and a
minimum break time of 14 ms) will lead to a speed
change of 0.1% (reference) or 0.1 Hz (output frequency). Example:
Term.33Freeze ref/
Term
.29
001No speed change
0
1
1
freeze outp.
11Speed up
01Slow
11Slow
Function
Preset ref.
msb
00Preset ref. 1
0
1
1
Preset reference on is used for shifting between a remote-controlled reference and a preset reference. It is
assumed that External/preset [2] has been selected in
parameter 214 Reference function. Logic '0' means that
remote-controlled references are active, while logic '1'
means that one of the four preset references is active,
as can be seen from the table above.
Thermistor is to be selected if a possibly integrated
thermistor in the motor is to be able to stop the adjustable frequency drive if the motor overheats. The cutout value is 3 k.
Preset ref.
lsb
1Preset ref. 2
0Preset ref. 3
1Preset ref. 4
Function
Programming
Freeze reference can be changed even if the adjustable
frequency drive has stopped. The reference will also
be saved if line power is disconnected.
Catch-up/Slow-down is selected if the reference value
is to be increased or reduced by a programmable percentage value set in parameter 219 Catch-up/Slow-down reference.
Slow-down
00Unchanged speed
0
1
1
Ramp 2 is selected if a shift between ramp 1 (parameters 207-208) and ramp 2 (parameters 209-210) is
required. Logic '0' leads to ramp 1 and logic '1' leads
to ramp 2.
Preset reference, lsb and Preset reference, msb makes
it possible to select one of the four preset references;
see the table below:
Catch-upFunction
1Increase by % value
0Reduce by % value
1Reduce by % value
If a motor features a Klixon thermal switch instead, this
can also be connected to the input. If motors operate
in parallel, the thermistors/thermal switches can be
connected in series (total resistance lower than 3 k).
Parameter 128 Motor thermal protection must be programmed for Thermistor warning [1] or Thermistor trip
[2], and the thermistor is to be connected between a
digital input and terminal 50 (+10 V supply).
Precise stop, inverse is selected to obtain a high degree
of accuracy when a stop command is repeated. A logic
0 means that the motor speed is ramped down to stop
via the selected ramp.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 61
VLT® 2800 Series
Precise start/stop is selected to obtain a high degree
of accuracy when a start and stop command is repeated.
Pulse reference is selected if the reference signal applied is a pulse train (frequency). 0 Hz corresponds to
parameter 204 Minimum reference, Ref
. The fre-
MIN
quency, set in parameter 327 Pulse reference/feedback, corresponds to parameter 205 Maximum reference Ref
MAX
.
Pulse feedback is selected if the feedback signal usedis a pulse train (frequency). In parameter 327 Pulse
reference/feedback, the maximum pulse feedback fre-
quency is set.
Pulse input is selected if a specific number of pulses
must lead to a Precise stop; see parameter 343 Precise
stop and parameter 344 Counter value.
Selection of Set-up, lsb and Selection of Set-up, msb
provides the option of selecting one of the four set-ups.
It is, however, a condition that parameter 004 is set to
Multi-set-up.
Reset and start can be used as a start function. If 24 V
are connected to the digital input, this will cause the
adjustable frequency drive to reset, and the motor will
ramp up to the preset reference.
Pulse counter start is used to start a counter stop sequence with a pulse signal. The pulse width must be
at least 14 ms and not longer than the count period.
See also parameter 343 and the instruction,
MI28CXYY.
308Terminal 53, analogue input voltage
(AI [V]53FUNCT.)
Value:
No function (NO OPERATION)[0]
Reference (reference)[1]
Feedback (feedback)[2]
Wobble (WOBB.DELTA FREQ [%])[10]
Function:
In this parameter, it is possible to select the function
required to be connected to terminal 53. Scaling of the
input signal is made in parameter 309 Terminal 53, min.scaling and parameter 310 Terminal 53, max. scaling.
Description of choice:
No function [0]. Is selected if the adjustable frequency
drive is not to react to signals connected to the terminal. Reference [1]. If this function is selected, the reference can be changed by means of an analog
reference signal. If reference signals are connected to
more than one input, these reference signals must be
added up.If a voltage feedback signal is connected,
select Feedback [2] on terminal 53.
Wobble [10]
The delta frequency can be controlled by the analog
input. If WOBB.DELTA FREQ is selected as analog input (par. 308 or par. 314) the value selected in par. 702
equals 100 % analog input.
Example: Analog input = 4-20 mA, Delta freq. par. 702
= 5 Hz • 4 mA = 0 Hz and 20 mA = 5 Hz. If this function
is chosen, see Wobble Instruction MI28JXYY for further information.
309Terminal 53 Min. scaling
(AI 53 SCALE LOW)
Value:
0.0 - 10.0 Volt
0.0 Volt
Function:
This parameter is used for setting the signal value that
is to correspond to the minimum reference or the minimum feedback, parameter 204 Minimum reference,
/ 414 Minimum feedback, FB
Ref
MIN
MIN
.
Description of choice:
Set the required voltage value. For reasons of accuracy, compensation should be made for voltage loss
in long signal cables. If the Time out function is to be
used (parameter 317 Time out and 318 Function aftertime out), the value set must be higher than 1 Volt.
310Terminal 53 Max. scaling
(AI 53 SCALE HIGH)
Value:
0 - 10.0 Volt
10.0 Volt
Function:
This parameter is used for setting the signal value that
is to correspond to the maximum reference value or
= factory setting, () = display text, [] = value for use in communication via serial communication port
62 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
maximum feedback, parameter 205 Maximum reference, Ref
/ 414 Maximum feedback, FB
MAX
MAX
.
Description of choice:
Set the required voltage value. For reasons of accuracy, compensation should be made for voltage losses
in long signal cables.
314Terminal 60, analogue input current
(AI [mA] 60 FUNCT)
Value:
No function (no operation)[0]
Reference (reference)[1]
Feedback (feedback)[2]
Wobble (WOBB.DELTA FREQ [%])[10]
Function:
This parameter allows a choice between the different
functions available for the input, terminal 60. Scaling
of the input signal is effected in parameter 315 Terminal
60, min. scaling and parameter 316 Terminal 60, max.
scaling.
Description of choice:
No function [0]. Is selected if the adjustable frequency
drive is not to react to signals connected to the terminal. Reference [1]. If this function is selected, the reference can be changed by means of an analog
reference signal. If reference signals are connected to
more than one input, these reference signals must be
added up.
If one current feedback signal is connected, select
Feedback [2] on terminal 60.
Wobble [10]
The delta frequency can be controlled by the analog
input. If WOBB.DELTA FREQ is selected as analog input (par. 308 or par. 314) the value selected in par. 702
equals 100 % analog input.
Example: Analog input = 4-20 mA, Delta freq. par. 702
= 5 Hz • 4 mA = 0 Hz and 20 mA = 5 Hz. If this function
is chosen, see Wobble Instruction MI28JXYY for further information.
315Terminal 60 Min. scaling
(AI 60 SCALE LOW)
Value:
0.0 - 20.0 mA
4.0 mA
Function:
In this parameter, you can set the signal value that will
correspond to the minimum reference or minimum
feedback, parameter 204 Minimum reference, Ref
414 Minimum feedback, FB
MIN
.
MIN
Description of choice:
Set the required current value. If the Timeout function
is to be used (parameter 317 Time out and 318 Func-tion after time out ), the value set must be higher than
2 mA.
316Terminal 60 Max. scaling
(AI 60 SCALE HIGH)
Value:
0.0 - 20.0 mA
20.0 mA
Function:
This parameter is used for setting the signal value that
is to correspond to the maximum reference value, parameter 205 Maximum reference value, Ref
MAX
.
Description of choice:
Set the required current value.
317Time out
(LIVE ZERO TIME O)
Value:
1 - 99 sec.
10 sec.
Function:
If the signal value of the reference or feedback signal
connected to one of the input terminals 53 or 60 falls
below 50 % of the minimum scaling for a period longer
than the time set, the function selected in parameter
318 Function after time out will be activated. This function is only active if in parameter 309 Terminal 53, min.scaling a value higher than 1 Volt has been selected,
or if in parameter 315 Terminal 60, min. scaling a value
higher than 2 mA has been selected.
/
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 63
VLT® 2800 Series
Description of choice:
Set the required time.
318Function after time out
(LIVE ZERO FUNCT.)
Value:
No operation (NO OPERATION)[0]
Freeze output frequency
(FREEZE OUTPUT FREQ.)[1]
Stop (stop)[2]
Jog (jog)[3]
Max. speed (MAX SPEED)[4]
Stop and trip (STOP AND TRIP)[5]
Function:
This parameter allows a choice of the function to be
activated after the expiry of the Time out (parameter
317 Time out ). If a time-out function occurs at the same
time as a bus time-out function (parameter 513 Bustime interval function ), the time-out function in parameter 318 will be activated.
Description of choice:
The output frequency of the adjustable frequency drive
can be:
frozen at the present frequency [1]
-
overruled to stop [2]
-
(fb min-max = 4-20 mA)
Output frequency 0-max 0-20 mA
(0-fmax = 0-20 mA)[5]
Output frequency 0-max 4-20 mA
(0-fmax = 4-20 mA)[6]
Output current 0-I
0-20 mA
INV
(0-iinv = 0-20 mA)[7]
Output current 0-I
4-20 mA
IINV
(0-iinv = 4-20 mA)[8]
Output power 0-P
0-20 mA
M,N
(0-Pnom = 0-20 mA)[9]
Output power 0-P
4-20 mA
M,N
(0-Pnom = 4-20 mA)[10]
Inverter temperature 68-212 °F [20-100 °C]
0-20 mA
(TEMP 20-100 C=0-20 mA)[11]
Inverter temperature 68-212 °F [20-100 °C]
4-20 mA
(TEMP 20-100 C=4-20 mA)[12]
Function:
The analog output can be used for stating a process
value. It is possible to choose two types of output signals 0-20 mA or 4-20 mA.
If used as a voltage output (0-10 V), a pull-down resistor of 500 must be fitted to common (terminal 55).
If the output is used as a current output, the resulting
resistance from the equipment connected may not exceed 500 .
overruled to jog frequency [3]
Description of choice:
overruled to max. output frequency [4]
-
overruled to stop with subsequent trip [5]
-
No function. Is selected if the analog output is not to be
used.
External Ref
MIN
- Ref
0-20 mA/4-20 mA.
MAX
An output signal is obtained, which is proportional to
319Analog output terminal 42
(AO 42 FUNCTION)
Value:
No function (NO OPERATION)[0]
External reference min.-max. 0-20 mA
(ref min-max = 0-20 mA)[1]
External reference min.-max. 4-20 mA
(ref min-max = 4-20 mA)[2]
Feedback min.-max. 0-20 mA
the resulting reference value in the interval Minimum
reference, Ref
- Maximum reference, Ref
MIN
MAX
(pa-
rameters 204/205).
-FB
FB
MIN
0-20 mA/ 4-20 mA.
MAX
An output signal is obtained, which is proportional to
the feedback value in the interval Minimum feedback,
FB
- Maximum feedback, FB
MIN
(parameter
MAX
414/415).
0-20 mA/4-20 mA.
0-f
MAX
(fb min-max = 0-20 mA)[3]
Feedback min.-max. 4-20 mA[4]
= factory setting, () = display text, [] = value for use in communication via serial communication port
64 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
202 Output frequency, high limit, f
0-20 mA/4-20 mA.
0 - I
INV
MAX
MAX
).
(parameter
An output signal is obtained, which is proportional to
the output current in the interval 0 - I
0 - P
0-20 mA/4-20 mA.
M,N
INV
An output signal is obtained, which is proportional to
the present output power. 20 mA corresponds to the
value set in parameter 102 Motor power, P
0 - Temp.
0-20 mA/4-20 mA.
MAX
M,N
.
An output signal is obtained, which is proportional to
the present heatsink temperature. 0/4 mA corresponds to a heatsink temperature of less than 68 °F
[20 °C], and 20 mA corresponds to 100 °C.
323Relay output 1-3
(RELAY 1-3 FUNCT.)
Value:
No function (no operation)[0]
Unit ready (unit ready)[1]
Enable/no warning (enable/no warning)[2]
Running (RUNNING)[3]
Running in reference, no warning
(run on ref/no warn)[4]
Running, no warnings
(RUNNING/NO WARNING)[5]
Running in reference range, no warnings
(RUN IN RANGE/ NO WARN)[6]
Ready - AC line voltage within range
(RDY NO OVER/UNDERVOL)[7]
Alarm or warning
(ALARM OR WARNING)[8]
Current higher than current limit, par. 221
(Current limit)[9]
Alarm (ALARM)[10]
Output frequency higher than f
par. 225
LOW
(above frequency low)[11]
Output frequency lower than f
HIGH
par. 226
(below frequency high)[12]
Output current higher than I
LOW
par. 223
(above current low)[13]
Output current lower than I
HIGH
par. 224
(below current high)[14]
Feedback higher than FB
LOW
par. 227
(above feedback low)[15]
Feedback lower than FB
HIGH
par. 228
(under feedback high)[16]
Relay 123 (RELAY 123)[17]
Reversing (REVERSE)[18]
Thermal warning (THERMAL WARNING)[19]
Local operation (LOCAL MODE)[20]
Out of frequency range par. 225/226
(out of freq. range)[22]
Out of current range
(out of current range)[23]
Out of feedback range
(out of fdbk. range)[24]
Mechanical brake control
(Mech. brake control)[25]
Control word bit 11
(control word bit 11)[26]
Function:
The relay output can be used for giving the present
status or warning. The output is activated (1-2 make)
when a given condition is fulfilled.
Description of choice:
No function is selected if the adjustable frequency drive
is not to react to signals.
Unit ready: there is a supply voltage on the control card
of the adjustable frequency drive, and the adjustable
frequency drive is ready for operation.
Enable, no warning: the adjustable frequency drive is
ready for operation, but no start command has been
given. No warning.
Running is active when there is a start command or the
output frequency is above 0.1 Hz. Also active during
ramp-down.
Running in reference, no warning: speed according to
reference.
Running, no warning: a start command has been given.
No warning.
Ready - line voltage within range: the adjustable frequency drive is ready for use, the control card is receiving supply voltage, and there are no active control
signals on the inputs. The AC line voltage lies within
the voltage limits.
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 65
VLT® 2800 Series
Alarm or warning: the output is activated by an alarm
or warning.
Current limit: the output current is higher than the value
programmed in parameter 221 Current limit I
LIM
.
Alarm: the output is activated by an alarm.
Output frequency higher than f
: the output frequen-
LOW
cy is higher than the value set in parameter 225
Warning: Low frequency, f
Output frequency lower than f
.
LOW
: the output frequen-
HIGH
cy is lower than the value set in parameter 226 Warning: High frequency, f
Output current higher than I
HIGH
.
: the output current is
LOW
higher than the value set in parameter 223 Warning:
Low current, I
Output current lower than I
LOW
.
: the output current is
HIGH
lower than the value set in parameter 224 Warning:
High current, I
Feedback higher than FB
HIGH
.
: the feedback value is
LOW
higher than the value set in parameter 227 Warning:
Low feedback, FB
Feedback lower than FB
LOW
.
: the feedback value is
HIGH
lower than the value set in parameter 228 Warning:
High current, I
HIGH
.
Relay 123 is only used in connection with Profidrive.
Reversing: the relay output is activated when the di-
rection of motor rotation is counter-clockwise. When
the direction of motor rotation is clockwise, the value
is 0 V DC.
Thermal warning: above the temperature limit in either
the motor or the adjustable frequency drive, or from a
thermistor connected to a digital input.
Local operation: the output is active when in parameter
002 Local/remote operation,Local operation [1] has
been selected.
Mechanical brake control: enables you to control an
external mechanical brake (see section about control
of mechanical brake in the VLT 2800 Design Guide).
327Pulse/reference feedback
(PULSE REF/FB MAX)
Value:
150 - 67600 Hz
5000 Hz
Function:
This parameter is used for setting the signal value that
corresponds to the maximum value set in parameter
205 Maximum reference, Ref
or to the maximum
MAX
feedback value set in parameter 415 Maximum feedback, FB
MAX
.
Description of choice:
Set the required pulse reference or pulse feedback to
be connected to terminal 33.
328Maximum Pulse 29
(MAX PULSE 29)
Value:
150 - 67600 Hz
5000 Hz
Function:
This parameter is used for setting the signal value that
corresponds to the maximum value set in parameter
205 Maximum reference, Ref
or to the maximum
MAX
feedback value set in parameter 415 Maximum feedback, FB
MAX
.
NOTE
Only relevant for DeviceNet. See
MG90BXYY for further information.
Out of the frequency range: the output frequency is out
of the programmed frequency range in parameters
225 and 226.
Out of the current range: the motor current is out of the
programmed range in parameters 223 and 224.
Out of the feedback range: the feedback signal is out
of the programmed range in parameters 227 and 228.
341Digital / pulse output terminal 46
(DO 46 FUNCTION)
Value:
Unit ready (Unit ready)[0]
Parameter [0] - [20] see parameter 323
Pulse reference (PULSE REFERENCE)[21]
Parameter [22] - [25] see parameter 323
= factory setting, () = display text, [] = value for use in communication via serial communication port
66 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Pulse feedback (PULSE FEEDBACK)[26]
Output frequency (PULSE OUTPUTFREQ)[27]
Pulse current (PULSE CURRENT)[28]
Pulse power (PULSE POWER)[29]
Pulse temperature (PULSE TEMP)[30]
Function:
The digital output can be used for giving the present
status or warning. The digital output (terminal 46) gives
a 24 V DC signal when a given condition is fulfilled.
Terminal can also be used for frequency output.
Parameter 342 sets the maximum pulse frequency.
Description of choice:
Pulse reference Ref
MIN
- Ref
MAX
An output signal is obtained, which is proportional to
the resulting reference value in the interval Minimum
reference, Ref
- Maximum reference, Ref
MIN
MAX
(pa-
rameters 204/205).
Pulse feedback FB
MIN
-FB
MAX
.
An output signal is obtained, which is proportional to
the feedback value in the interval Minimum feedback,
FB
- Maximum feedback, FB
MIN
(parameter
MAX
414/415).
Output frequency 0-f
MAX
.
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
202 Output frequency, high limit, f
Pulse current 0 - I
INV.
.
MAX
(parameter
MAX
).
An output signal is obtained, which is proportional to
the output current in the interval 0 - I
Pulse power 0 - P
M,N
.
INV
.
An output signal is obtained, which is proportional to
the present output power. Par. 342 corresponds to the
value set in parameter 102 Motor power, P
Pulse temperature 0 - Temp.
MAX
.
M,N
.
An output signal is obtained, which is proportional to
the present heatsink temperature. 0 Hz corresponds
to a heatsink temperature of less than 68 °F (20° C),
and 20 mA corresponds to 212 °F (100° C).
NOTE
Output terminal 46 is not available on DeviceNet. Minimum output frequency at frequency output = 16 Hz
342Terminal 46, max. pulse scaling
(DO 46 MAX. PULS)
Value:
150 - 10000 Hz
5000 Hz
Function:
This parameter is used for setting the pulse output signal's maximum frequency.
Description of choice:
Set the required frequency.
343Precise stop function
(Precise stop)
Value:
Precise ramp stop (normal)[0]
Counter stop with reset
(Count stop reset)[1]
Counter stop without reset
(Count stop no reset)[2]
Speed-compensated stop (Spd cmp stop)[3]
Speed-compensated counter stop with reset
(Spd cmp cstop w. res)[4]
Speed-compensated counter stop without reset
(Spd cmp cstop no res)[5]
Function:
In this parameter you select which stop function is performed in response to a stop command. All six data
selections contain a precise stop routine, thus ensuring a high level of repeat accuracy.
The selections are a combination of the functions described below.
NOTE
Pulse start [8] may
not be used together
with the precise stop function.
Description of choice:
Precise ramp stop [0] is selected to achieve high repetitive precision at the stopping point.
Counter stop. Once it has received a pulse start signal
the adjustable frequency drive runs until the number of
pulses programmed by the user have been received
at input terminal 33. In this way an internal stop signal
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 67
VLT® 2800 Series
will activate the normal ramp down time (parameter
208).
The counter function is activated (starts timing) at the
flank of the start signal (when it changes from stop to
start).
Speed compensated stop. To stop at precisely the
same point, regardless of the present speed, a stop
signal received is delayed internally when the present
speed is lower than the maximum speed (set in parameter 202).
Reset. Counter stop and Speed-compensated stop can
be combined with or without reset.
Counter stop with reset [1]. After each precise stop the
number of pulses counted during ramp down 0 Hz is
reset.
Counter stop without reset [2]. The number of pulses
counted during ramp down to 0 Hz is deducted from
the counter value in parameter 344.
344Counter value
(Pulse count pre.)
Value:
0 - 999999
Function:
In this parameter, you can select the counter value to
be used in the integrated precise stop function (parameter 343).
100,000 pulses
Description of choice:
The factory setting is 10 ms. This means that it is assumed that the total delay from the Sensor, PLC and
other hardware corresponds to this setting.
NOTE
Only active for speed-compensated stop.
Description of choice:
The factory setting is 100,000 pulses. The highest frequency (max. resolution) that can be registered at
terminal 33 is 67.6 kHz.
349Speed comp delay
(SPEED COMP DELAY)
Value:
0 ms - 100 ms
Function:
In this parameter the user can set the system's delay
time (Sensor, PLC, etc.). If you are running speedcompensated stop, the delay time at different frequencies has a major influence on the way in which you
stop.
= factory setting, () = display text, [] = value for use in communication via serial communication port
68 MG.27.A2.22 - VLT® is a registered Danfoss trademark
10 ms
VLT® 2800 Series
Special functions
400Brake function
(Brake function)
Value:
Off (off)[0]
Resistor brake
(Resistor)[1]
AC brake (AC Brake)[4]
Load sharing (load sharing)[5]
Factory setting depends on unit type.
Function:
Resistor brake [1] is selected if the adjustable frequency drive has an integral brake transistor and brake
resistor is connected to terminals 81, 82. A higher intermediate circuit voltage is permitted during braking
(generated operation) when a brake resistor is connected.
AC brake [4] can be selected to improve braking without using brake resistors. Please note that AC brake
[4] is not as effective as Resistor brake [1].
Description of choice:
Select Resistor brake [1] if a brake resistor is connected.
Select AC brake [4] if short-term generated loads occur. See parameter 144 Gain AC brake to set the brake.
Select Load sharing [5] if this is used.
NOTE
A change of selection will not become active until the mains voltage has been disconnected and reconnected.
405Reset function
(reset mode)
Value:
Manual reset (manual reset)[0]
Automatic reset x 1
(AUTOMATIC x 1)[1]
Automatic reset x 3
(AUTOMATIC x 3)[3]
Automatic reset x 10[10]
(AUTOMATIC x 10)
Reset at power-up
(RESET AT POWER UP)[11]
Function:
This parameter makes it possible to select whether reset and restart after a trip are to be manual or whether
the adjustable frequency drive is to be reset and restarted automatically. Furthermore, it is possible to
select the number of times a restart is to be attempted.
The time between each attempt is set in parameter 406
Automatic restart time.
Description of choice:
If Manual reset [0] is selected, reset is to be carried out
via the [STOP/RESET] key, a digital input or serial
communication. If the adjustable frequency drive is to
carry out an automatic reset and restart after a trip,
select data value [1], [3] or [10].
If Reset at power-up [11] is selected, the adjustable
frequency drive will carry out a reset if there has been
a fault in connection with the mains failure.
The motor may start without warning.
406Automatic restart time
(autorestart time)
Value:
0 - 10 sec.
5 sec.
Function:
This parameter allows setting of the time from tripping
until the automatic reset function begins. It is assumed
that automatic reset has been selected in parameter
405 Reset function.
Description of choice:
Set the required time.
409
Trip delay overcurrent, I
LIM
(trip delay cur.)
Value:
0 - 60 sec. (61=OFF)
OFF
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 69
Function:
When the adjustable frequency drive registers that the
output current has reached the current limit I
LIM
(parameter 221 Current limit) and remains there for the
preset time, it is disconnected. Can be used to protect
the application, like the ETR will protect the motor if
selected.
Description of choice:
Select how long the adjustable frequency drive should
maintain the output current at the current limit I
LIM
be-
fore it disconnects. At OFF parameter 409 Trip delay
overcurrent, I
is not working, i.e. disconnection will
LIM
not take place.
411Switching frequency
(Switch freq.)
Value:
3000 - 14000 Hz (VLT 2803 - 2875)
3000 - 10000 Hz (VLT 2880 - 2882)
4500 Hz
4500 Hz
Function:
The set value determines the switching frequency of
the inverter. If the switching frequency is changed, this
may help to minimise possible acoustic noise from the
motor.
NOTE
The output frequency of the adjustable
frequency drive can never assume a value
higher than 1/10 of the switching frequency.
Description of choice:
When the motor is running, the switching frequency is
adjusted in parameter 411 Switching frequency until
the frequency has been obtained at which the motor is
as low-noise as possible.
NOTE
The switching frequency is reduced automatically as a function of the load. See
Temperature-Dependent Switching Frequency under Special Conditions .
When LC-filter connected is selected in
parameter 412, the minimum switching
frequency is 4.5 kHz.
VLT® 2800 Series
412Variable switching frequency
(Var carrier freq.)
Value:
Without LC-filter (WITHOUT LC-FILTER)[2]
LC-filter connected
(LC-filter connected)[3]
Function:
The parameter must be set to LC-filter connected if an
LC-filter is connected between the adjustable frequency drive and the motor.
Description of choice:
The LC-filter connected [3] must be used if an LC-filter
is connected between the adjustable frequency drive
and the motor, as otherwise the adjustable frequency
drive cannot protect the LC-filter.
NOTE
When the LC filter is selected the switching frequency is changed to 4.5 kHz.
413Overmodulation function
(OVERMODULATION)
Value:
Off (off)[0]
On (on)[1]
Function:
This parameter allows connection of the overmodulation function for the output voltage.
Description of choice:
Off [0] means that there is no overmodulation of the
output voltage, which means that torque ripple on the
motor shaft is avoided. This can be a good feature, e.g.
on grinding machines. On [1] means that an output
voltage can be obtained which is greater than the
mains voltage (up to 5 %).
= factory setting, () = display text, [] = value for use in communication via serial communication port
70 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
414
Minimum feedback, FB
MIN
(Min. feedback)
Value:
-100,000.000 - par. 415 FB
MAX
0.000
Function:
Parameter 414 Minimum feedback, FB
Maximum feedback, FB
are used to scale the dis-
MAX
and 415
MIN
play text to make it show the feedback signal in a
process unit proportionally to the signal on the input.
Description of choice:
Set the value to be shown on the display as the minimum feedback signal value on the selected feedback
input (parameters 308/314 Analog inputs).
415
Maximum feedback, FB
MAX
(Max. feedback)
Value:
- 100,000.000
FB
MIN
1500.000
Function:
See description of parameter 414 Minimum feedback,
.
FB
MIN
Description of choice:
Set the value to be shown on the display when the
maximum feedback has been obtained on the selected
feedback input (parameter 308/314 Analog inputs).
416Process units
(REF/FEEDB. UNIT)
Value:
No unit (No unit)[0]
% (%)[1]
ppm (ppm)[2]
rpm (rpm)[3]
bar (bar)[4]
Cycles/min. (CYCLE/MIN.)[5]
Pulses/sec. (PULSE/SEC.)[6]
Units/sec. (UNITS/SEC.)[7]
Units/min. (UNITS/MIN.)[8]
Units/h (Units/h)[9]
°C (°C)[10]
Pa (pa)[11]
l/s (l/s)[12]
3
m
/s (m3/s)[13]
l/min. (l/min.)[14]
3
/min. (m3/min)[15]
m
l/h (l/h)[16]
3
m
/h (m3/h)[17]
kg/sec. (kg/sec.)[18]
kg/min. (kg/min.)[19]
kg/hour (kg/h)[20]
tons/min. (T/min)[21]
tons/hour (T/h)[22]
Meters (m)[23]
Nm (nm)[24]
m/sec. (m/sec.)[25]
m/min. (m/min)[26]
°F (°F)[27]
In wg (in wg)[28]
gal/sec. (gal/sec.)[29]
3
ft
/sec. (ft3/sec.)[30]
gal/min. (gal/min)[31]
3
ft
/min. (ft3/min)[32]
gal/h (gal/h)[33]
3
ft
/h (ft3/h)[34]
lb/sec. (lb/sec.)[35]
lb/min. (lb/min.)[36]
lb/hour (lb/h)[37]
lb ft (lb ft)[38]
ft/s (ft/s)[39]
ft/min. (ft/min.)[40]
psi (psi)[41]
Function:
Select which of the different units are to be shown on
the display. The unit is read out if an LCP control unit
can be connected, and if Reference [unit] [2] or Feed-back [unit] [3] has been selected in one of parameters
009-012 Display readout, and in display mode. The unit
is used in Closed-loop also as a unit for minimum/
maximum reference and minimum/maximum feedback.
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 71
VLT® 2800 Series
Description of choice:
Select the required unit for the reference/feedback signal.
NOTE
Parameters 417-421 are only used, if in
parameter 100 Configuration the selection
made is Speed regulation, closed loop [1].
417Speed PID proportional gain
(SPEED PROP GAIN)
Value:
0.000 (OFF) - 1.000
Function:
Proportional gain indicates how many times the fault
(deviation between the feedback signal and the setpoint) is to be amplified.
Description of choice:
Quick regulation is obtained at high amplification, but
if the amplification is too high, the process may become unstable in the case of overshooting.
418Speed PID integral time
(SPEED int. time)
Value:
20.00 - 999.99 ms (1000 = OFF)
Function:
The integral time determines how long the PID regulator takes to correct the error. The greater the error,
the quicker the integrator frequency contribution will
increase. The integral time is the time the integrator
needs to achieve the same change as the proportional
amplification.
Description of choice:
Quick regulation is obtained through a short integral
time. However, if this time is too short, it can make the
process unstable. If the integral time is long, major deviations from the required reference may occur, since
the process regulator will take long to regulate if an
error has occurred.
0.010
100 ms
419Speed PID differential time
(SPEED diff. time)
Value:
0.00 (OFF) - 200.00 ms
Function:
The differentiator does not react to a constant error. It
only makes a contribution when the error changes.
The quicker the error changes, the stronger the gain
from the differentiator will be. The contribution is proportional to the speed at which errors change.
Description of choice:
Quick control is obtained by a long differential time.
However, if this time is too long, it can make the process unstable. When the differential time is 0 ms, the Dfunction is not active.
420Speed PID D- gain limit
(SPEED D-GAIN LIM)
Value:
5.0 - 50.0
Function:
It is possible to set a limit for the gain provided by the
differentiator. Since the D-gain increases at higher frequencies, limiting the gain may be useful. This enables
obtaining a pure D-gain at low frequencies and a constant D-gain at higher frequencies.
Description of choice:
Select the required gain limit.
421Speed PID lowpass filter time
(speed filt. time)
Value:
20 - 500 ms
Function:
Noise in the feedback signal is dampened by a first
order lowpass filter to reduce the noise's impact on the
regulation. This might be an advantage, e.g. if there is
a great amount of noise on the signal. See drawing.
20.00 ms
5.0
100 ms
= factory setting, () = display text, [] = value for use in communication via serial communication port
72 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Description of choice:
If a time constant (t) of 100 ms is programmed, the cutoff frequency for the lowpass filter will be 1/0.1 = 10
RAD/sec., corresponding to (10 / 2 x ) = 1.6 Hz. The
PID regulator will then only regulate a feedback signal
that varies with a frequency of less than 1.6 Hz. If the
feedback signal varies by a higher frequency than 1.6
Hz, it will be dampened by the lowpass filter.
VLT® 2800 Series
Description of choice:
Set the output voltage (U1) that is to match the first
output frequency (F1), parameter 424 F1 frequency.
424F1 frequency
(F1 frequency)
Value:
0.0 - par. 426 F2 frequency
Function:
See parameter 423 U1 voltage .
Description of choice:
Set the output frequency (F1) that is to match the first
output voltage (U1), parameter 423 U1 voltage .
Par. 104 Motor fre-
quency
Programming
425U2 voltage
423U1 voltage
(U1 voltage)
Value:
0.0 - 999.0 V
Function:
Parameters 423-428 are used when in parameter
101Torque characteristic a selection has been made ofSpecial motor characteristic [8]. It is possible to determine a U/f characteristic on the basis of four definable
voltages and three frequencies. The voltage at 0 Hz is
set in parameter 133 Start voltage.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 73
par. 103
Value:
0.0 - 999.0 V
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output voltage (U2) that is to match the second
output frequency (F2), parameter 426 F2 frequency.
426F2 frequency
Value:
Par. 424 F1 frequency - par. 428
F3 frequency
(U2 voltage)
par. 103
(F2 frequency)
Par. 104 Mo-
tor frequency
VLT® 2800 Series
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output frequency (F2) that is to match the second output voltage (U2), parameter 425 U2 voltage.
427U3 voltage
(U3 voltage)
Value:
0.0-999.0 V
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output voltage (U3) that is to match the third
output frequency (F3), parameter 428 F3 frequency .
428F3 frequency
(F3 frequency)
Value:
Par. 426 F2 frequency - 1000
Hz
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output frequency (F3) that is to match the third
output voltage (U3), parameter 427 U3 voltage .
NOTE
Parameters 437-444 are only used if in
parameter 100 Configuration a selection
has been made of Process regulation,closed loop. [3].
437Process PID normal/inverse control
(proc no/inv ctrl)
Value:
Normal (normal)[0]
Inverse (inverse)[1]
par. 103
Par. 104 Motor
frequency
Function:
It is possible to choose whether the process regulator
is to increase/reduce the output frequency if there is a
deviation between the reference/setpoint and the actual process mode.
Description of choice:
If the adjustable frequency drive is to reduce the output
frequency in case the feedback signal increases, select Normal [0].If the adjustable frequency drive is to
increase the output frequency in case the feedback
signal increases, select Inverse [1].
438Proces PID anti windup
(proc anti windup)
Value:
Not active (DISABLE)[0]
Active (ENABLE)[1]
Function:
It is possible to select whether the process regulator is
to continue regulating on a deviation even if it is not
possible to increase/reduce the output frequency.
Description of choice:
The factory setting is Enable [1], which means that the
integration link is initialised in relation to the actual output frequency if either the current limit, the voltage limit
or the max./min. frequency has been reached. The
process regulator will not engage again until either the
error is zero or its sign has changed. Select Disable [0]
if the integrator is to continue integrating on the deviation, even if it is not possible to remove the fault by
such control.
NOTE
If Disable [0] is selected, it will mean that
when the deviation changes its sign, the
integrator will first have to integrate down
from the level obtained as a result of the
former error, before any change in output
frequency occurs.
= factory setting, () = display text, [] = value for use in communication via serial communication port
74 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
439Process PID start frequency
(PROC START VALUE)
Value:
- f
MAX
(pa-
Par. 201 Output frequency, low
limit, f
MIN
f
MIN
rameter
201/202)
Function:
When the start signal comes, the adjustable frequency
drive will react in the form of Open loop and will not
change to Closed loop until the programmed start frequency is reached. This makes it possible to set a
frequency that corresponds to the speed at which the
process normally runs, which will enable the required
process conditions to be reached sooner.
Description of choice:
Set the required start frequency.
NOTE
If the adjustable frequency drive is running
a the current limit before the required start
frequency is obtained, the process regulator will not be activated. For the regulator
to be activated anyway, the start frequency must be lower to the required output
frequency. This can be done during operation.
440Proces PID proportioanl gain
(PROC. PROP. GAIN)
Value:
0.0 - 10.00
0.01
Function:
The proportional gain indicates the number of times
the deviation between the setpoint and the feedback
signal is to be applied.
441Process PID integration time
(PROC. INTEGR. T.)
Value:
0.01 - 9999.99 (OFF)
OFF
Function:
The integrator provides an increasing gain at a constant error between the reference/setpoint and the
feedback signal. The greater the error, the quicker the
integrator frequency contribution will increase.The integral time is the time needed by the integrator to make
the same change as the proportional gain.
Description of choice:
Quick regulation is obtained at a short integral time.
However, this time may become too short, which can
make the process unstable due to overswing. If the integral time is long, major deviations from the required
setpoint may occur, since the process regulator will
take a long time to regulate in relation to a given error.
442Process PID differentiation time
(PROC. DIFF. time)
Value:
0.00 (OFF) - 10.00 sec.
0.00 sec.
Function:
The differentiator does not react to a constant error. It
only makes a gain when an error changes. The quicker
the deviation changes, the stronger the gain from the
differentiator. The gain is proportional to the speed at
which the deviation changes.
Description of choice:
Quick regulation is obtained with a long differentiation
time. However, this time may become too long, which
can make the process unstable due to overswing.
Programming
Description of choice:
Quick regulation is obtained by a high gain, but if the
gain is too high, the process may become unstable due
to overshoot.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 75
443Process PID diff. gain limit
(PROC. DIFF.GAIN)
Value:
5.0 - 50.0
5.0
VLT® 2800 Series
Function:
It is possible to set a limit for the differentiator gain. The
differentiator gain will increase if there are fast
changes, which is why it can be beneficial to limit this
gain. Thereby a pure differentiator gain is obtained at
slow changes and a constant differentiator gain where
quick changes to the deviation occur.
Description of choice:
Select a differentiator gain limit as required.
444Process PID lowpass filter time
(proc filter time)
Value:
0.02 - 10.00
0.02
Function:
Noise in the feedback signal is dampened by a first
order lowpass filter to reduce the noise's impact on the
process regulation. This can be an advantage e.g. if
there is a lot of noise on the signal.
Description of choice:
Select the required time constant (t). If a time constant
(t) of 0.1 s is programmed, the cut-off frequency for the
lowpass filter will be 1/0.1 = 10 RAD/sec., corresponding to (10 / 2 x ) = 1.6 Hz. The process regulator will
thus only regulate a feedback signal that varies by a
frequency lower than 1.6 Hz. If the feedback signal
varies by a higher frequency than 1.6 Hz, it will be
dampened by the lowpass filter.
Function:
This function makes it possible to 'catch' a rotating
motor shaft, which is no longer controlled by the adjustable frequency drive, e.g. because of a mains dropout. The function is activated each time a start
command is enabled. For the adjustable frequency
drive to be able to 'catch' the rotating motor shaft, the
motor speed must be lower than the frequency that
corresponds to the frequency in parameter 202 Output
frequency, high limit, f
MAX
.
Description of choice:
Select Disable [0] if this function is not required.
Select OK - same direction [1] if the motor shaft is only
able to rotate in the same direction when cutting in. OK
- same direction [1] should be selected if in parameter
200 Output frequency range a selection has been of
Clockwise only .
Select OK - both directions [2] if the motor is able to
rotate in both directions when cutting in.
Select DC brake and start [3] if the adjustable frequency drive is to be able to brake the motor using the DC
brake first, followed by start. It is assumed that parameters 126-127/132 DC brake are enabled. In the case
of higher 'Windmilling' (rotating motor) effects, the adjustable frequency drive is not able to 'catch' a rotating
motor without selecting DC brake and start .
Limitations:
Too low inertia will lead to load acceleration,
-
which can be dangerous or prevent correct
catching of a rotating motor. Use the DC
brake instead.
If the load is driven, e.g. by 'Windmilling' (ro-
-
445Flying start
(flyingstart)
Value:
Off (DISABLE)[0]
tating motor) effects, the unit may cut out
because of overvoltage.
Flying start does not work at lower values
-
than 250 rpm.
OK - same direction
(OK-same direction)[1]
OK - both directions
(OK-both directions)[2]
DC brake and start
(DC-BRAKE BEF. START)[3]
= factory setting, () = display text, [] = value for use in communication via serial communication port
76 MG.27.A2.22 - VLT® is a registered Danfoss trademark
451Speed PID feedforward factor
(feedforward fact)
Value:
0 - 500 %
100 %
VLT® 2800 Series
Function:
This parameter is only active if in parameter 100 Configuration the selection made is Speed regulation,
closed loop. The FF function sends a larger or smaller
part of the reference signal outside the PID controller
in such a way that the PID controller only has an influence on part of the control signal. Any change to the
set point will thus have a direct effect on the motor
speed. The FF factor provides high dynamism when
changing the set point and less overswing.
Description of choice:
The required % value can be selected in the interval f
- f
MIN
. Values over 100 % are used if the set point
MAX
variations are only small.
452Controller range
(pid contr. range)
Value:
0 - 200 %
10 %
Function:
This parameter is only active if Speed regulation,
closed-loop is madein parameter 100 Configuration.
The controller range (bandwidth) limits the output from
the PID controller as a % of motor frequency f
M,N
.
Description of choice:
The required % value can be selected for motor frequency f
. If the controller range is reduced, the
M,N
speed variations will be less during initial tuning.
Description of choice:
Select Enable [1] to enable the readout in the display
if warning 33 Out of frequency range occurs. Select
Disable [0] to disable the readout in the display if warning 33 Out of frequency range occurs.
456Brake Voltage Reduce
(BRAKE VOL REDUCE)
Value:
0 - 25 V if 200 V device
0 - 50 V if 400 V device
Function:
The user sets the voltage by which the level for resistor
braking is reduced. It is only active when resistor in
parameter 400 is selected.
Description of choice:
The greater the reduction value, the faster the reaction
to a generator overload. Should only be used if there
are problems with overvoltage in the intermediate circuit.
457Phase loss function
(PHASE LOSS FUNCT)
Value:
Trip (TRIP)[0]
Autoderate & warning (AUTODERATE &
WARNING)[1]
Warning (WARNING)[2]
0
0
Programming
455Frequency range monitor
(MON. FREQ. RANGE)
Function:
Select the function which is to be activated if the mains
imbalance becomes too high or if a phase is missing.
Value:
Disable[0]
Enable[1]
Description of choice:
At Trip [0] the adjustable frequency drive will stop the
motor within a few seconds (depending on drive size).
Function:
This parameter is used if warning 33 Out of frequency
range must be turned off in the display in process con-
trol closed-loop. This parameter does not affect the
extended status word.
If Autoderate & warning [1] is selected, the drive will
export a warning and reduce the output current to 50
% of I
to maintain operation.
VLT,N
At Warning [2] only a warning will be exported when a
mains failure occurs, but in severe cases, other extreme conditions might result in a trip.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 77
NOTE
If Warning has been selected, the life expectancy of the drive will be reduced when
the mains failure persists.
461Feedback conversion
(FEEDBACK CONV.)
Value:
Linear (LINEAR)[0]
Square root (SQUARE ROOT)[1]
Function:
In this parameter, a function is selected which converts
a connected feedback signal from the process to a
feedback value that equals the square root of the connected signal. For example, this is used when flow
(volume) regulation is required on the basis of pressure as feedback signal (flow = constant x
pressure
the reference in such a way that there is a linear connection between the reference and the flow required.
). This conversion makes it possible to set
VLT® 2800 Series
Description of choice:
If Linear [0] is selected, the feedback signal and the
feedback value will be proportional. If Square root [1]
is selected, the adjustable frequency drive translates
the feedback signal to a squared feedback value.
78 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Enhanced Sleep Mode
The enhanced sleep mode has been developed to
work under all conditions and to overcome problems
when using pumps with flat pump curves, or when
suction pressure varies. Enhanced sleep mode provides excellent control for shutting down the pump at
low-flow, thus saving energy.
If operating with constant pressure control in the SYSTEM, for instance a drop in the suction pressure will
lead to an increase in frequency to maintain pressure.
Consequently there is a situation, where the frequency
will vary independent of the flow. This can lead to inappropriate activation of sleep mode or wake-up of the
adjustable frequency drive.
Flat pump curves leads to a situation where there will
be little or no change in frequency in response to flow
variation. Consequently, the adjustable frequency
drive might not reach the sleep frequency when setting
it at a low value.
Enhanced sleep mode is based on power/frequency
monitoring and works in closed loop only. Stop due to
the enhanced sleep mode function is initiated under
the following conditions:
•Power consumption is below the no/low flow
power curve and stays there for a certain time
(parameter 462 Enhanced sleep mode timer)
or
•The pressure feedback is above the reference when running at minimum speed and
stays there for a certain time (parameter 462
Enhanced sleep mode timer).
If the feedback pressure falls below the wakeup pressure (Parameter 464 Wakeup pressure), the adjustable
frequency drive restarts the motor.
Dry Run Detection
For most pumps, especially submersible bore-hole
pumps, it must be assured that the pump is stopped in
case of dry run. This is assured by the Dry run detection feature.
How Does It Work?
Dry run detection is based on power/frequency monitoring and works in both closed and open loop.
Stop (trip) due to dry run is initiated under following
conditions:
Closed loop:
•The adjustable frequency drive is running at
maximum frequency (parameter 202 Outputfrequency high limit, f
MAX
) and
•Feedback is below minimum reference (parameter 204 Minimum reference, Ref,
MIN
) and
•Power consumption is below the no/low flow
power curve for a certain time (parameter
470 Dry run time out)
Open loop:
•Whenever the power consumption is below
the no/low flow power curve for a certain time
(parameter 470 Dry run time out) the adjustable frequency drive will trip.
The adjustable frequency drive can be set up for either
manual or automatic restart after stop (parameters 405
Reset function and 406 Automatic restart time).
•Enhanced Sleep Mode and Dry Run Detection can be enabled and disabled independently. This is done in parameter 462
Enhanced sleep mode timer and parameter
470 Dry run timeout.
Centrifugal pumps with radial impellers show a clear
one-to-one relation between power consumption and
flow, which is utilized to detect a no or low flow situation.
It is only necessary to enter two sets of values for power and frequency (min and max) at no or low flow. The
adjustable frequency drive then automatically calculates all data in-between those two sets of values and
generates the no/low flow power curve.
If the power consumption falls below the power curve,
the adjustable frequency drive enters Sleep-mode or
trips due to dry run, depending on the configuration.
Programming
MG.27.A2.22 - VLT® is a registered Danfoss trademark 79
•Dry run protection. Shuts down at no or lowflow and protects the motor and pump from
overheating.
•Improved energy savings with enhanced
sleep mode.
•Minimized risk of bacterial growth in drinking
water because of insufficient motor cooling.
•Easy commissioning.
Only centrifugal pumps with radial impellers show a
clear one-to-one relationship between flow and power.
Consequently, proper functionality of the Enhanced
Sleep Mode and Dry Run Detection is only given for
this type of pump.
462Enhanced Sleep Mode Timer
(ESL timer)
Value:
Value 0 – 9999 sec.
Function:
The timer prevents cycling between Sleep mode and
normal operation. If for instance the power consumption falls below the no/low flow power curve the adjustable frequency drive will change mode when the
timer expires.
0 = OFF
VLT® 2800 Series
463Boost setpoint
(BOOST SETPOINT)
Value:
1 - 200 %
Function:
This function can only be used if Closed loop has been
selected in parameter 100.
In systems with constant pressure regulation, it is advantageous to increase the pressure in the system
before the adjustable frequency drive stops the motor.
This extends the time during which the adjustable frequency drive stops the motor and helps to avoid frequent starting and stopping of the motor, e.g. in the
case of leaks in the water supply system.
There is a fixed boost time-out on 30 sec. in case the
boost setpoint cannot be reached.
Description of choice:
Set the required Boost setpoint as a percentage of the
resulting reference under normal operation. 100% corresponds to the reference without boost (supplement).
100 % of setpoint
Description of choice:
In case of cycling, set the timer to an appropriate value
that limits the number of cycles.
The value 0 disables Enhanced sleep mode.
Note: In parameter 463 Boost set point it is possible to
set up the adjustable frequency drive to provide a
pressure boost before the pump is stopped.
= factory setting, () = display text, [] = value for use in communication via serial communication port
80 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
464Wakeup Pressure
(Wakeup Pressure)
Value:
Par. 204 Ref
– par. 215 - 218 Setpoint
MIN
Function:
When in Sleep mode the adjustable frequency drive
will wake up when the pressure is below the Wakeup
pressure for the time set in parameter 462 Enhancedsleep mode timer.
Description of choice:
Set an appropriate value for the system. The unit is set
in parameter 416.
465Minimum pump frequency
(Pump min. freq.)
Value:
Value par. 201 f
– par. 202 f
MIN
MAX
(Hz)
20
Function:
This parameter is linked to parameter 467 Minimum
Power and is used for no/low-flow power curve.
467Minimum Pump Power
(Min. pump power)
Value:
0
0–500.000 W
0
Function:
The associated power consumption at the frequency
entered in parameter 465 Minimum pump frequency.
Description of choice:
Enter the no/low-flow power reading at minimum pump
frequency entered in parameter 465.
Depending on pump size or curve, select W or kW in
par. 009 index [32] and [8] for fine tuning.
468Maximum Pump Power
(Max. pump power)
Value:
0–500.000 W
0
Function:
The associated power consumption at the frequency
entered in parameter 466 Minimum pump frequency.
Programming
Description of choice:
Enter a value equal or close to the desired minimum
frequency set in parameter 201 Output frequency low
limit, f
. Please note that the extension of the no/low-
MIN
flow power curve is limited by parameters 201 and 202,
and not by parameters 465 and 466.
466Maximum Pump Frequency
(Pump max. freq)
Value:
Value par. 201 f
- par. 202 f
MIN
MAX
(Hz)
50
Function:
This parameter is linked to parameter 468 Maximum
pump power and is used for the no/low-flow power
curve.
Description of choice:
Enter a value equal or close to the desired maximum
frequency set in parameter 202 Output frequency high
limit, f
MAX
.
Description of choice:
Enter the no/low-flow power reading at maximum
pump frequency entered in parameter 466.
Depending on pump size or curve, select W or kW in
par. 009 index [32] and [8] for fine tuning.
469No Flow Power Compensation
(NF power comp)
Value:
0.01 - 2
1.2
Function:
This function is used for an off-set of the no/low-flow
power curve, which can be used as a safety factor or
for fine tuning the system.
Description of choice:
Description The factor is multiplied to the power values. E.g., 1.2 will increase the power value with 1.2
over the whole frequency range.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 81
VLT® 2800 Series
470Dry Run Time Out
(DRY RUN TIME OUT)
Value:
5-30 sec.
Function:
If the power is below the no/low flow power curve, running at max speed for the time set in this parameter,
the adjustable frequency drive will trip on Alarm 75: Dry
run. In open loop operation the maximum speed does
not necessarily need to be reached before tripping.
Description of choice:
Set the value to obtain the desired delay before tripping. Manual or automatic restart can be programmed
in parameter 405 Reset function and 406 automatic re-start time.
The value 30 disables Dry run detection.
471Dry Run Interlock Timer
(Dry run int time)
Value:
0.5-60 min.
Function:
This timer determines when a trip due to dry run can
be automatically reset. When the timer expires, the
automatic reset of the trip can automatically restart the
adjustable frequency drive again.
31 = OFF
30 min.
484Initial ramp
(INITIAL RAMP)
Value:
OFF/000.1s - 360.0 s
Function:
Allows the motor/equipment to be brought up to minimum speed (frequency) at a rate different than the
normal ramp-up rate (param. 207).
Description of choice:
For example, vertical pumps and other equipment often have a requirement to not operate below a minimum speed any longer than necessary. Damage and
excessive wear can occur when operating below minimum speed (frequency) for too long. The initial ramp
is used to quickly accelerate the motor/equipment to
minimum speed at which point, the normal ramp-up
rate (parameter 207) is made active. The range of adjustment of the initial ramp is from 000.1 second to
360.0 seconds; it can be adjusted in 0.1 second increments. OFF is displayed in this parameter if it is set to
000.0, and the initial ramp is not active and the normal
ramp-up is active.
OFF
Description of choice:
Parameter 406 Automatic restart time still determines
how frequent an attempt to reset a trip will be performed. If for instance parameter 406 Automatic restart
time is set to 10 sec. and parameter 405 Reset function is set to Automatic Reset x10 the adjustable fre-
quency drive will attempt to reset the trip 10 times
within 100 seconds. If parameter 471 is set to 30 min.
the adjustable frequency drive will consequently not be
able to perform automatic reset of dry run trip and will
need a manual reset.
= factory setting, () = display text, [] = value for use in communication via serial communication port
82 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Fill Mode
Fill Mode eliminates the occurrence of water hammer
associated with the rapid exhausting of air from piping
systems (such as Irrigation systems).
The adjustable frequency drive, set for Closed Loop
operation uses an adjustable Fill Rate, a "Filled Pressure" setpoint, an operating pressure setpoint, and a
pressure feedback.
Fill Mode is available when:
•
The VLT 2800 drive is in Closed Loop mode
(parameter 100).
•
Parameter 485 is not 0
•
Parameter 437 is set to NORMAL
After a start command, Fill Mode operation begins
when the adjustable frequency drive reaches minimum frequency - set in parameter 201.
The "Filled" Setpoint - parameter 486- is actually a
setpoint limit. When minimum speed is reached, the
pressure feedback is looked at, and the adjustable frequency drive begins to ramp to the "Filled" pressure
setpoint at the rate established by Fill Rate parameter
485.
The Fill Rate - parameter 485- is dimensioned in Units/
Second. The Units will be the units selected in parameter 416.
When the pressure feedback equals the "Filled" Setpoint, the control transitions to the operating setpoint
(Setpoint 1-4, param. 215-218) and continues operation in standard (normal) "closed loop" mode.
The value to use for the "Filled" Setpoint parameter
486, can be determined by:
1.Use the DISPLAY MODE key on the LCP to
display FEEDBACK 1.
IMPORTANT! Be sure that you have selected the UNITS in parameter 416 before this
step.
2.
Operate the VLT 2800 in HAND mode and
slowly advance the speed to fill the pipe while
being careful not to create a water hammer.
3.An observer at the end of the pipe must be
able to report when the pipe is filled.
4.At that instant, stop the motor, and observe
the value of pressure feedback (have the
LCP display set to observe the feedback before starting).
VLT® 2800 Series
485Fill Rate
(FILL RATE)
Value:
OFF/000000.001 - 999999.999 (units/s) -
Function:
Establishes the rate at which the pipe is filled.
Description of choice:
The dimension of this parameter is units/second. The
units will be the value selected in parameter 416. For
example, the units could be bar, MPa, PSI, etc. If bar
is the selected unit in parameter 416, then the number
set in this parameter (485) would be dimensioned as
bar/second. Changes to this parameter can be made
in steps of .001 units.
486Filled Setpoint
(FILLED SETPOINT)
Value:
Param. 414 - Param. 205 -
Param. 414
Function:
The value set in this parameter corresponds to the
pressure that exists at the pressure sensor when the
pipe is filled.
OFF
Programming
5.The value of feedback in step 4) is the value
to use in parameter 486 - "Filled" Setpoint.
The value to set in parameter 485- Fill Rate can be
supplied by the system engineer from proper calculation or from experience, or it can be determined experimentally by performing numerous fill mode se-
Description of choice:
The units of this parameter correspond to the units selected in Parameter 416. The minimum value of this
parameter is Fb
for this parameter is Ref
(param. 414). The maximum value
min
(param. 205). The setpoint
max
can be changed in .01 steps.
quences and either increasing or decreasing the value
of this parameter to obtain the fastest fill without causing a water hammer.
The Fill Mode is also beneficial when bringing the motor to a stop as it prevents sudden changes in pressure
and flow which could also cause a water hammer.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 83
VLT® 2800 Series
Serial communication
500Address
(BUS ADDRESS)
Value:
Parameter 500 Protocol = FC protolkol [0]
0 - 247
Parameter 500 Protocol = Metasys N2 [1]
1 - 255
Parameter 500 Protocol = MODBUS RTU [3]
1 - 247
Function:
This parameter allows the allocation of an address to
each variable frequency drive in a serial communication network.
Description of choice:
The individual variable frequency drive must be allocated a unique address.
If the number of units connected (variable frequency
drives + master) is higher than 31, a repeater must be
used.
Parameter 500 Address cannot be selected via the
serial communication, but must be preset via the control unit.
501Baudrate
(BAUDRATE)
Value:
300 Baud (300 BAUD)[0]
600 Baud (600 BAUD)[1]
1200 Baud (1200 BAUD)[2]
2400 Baud (2400 BAUD)[3]
4800 Baud (4800 BAUD)[4]
9600 Baud (9600 BAUD)[5]
Function:
This parameter is for programming the speed at which
data is transmitted via the serial port. Baud rate is defined as the number of bits transmitted per second.
Description of choice:
The variable frequency drive's transmission speed
must be set at a value corresponding to the transmission speed of the master.
Parameter 501 Baudrate cannot be selected via the
serial port, but must be preset via the operating unit.
502Coasting Stop
(COASTING SELECT)
1
Value:
Digital input (DIGITAL INPUT)[0]
1
Serial port (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
1
Logic or (LOGIC OR)[3]
Function:
Parameters 502-508 allow a choice between controlling the adjustable frequency drive via the digital inputs
and/or via the serial port.
If Serial port [1] is selected, the relevant command can
only be activated if a command is given via the serial
port.
In the case of Logic and [2] the function must also be
activated via a digital input.
Description of choice:
The table below shows when the motor is running and
when it is coasting, when each of the following is selected: Digital input [0], Serial port [1], Logic and [2] or
Logic or [3].
NOTE
Note that Coasting stop and Bit 03 in the
control word are active at logic '0'.
= factory setting, () = display text, [] = value for use in communication via serial communication port
84 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Logic or [3]
Dig. input
00Coasting
01Coasting
10Coasting
11Motor running
Ser. portFunction
503Quick-stop
(Q STOP SELECT)
Value:
Digital input (DIGITAL INPUT)[0]
Serial port (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
Logic or (LOGIC OR)[3]
Function:
See function description for parameter 502 Coasting
stop.
Description of choice:
The table below shows when the motor is running and
when it is in Quick stop mode, when each of the following is selected: Digital input [0], Serial port [1], Logicand [2] or Logic or [3].
NOTE
Note that Quick stop inverse and Bit 04 in
the control word are active at logic '0'.
Digital input [0]
Dig. input
Serial portFunction
00Quick stop
01Quick stop
10Motor running
11Motor running
Serial port [1]
Dig. input
Serial portFunction
00Quick stop
01Motor running
10Quick stop
11Motor running
Logic and [2]
Dig. input
Serial portFunction
00Quick stop
01Motor running
10Motor running
11Motor running
Logic or [3]
Dig. input
Serial portFunction
00Quick stop
01Quick stop
10Quick stop
11Motor running
504DC brake
(DC BRAKE SELECT)
Value:
Digital input (DIGITAL INPUT)[0]
Serial port (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
Logic or (LOGIC OR)[3]
Function:
See function description for parameter 502 Coasting
stop.
Description of choice:
The table below shows when the motor is running and
the DC braking when each of the following is selected
Digital input [0], Serial port [1], Logic and [2] or Logic
or [3].
NOTE
Note that DC braking inverse and Bit 02 in
the control word are active at logic '0'.
See function description for parameter 502 Coasting
stop.
Description of choice:
The table below shows when the motor has stopped
and when the variable frequency drive has a start command when each of the following is selected: Digital
input [0], Serial port [1], Logic and [2] or Logic or [3].
Digital input [0]
Dig. input
00Stop
01Stop
10Start
11Start
Serial port [1]
Dig. input
00Stop
01Start
10Stop
11Start
Ser. portFunction
Ser. portFunction
Function:
See function description for parameter 502 Coasting
stop.
Description of choice:
The table below shows when the motor is running
clockwise and counter-clockwise when each of the following is selected: Digital input [0], Serial port [1], Logic
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 87
VLT® 2800 Series
508Selection of preset ref.
(PRES.REF. SELECT)
Value:
Digital input (DIGITAL INPUT)[0]
Serial comunication (SERIAL PORT)[1]
Logic and (LOGIC AND)[2]
Logic or (LOGIC OR)[3]
Function:
See function description of parameter 502 Coasting
stop.
Description of choice:
Preset references via serial communication are active
when parameter 512 Telegram profile is set to FC pro-tocol [1].
509Bus jog 1 (BUS JOG 1 FREQ.)
510Bus jog 2 (BUS JOG 2 FREQ.)
Value:
0.0 - par. 202 Output frequency high
limit
10,0 Hz
Function:
If parameter 512 Telegram Profile shows the selection
Profidrive [0], two fixed speeds (Jog 1 or Jog 2) can be
selected via the serial port.
The function is the same as in parameter 213 Jog fre-quency .
Description of choice:
Jog frequency f
.
f
MAX
can be selected between 0 Hz and
JOG
512Telegram Profile
(Telegram Profile)
Value:
Profidrive (Profidrive)[0]
FC protocol (FC protocol)[1]
Function:
It is possible to choose between two different control
word profiles.
Description of choice:
Select the desired control word profile.
See Serial port for VLT 2800 for further details of control word profiles.
513Bus time interval
(BUS TIMEOUT TIME)
Value:
1 - 99 sec.
1 sec.
Function:
In this parameter it is possible to preset the maximum
time expected to elapse between receipt of two consecutive telegrams. If this time is exceeded, the serial
communication is assumed to have stopped and the
desired reaction is preset in parameter 514 Bus timeinterval function.
Description of choice:
Preset the required time.
514Bus time interval function
(BUS TIMEOUT FUNC)
Value:
Off (off)[0]
Freeze output frequency (FREEZE OUTPUT) [1]
Stop (STOP)[2]
Jogging (JOGGING)[3]
Max. speed (MAX SPEED)[4]
Stop and trip (STOP AND TRIP)[5]
Function:
In this parameter you can select the required reaction
for the variable frequency drive when the preset time
in parameter 513 Bus time interval has been exceeded. If choices [1] to [5] are activated the output relay
will be deactivated.
Description of choice:
The output frequency of the variable frequency drive
can be frozen at the present value, stop the motor, be
frozen at parameter 213 Jogging frequency, be frozen
at parameter 202 Output frequency, high limit f
MAX
or
stop and activate a cut out.
= factory setting, () = display text, [] = value for use in communication via serial communication port
88 MG.27.A2.22 - VLT® is a registered Danfoss trademark
These parameters can be read out via the serial communication port and the LCP display. See also parameters 009-012 Display readout.
Resulting reference [unit], parameter 516:
Gives the resulting reference in Hz in Open loop (parameter 100). In a closed loop the reference unit is
selected in parameter 416 Process units.
Feedback [unit], parameter 517:
NOTE
Parameters 515-541 can only be read out
via an LCP control unit.
Gives the resulting feedback value with the unit/scaling selected in parameters 414, 415 and 416. See also
dealing with feedback.
Frequency [Hz], parameter 518:
Description of choice:
Resulting reference %, parameter 515:
Gives the resulting reference as a percentage in the
range from Minimum reference, Ref
reference, Ref
. See also Dealing with references.
MAX
to Maximum
MIN
Gives the output frequency from the adjustable frequency drive.
Frequency x scaling [-], parameter 519:
corresponds to the present output frequency f
multi-
M
plied by the factor preset in parameter 008 Displayscaling of output frequency .
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 89
VLT® 2800 Series
Motor current [A], parameter 520:
Gives the motor's phase current measured as an effective value.
Torque [Nm], parameter 521:
Gives the motor's present load in relation to the motor's
rated torque.
Power [kW], parameter 522:
Gives the present power absorbed by the motor in kW.
Power [HP], parameter 523:
Gives the present power absorbed by the motor in HP.
Motor voltage, parameter 524:
Gives the voltage being supplied to the motor.
DC link voltage, parameter 525:
Gives the intermediate circuit voltage in the adjustable
frequency drive.
Thermal load, motor [%], parameter 526:
Gives the calculated/estimated thermal load on the
motor. 100% is the cut-out limit. See also parameter
128 Thermal motor protection.
Thermal load INV [%], parameter 527:
Gives the calculated/estimated thermal load on the
adjustable frequency drive. 100% is the cut-out limit.
Digital input, parameter 528:
Gives the signal status from the 5 digital inputs (18, 19,
27, 29 and 33). Input 18 corresponds to the bit on the
extreme left. '0' = no signal, '1' = connected signal.
Terminal 53 analogue input [V], parameter 529:
Gives the voltage value for the signal on terminal 53.
Terminal 60 analogue input [mA], parameter 531:
Gives the present value for the signal on terminal 60.
Allows writing of a bus feedback value which will then
form part of the feedback handling.
Inverter temperature, parameter 537:
Gives the present inverter temperature on the adjustable frequency drive. The cut-out limit is 90-100 °C,
with cut back in at 70 ± 5 °C.
Alarm word, parameter 538:
Gives in Hex code which alarm is on the adjustable
frequency drive. See Warning word, extended status
word and alarm word.
Control word, parameter 539:
Gives the present control word on the adjustable frequency drive in Hex. See Serial communication for the
VLT 2800.
Warning word, parameter 540:
States whether there is a warning on the adjustable
frequency drive in Hex. See Warning word, extended
status word and alarm word.
Extended status word, parameter 541:
States whether there is a warning on the adjustable
frequency drive in Hex code. See Warning word, ex-
tended status word and alarm word.
Pulse count, parameter 544:
This parameter can be read out via the LCP display
(009-012). When you run with counter stop, this parameter enables you, either with or without reset, to
read the number of pulses registered by the device.
The highest frequency is 67.6 kHz, while the lowest is
5 Hz. The counter is reset when counter stop is restarted.
Pulse reference [Hz], parameter 532:
Gives a pulse frequency in Hz connected to terminal
33.
560N2 Override release time
(N2 OVER.REL.TIME)
Value:
External reference, parameter 533:
Gives the sum of external references as a percentage
(sum of analogue/pulse/serial communication) in the
range from Minimum reference, Ref
reference, Ref
MAX
.
to Maximum
MIN
Status word, parameter 534:
Gives the present status word for the adjustable frequency drive in Hex. See Serial communication for the
1 - 65534 (OFF) sec.
OFF
Function:
In this parameter, the maximum time that is expected
to pass between the reception of two consecutive N2
telegrams is set. If this time is exceeded, the serial
communication is assumed to have stopped, and all
points in the N2 point-map that are overridden will be
released in the order below:
VLT 2800.
Bus feedback 1, parameter 535:
= factory setting, () = display text, [] = value for use in communication via serial communication port
90 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
1.Release Analog Outputs from point address
(NPA) 0 to 255.
2.Release Binary Outputs from point address
(NPA) 0 to 255.
3.Release Internal Floating Points from point
address (NPA) 0 to 255.
4.Release Internal Integer Points from point
address (NPA) 0 to 255.
5.Release Internal Byte points from point address (NPA) 0 to 255.
Description of choice:
Set the required time.
561Protocol
(PROTOCOL)
Value:
FC protocol (FC PROTOKOL)[0]
Metasys N2 (METASYS N2)[1]
Modbus RTU[2]
Function:
There is a choice of three different protocols.
Description of choice:
Select the required control word protocol.
For further information about using the Metasys N2
Protocol, see MG91CX; for Modbus RTU, see
MG10SX.
570Modbus parity and message framing
(M.BUS PAR./FRAME)
Value:
(EVEN/1 STOPBIT)[0]
(ODD/1 STOPBIT)[1]
(NO PARITY/1 STOPBIT)[2]
(NO PARITY/2 STOPBIT)[3]
Function:
This parameter sets up the drive’s Modbus RTU interface to communicate properly with the master control-
ler. The parity (EVEN, ODD, or NO PARITY) must be
set to match the setting of the master controller.
Description of choice:
Select the parity that matches the setting for the Modbus master controller. Even or odd parity is sometimes
used to allow a transmitted word to be checked for errors. Because Modbus RTU uses the more efficient
CRC (Cyclic Redundancy Check) method of checking
for errors, parity checking is seldom used in Modbus
RTU networks.
571Modbus communications timeout
(M.BUS COM.TIME.)
Value:
10 ms - 2000 ms
Function:
This parameter determines the maximum amount of
time that the drive’s Modbus RTU will wait between
characters that are sent by the master controller.
When this amount of time expires, the drive’s Modbus
RTU interface will assume that it has received the entire message.
Description of choice:
Generally, the value of 100 ms is sufficient for Modbus
RTU networks, although some Modbus RTU networks
may operate on a timeout value as short as 35 ms.
If this value is set too short, the drive’s Modbus RTU
interface may miss a part of the message. Since the
CRC check will not be valid, the drive will ignore the
message. The resulting retransmissions of messages
will slow communications on the network.
If this value is set too long, the drive will wait longer
than necessary to determine that the message is completed. This will delay the drive’s response to the message and possibly cause the master controller to time
out. The resulting retransmissions of messages will
slow communications on the network.
580-582 Defined parameters
(defined pnu's)
Value:
Read only
100 ms
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 91
Function:
The three parameters hold a list of all the parameters
that are defined in the VLT 2800. It is possible to read
single elements of the list by using the corresponding
subindex. The subindexes start at 1 and follow the order of the parameter numbers.
Each parameter holds up to 116 elements (parameter
numbers).
When a 0 is returned as parameter number the list
ends.
VLT® 2800 Series
92 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Technical functions
600-605 Operating Data
Value:
Par. no.DescriptionDisplay textUnitRange
600Operating hours(OPERATING HOURS)Hours0-130,000.0
601Hours run(RUNNING HOURS)Hours0-130,000.0
602kWh counter(KWH COUNTER)kWhDepends on unit
603Number of power-ups(POWER-UPS)Number of times0-9999
604Number of overtemperatures (OVERTEMPS)Number of times0-9999
605Number of overvoltages(OVERVOLTS)Number of times0-9999
Function:
These parameters can be read out via the serial communication port and the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the adjustable frequency
drive has been operating. The value is saved every
hour and when there is a line failure. This value cannot
be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been operating since the reset in parameter 619 Reset of hoursrun counter. The value is saved every hour and when
there is a line failure.
Parameter 602, kWh counter:
Gives the adjustable frequency drive's output energy
in kWh. The calculation is based on the mean kW value
over one hour. This value can be reset using parameter 618 Reset of kWh counter.
Range: 0 - depends on unit.
615Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for a
trip (cut-out of the variable frequency drive) occurring.
10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most recently saved data value. The highest log number [10]
contains the oldest data value saved. If a trip occurs,
it is possible to see the cause, time and a possible value of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a
table. See the table in Warnings/alarm messages.
Programming
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage
undertaken on the adjustable frequency drive.
Parameter 604, Number of overtemperatures:
gives the number of overtemperature faults that have
been registered on the adjustable frequency drive's
heatsink.
Parameter 605, Number of overvoltages:
gives the number of overvoltages of the intermediate
circuit voltage in the adjustable frequency drive. This
is only counted when Alarm 7 Overvoltage is active.
616Fault log: Time
(F. LOG: TIME)
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter, it is possible to see the total number
of operating hours in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest log number [1] contains the latest/most recently saved data
value, and the highest log number [10] contains the
oldest data value.
Description of choice:
NOTE
Read out as one value.
Parameters 615-617 Fault log cannot be
read out via the integral control unit.
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 93
VLT® 2800 Series
617Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a
trip occurred. The unit of the value depends on which
alarm is active in parameter 615 Fault log: Faultcode .
Description of choice:
Read out as one value.
618Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET)[0]
Reset (RESET COUNTER)[1]
Function:
Resetting parameter 602 kWh counter to zero.
Description of choice:
If Reset [1]is selected and you press the [OK] key, the
variable frequency drive's kWh counter is reset to zero.
This parameter cannot be selected via serial communication.
NOTE
When the [OK] key is activated, the counter is reset to zero.
619RESET RUNNING HOURS COUNTER
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET)[0]
Reset (RESET COUNTER)[1]
Function:
Resetting of parameter 601 Hours run to zero.
Description of choice:
If Reset [1] is selected and you press the [OK] key, the
variable frequency drive's parameter 601 is reset to
zero Hours run. This parameter cannot be selected via
serial communication.
NOTE
When the [OK] key is activated the parameter is reset to zero.
620Operation Mode
(OPERATION MODE)
Value:
Normal operation (NORMAL OPERATION)[0]
Control card test (CONTROL CARD TEST)[2]
Initialize (INITIALIZE)[3]
Function:
In addition to its normal function, this parameter can
be used to test the control card.
There is also the opportunity to perform an initialization
at the factory setting for all parameters in all Setups,
with the exception of parameters 500 Address, 501
Baudrate, 600-605 Operating data and 615-617 Fault
log.
Description of choice:
Normal function [0] is used for normal operation of the
motor.
Control card test [2] is selected if you wish to check the
control card's analog/digital inputs, analog/digital out-
puts, relay outputs and 10 V and 24 V voltages.
The test is performed as follows:
27 - 29 - 33 - 46 are connected.
50 - 53 are connected.
42 - 60 are connected.
12 - relay terminal 01 is connected.
18 - relay terminal 02 is connected.
19 - relay terminal 03 is connected.
See also the DeviceNet manual MG.90.BX.YY for fur-
ther details.
= factory setting, () = display text, [] = value for use in communication via serial communication port
94 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Use the following procedure for the control card test:
1.Select control card test.
2.Disconnect the AC line voltage and wait until
the light in the display has disappeared.
3.Mount according to drawing and description.
4.Connect the AC line voltage.
5.The adjustable frequency drive automatically
undertakes a test of the control card.
VLT® 2800 Series
If the adjustable frequency drive displays a fault code
from 37-45, the control card test has failed. Change
the control card to start up the adjustable frequency
drive.
If the adjustable frequency drive comes into Display
mode, the test is OK. Remove the test connector and
the adjustable frequency drive is ready for operation.
Parameter 620 Operating mode is automatically set to
Normal operation [0].
Initialization [3] is selected if you wish to use the unit's
factory setting.
Procedure for initialization:
1.
Select Initialization [3].
2.Disconnect the AC line voltage and wait until
the light in the display has disappeared.
3.Connect the AC line voltage.
4.An initialization is performed in all parameters in all Setups, with the exception of parameters 500 Address, 501 Baudrate,
600-605 Operating data and 615-617 Faultlog.
Programming
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.22 - VLT® is a registered Danfoss trademark 95
VLT® 2800 Series
621-642 Nameplate
Value:
Par.
no
621Unit type(DRIVE TYPE)
624Software version(SOFTWARE VERSION)
625LCP identification no.(LCP VERSION)
626Database identification no.(DATABASE VER.)
627Power parts version(POWER UNIT DB ID)
628Application option type(APP. OPTION)
630Communication option type(COM. OPTION)
632BMC software identification(BMC SOFTWARE ID)
634Unit identification for communication(UNIT ID)
635Software parts no.(SW. PART NO.)
640Software version(SOFTWARE VERSION)
641BMC software identification(BMC2 SW)
642Power card identification(POWER ID)
Description
Nameplate
Display text
Function:
The unit's main data can be read out from parameters
621 to 635 Nameplate using the LCP 2 control unit or
serial communication. Parameters 640-642 can also
be seen on the unit's integral display.
Description of choice:
Parameter 621 Nameplate: Unit type:
Gives unit size and line voltage.
Example: VLT 2811 380 - 480 V.
Parameter 624 Nameplate: Software version no.
The unit's present software version number appears
here.
Example: V 1.00
Parameter 625 Nameplate: LCP 2 ID number:
The ID number of the unit's LCP 2 appears here.
Example: ID 1.42 2 kB
Parameter 626 Nameplate: Database ID number:
The ID number of the software's database appears
here.
Example: ID 1.14.
Parameter 627 Nameplate: Power section version:
The ID number of the unit's power section appears
here.
Example: ID 1.15.
Parameter 628 Nameplate: Application option type:
Here you can see which types of application options
are installed in the adjustable frequency drive.
Parameter 630 Nameplate: Communication option
type:
Here you can see which types of communication options are installed in the adjustable frequency drive.
Parameter 642 Nameplate: Power card identification:
The ID number of the unit's power part appears here.
Example: 1.15
Parameter 700 -
Only for wobble functions: To use this function or for
further information, please see MI29J2xx.
= factory setting, () = display text, [] = value for use in communication via serial communication port
96 MG.27.A2.22 - VLT® is a registered Danfoss trademark
678Configure Control Card
(CONFIG CONTROL CARD)
Value:
Standard version (STANDARD VERSION)[1]
Profibus 3 Mbaud Version (PROFIBUS 3 MB
Ver.)[2]
Profibus 12 Mbaud Version (PROFIBUS 12
MB Ver.)[3]
Function:
This parameter enables a configuration of a Profibus
control card. The default value depends on the produced unit, which is also the maximum obtainable
value. This means that a control card can only be
downgraded to a lower performance version.
VLT® 2800 Series
Programming
MG.27.A2.22 - VLT® is a registered Danfoss trademark 97
VLT® 2800 Series
Warnings/alarm messages
A warning or an alarm will appear in the display as a
numerical code Err. xx. A warning will be shown on
the display until the fault has been corrected, while an
alarm will continue to flash until the [STOP/RESET]
key is activated.The table shows the various warnings
and alarms, and whether the fault locks the adjustable
frequency drive. After a Trip-locked the line supply is
cut off and the fault is corrected. The line supply is reconnected and the adjustable frequency drive is reset.
The adjustable frequency drive is now ready. A Trip
can be reset manually in three ways:
1.Via the operating key [STOP/RESET].
2.Via a digital input.
NoDescriptionWarningAlarmTrip
2Live zero error (LIVE ZERO ERROR)XXX
4Line phase loss (LINE PHASE LOSS)XXX
5Voltage warning high (DC LINK VOLTAGE HIGH)X
6Voltage warning low (DC LINK VOLTAGE LOW)X
7Overvoltage (DC LINK OVERVOLT)XXX
8Undervoltage (DC LINK UNDERVOLT)XXX
9Inverter overload (INVERTER TIME)XX
10Motor overloaded (MOTOR, TIME)XX
11Motor thermistor (MOTOR THERMISTOR)XX
12Current limit (CURRENT LIMIT)XX
13Overcurrent (OVERCURRENT)XXX
14Ground fault (GROUND FAULT)XX
15Switch mode fault (SWITCH MODE FAULT)XX
16Short-circuit (CURR. SHORT CIRCUIT)XX
17Serial communication timeout (STD BUS TIMEOUT)XX
18HPFB bus timeout (HPFB TIMEOUT)XX
33Out of frequency range (OUT FREQ RNG/ROT LIM)X
34HPFB communication fault (PROFIBUS OPT. FAULT)XX
35Soft-charge fault (SOFT-CHARGE FAULT)XX
36Overtemperature (OVERTEMPERATURE)XX
37-45Internal fault (INTERNAL FAULT)XX
50AMT not possibleX
51AMT fault re. nameplate data (AMT TYPE.DATA FAULT)X
54AMT wrong motor (AMT WRONG MOTOR)X
55AMT timeout (AMT TIMEOUT)X
56AMT warning during AMT (AMT WARN. DURING AMT)X
99Locked (LOCKED)X
3.Via serial communication.
It is also possible to choose an automatic reset in parameter 405 Reset function. When a cross appears in
both warning and alarm, this can mean that a warning
comes before an alarm. It can also mean that it is possible for the user to program whether a warning or an
alarm will appear for a given fault. For example, this is
possible in parameter 128 Motor thermal protection.
After a trip, the motor will coast, and alarm and warning
will blink on the adjustable frequency drive; but if the
fault disappears, only the alarm will blink. After a reset,
the adjustable frequency drive will be ready to start
operation again.
locked
LED indication
Warning
Alarmred
Trip-lockedyellow and red
98 MG.27.A2.22 - VLT® is a registered Danfoss trademark
yellow
WARNING/ALARM 2: Live zero fault
The voltage or current signal on terminal 53 or 60 is
below 50% of the preset value in parameter 309 or 315
Terminal, min. scaling.
VLT® 2800 Series
WARNING/ALARM 4: Mains phase fault
No phase on mains supply side. Check the supply
voltage to the adjustable frequency drive. This fault is
only active in 3-phase mains supply. The alarm can
also occur when the load is pulsing. In this instance the
pulses must be dampened, e.g. using an inertia disc.
WARNING 5: Voltage warning high
If the intermediate circuit voltage (UDC) is higher than
Voltage warning high the adjustable frequency drive will
give a warning and the motor will continue to run unchanged. If the UDC remains above the voltage warning limit, the inverter will trip after a set time. The time
depends on the device, and is set at 5 - 10 sec. Note:
The adjustable frequency drive will trip with an alarm
7 (overvoltage). A voltage warning can occur when the
connected mains voltage is too high. Check whether
the supply voltage is suitable for the adjustable frequency drive, see Technical data. A voltage warning
can also occur if the motor frequency is reduced too
quickly due to ramp down time being too short.
WARNING 6: Voltage warning low
If the intermediate circuit voltage (UDC) is lower than
Voltage warning low the adjustable frequency drive will
give a warning and the motor will continue to run unchanged. A voltage warning can occur when the connected mains voltage is too low. Check whether the
supply voltage is suitable for the adjustable frequency
drive, see Technical data. When the adjustable frequency drive is switched off a brief warning 6 (and
warning 8) appears.
WARNING/ALARM 7: Overvoltage
If the intermediate voltage (UDC) goes over the inverter's Overvoltage limit the inverter will be switched off
until the UDC has once more fallen below the overvoltage limit. If the UDC remains above the overvoltag
limit the inverter will trip after a set time. The time depends on the device, and is set at 5 - 10 sec. An
overvoltage in the UDC can occur when the motor frequency is reduced too quickly due to ramp down time
being too short. When the inverter is switched off a trip
reset is generated. Note: Voltage warning high (warning 5) will thus also be able to generate an alarm 7.
dervoltage limit, the inverter will trip after a set time. The
time depends on the device, and is set at 2 - 15 sec.
An undervoltage can occur when the connected mains
voltage is too low. Check whether the supply voltage
is suitable for the adjustable frequency drive, see
Technical data. When the adjustable frequency drive is
switched off a alarm 8 (and alarm 6) is displayed briefly
and a trip reset is generated. Note: Voltage warninglow (warning 6) will thus also be able to generate an
alarm 8.
WARNING/ALARM 9: Inverter overload
Electronic thermal inverter protection indicates that the
adjustable frequency drive is close to tripping due to
overloading (output current too high for too long). The
counter for electronic thermal inverter protection gives
a warning at 98% and trips at 100% accompanied by
an alarm. The adjustable frequency drive cannot be
reset until the counter drops below 90%. This fault arises because the adjustable frequency drive has been
overloaded for too long.
WARNING/ALARM 10: Motor overloaded
According to the electronic thermal inverter protection
the motor is too hot. In parameter 128 the user can
select whether the adjustable frequency drive should
emit a warning or an alarm when the counter reaches
100%. This fault is due to the motor being overloaded
by more than 100% for too long. Check that motor parameters 102-106 are set correctly.
WARNING/ALARM 11: Motor thermistor
The motor is too hot or the thermistor/thermistor connection has been disconnected. In parameter 128
Thermal motor protection the user can select whether
the frequency transformer emits a warning or an alarm.
Check that the PTC thermistor is correctly connected
between terminals 18, 19, 27 or 29 (digital input) and
terminal 50 (+ 10 V supply).
WARNING/ALARM 12: Current limit
The output current is greater than the value in parameter 221 Current Limit
, and the adjustable frequen-
LIM
cy drive will trip after a set time, selected in parameter
409 Trip delay overcurrent.
All about VLT 2800
WARNING/ALARM 8: Undervoltage
If the intermediate circuit voltage (UDC) is lower than
the inverter's Undervoltage limit the inverter will be
switched off until the UDC once more goes above the
undervoltage limit. If the UDC remains under the un-
MG.27.A2.22 - VLT® is a registered Danfoss trademark 99
VLT® 2800 Series
WARNING/ALARM 13: Overcurrent
The inverter's peak current limit (approx. 200% of rated
output current) has been exceeded. The warning will
last approx. 1-2 sec, and the adjustable frequency
drive will then trip and emit an alarm. Switch off the
adjustable frequency drive and check whether the motor shaft can be turned, and whether the size of the
motor is suitable for the adjustable frequency drive.
ALARM 14: Earth fault
There is a discharge from the output phases to earth,
either in the cable between the adjustable frequency
drive and the motor, or in the motor. Turn off the adjustable frequency drive and remove the earth fault.
ALARM 15: Switch mode fault
Fault in switch mode power supply (internal supply).
Contact your Danfoss supplier.
ALARM: 16: Short-circuit
There is a short-circuit on the motor terminals or in the
motor. Disconnect the mains supply to the adjustable
frequency drive and remove the short-circuit.
WARNING/ALARM 17: Serial communication timeout
There is no serial communication to the adjustable frequency drive. The warning will only be active when 514
Bus timeout function is set to a value other than OFF.
If parameter 514 Bus timeout function is set to Stopand trip [5], it will first give a warning and then ramp
down and trip out accompanied by an alarm. Parameter 513 Bus timeout can if required be increased.
WARNING/ALARM 18: HPFB bus timeout
There is no serial communication to the adjustable frequency drive's communication option card. This warning will only be active when parameter 804 Bus timeoutfunction is set to a value other than OFF. If parameter
804 Bus timeout function is set to Stop and trip, it will
first give a warning and then ramp down and trip out
accompanied by an alarm. Parameter 803 Bus time-out can if required be increased.
WARNING 33: Out of frequency range
This warning is active if the output frequency has
reached Output frequency low limit (parameter 201) or
Output frequency high limit (parameter 202). If the adjustable frequency drive is in Process regulation, closedloop (parameter 100) the warning will be active in the
display. If the adjustable frequency drive is in another
mode than Process regulation, closed loop, bit 008000
Out of frequency range in extended status word will be
active, but there will not be a warning in the display.
WARNING/ALARM 34: HPFB communication fault
Communication fault only occurs in Fieldbus versions.
Regarding alarmtype, please see parameter 953 in
fieldbus literature.
ALARM 35: Inrush fault
This alarm occurs when the adjustable frequency drive
has been connected to the mains supply too many
times within 1 minute.
WARNING/ALARM 36: Overtemperature
If the temperature inside the power module rises
above 75 - 85 °C (depending on the device) the adjustable frequency drive will emit a warning, and the
motor will continue to run unchanged. If the temperature continues to rise, the switch frequency is reduced
automatically. See Temperature-dependent switchingfrequency.
If the temperature inside the power module rises
above 92 - 100 °C (depending on the unit) the adjustable frequency drive will cut out. The temperature fault
cannot be reset until the temperature has dropped to
below 70 °C. The tolerance is ± 5 °C. The temperature
can be caused by the following:
The ambient temperature too high.
-
Motor cable too long.
-
Too high mains voltage.
-
ALARM 37-45: Internal fault
If one of these failures occurs, please contact Danfoss.
Alarm 37, internal fault number 0: Communication fault
between control card and BMC.
Alarm 38, internal fault number 1: Flash EEPROM fault
on control card.
Alarm 39, internal fault number 2: RAM fault on control
card.
Alarm 40, internal fault number 3: Calibration constant
in EEPROM.
Alarm 41, internal fault number 4: Data values in EEPROM.
Alarm 42, internal fault number 5: Fault in motor parameter database.
Alarm 43, internal fault number 6: General power card
fault.
100 MG.27.A2.22 - VLT® is a registered Danfoss trademark